0% found this document useful (0 votes)
121 views2 pages

Split EM341 4 Smart G Indirect

This document provides information on the EM341-4 Smart G electric energy metering system. It is an indirect three phase meter that can measure active and reactive energy. It supports wireless M-Bus technology and RFID cards to allow two-way communication between utilities and customers. The meter is upgradeable to directly communicate consumption and other data without the need for physical access. It meets IEC standards and has features such tamper detection, load profiling, and alarm capabilities.

Uploaded by

Amr Ahmed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
121 views2 pages

Split EM341 4 Smart G Indirect

This document provides information on the EM341-4 Smart G electric energy metering system. It is an indirect three phase meter that can measure active and reactive energy. It supports wireless M-Bus technology and RFID cards to allow two-way communication between utilities and customers. The meter is upgradeable to directly communicate consumption and other data without the need for physical access. It meets IEC standards and has features such tamper detection, load profiling, and alarm capabilities.

Uploaded by

Amr Ahmed
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

ADVANCED PAYMENT

INDIRECT THREE PHASE METER

EM341-4 Smart G
Commercial Applications (Low Voltage)

INTRODUCTION
The EM341-4 Smart G is a highly efficient electric energy metering system
upgradeable to support the latest wireless M-Bus technology, to communicate
with a Customer Interface Unit (CIU).
The EM341-4 Smart G benefits from the RFID technology which allows a two-way
communication path between the utility company and the consumer. Various
forms of information and data can be transferred securely via the RFID card(s)
including but not limited to customer data, meter configuration and monthly
consumption.
Furthermore the meter is upgradeable to support a direct communication
path between the consumer and the utility company without the use of meter
readers, money collectors or vending stations via an AMM interface, hence
Upgradeable to support reducing operational expenditure to the utility company and saving time for the
consumer.
The EM341-4 Smart G is an indirect connection meter, capable of measuring
active and reactive energy and meets the requirements of the IEC Standards.

STANDARDS
• IEC 60060 • IEC 60068
• IEC 60387 • IEC 60529
• IEC 61036 • IEC 62052
• IEC 62053 • IEC 62056-41
• IEC 62056-51

www.elsewedyemg.com
[email protected]
METER SPECIFICATIONS METER FEATURES
Electrical Characteristics Feature Description
Accuracy Class 0.5
• The EM341-4 Smart G is capable of measuring the
Measurements
active and reactive energy consumed
Nominal Voltage 230 V

Supply Variation ±30% Vn


• Each profile has an integration period of fifteen
Spike Voltage Tolerance 8KV minutes
Load Profile
• The profiling period extends over a range of thirty
Starting Current 5mA five days

Nominal Current 5A

Maximum Current 10A • The EM341-4 Smart G records a considerable


amount of data for extended periods of time
Nominal Frequency 50Hz Events • In addition the EM341-4 Smart G stores up to one
hundred tamper events
Frequency Variation ±5%
• Events are logged with a date/time stamp
Inherent Consumption of
<2W,<10VA
Voltage Circuit
• The EM341-4 Smart G has the ability to detect the
Inherent Consumption of following types of tamper attempts:
<0.5VA
Current Circuit
3  Terminal Open
Back-up Battery Lifetime 10 Years 3  Reverse Connection
3  Current Bypass Connection
Memory Tamper Proofing
3  Overload
3  Overvoltage
Type EEPROM
3  Undervoltage
Retention Period 40 Years 3  Parameter Change
3  Phase Sequence
Environmental Conditions

IP Rating IP54 • The meter supports two alarm methods:

Temperature Range –5°C to +60°C 3  LED Indicator


Alarms 3  Audible Alarm
Storage Temperature –25°C to +70°C
• The meter can be configured to give any
combination of alarms as required
Humidity Range 85%

Communication • With each power-up or firmware update, the


meter shall diagnose:
Standard Optical Port - IEC
Optical Interface 3  Meter and memory integrity
62056-21 Auto-diagnostics
3  Display, alarms & battery status
Upgradeable to support 3  External communication module status
AMM Module
GSM/GPRS

Upgradeable to support
Radio Frequency Link
M-Bus • The meter is fully configurable via the RFID cards
• Various data can be retrieved from the meter
Serial Communication Port RS-485 including but not limited to data relating to
consumption, remaining credit, tamper attempts
Optical Port: 2400 Kbit/s RFID Operation
• The meter can be recharged via the RFID cards
GPRS: 56–114 Kbit/s
Data Transmission Rate • Extremely secure as it includes a MIFARE CLASSIC
M-Bus: 16.384 Kbit/s
encryption/decryption module to verify and
RS-485: 2400 Kbit/s validate the authenticity of the card used

MECHANICAL SPECIFICATIONS
4 Dimensions: (L x W x D) = W
L
277.3 mm x 177.4 mm x 88.5 mm
4 Weight: Approximately 1.3Kg
4 Meter Housing: Flame Retardant Polycarbonate

You might also like