Fanuc Focas Ethernet Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 70

Fanuc Focas Ethernet Driver

© 2019 PTC Inc. All Rights Reserved.


Fanuc Focas Ethernet Driver 2

Table of Contents
Fanuc Focas Ethernet Driver 1

Table of Contents 2

Fanuc Focas Ethernet Driver 5

Overview 5

External Dependencies 5

Install a Focas Library 5

Additional Software Requirements 6

Setup 8
Channel Properties — General 8
Channel Properties — Ethernet Communications 9
Channel Properties — Write Optimizations 10
Channel Properties — Advanced 11
Device Properties — General 11
Operating Mode 12
Device Properties — Scan Mode 13
Device Properties — Timing 14
Device Properties — Auto-Demotion 15
Device Properties — Communications Parameters 15
Device Properties — Unsolicited Transfer Control 16
Device Properties — Unsolicited Data Areas 17
Device Properties — Redundancy 18
Unsolicited Messaging 18

Optimizing Communications 21

Data Types Description 22

Address Descriptions 22

Series 15i 23

Series 16i 25

Series 18i 27

Series 21i 29

Power Mate i 32

Open 34
Status Info Tags 37
Tool Offset 41
Workpiece Zero Offset 42
Parameter Read Values 43

www. ptc.com
3 Fanuc Focas Ethernet Driver

Alarm Values 44
Diagnostic Values 44
Path Values 45
Read Axis Data Values 45

Error Descriptions 46

Address Validation 46
Address <address> is out of range for the specified device or register. 46
Array size is out of range for address <address>. 46
Array support is not available for the specified address: <address>. 47
Data Type <type> is not valid for device address <address>. 47
Device address <address> contains a syntax error. 47
Device address <address> is read only. 47
Missing address. 47

Device Status Messages 48


Device <device name> is not responding. 48
Unable to write to <address> on device <device name>. 48

General Driver Messages 49


Could not acquire library handle for device <channel.device>. FWLIB error: <code>. 49
Could not read one or more vacant macros in range starting at <address> on device <device>. 49
Could not set request timeout for device <channel.device>. FWLIB error: <code>. 50
Invalid XML document. Reason: Error loading Unsolicited Data Areas for device <device-name>.
End address can not be less than start address for area <area-number>. 50
Invalid XML document. Reason: Error loading Unsolicited Data Areas for device <device-name>.
Invalid area order or duplicate area number. 50
Invalid XML document. Reason: Error loading Unsolicited Data Areas for device <device-name>.
Maximum size of area <area-number> is <size> bytes. 51
Read error occurred for address starting at <address> on device <channel.device>. FWLIB error:
<code>. 51
Unable to start the Fanuc Focas Data Window Library services. 52
Write error occurred for address <address> on device <channel.device>. FWLIB error: <code>. 52

Slave Device Driver Messages 52


Attempt to launch unsolicited message server failed. 53
Could not access necessary system resources for slave device: <channel.device>. 54
Failed to connect slave device <channel.device>. Could not acquire library handle. FWLIB error:
<code>. 54
Failed to connect slave device <channel.device>. Could not determine host IP address. 54
Failed to connect slave device <channel.device>. Could not set data area size. 55
Failed to connect slave device <channel.device>. Could not set data area start address. 55
Failed to connect slave device <channel.device>. Could not set data area type. 56

www. ptc.com
Fanuc Focas Ethernet Driver 4

Failed to connect slave device <channel.device>. Could not set host IP. 56
Failed to connect slave device <channel.device>. Could not set host port. 56
Failed to connect slave device <channel.device>. Could not set message alive time. 57
Failed to connect slave device <channel.device>. Could not set message retries. 57
Failed to connect slave device <channel.device>. Could not set message timeout. 58
Failed to connect slave device <channel.device>. Could not set messaging properties. FWLIB data
error <code>. 58
Failed to connect slave device <channel.device>. Could not set messaging properties. FWLIB
error: <code>. 59
Failed to connect slave device <channel.device>. Could not set number of data areas. 59
Failed to connect slave device <channel.device>. Could not set request timeout. FWLIB error:
<code>. 60
Failed to connect slave device <channel.device>. Could not set transmission control PMC type. 60
Failed to connect slave device <channel.device>. Could not set transmission control start address. 60
Failed to connect slave device <channel.device>. Could not start messaging session. FWLIB error:
<code>. 61
Installed version of Focas Data Window Library does not support unsolicited communication.
Device <device> deactivated. 61
Received CNC power down notification from unsolicited message server. Reconnecting slave
devices. 62
Received CNC power up notification from unsolicited message server. 62
Received socket error notification from unsolicited message server. 62
Received unsolicited message server shutdown notification. 63
Unsolicited message server does not seem to be running. Attempting to launch. 63

Focas 1 Data Window Library Error Codes 64

Index 66

www. ptc.com
5 Fanuc Focas Ethernet Driver

Fanuc Focas Ethernet Driver


Help version 1.055

CONTENTS

Overview
What is the Fanuc Focas Ethernet Driver ?

Device Setup
How do I configure a device for use with this driver?

Optimizing Fanuc Focas Ethernet Communications


How do I get the best performance from the Fanuc Focas Ethernet Driver ?

Data Types Description


What data types does this driver support?

Address Descriptions
How do I address a data location on a Fanuc Focas device?

Error Descriptions
What error messages does the Fanuc Focas Ethernet Driver produce?

Overview
The Fanuc Focas Ethernet Driver provides a reliable way to connect Fanuc Focas Ethernet controllers to OPC
Client applications, including HMI, SCADA, Historian, MES, ERP, and countless custom applications. This
driver is intended for use with Fanuc Focas Programmable Logic Controllers (PLC).

For more information on the additional software that is required for use with this driver, refer to Additional
Software Requirements.

External Dependencies
This driver has external dependencies. For this driver to communicate with the hardware, the Fanuc CNC
Focas 1 / Ethernet Library (part number A02B-0207-K732) or Fanuc Focas 2 Library (part number A02B-
0207-K737) must be installed on the system. For more information, refer to Additional Software Require-
ments.

Note: The Focas 2 Library combines both Ethernet and HSSB capabilities and can be obtained from the
FANUC distributor or by calling 1-888-326-8287. Choose CNC, PARTS, place the order, and request the part
number.

Install a Focas Library


This driver requires a Focas library to communicate with the hardware, either FANUC CNC Focas 1 / Eth-
ernet Library (part number A02B-0207-K732) or FANUC Focas 2 Library (part number A02B-0207-K737).
Only 32-bit DLL files are compatible with Fanuc Focas Ethernet Driver. Follow these steps to install a library:

www. ptc.com
Fanuc Focas Ethernet Driver 6

1. Obtain a library from the distributor (typically Fwlib*.zip).

2. Move or paste the Fwlib*.zip file to the appropriate Windows system folder:

On a 64-bit Windows OS, the destination folder is C:\Windows\SysWOW64

On a 32-bit Windows OS, the destination folder is C:\Windows\System32

3. Once the zip file is in the appropriate destination folder, unzip / extract the contents of the Fwlib*.zip.

4. Verify the 32-bit DLL files are located in the aforementioned folder.

5. Reboot the computer.

6. Run the OPC server and configure a Focas 1 project.

See Also: External Dependencies

Additional Software Requirements


Winsock
The host computer must have Winsock version 1.1 or later installed. This is normally done by default when
Windows is installed.

Focas 1 / HSSB or Focas 2 Library


This driver requires that either the FANUC CNC Focas 1 / Ethernet Library (part number A02B-0207-K732) or
FANUC Focas 2 Library (part number A02B-0207-K737) is installed on the system. Although the library does
not need to be installed to create a server project, the project will not run without it. This software may be
obtained from the FANUC distributor or by calling 1-888-326-8287.

Note: The Focas 2 Library combines both Ethernet and HSSB capabilities.

Unsolicited Message Server


This driver requires that the unsolicited message server application "UMsgServ.exe" (version 1.0.0.1 or
later) is installed to use unsolicited messaging. This application is available from the distributor. For more
information, refer to the instructions below.

1. To start the installation, copy the executable file to the System folder.

2. Access the command prompt to type "UMsgServ.exe –Install." This causes the message server to
automatically launch every time the computer is started.

3. Once the message server is running, its icon is visible in the System Tray.

4. Next, configure the TCP port number on which the message server listens (in addition to the mes-
sage timeout and the maximum number of CNCs). To do so, right-click the icon and then select Set-
ting. The default settings are as follows:

l TCP Port Number: 8196

l Message Timeout: 30 seconds

l Maximum Number of CNCs: 32

www. ptc.com
7 Fanuc Focas Ethernet Driver

5. To uninstall the message server, use the command prompt to type "UMsgServ.exe –Remove" and
then delete the executable file.

CNC Control Software


The table below displays the software that must be installed on the controller to use its unsolicited mes-
saging capabilities.

Model Software
B0F4/K1(M) or later
16i
B0H1/P5(M) or later
DDF4/K1(M) or later
18i
BDH1/P5(M) or later
BDF4/K1(M) or later
21i
DDH1/P5(M) or later

Note: Set the CNC parameter 904, bit 4 to 1 for unsolicited messaging by using the controller’s pro-
gramming software.

Fast Ethernet Firmware


Firmware 6567/E2 or later (registered onto F-ROM of CNC) must be installed on the controller to use its unso-
licited messaging capabilities.

Ladder
A ladder program must be created that constructs and controls the transmission of unsolicited messages to
use the controllers unsolicited messaging capabilities. For more information, refer to Unsolicited Mes-
saging.

www. ptc.com
Fanuc Focas Ethernet Driver 8

Setup
Supported Devices
The Fanuc Focas Ethernet Driver can communicate to controllers that are compatible with the Focas 1 or
Focas 2 CNC / PMC data window control libraries. This includes, but is not limited to, the following:

Series 0i
Series 15
Series 15i
Series 16
Series 16i
Series 18
Series 18i
Series 21
Series 21i
Series 30i
Series 31i
Series 32i
Power Mate i
Open Addressing

Maximum Number of Channels and Devices


The maximum number of supported channels is 256. The maximum number of devices supported per chan-
nel is 20.

Connect Timeout
Specify the amount of time that the driver waits for a connection to be made with a device. The connection
time depends on the network load and may vary with each connection attempt. The valid range is 1 to 60
seconds. The default setting is 3 seconds.

Request Timeout
Specify the amount of time that the driver waits on a response from the device before giving up and going
on to the next request. Longer timeouts only affect performance when a device is not responding. The valid
range is 100 to 9999 milliseconds. The default setting is 1000 milliseconds.

Retry Attempts
Specify the number of times that the driver retries a message before giving up and going on to the next mes-
sage. The valid range is 1 to 10. The default setting is 3.

Device IDs
Up to 20 devices may be defined on a given channel. Each device on the channel must be uniquely identified
by its own IP address.

Channel Properties — General


This server supports the use of simultaneous multiple communications drivers. Each protocol or driver used
in a server project is called a channel. A server project may consist of many channels with the same com-
munications driver or with unique communications drivers. A channel acts as the basic building block of an
OPC link. This group is used to specify general channel properties, such as the identification attributes and
operating mode.

www. ptc.com
9 Fanuc Focas Ethernet Driver

Identification

Name: User-defined identity of this channel. In each server project, each channel name must be unique.
Although names can be up to 256 characters, some client applications have a limited display window when
browsing the OPC server's tag space. The channel name is part of the OPC browser information. The prop-
erty is required for creating a channel.
For information on reserved characters, refer to "How To... Properly Name a Channel, Device, Tag, and Tag
Group" in the server help.

Description: User-defined information about this channel.


 Many of these properties, including Description, have an associated system tag.

Driver: Selected protocol / driver for this channel. This property specifies the device driver that was selected
during channel creation. It is a disabled setting in the channel properties. The property is required for cre-
ating a channel.
Note: With the server's online full-time operation, these properties can be changed at any time. This
includes changing the channel name to prevent clients from registering data with the server. If a client has
already acquired an item from the server before the channel name is changed, the items are unaffected. If,
after the channel name has been changed, the client application releases the item and attempts to re-
acquire using the old channel name, the item is not accepted. With this in mind, changes to the properties
should not be made once a large client application has been developed. Utilize the User Manager to prevent
operators from changing properties and restrict access rights to server features.

Diagnostics

Diagnostics Capture: When enabled, this option makes the channel's diagnostic information available to
OPC applications. Because the server's diagnostic features require a minimal amount of overhead pro-
cessing, it is recommended that they be utilized when needed and disabled when not. The default is dis-
abled.
Note: This property is not available if the driver does not support diagnostics.
For more information, refer to "Communication Diagnostics" in the server help.

Channel Properties — Ethernet Communications


Ethernet Communication can be used to communicate with devices.

Ethernet Settings

www. ptc.com
Fanuc Focas Ethernet Driver 10

Network Adapter:  Specify the network adapter to bind. When left blank or Default is selected, the oper-
ating system selects the default adapter.

Channel Properties — Write Optimizations


As with any server, writing data to the device may be the application's most important aspect. The server
intends to ensure that the data written from the client application gets to the device on time. Given this goal,
the server provides optimization properties that can be used to meet specific needs or improve application
responsiveness.

Write Optimizations

Optimization Method: Controls how write data is passed to the underlying communications driver. The
options are:

l Write All Values for All Tags:  This option forces the server to attempt to write every value to the
controller. In this mode, the server continues to gather write requests and add them to the server's
internal write queue. The server processes the write queue and attempts to empty it by writing data
to the device as quickly as possible. This mode ensures that everything written from the client applic-
ations is sent to the target device. This mode should be selected if the write operation order or the
write item's content must uniquely be seen at the target device.
l Write Only Latest Value for Non-Boolean Tags: Many consecutive writes to the same value can
accumulate in the write queue due to the time required to actually send the data to the device. If the
server updates a write value that has already been placed in the write queue, far fewer writes are
needed to reach the same final output value. In this way, no extra writes accumulate in the server's
queue. When the user stops moving the slide switch, the value in the device is at the correct value at
virtually the same time. As the mode states, any value that is not a Boolean value is updated in the
server's internal write queue and sent to the device at the next possible opportunity. This can greatly
improve the application performance.
Note: This option does not attempt to optimize writes to Boolean values. It allows users to optimize
the operation of HMI data without causing problems with Boolean operations, such as a momentary
push button.
l Write Only Latest Value for All Tags:  This option takes the theory behind the second optimization
mode and applies it to all tags. It is especially useful if the application only needs to send the latest
value to the device. This mode optimizes all writes by updating the tags currently in the write queue
before they are sent. This is the default mode.

Duty Cycle: is used to control the ratio of write to read operations. The ratio is always based on one read for
every one to ten writes. The duty cycle is set to ten by default, meaning that ten writes occur for each read
operation. Although the application is performing a large number of continuous writes, it must be ensured
that read data is still given time to process. A setting of one results in one read operation for every write
operation. If there are no write operations to perform, reads are processed continuously. This allows optim-
ization for applications with continuous writes versus a more balanced back and forth data flow.
Note: It is recommended that the application be characterized for compatibility with the write optimization
enhancements before being used in a production environment.

www. ptc.com
11 Fanuc Focas Ethernet Driver

Channel Properties — Advanced


This group is used to specify advanced channel properties. Not all drivers support all properties; so the
Advanced group does not appear for those devices.

Non-Normalized Float Handling: A non-normalized value is defined as Infinity, Not-a-Number (NaN), or as


a Denormalized Number. The default is Replace with Zero. Drivers that have native float handling may
default to Unmodified. Non-normalized float handling allows users to specify how a driver handles non-nor-
malized IEEE-754 floating point data. Descriptions of the options are as follows:

l Replace with Zero:  This option allows a driver to replace non-normalized IEEE-754 floating point val-
ues with zero before being transferred to clients.
l Unmodified:  This option allows a driver to transfer IEEE-754 denormalized, normalized, non-num-
ber, and infinity values to clients without any conversion or changes.

Note: This property is not available if the driver does not support floating point values or if it only supports
the option that is displayed. According to the channel's float normalization setting, only real-time driver tags
(such as values and arrays) are subject to float normalization. For example, EFM data is not affected by this
setting.

For more information on the floating point values, refer to "How To ... Work with Non-Normalized Floating
Point Values" in the server help.

Inter-Device Delay: Specify the amount of time the communications channel waits to send new requests to
the next device after data is received from the current device on the same channel. Zero (0) disables the
delay.

Note: This property is not available for all drivers, models, and dependent settings.

Device Properties — General


A device represents a single target on a communications channel. If the driver supports multiple controllers,
users must enter a device ID for each controller.

Identification

www. ptc.com
Fanuc Focas Ethernet Driver 12

Name:  This property specifies the name of the device. It is a logical user-defined name that can be up to
256 characters long, and may be used on multiple channels.

Note: Although descriptive names are generally a good idea, some OPC client applications may have a
limited display window when browsing the OPC server's tag space. The device name and channel name
become part of the browse tree information as well. Within an OPC client, the combination of channel name
and device name would appear as "ChannelName.DeviceName".
For more information, refer to "How To... Properly Name a Channel, Device, Tag, and Tag Group" in server
help.

Description: User-defined information about this device.


Many of these properties, including Description, have an associated system tag.

Channel Assignment: User-defined name of the channel to which this device currently belongs.

Driver: Selected protocol driver for this device.

Model:  This property specifies the specific type of device that is associated with this ID. The contents of the
drop-down menu depends on the type of communications driver being used. Models that are not supported
by a driver are disabled. If the communications driver supports multiple device models, the model selection
can only be changed when there are no client applications connected to the device.
Note: If the communication driver supports multiple models, users should try to match the model selec-
tion to the physical device. If the device is not represented in the drop-down menu, select a model that con-
forms closest to the target device. Some drivers support a model selection called "Open," which allows users
to communicate without knowing the specific details of the target device. For more information, refer to the
driver help documentation.

ID:  This property specifies the device's driver-specific station or node. The type of ID entered depends on
the communications driver being used. For many communication drivers, the ID is a numeric value. Drivers
that support a Numeric ID provide users with the option to enter a numeric value whose format can be
changed to suit the needs of the application or the characteristics of the selected communications driver.
The format is set by the driver by default. Options include Decimal, Octal, and Hexadecimal.
Note: If the driver is Ethernet-based or supports an unconventional station or node name, the device's
TCP/IP address may be used as the device ID. TCP/IP addresses consist of four values that are separated by
periods, with each value in the range of 0 to 255. Some device IDs are string based. There may be additional
properties to configure within the ID field, depending on the driver. For more information, refer to the driver's
help documentation.

Operating Mode

Data Collection:  This property controls the device's active state. Although device communications are
enabled by default, this property can be used to disable a physical device. Communications are not attemp-
ted when a device is disabled. From a client standpoint, the data is marked as invalid and write operations
are not accepted. This property can be changed at any time through this property or the device system tags.

www. ptc.com
13 Fanuc Focas Ethernet Driver

Simulated:  This option places the device into Simulation Mode. In this mode, the driver does not attempt to
communicate with the physical device, but the server continues to return valid OPC data. Simulated stops
physical communications with the device, but allows OPC data to be returned to the OPC client as valid data.
While in Simulation Mode, the server treats all device data as reflective: whatever is written to the simulated
device is read back and each OPC item is treated individually. The item's memory map is based on the group
Update Rate. The data is not saved if the server removes the item (such as when the server is reinitialized).
The default is No.
Notes:

1. This System tag (_Simulated) is read only and cannot be written to for runtime protection. The System
tag allows this property to be monitored from the client.

2. In Simulation mode, the item's memory map is based on client update rate(s) (Group Update Rate for
OPC clients or Scan Rate for native and DDE interfaces). This means that two clients that reference
the same item with different update rates return different data.

 Simulation Mode is for test and simulation purposes only. It should never be used in a production envir-
onment.

Device Properties — Scan Mode


The Scan Mode specifies the subscribed-client requested scan rate for tags that require device com-
munications. Synchronous and asynchronous device reads and writes are processed as soon as possible;
unaffected by the Scan Mode properties.

Scan Mode: Specifies how tags in the device are scanned for updates sent to subscribing clients. Descrip-
tions of the options are:

l Respect Client-Specified Scan Rate:  This mode uses the scan rate requested by the client.
l Request Data No Faster than Scan Rate:  This mode specifies the value set as the maximum scan
rate. The valid range is 10 to 99999990 milliseconds. The default is 1000 milliseconds.
Note: When the server has an active client and items for the device and the scan rate value is
increased, the changes take effect immediately. When the scan rate value is decreased, the changes
do not take effect until all client applications have been disconnected.
l Request All Data at Scan Rate:  This mode forces tags to be scanned at the specified rate for sub-
scribed clients. The valid range is 10 to 99999990 milliseconds. The default is 1000 milliseconds.
l Do Not Scan, Demand Poll Only:  This mode does not periodically poll tags that belong to the
device nor perform a read to get an item's initial value once it becomes active. It is the client's
responsibility to poll for updates, either by writing to the _DemandPoll tag or by issuing explicit device
reads for individual items. For more information, refer to "Device Demand Poll" in server help.
l Respect Tag-Specified Scan Rate:  This mode forces static tags to be scanned at the rate specified
in their static configuration tag properties. Dynamic tags are scanned at the client-specified scan
rate.

Initial Updates from Cache: When enabled, this option allows the server to provide the first updates for
newly activated tag references from stored (cached) data. Cache updates can only be provided when the
new item reference shares the same address, scan rate, data type, client access, and scaling properties. A

www. ptc.com
Fanuc Focas Ethernet Driver 14

device read is used for the initial update for the first client reference only. The default is disabled; any time a
client activates a tag reference the server attempts to read the initial value from the device.

Device Properties — Timing


The device Timing properties allow the driver's response to error conditions to be tailored to fit the applic-
ation's needs. In many cases, the environment requires changes to these properties for optimum per-
formance. Factors such as electrically generated noise, modem delays, and poor physical connections can
influence how many errors or timeouts a communications driver encounters. Timing properties are specific
to each configured device.

Communications Timeouts
Connect Timeout:  This property (which is used primarily by Ethernet based drivers) controls the amount of
time required to establish a socket connection to a remote device. The device's connection time often takes
longer than normal communications requests to that same device. The valid range is 1 to 30 seconds. The
default is typically 3 seconds, but can vary depending on the driver's specific nature. If this setting is not sup-
ported by the driver, it is disabled.
Note: Due to the nature of UDP connections, the connection timeout setting is not applicable when com-
municating via UDP.

Request Timeout:  This property specifies an interval used by all drivers to determine how long the driver
waits for a response from the target device to complete. The valid range is 50 to 9,999,999 milliseconds
(167.6667 minutes). The default is usually 1000 milliseconds, but can vary depending on the driver. The
default timeout for most serial drivers is based on a baud rate of 9600 baud or better. When using a driver
at lower baud rates, increase the timeout to compensate for the increased time required to acquire data.

Attempts Before Timeout:  This property specifies how many times the driver issues a communications
request before considering the request to have failed and the device to be in error. The valid range is 1 to
10. The default is typically 3, but can vary depending on the driver's specific nature. The number of attempts
configured for an application depends largely on the communications environment. This property applies to
both connection attempts and request attempts.

Timing

Inter-Request Delay:  This property specifies how long the driver waits before sending the next request to
the target device. It overrides the normal polling frequency of tags associated with the device, as well as
one-time reads and writes. This delay can be useful when dealing with devices with slow turnaround times
and in cases where network load is a concern. Configuring a delay for a device affects communications with
all other devices on the channel. It is recommended that users separate any device that requires an inter-
request delay to a separate channel if possible. Other communications properties (such as communication
serialization) can extend this delay. The valid range is 0 to 300,000 milliseconds; however, some drivers may
limit the maximum value due to a function of their particular design. The default is 0, which indicates no
delay between requests with the target device.
Note: Not all drivers support Inter-Request Delay. This setting does not appear if it is not available.

www. ptc.com
15 Fanuc Focas Ethernet Driver

Device Properties — Auto-Demotion


The Auto-Demotion properties can temporarily place a device off-scan in the event that a device is not
responding. By placing a non-responsive device offline for a specific time period, the driver can continue to
optimize its communications with other devices on the same channel. After the time period has been
reached, the driver re-attempts to communicate with the non-responsive device. If the device is responsive,
the device is placed on-scan; otherwise, it restarts its off-scan time period.

Demote on Failure: When enabled, the device is automatically taken off-scan until it is responding again.
Tip: Determine when a device is off-scan by monitoring its demoted state using the _AutoDemoted sys-
tem tag.

Timeouts to Demote: Specify how many successive cycles of request timeouts and retries occur before the
device is placed off-scan. The valid range is 1 to 30 successive failures. The default is 3.

Demotion Period: Indicate how long the device should be placed off-scan when the timeouts value is
reached. During this period, no read requests are sent to the device and all data associated with the read
requests are set to bad quality. When this period expires, the driver places the device on-scan and allows for
another attempt at communications. The valid range is 100 to 3600000 milliseconds. The default is 10000
milliseconds.

Discard Requests when Demoted: Select whether or not write requests should be attempted during the
off-scan period. Disable to always send write requests regardless of the demotion period. Enable to discard
writes; the server automatically fails any write request received from a client and does not post a message
to the Event Log.

Device Properties — Communications Parameters

TCP/IP Port: Specify the TCP/IP port number that the remote device is configured to use. The default setting
is 8193.

Maximum Request Size: Specify the number of bytes that may be requested from a device at one time. To
refine the driver's performance, configure the request size to one of the following settings: 8, 16, 32, 64, 128,
256, or 512 bytes. The default setting is 256 bytes.

www. ptc.com
Fanuc Focas Ethernet Driver 16

Device Properties — Unsolicited Transfer Control

Slave Device: This option should be enabled if the device receives unsolicited data from the CNC. All tags
belonging to a slave device read data cached in the driver, not directly from the CNC. The slave device's tags
displays a value of zero until it receives its first unsolicited data update. When disabled, all tags belonging to
the device read and write directly to the CNC. The default setting is disabled.

Unsolicited Message Server Port: Specify the port that the unsolicited message server application has
been configured to use. The default setting is 8196.

Transfer Control Memory Type: Specify the registers' PMC memory type for unsolicited message transfer
control. Options include R (internal relay) and E (extended relay). The default setting is R.

Transfer Control Start Address: Specify the start address of the registers used for unsolicited message
transfer control. The valid range is 0 to 7999, although the actual range of valid addresses depends on the
hardware. The default setting is 0.

Message Retries: Specify the number of times that the CNC should retry sending unsolicited messages. The
valid range is 0 to 10. The default setting is 3.

Message Timeout: Specify the unsolicited message timeout, which is the amount of time that the CNC waits
for the driver to respond to an unsolicited message. The valid range is 0 to 30. The default setting is 10
seconds.

Message Alive Time: Specify the unsolicited message alive time, which is the amount of time that the CNC
retains an unsolicited message for the driver to read. This setting must be less than the message timeout.
The valid range is 0 to 30. The default setting is 5 seconds.

See Also: Unsolicited Messaging

www. ptc.com
17 Fanuc Focas Ethernet Driver

Device Properties — Unsolicited Data Areas


Users can configure up to three areas in PMC memory for unsolicited messaging. These areas' data content
is sent to the driver in each unsolicited message. As such, these areas should be made as small as possible.

Data Area n

Note: All tags that are created for a slave device are validated according to the configured data areas. For
example, if a slave device is configured with a single area with D1000 to D1100, then a tag with address
D1000 would be valid, but tags with addresses D1101 or C0001 would be invalid. All tags belonging to a
slave device are Read Only.

l Data Area n: When enabled, this data area is in use.


l PMC Address Type: Specify the area's PMC address type. The default setting is D. Supported types
include the following:

l G: Signal to PMC->CNC
l F: Signal to CNC->PMC
l Y: Signal to PMC->machine
l X: Signal to machine->PMC
l A: Message demand
l R: Internal relay
l T: Changeable timer
l K: Keep relay
l C: Counter
l D: Data table
l Start Address: Specify an area's start address. The valid range is 0 and 7999, although the actual
range of valid addresses depends on the hardware. The default setting is 0.
l End Address: Specify an area's end address. The valid range is 0 and 7999, although the actual
range of valid addresses depends on the hardware. The total number of bytes must not exceed 1430,
1414, or 1398 for areas 1, 2, or 3 respectively. The default value is 0.

See Also: Unsolicited Messaging

www. ptc.com
Fanuc Focas Ethernet Driver 18

Device Properties — Redundancy

Redundancy is available with the Media-Level Redundancy Plug-In.


Consult the website, a sales representative, or the user manual for more information.

Unsolicited Messaging
Before configuring a system for unsolicited messaging, it is important that users understand how the vari-
ous hardware and software components work together to transfer data. These components include one or
more CNC controllers equipped with Fast Ethernet communications boards, firmware that supports unso-
licited messaging, and a ladder program. To receive unsolicited data, a host computer must be equipped
with the OPC server, its Fanuc Focas Ethernet Driver , the Focas 1 Data Window Library software, and the
Unsolicited Message Server. Data can be read from the OPC server with OPC or DDE client applications run-
ning on the host or remote computer. For more information, refer to Additional Software Requirements.

During an unsolicited messaging session, the controller is only in direct communication with the Unsolicited
Message Server. The message server notifies the driver when the controller makes a request to send unso-
licited data. The Focas 1 Data Window Library allows the driver to receive the unsolicited data via the mes-
sage server, and also enables direct communications with the controllers for starting and ending unsolicited
messaging sessions.

Note: If unsolicited messaging is not used, the driver uses the library to issue read and write requests dir-
ectly to the controller. It is possible to simultaneously use both types of communication with a controller by
creating a slave and a non-slave device in the OPC server project.

Unsolicited Data Transmission


Ladder programs coordinate the transfer of unsolicited data from their respective controllers, and must be
tailored to each application. For more information on unsolicited data transmission, refer to the instructions
below.

1. To start, the ladder program places the message contents in a designated area of the PMC memory.
Once the message is prepared, the ladder controls the data transmission by setting and monitoring
bits in the Unsolicited Transfer Control area of PMC memory.

2. To trigger the unsolicited message transmission, the ladder sets the "REQ" (request to send) transfer
control bit. The controller sends an "Unsolicited data ready" notification to the message server imme-
diately after.

3. The message server relays the notification to the driver, which then responds by issuing a "Read
unsolicited message" command to the message server.

4. The driver receives the unsolicited message data in response to this command, and then replies to
the data ready notification with a response code indicating success or failure. The message server
then passes this response code to the controller.

www. ptc.com
19 Fanuc Focas Ethernet Driver

5. When the controller receives the response code, it copies it to the "RES_CODE" memory area. The
controller sets the "RES" (response ready) bit to indicate that the transaction completed immediately
after.

Note: The ladder program must be designed to detect when the RES bit has been set. Once it
detects that the RES bit has been set, it can read the response code and react as needed. If the data
fails to reach the driver, the controller will place its own response code that describes the problem in
RES_CODE and set the RES bit.

6. Once the ladder has read the response code, it must clear the REQ bit to ready the system for the
next message.

PMC Memory
The PMC memory area included in unsolicited messages is defined with the Fanuc Focas Ethernet Driver .
The driver transfers these area properties to the controller at the start of an unsolicited messaging session.
Data from the range of all areas is included each time an unsolicited message is sent. As such, these areas
should be made as small as possible. The ladder program must be written to use the exact address ranges
specified in the driver configuration.

Unsolicited data transmission is coordinated between the ladder program and communications board via 2
bytes of PMC R or E memory. This transfer control area is defined with the Fanuc Focas Ethernet Driver . The
transfer control area properties are then sent to the controller along with the data area properties when an
unsolicited messaging session starts. The ladder program must be written to use the specific addresses spe-
cified in the driver configuration. The various bits in the transfer control area, with starting address xxxx,
have the following locations and meanings:

REQ
Rxxxx.7 (or Exxxx.7)
After the ladder program constructs a message, it must set this bit to 1. This signals the communications
board to issue a notification that a new message is ready to be read.

COM
Rxxxx+1.6 (or Exxxx+1.6)
The communications board sets this bit to 1 when message transmission begins. The communications board
sets this bit back to 0 immediately before it sets RES to 1, and places the response code in RES_CODE.

RES
Rxxxx+1.7 (or Exxxx+1.7)
The communications board sets this bit to 1 immediately after message transmission completes. When the
ladder program detects that this bit is set to 1, it can read the response code from RES_CODE. The ladder
then acts depending on the value of RES_CODE. Once this is done, the ladder must set REQ back to 0. This
causes the communications board to clear RES_CODE and set the bit back to 0. Then the communications
board is ready to perform the next unsolicited transaction.

RES_CODE

www. ptc.com
Fanuc Focas Ethernet Driver 20

Rxxxx+1.0 to Rxxxx+1.5 (or Exxxx+1.0 to Exxxx+1.5)


The result of the unsolicited transaction is placed here. It can be a code passed down from the driver, or a
code set by the communications board if there was a communications failure. The possible values are dis-
played in the table below.

RES_ Meaning
CODE
Success. The communications board did not detect any failures in communication, and the driver
0x00
reported that it processed the received data successfully.
The transmission control properties are invalid or the unsolicited messaging session was not
0x01
started.
0x02 The unsolicited message server is not running.
0x03 The CNC failed to transmit message.
0x04 The CNC failed to receive response.
0x05 The transmission retry count was exceeded.
0x06 The CNC failed to construct the message data.
0x07 The CNC received an invalid packet.
0x08 The CNC accepted termination of unsolicited messaging session.
0x10 The driver experienced a Focas 1 Library error while reading message.
The driver found the message data to be invalid or experienced other problems while processing
0x11
message data.
The PC application to receive the message does not exist, though the message was received by
0x21
the PC. Either the OPC server or this driver is not running.
The PC application to receive the message was not recognized by the unsolicited message
server, though the message was received by the PC. The unsolicited message server may need
0x22
be restarted, or there may have been a problem when the driver was starting the unsolicited
messaging session.
0x23 The CNC failed in writing the received message to the PC.
0x24 The timeout period and retry count have expired.
0x25 Illegal data was included in the received message.

The Fanuc Focas Ethernet Driver stores unsolicited data in a memory cache. The OPC server makes this
data visible to client applications via tags, whose addresses must be the same as the controller's data
source. For example, if an unsolicited data area is configured to include the byte at D1000, then a tag with an
address of D1000 must be used to view the data. These tags show the last values sent to the driver, which
may not necessarily be the current values in the controller. To poll current values directly from the con-
troller, users would need additional tags belonging to a non-slave device. Slave device tags display a value of
zero until the driver receives its first unsolicited data update from the controller.

Notes:

1. In addition to data ready notifications, the Unsolicited Message Server also apprises the driver of
other important events. These include CNC power up, CNC power down, Unsolicited Message Server
shutdown, and communications error notifications. The driver responds to each of these events in
such a way that communication with the hardware is maintained, if possible.

www. ptc.com
21 Fanuc Focas Ethernet Driver

2. The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or
restarts the session after detecting a communications problem. Tags that belong to a slave device in
an error state will continue to display the last value received from the device or the initial value of
zero.

Optimizing Communications
The Fanuc Focas Ethernet Driver has been designed to provide the best performance with the least amount
of impact on the system's overall performance. While the driver is fast, there are a couple of guidelines that
can be used to control and optimize the application and gain maximum performance.

This server refers to communications protocols like Fanuc Focas Ethernet as a channel. Each channel
defined in the application represents a separate path of execution in the server. Once a channel has been
defined, a series of devices must then be defined under that channel. Each of these devices represents a
single Fanuc Focas controller from which data iscollected. While this approach to defining the application
provides a high level of performance, it won't take full advantage of the Fanuc Focas Ethernet Driver or the
network. An example of how the application may appear when configured using a single channel is shown
below.

Each device appears under a single channel. In this configuration, the driver must
move from one device to the next as quickly as possible to gather information at an
effective rate. As more devices are added or more information is requested from a
single device, the overall update rate begins to suffer.

If the Fanuc Focas Ethernet Driver could only define one single channel, then the example shown above
would be the only option available; however, the driver can define up to 256 channels. Using multiple chan-
nels distributes the data collection workload by simultaneously issuing multiple requests to the network. An
example of how the same application may appear when configured using multiple channels to improve per-
formance is shown below.

Each device has now been defined under its own channel. In this new configuration,
a single path of execution is dedicated to the task of gathering data from each
device. If the application has 256 or fewer devices, it can be optimized exactly how
it is shown here.
There is performance improvement even if the application has more than 256
devices. While 256 or fewer devices may be ideal, the application still benefits from
additional channels. Although spreading the device load across all channels causes
the server to move from device to device again, it can now do so with far less
devices to process on a single channel.

Request Size can also affect the Fanuc Focas Ethernet Driver performance. The request size refers to the
number of bytes that may be requested from a device at one time, and is available on every defined device.
To refine the driver's performance, configure the request size to one of the following settings: 8, 16, 32, 64,
128, 256, or 512 bytes. Depending on the model of the device being used, the setting chosen for request size
can dramatically affect the application. The default value of 256 bytes is recommended. If the application

www. ptc.com
Fanuc Focas Ethernet Driver 22

consists of large requests for consecutively ordered data, try increasing the request size setting for the
device. For more information, refer to Setup.

Data Types Description

Data Type Description


Boolean Single bit
Unsigned 8-bit value
Byte
bit 0 is the low bit
bit 7 is the high bit
Unsigned 16-bit value

Word
bit 0 is the low bit
bit 15 is the high bit
Signed 16-bit value

Short bit 0 is the low bit


bit 14 is the high bit
bit 15 is the sign bit
Unsigned 32-bit value

DWord
bit 0 is the low bit
bit 31 is the high bit
Signed 32-bit value

Long bit 0 is the low bit


bit 30 is the high bit
bit 31 is the sign bit
Float 32-bit floating point value
String Null terminated ASCII string

Address Descriptions
Address specifications may vary depending on the model in use. Select a link from the following list to obtain
specific address information for the model of interest.

Note: If the model of interest is listed as supported but is not selectable, use the Open model.

Series 15i
Series 16i
Series 18i
Series 21i
Power Mate i
Open

www. ptc.com
23 Fanuc Focas Ethernet Driver

Series 15i
The following addresses are supported for this model. Not all address ranges may be valid for the particular
device being used. For more information, refer to the specific device's documentation. To jump to a specific
section, select a link from the list below.

CNC Data
Arrays
Strings

PMC Data
The default data types for dynamically defined DDE tags are shown in bold.

Address Type Range Data Type Access


A00000-A00124 Byte, Char
A00000-A00123 Word, Short
A (Message demand) Read/Write
A00000-A00121 DWord, Long, Float
Axxxxx.0-Axxxxx.7 Boolean
C00000-C00199 Byte, Char
C00000-C00198 Word, Short
C (Counter) Read/Write
C00000-C00196 DWord, Long, Float
Cxxxxx.0-Cxxxxx.7 Boolean
D00000-D09999 Byte, Char
D00000-D09998 Word, Short
D (Data table) Read/Write
D00000-D09996 DWord, Long, Float
Dxxxxx.0-Dxxxxx.7 Boolean
F00000-F00511 Byte, Char
F (Signal to CNC->PMC) F00000-F00510 Word, Short
Read Only
F00000-F00508 DWord, Long, Float
Fxxxxx.0-Fxxxxx.7 Boolean
G00000-G00511 Byte, Char
G00000-G00510 Word, Short
G (Signal to PMC->CNC) Read/Write
G00000-G00508 DWord, Long, Float
Gxxxxx.0-Gxxxxx.7 Boolean
K00000-K00909 Byte, Char
K00000-K00908 Word, Short Read/Write
K (Keep relay)
K00000-K00906 DWord, Long, Float
Kxxxxx.0-Kxxxxx.7 Boolean
R00000-R09199 Byte, Char
R00000-R09198 Word, Short
R (Internal relay) Read/Write
R00000-R09196 DWord, Long, Float
Rxxxxx.0-Rxxxxx.7 Boolean
T00000-T00299 Byte, Char
T00000-T00298 Word, Short
T (Changeable timer) Read/Write
T00000-T00296 DWord, Long, Float
Txxxxx.0-Txxxxx.7 Boolean
X00000-X00127 Byte, Char
X (Signal to machine->PMC) Read Only
X00000-X00126 Word, Short

www. ptc.com
Fanuc Focas Ethernet Driver 24

Address Type Range Data Type Access


X00000-X00124 DWord, Long, Float
Xxxxxx.0-Xxxxxx.7 Boolean
Y00000-Y00127 Byte, Char
Y00000-Y00126 Word, Short
Y (Signal to PMC->machine) Read/Write
Y00000-Y00124 DWord, Long, Float
Yxxxxx.0-Yxxxxx.7 Boolean
Custom Macro Value (common range) #0100-#0999 Float, Double Read/Write
Custom Macro Value (local range) #0001-#0033 Float, Double Read Only
Custom Macro Value (system range) #1000-#9999 Float, Double Read/Write

CNC Data
Status Info Tags
Tool Offset
Workpiece Zero Offset
Parameter Read Values
Alarms Values
Diagnostic Values
Path Value
Read Axis Data Values

Arrays
Arrays are supported for all PMC addresses, except for Custom Macros in the system range and where
Boolean or string data types are used. Tool Offset data cannot be addressed as an array. The syntax for
declaring an array is as follows:

Mxxxx[cols] with assumed row count of 1.


Mxxxxx[rows][cols] where M is the address type and xxxxx is the byte offset of the first element in the array.

Note: For all arrays, the total number of bytes being requested cannot exceed the specified request size.

Strings
All address types can be read and written to as ASCII strings. Each byte of memory contains one ASCII char-
acter. The length of strings can range from 1 to 120 and is entered in place of the bit number. An additional
character "M" is appended to the address to distinguish string addresses from bit addresses.

Example
To address a string of length 100 characters, starting at D00200, enter: D00200.100 M.

Note: Use caution when modifying Word, Short, DWord, Long, and Float types. Since all addresses start at
a byte offset within the device, it is possible for the memory associated with tags to overlap. For example,
word tags D00000 and D00001 overlap at byte 1. Writing to D00000 also modifies the value held in D00001.
It is recommended that these memory types be used such that each value to be read and written to by the
driver occupy a unique range of memory in the device. For example, map 3 Word values to bytes D00000-
D00001, D00002-D00003, and D00004-D00005. Tags to access these values would then have addresses
D00000, D00002, and D00004 respectively, and a data type of Word.

www. ptc.com
25 Fanuc Focas Ethernet Driver

Series 16i
The following addresses are supported for this model. Not all address ranges may be valid for the particular
device being used. For more information, refer to the specific device's documentation. To jump to a specific
section, select a link from the list below.

CNC Data
Arrays
Strings
Unsolicited Data

PMC Data
The default data types for dynamically defined DDE tags are shown in bold.

Address Type Range Data Type Access


A00000-A00124 Byte, Char
A00000-A00123 Word, Short
A (Message demand) Read/Write
A00000-A00121 DWord, Long, Float
Axxxxx.0-Axxxxx.7 Boolean
C00000-C00199 Byte, Char
C00000-C00198 Word, Short
C (Counter) Read/Write
C00000-C00196 DWord, Long, Float
Cxxxxx.0-Cxxxxx.7 Boolean
D00000-D09999 Byte, Char
D00000-D09998 Word, Short
D (Data table) Read/Write
D00000-D09996 DWord, Long, Float
Dxxxxx.0-Dxxxxx.7 Boolean
E00000-E07999 Byte, Char
E00000-E07998 Word, Short
E (Extended relay) Read/Write
E00000-E07996 DWord, Long, Float
Exxxxx.0-Exxxxx.7 Boolean
F00000-F02511 Byte, Char
F00000-F02510 Word, Short
F (Signal to CNC->PMC) Read Only
F00000-F02508 DWord, Long, Float
Fxxxxx.0-Fxxxxx.7 Boolean
G00000-G02511 Byte, Char
G00000-G02510 Word, Short
G (Signal to PMC->CNC) Read/Write
G00000-G02508 DWord, Long, Float
Gxxxxx.0-Gxxxxx.7 Boolean
K00000-K00909 Byte, Char
K00000-K00908 Word, Short
K (Keep relay) Read/Write
K00000-K00906 DWord, Long, Float
Kxxxxx.0-Kxxxxx.7 Boolean
M00000-M00511 Byte, Char
M00000-M00510 Word, Short
M (Input signal from other devices) Read Only
M00000-M00508 DWord, Long, Float
Mxxxxx.0-Mxxxxx.7 Boolean
N (Output signal from other devices) N00000-N00511 Byte, Char Read/Write

www. ptc.com
Fanuc Focas Ethernet Driver 26

Address Type Range Data Type Access


N00000-N00510 Word, Short
N00000-N00508 DWord, Long, Float
Nxxxxx.0-Nxxxxx.7 Boolean
R00000-R09119 Byte, Char
R00000-R09118 Word, Short
R (Internal relay) Read/Write
R00000-R09116 DWord, Long, Float
Rxxxxx.0-Rxxxxx.7 Boolean
T00000-T00299 Byte, Char
T00000-T00298 Word, Short
T (Changeable timer) Read/Write
T00000-T00296 DWord, Long, Float
Txxxxx.0-Txxxxx.7 Boolean
X00000-X00127 Byte, Char
X00000-X00126 Word, Short
X (Signal to machine->PMC) Read Only
X00000-X00124 DWord, Long, Float
Xxxxxx.0-Xxxxxx.7 Boolean
Y00000-Y00127 Byte, Char
Y00000-Y00126 Word, Short
Y (Signal to PMC->machine) Read/Write
Y00000-Y00124 DWord, Long, Float
Yxxxxx.0-Yxxxxx.7 Boolean
Custom Macro Value (common range) #0100-#0999 Float, Double Read/Write
Custom Macro Value (local range) #0001-#0033 Float, Double Read Only
Custom Macro Value (system range) #1000-#9999 Float, Double Read/Write

CNC Data
Status Info Tags
Tool Offset
Workpiece Zero Offset
Parameter Read Values
Alarms Values
Diagnostic Values
Path Value
Read Axis Data Values

Arrays
Arrays are supported for all PMC addresses, except for Custom Macros in the system range and where
Boolean or string data types are used. Tool Offset data cannot be addressed as an array. The syntax for
declaring an array is as follows:

Mxxxxx[cols] with assumed row count of 1.


Mxxxxx[rows][cols] where M is the address type and xxxxx is the byte offset of the first element in the array.

Note: For all arrays, the total number of bytes being requested cannot exceed the specified request size.

Strings

www. ptc.com
27 Fanuc Focas Ethernet Driver

All address types can be read and written to as ASCII strings. Each byte of memory contains one ASCII char-
acter. The length of strings can range from 1 to 120 and is entered in place of the bit number. An additional
character "M" is appended to the address to distinguish string addresses from bit addresses.

Example
To address a string of length 100 characters, starting at D00200, enter D00200.100 M.

Unsolicited Data
If tags belong to a slave device, then their address types and ranges are validated according to the data
areas configured for that device) For example, if the slave device is configured with a single area with
D01000 to D01100, then a tag with address D01000 would be valid, but tags with addresses D01101 or
C00001 would be invalid. All tags belonging to a slave device are Read Only.

See Also: Unsolicited Data Areas

Note: Use caution when modifying Word, Short, DWord, Long, and Float types. Since all addresses start at
a byte offset within the device, it is possible for the memory associated with tags to overlap. For example,
word tags D00000 and D00001 overlap at byte 1. Writing to D00000 also modifies the value held in D00001.
It is recommended that these memory types be used such that each value to be read and written to by the
driver occupy a unique range of memory in the device. For example, map 3 Word values to bytes D00000-
D00001, D00002-D00003, and D00004-D00005. Tags to access these values would then have addresses
D00000, D00002, and D00004 respectively, and a data type of Word.

Series 18i
The following addresses are supported for this model. Not all address ranges may be valid for the particular
device being used. For more information, refer to the specific device's documentation. To jump to a specific
section, select a link from the list below.

CNC Data
Arrays
Strings
Unsolicited Data

PMC Data
The default data types for dynamically defined DDE tags are shown in bold.

Address Type Range Data Type Access


A00000-A00124 Byte, Char
A00000-A00123 Word, Short
A (Message demand) Read/Write
A00000-A00121 DWord, Long, Float
Axxxxx.0-Axxxxx.7 Boolean
C00000-C00199 Byte, Char
C00000-C00198 Word, Short
C (Counter) Read/Write
C00000-C00196 DWord, Long, Float
Cxxxxx.0-Cxxxxx.7 Boolean
D00000-D09999 Byte, Char
D00000-D09998 Word, Short
D (Data table) Read/Write
D00000-D09996 DWord, Long, Float
Dxxxxx.0-Dxxxxx.7 Boolean

www. ptc.com
Fanuc Focas Ethernet Driver 28

Address Type Range Data Type Access


E00000-E07999 Byte, Char
E00000-E07998 Word, Short
E (Extended relay) Read/Write
E00000-E07996 DWord, Long, Float
Exxxxx.0-Exxxxx.7 Boolean
F00000-F02511 Byte, Char
F00000-F02510 Word, Short
F (Signal to CNC->PMC) Read Only
F00000-F02508 DWord, Long, Float
Fxxxxx.0-Fxxxxx.7 Boolean
G00000-G02511 Byte, Char
G00000-G02510 Word, Short
G (Signal to PMC->CNC) Read/Write
G00000-G02508 DWord, Long, Float
Gxxxxx.0-Gxxxxx.7 Boolean
K00000-K00909 Byte, Char
K00000-K00908 Word, Short
K (Keep relay) Read/Write
K00000-K00906 DWord, Long, Float
Kxxxxx.0-Kxxxxx.7 Boolean
M00000-M00511 Byte, Char
M00000-M00510 Word, Short
M (Input signal from other devices) Read Only
M00000-M00508 DWord, Long, Float
Mxxxxx.0-Mxxxxx.7 Boolean
N00000-N00511 Byte, Char
N00000-N00510 Word, Short
N (Output signal from other devices) Read/Write
N00000-N00508 DWord, Long, Float
Nxxxxx.0-Nxxxxx.7 Boolean
R00000-R09119 Byte, Char
R00000-R09118 Word, Short
R (Internal relay) Read/Write
R00000-R09116 DWord, Long, Float
Rxxxxx.0-Rxxxxx.7 Boolean
T00000-T00299 Byte, Char
T00000-T00298 Word, Short
T (Changeable timer) Read/Write
T00000-T00296 DWord, Long, Float
Txxxxx.0-Txxxxx.7 Boolean
X00000-X00127 Byte, Char
X00000-X00126 Word, Short
X (Signal to machine->PMC) Read Only
X00000-X00124 DWord, Long, Float
Xxxxxx.0-Xxxxxx.7 Boolean
Y00000-Y00127 Byte, Char
Y00000-Y00126 Word, Short
Y (Signal to PMC->machine) Read/Write
Y00000-Y00124 DWord, Long, Float
Yxxxxx.0-Yxxxxx.7 Boolean
Custom Macro Value (common range) #0100-#0999 Float, Double Read/Write
Custom Macro Value (local range) #0001-#0033 Float, Double Read Only
Custom Macro Value (system range) #1000-#9999 Float, Double Read/Write

CNC Data
Status Info Tags

www. ptc.com
29 Fanuc Focas Ethernet Driver

Tool Offset
Workpiece Zero Offset
Parameter Read Values
Alarms Values
Diagnostic Values
Path Value
Read Axis Data Values

Arrays
Arrays are supported for all PMC addresses, except for Custom Macros in the system range and where
Boolean or string data types are used. Tool Offset data cannot be addressed as an array. The syntax for
declaring an array is as follows:

Mxxxxx[cols] with assumed row count of 1.


Mxxxxx[rows][cols] where M is the address type and xxxxx is the byte offset of the first element in the array.

Note: For all arrays, the total number of bytes being requested cannot exceed the specified request size.

Strings
All address types can be read and written to as ASCII strings. Each byte of memory contains one ASCII char-
acter. The length of strings can range from 1 to 120 and is entered in place of the bit number. An additional
character "M" is appended to the address to distinguish string addresses from bit addresses.

Example
To address a string of length 100 characters, starting at D00200, enter D00200.100 M.

Unsolicited Data
If tags belong to a slave device, then their address types and ranges are validated according to the data
areas configured for that device. For example, if the slave device is configured with a single area with
D01000 to D01100, then a tag with address D01000 would be valid, but tags with addresses D01101 or
C00001 would be invalid. All tags belonging to a slave device are Read Only.

See Also: Unsolicited Data Areas

Note: Use caution when modifying Word, Short, DWord, Long, and Float types. Since all addresses start at
a byte offset within the device, it is possible for the memory associated with tags to overlap. For example,
word tags D00000 and D00001 overlap at byte 1. Writing to D00000 also modifies the value held in D00001.
It is recommended that these memory types be used such that each value to be read and written to by the
driver occupy a unique range of memory in the device. For example, map 3 Word values to bytes D00000-
D00001, D00002-D00003, and D00004-D00005. Tags to access these values would then have addresses
D00000, D00002, and D00004 respectively, and a data type of Word.

Series 21i
The following addresses are supported for this model. Not all address ranges may be valid for the particular
device being used. For more information, refer to the specific device's documentation. To jump to a specific
section, select a link from the list below.

CNC Data

www. ptc.com
Fanuc Focas Ethernet Driver 30

Arrays
Strings
Unsolicited Data

PMC Data
The default data types for dynamically defined DDE tags are shown in bold.

Address Type Range Data Type Access


A00000-A00124 Byte, Char
A00000-A00123 Word, Short
A (Message demand) Read/Write
A00000-A00121 DWord, Long, Float
Axxxxx.0-Axxxxx.7 Boolean
C00000-C00199 Byte, Char
C00000-C00198 Word, Short
C (Counter) Read/Write
C00000-C00196 DWord, Long, Float
Cxxxxx.0-Cxxxxx.7 Boolean
D00000-D09999 Byte, Char
D00000-D09998 Word, Short
D (Data table) Read/Write
D00000-D09996 DWord, Long, Float
Dxxxxx.0-Dxxxxx.7 Boolean
E00000-E07999 Byte, Char
E00000-E07998 Word, Short
E (Extended relay) Read/Write
E00000-E07996 DWord, Long, Float
Exxxxx.0-Exxxxx.7 Boolean
F00000-F02511 Byte, Char
F00000-F02510 Word, Short
F (Signal to CNC->PMC) Read Only
F00000-F02508 DWord, Long, Float
Fxxxxx.0-Fxxxxx.7 Boolean
G00000-G02511 Byte, Char
G00000-G02510 Word, Short
G (Signal to PMC->CNC) Read/Write
G00000-G02508 DWord, Long, Float
Gxxxxx.0-Gxxxxx.7 Boolean
K00000-K00909 Byte, Char
K00000-K00908 Word, Short
K (Keep relay) Read/Write
K00000-K00906 DWord, Long, Float
Kxxxxx.0-Kxxxxx.7 Boolean
M00000-M00511 Byte, Char
M00000-M00510 Word, Short
M (Input signal from other devices) Read Only
M00000-M00508 DWord, Long, Float
Mxxxxx.0-Mxxxxx.7 Boolean
N00000-N00511 Byte, Char
N00000-N00510 Word, Short
N (Output signal from other devices) Read/Write
N00000-N00508 DWord, Long, Float
Nxxxxx.0-Nxxxxx.7 Boolean
R00000-R09119 Byte, Char
R (Internal relay) R00000-R09118 Word, Short Read/Write
R00000-R09116 DWord, Long, Float

www. ptc.com
31 Fanuc Focas Ethernet Driver

Address Type Range Data Type Access


Rxxxxx.0-Rxxxxx.7 Boolean
T00000-T00299 Byte, Char
T00000-T00298 Word, Short
T (Changeable timer) Read/Write
T00000-T00296 DWord, Long, Float
Txxxxx.0-Txxxxx.7 Boolean
X00000-X00127 Byte, Char
X00000-X00126 Word, Short
X (Signal to machine->PMC) Read Only
X00000-X00124 DWord, Long, Float
Xxxxxx.0-Xxxxxx.7 Boolean
Y00000-Y00127 Byte, Char
Y00000-Y00126 Word, Short
Y (Signal to PMC->machine) Read/Write
Y00000-Y00124 DWord, Long, Float
Yxxxxx.0-Yxxxxx.7 Boolean
Custom Macro Value (common range) #0100-#0999 Float, Double Read/Write
Custom Macro Value (local range) #0001-#0033 Float, Double Read Only
Custom Macro Value (system range) #1000-#9999 Float, Double Read/Write

CNC Data
Status Info Tags
Tool Offset
Workpiece Zero Offset
Parameter Read Values
Alarms Values
Diagnostic Values
Path Value
Read Axis Data Values

Arrays
Arrays are supported for all PMC addresses, except for Custom Macros in the system range and where
Boolean or string data types are used. Tool Offset data cannot be addressed as an array. The syntax for
declaring an array is as follows:

Mxxxxx[cols] with assumed row count of 1.


Mxxxxx[rows][cols] where M is the address type and xxxxx is the byte offset of the first element in the array.

Note: For all arrays, the total number of bytes being requested cannot exceed the specified request size.

Strings
All address types can be read and written to as ASCII strings. Each byte of memory contains one ASCII char-
acter. The length of strings can range from 1 to 120 and is entered in place of the bit number. An additional
character "M" is appended to the address to distinguish string addresses from bit addresses.

Example
To address a string of length 100 characters, starting at D00200, enter D00200.100 M.

Unsolicited Data

www. ptc.com
Fanuc Focas Ethernet Driver 32

If tags belong to a slave device, then their address types and ranges are validated according to the data
areas configured for that device. For example, if the slave device is configured with a single area with
D01000 to D01100, then a tag with address D01000 would be valid, but tags with addresses D01101 or
C00001 would be invalid. All tags belonging to a slave device are Read Only.

See Also: Unsolicited Data Areas

Note: Use caution when modifying Word, Short, DWord, Long, and Float types. Since all addresses start at
a byte offset within the device, it is possible for the memory associated with tags to overlap. For example,
word tags D00000 and D00001 overlap at byte 1. Writing to D00000 also modifies the value held in D00001.
It is recommended that these memory types be used such that each value to be read and written to by the
driver occupy a unique range of memory in the device. For example, map 3 Word values to bytes D00000-
D00001, D00002-D00003, and D00004-D00005. Tags to access these values would then have addresses
D00000, D00002, and D00004 respectively, and a data type of Word.

Power Mate i
The following addresses are supported for this model. Not all address ranges may be valid for the particular
device being used. For more information, refer to the specific device's documentation. To jump to a specific
section, select a link from the list below.

CNC Data
Arrays
Strings

PMC Data
The default data types for dynamically defined DDE tags are shown in bold.

Address Type Range Data Type Access


A00000-A00124 Byte, Char
A00000-A00123 Word, Short
A (Message demand) Read/Write
A00000-A00121 DWord, Long, Float
Axxxxx.0-Axxxxx.7 Boolean
C00000-C00199 Byte, Char
C00000-C00198 Word, Short
C (Counter) Read/Write
C00000-C00196 DWord, Long, Float
Cxxxxx.0-Cxxxxx.7 Boolean
D00000-D09999 Byte, Char
D00000-D09998 Word, Short
D (Data table) Read/Write
D00000-D09996 DWord, Long, Float
Dxxxxx.0-Dxxxxx.7 Boolean
E00000-E07999 Byte, Char
E00000-E07998 Word, Short
E (Extended relay) Read/Write
E00000-E07996 DWord, Long, Float
Exxxxx.0-Exxxxx.7 Boolean
F00000-F02511 Byte, Char
F00000-F02510 Word, Short
F (Signal to CNC->PMC) Read Only
F00000-F02508 DWord, Long, Float
Fxxxxx.0-Fxxxxx.7 Boolean

www. ptc.com
33 Fanuc Focas Ethernet Driver

Address Type Range Data Type Access


G00000-G02511 Byte, Char
G00000-G02510 Word, Short
G (Signal to PMC->CNC) Read/Write
G00000-G02508 DWord, Long, Float
Gxxxxx.0-Gxxxxx.7 Boolean
K00000-K00909 Byte, Char
K00000-K00908 Word, Short
K (Keep relay) Read/Write
K00000-K00906 DWord, Long, Float
Kxxxxx.0-Kxxxxx.7 Boolean
M00000-M00511 Byte, Char
M00000-M00510 Word, Short
M (Input signal from other devices) Read Only
M00000-M00508 DWord, Long, Float
Mxxxxx.0-Mxxxxx.7 Boolean
N00000-N00511 Byte, Char
N00000-N00510 Word, Short
N (Output signal from other devices) Read/Write
N00000-N00508 DWord, Long, Float
Nxxxxx.0-Nxxxxx.7 Boolean
R00000-R09119 Byte, Char
R00000-R09118 Word, Short
R (Internal relay) Read/Write
R00000-R09116 DWord, Long, Float
Rxxxxx.0-Rxxxxx.7 Boolean
T00000-T00299 Byte, Char
T00000-T00298 Word, Short
T (Changeable timer) Read/Write
T00000-T00296 DWord, Long, Float
Txxxxx.0-Txxxxx.7 Boolean
X00000-X00127 Byte, Char
X (Signal to machine->PMC) X00000-X00126 Word, Short
Read Only
X00000-X00124 DWord, Long, Float
Xxxxxx.0-Xxxxxx.7 Boolean
Y00000-Y00127 Byte, Char
Y00000-Y00126 Word, Short
Y (Signal to PMC->machine) Read/Write
Y00000-Y00124 DWord, Long, Float
Yxxxxx.0-Yxxxxx.7 Boolean
Custom Macro Value (common range) #0100-#0999 Float, Double Read/Write
Custom Macro Value (local range) #0001-#0033 Float, Double Read Only
Custom Macro Value (system range) #1000-#9999 Float, Double Read/Write

CNC Data
Status Info Tags
Tool Offset
Workpiece Zero Offset
Parameter Read Values
Alarms Values
Diagnostic Values
Path Value
Read Axis Data Values

www. ptc.com
Fanuc Focas Ethernet Driver 34

Arrays
Arrays are supported for all PMC addresses, except for Custom Macros in the system range and where
Boolean or string data types are used. Tool Offset data cannot be addressed as an array. The syntax for
declaring an array is as follows:

Mxxxx[cols] with assumed row count of 1.


Mxxxxx[rows][cols] where M is the address type and xxxxx is the byte offset of the first element in the array.

Note: For all arrays, the total number of bytes being requested cannot exceed the specified request size.

Strings
All address types can be read and written to as ASCII strings. Each byte of memory contains one ASCII char-
acter. The length of strings can range from 1 to 120 and is entered in place of the bit number. An additional
character "M" is appended to the address to distinguish string addresses from bit addresses.

Example
To address a string of length 100 characters, starting at D00200, enter D00200.100 M.

Note: Use caution when modifying Word, Short, DWord, Long, and Float types. Since all addresses start at
a byte offset within the device, it is possible for the memory associated with tags to overlap. For example,
word tags D00000 and D00001 overlap at byte 1. Writing to D00000 also modifies the value held in D00001.
It is recommended that these memory types be used such that each value to be read and written to by the
driver occupy a unique range of memory in the device. For example, map 3 Word values to bytes D00000-
D00001, D00002-D00003, and D00004-D00005. Tags to access these values would then have addresses
D00000, D00002, and D00004 respectively, and a data type of Word.

Open
The following addresses are supported for this model. Not all address ranges may be valid for the particular
device being used. For more information, refer to the specific device's documentation. To jump to a specific
section, select a link from the list below.

CNC Data
Arrays
Strings
Unsolicited Data

PMC Data
The default data types for dynamically defined DDE tags are shown in bold.

Address Type Range Data Type Access


A00000-A32767 Byte, Char
A00000-A32766 Word, Short
A (Message demand) Read/Write
00000-A32764 DWord, Long, Float
Axxxxx.0-Axxxxx.7 Boolean
C00000-C32767 Byte, Char
C00000-C32766 Word, Short
C (Counter) Read/Write
C00000-C32764 DWord, Long, Float
Cxxxxx.0-Cxxxxx.7 Boolean

www. ptc.com
35 Fanuc Focas Ethernet Driver

Address Type Range Data Type Access


D00000-D32767 Byte, Char
D00000-D32766 Word, Short
D (Data table) Read/Write
D00000-D32764 DWord, Long, Float
Dxxxxx.0-Dxxxxx.7 Boolean
E00000-E32767 Byte, Char
E00000-E32766 Word, Short
E (Extended relay) Read/Write
E00000-E32764 DWord, Long, Float
Exxxxx.0-Exxxxx.7 Boolean
F00000-F32767 Byte, Char
F00000-F32766 Word, Short
F (Signal to CNC->PMC) Read Only
F00000-F32764 DWord, Long, Float
Fxxxxx.0-Fxxxxx.7 Boolean
G00000-G32767 Byte, Char
G00000-G32766 Word, Short
G (Signal to PMC->CNC) Read/Write
G00000-G32764 DWord, Long, Float
Gxxxxx.0-Gxxxxx.7 Boolean
K00000-K32767 Byte, Char
K00000-K32766 Word, Short
K (Keep relay) Read/Write
K00000-K32764 DWord, Long, Float
Kxxxxx.0-Kxxxxx.7 Boolean
M00000-M32767 Byte, Char
M00000-M32766 Word, Short
M (Input signal from other devices) Read Only
M00000-M32764 DWord, Long, Float
Mxxxxx.0-Mxxxxx.7 Boolean
N00000-N32767 Byte, Char
N00000-N32766 Word, Short
N (Output signal from other devices) Read/Write
N00000-N32764 DWord, Long, Float
Nxxxxx.0-Nxxxxx.7 Boolean
R00000-R32767 Byte, Char
R00000-R32766 Word, Short
R (Internal relay) Read/Write
R00000-R32764 DWord, Long, Float
Rxxxxx.0-Rxxxxx.7 Boolean
T00000-T32767 Byte, Char
T00000-T32766 Word, Short
T (Changeable timer) Read/Write
T00000-T32764 DWord, Long, Float
Txxxxx.0-Txxxxx.7 Boolean
X00000-X32767 Byte, Char
X00000-X32766 Word, Short
X (Signal to machine->PMC) Read Only
X00000-X32764 DWord, Long, Float
Xxxxxx.0-Xxxxxx.7 Boolean
Y00000-Y32767 Byte, Char
Y00000-Y32766 Word, Short
Y (Signal to PMC->machine) Read/Write
Y00000-Y32764 DWord, Long, Float
Yxxxxx.0-Yxxxxx.7 Boolean
Custom Macro Value (common range) #0100-#0999 Float, Double Read/Write
Custom Macro Value (local range) #0001-#0033 Float, Double Read Only

www. ptc.com
Fanuc Focas Ethernet Driver 36

Address Type Range Data Type Access


Custom Macro Value (system range) #1000-#9999 Float, Double Read/Write

CNC Data
Status Info Tags
Tool Offset
Workpiece Zero Offset
Parameter Read Values
Alarms Values
Diagnostic Values
Path Value
Read Axis Data Values

Arrays
Arrays are supported for all PMC addresses, except for Custom Macros in the system range and where
Boolean or string data types are used. Tool Offset data cannot be addressed as an array. The syntax for
declaring an array is as follows:

Mxxxxx[cols] with assumed row count of 1.


Mxxxxx[rows][cols] where M is the address type and xxxxx is the byte offset of the first element in the array.

Note: For all arrays, the total number of bytes being requested cannot exceed the specified request size.

Strings
All address types can be read and written to as ASCII strings. Each byte of memory contains one ASCII char-
acter. The length of strings can range from 1 to 120 and is entered in place of the bit number. An additional
character "M" is appended to the address to distinguish string addresses from bit addresses.

Example
To address a string of length 100 characters starting at D00200, enter D00200.100 M.

Unsolicited Data
If tags belong to a slave device, then their address types and ranges are validated according to the data
areas configured for that device. For example, if the slave device is configured with a single area with
D01000 to D01100, then a tag with address D01000 would be valid, but tags with addresses D01101 or
C00001 would be invalid. All tags belonging to a slave device are Read Only.

See Also: Unsolicited Data Areas

Note: Use caution when modifying Word, Short, DWord, Long, and Float types. Since all addresses start at
a byte offset within the device, it is possible for the memory associated with tags to overlap. For example,
word tags D00000 and D00001 overlap at byte 1. Writing to D00000 also modifies the value held in D00001.
It is recommended that these memory types be used such that each value to be read and written to by the
driver occupy a unique range of memory in the device. For example, map 3 Word values to bytes D00000-
D00001, D00002-D00003, and D00004-D00005. Tags to access these values would then have addresses
D00000, D00002, and D00004 respectively, and a data type of Word.

www. ptc.com
37 Fanuc Focas Ethernet Driver

Status Info Tags


Series 15i
Tag Name Data Type Access Description
statinfo_alarm Short Read Only Status of alarm
statinfo_aut Short Read Only Automatic mode selection
statinfo_battery Short Read Only Status of battery
statinfo_dummy1 Short Read Only Reserved for future use
statinfo_dummy2 Short Read Only Reserved for future use
statinfo_edit Short Read Only Status of program editing
statinfo_emergency Short Read Only Status of emergency
statinfo_labelskip Short Read Only Status of label skip
statinfo_manual Short Read Only Manual mode selection
statinfo_motion Short Read Only Status of axis movement, dwell
statinfo_mstb Short Read Only Status of M,S,T,B function
statinfo_run Short Read Only Status of automatic operation
statinfo_warning Short Read Only Status of warning
statinfo_write Short Read Only Status of writing backed up memory

Returned Status Codes


Tag Name Status Code
0 : No alarm
statinfo_alarm
1 : Alarm
0 : No selection
1 : MDI
2 : DNC
statinfo_aut
3 : Memory
4 : Edit
5 : Teach In
0 : Normal
statinfo_battery 1 : Battery low (backed up memory)
2 : Battery low (absolute position detector)
statinfo_dummy1 Not used
statinfo_dummy2 Not used
0 : Not editing
1 : Edit
2 : Search
statinfo_edit 3 : Verify
4 : Condense
5 : Read
6 : Punch
0 : Not emergency
statinfo_emergency
1 : Emergency
0 : Label skip
statinfo_labelskip
1 : Not label skip

www. ptc.com
Fanuc Focas Ethernet Driver 38

Tag Name Status Code


0: No selection
1 : Reference
2 : INC feed
3 : Handle
statinfo_manual
4 : Jog
5 : Angular Jog
6 : Inc+Handl
7 : Jog+Handl
1 : Motion
statinfo_motion 2 : Dwell
3 : Wait (Waiting: only TT)
statinfo_mstb 1 : FIN
0 : Stop
1 : Hold
2 : Start
3 : MSTR (Jog MDI)
4 : Restart (Not blinking)*
statinfo_run
5 : PRSR (Program restart)
6 : NSRC (Sequence number search)
7 : Restart (Blinking)**
8 : Reset
13 : HPCC (During RISC operation)
0 : No warning
statinfo_warning
1 : Warning
0 : Not writing
statinfo_write
1 : @Writing

*Except under manual mode and under cutter radius compensation outside corner.
**Under manual mode or under cutter radius compensation outside corner.

Series 16i/18i/21i/Power Mate i/Open


Tag Name Data Type Access Description
statinfo_alarm Short Read Only Status of alarm
statinfo_aut Short Read Only Automatic / Manual mode selection
statinfo_edit Short Read Only Status of program editing
statinfo_emergency Short Read Only Status of emergency
statinfo_hdck Short Read Only Status of manual handle re-trace
statinfo_motion Short Read Only Status of axis movement, dwell
statinfo_mstb Short Read Only Status of M,S,T,B function
statinfo_run Short Read Only Status of automatic operation
statinfo_tmmode Short Read Only T/M mode selection

Returned Status Codes

www. ptc.com
39 Fanuc Focas Ethernet Driver

Tag Name Status Code


0 : Others
1 : Alarm
statinfo_alarm
2 : Battery low
3 : Fan alarm
0 : MDI
1 : Memory
3 : Edit
4 : Handle
5 : Jog
statinfo_aut 6 : Teach in Jog
7 : Teach in Handle
8 : INC feed
9 : Reference
10 : Remote
11 : TEST(test operation mode)
M Series
0 : Not editing
1 : Edit
2 : Search
3 : Output
4 : Input
5 : Compare
6 : Label Skip (Label skip status)
7 : Restart (During program restart)
8 : HPCC (During RISC operation)
9 : PTRR (During tool retraction and recovery mode)
10 : RVRS (During retracing)
11 : RTRY (During reprogressing)
12 : RVED (End of retracing)
13 : Handle (During handle overlapping)
14 : Offset (During tool length measurement mode)
statinfo_edit 15 : Work Offset (During work zero point measurement mode)
16 : AICC (During AI contour control)
17 : Memory-Check (Checking tape memory)
18 : Customer's Board (During customer's board control)
19 : Save (Saving fine torque sensing data)
20 : AI NANO (During AI nano contour control)
21 : AI APC (During AI advanced preview control)
22 : MBL APC (During multi blocks advanced preview control)
23 : NANO HP (Running of AI High-precision Contour Control.
24 : AI HPCC (Running of AI Nano High-precision Contour Control)
25 : 5-AXIS (Running of 5-axes machining)
26 : LEN (Change the manual active offset value: length offset change mode)
27 : RAD (Change the manual active offset value: radius offset change mode)
28 : WZR (Change the manual active offset value: workpiece origin offset change mode)
39 : TCP (During tool center point control of 5-axes machining)
40 : TWP (During tilted working plane command)

www. ptc.com
Fanuc Focas Ethernet Driver 40

Tag Name Status Code


41 : TCP+TWP (During tool center point control of 5-axes machining and tilted working
plane command)
42 : APC (Advanced Preview Control)

T Series
0 : Not editing
1 : Edit
2 : Search
3 : Output
4 : Input
5 : Compare
6 : Label Skip (Label skip status)
7 : Offset (During writing mode of tool length compensation amount)
8 : Work Shift (During writing mode of work shift amount)
9 : Restart (During program restart)
14 : PTRR (During tool retraction and recovery mode)
17 : Memory-Check (Checking tape memory)
19 : Save (Saving fine torque sensing data)
23 : NANO HP (Running of AI High-precision Contour Control)
24 : AI HPCC (Running of AI Nano High-precision Contour Control)
26 : OFSX (Change the manual active offset value: X-axis offset change mode)
27 : OFSZ (Change the manual active offset value: Z-axis offset change mode)
28 : WZR (change the manual active offset value: workpiece origin offset change mode)
29 : OFSY (Change the manual active offset value: Y-axis offset change mode)
31 : TOFS (Change the manual active offset value: Tool offset change mode)
39 : TCP (During tool center point control of 5-axes machining)
40 : TWP (During tilted working plane command)
41 : TCP+TWP (During tool center point control of 5-axes machining and tilted working
plane command)
42 : APC (Advanced Preview Control)
0 : Not emergency
statinfo_emer-
1 : Emergency
gency
2 : Reset
statinfo_hdck N/A
1 : Motion
statinfo_motion
2 : Dwell
0 : Others
statinfo_mstb
1 : FIN
0 : Reset
1 : Stop
statinfo_run 2 : Hold
3 : Start
4 : MSTR*
statinfo_ 0 : T Mode
tmmode 1 : M Mode

*During operation of Jog MDI, and retraction and re-positioning of tool retraction and recovery.

www. ptc.com
41 Fanuc Focas Ethernet Driver

Tool Offset
CNC Data
Address Type Range Data Type Access
TOFS:nn:o

Tool Offset Long, DWord Read/Write


nn = Tool Number (01-64)
o = Offset Type (0-9)

Tool Offset Types


The meaning of the tool offset type depends upon the hardware. The following tables summarize the various
offset types.

Cutter Radius Tool Length


Wear 0 2
Geometry 1 3

Lathe Series (T series)


X-Axis Z-Axis Nose R Imaginary Tool Nose Y-Axis
Wear 0 2 4 6 8
Geometry 1 3 5 7 9

Tool Offset Values


Series 15, 150i
Linear axis mm Linear axis inch Rotation
6007#0 6004#0 6002#1 6002#0
input input axis
(OFE) (OFD) (OFC) (OFA)
[mm] [inch] [deg]
0 0 0 1 0.01 0.001 0.01
0 0 0 0 0.001 0.0001 0.001
0 0 1 0 0.0001 0.00001 0.0001
0 1 0 0 0.00001 0.000001 0.00001
1 0 0 0 0.000001 0.0000001 0.000001

Series 16/18/21, 160/180/210, 160i/180i/210i, 0i, Power Mate, Open


1004#1 1004#0 Linear axis mm input Linear axis inch input Rotation axis
(ISC) (ISA) [mm] [inch] [deg]
IS-A* 0 1 0.01 0.001 0.01
IS-B 0 0 0.001 0.0001 0.001
IS-
1 0 0.0001 0.00001 0.0001
C**

*IS-A is effective for Power Mate i-H.


**IS-C is effective for Power Mate i-D.

www. ptc.com
Fanuc Focas Ethernet Driver 42

Workpiece Zero Offset


Not all addresses are valid for all device models.

CNC Data
Address Type Range Data Type Access
ZOFS:aa:ooo

Workpiece Zero Offset Long, DWord Read/Write


aa = axis (01-32)
ooo = offset (000-306)

Workpiece Zero Offset Values


Series 150
Linear axis
1009#1 1004#5 1004#1 1004#0 Linear axis mm Rotation axis
inch
(ISE) (ISD) (ISF) (ISR) input [mm] [deg]
input [inch]
IS-
0 0 0 1 0.01 0.001 0.01
A
IS-
0 0 0 0 0.001 0.0001 0.001
B
IS-
0 0 1 0 0.0001 0.00001 0.0001
C
IS-
0 1 0 0 0.00001 0.000001 0.00001
D
IS-
1 0 0 0 0.000001 0.0000001 0.000001
E

Series 15, 150i


1012#3 1012#2 1012#1 1012#0 Linear axis mm Linear axis inch Rotation
(ISE) (ISD) (ISC) (ISA) input [mm] input [inch] axis [deg]
IS-
0 0 0 1 0.01 0.001 0.01
A
IS-
0 0 0 0 0.001 0.0001 0.001
B
IS-
0 0 1 0 0.0001 0.00001 0.0001
C
IS-
0 1 0 0 0.00001 0.000001 0.00001
D
IS-
1 0 0 0 0.000001 0.0000001 0.000001
E

Series 16/18/21, 160/180/210, 160i/180i/210i, 0i, Power Mate, Open


1004#1 1004#0 Linear axis inch Rotation axis
Linear axis mm input [mm]
(ISC) (ISA) input [inch] [deg]
IS- 0 1 0.01 0.001 0.01

www. ptc.com
43 Fanuc Focas Ethernet Driver

1004#1 1004#0 Linear axis inch Rotation axis


Linear axis mm input [mm]
(ISC) (ISA) input [inch] [deg]
A
IS-
0 0 0.001 0.0001 0.001
B
IS-
1 0 0.0001 0.00001 0.0001
C

Series 300i
1013#3 1013#2 1013#1 1013#0 Linear axis mm Linear axis inch Rotation
(ISE) (ISD) (ISC) ISA) input [mm] input [inch] axis [deg]
IS-
0 0 0 1 0.01 0.001 0.01
A
IS-
0 0 0 0 0.001 0.0001 0.001
B
IS-
0 0 1 0 0.0001 0.00001 0.0001
C
IS-
0 1 0 0 0.00001 0.000001 0.00001
D
IS-
1 0 0 0 0.000001 0.0000001 0.000001
E

Parameter Read Values


The values in a CNC machine's parameters can be read using the cnc_rdparam tags. Refer to the machine's
manual for specific parameters, and which data type to assign to them.

For axis access, append .A to the parameter number, followed by the axis number. The first axis in the para-
meter is axis 1, the second axis 2, and so on. The highest axis to access is 8. If no axis is added to the
address, the first axis is read.

For bit in parameter access, append a dot (.) to the parameter number, followed by the bit number. The first
bit is bit 0. The maximum accessible bit is the 32nd bit. Bit access is allowed on axis access. Bit access is not
allowed on parameters with default data types of float or double.

Address Type Range Data Type Access


cnc_rdparam.0 - cnc_rdparam.37267 Default*
cnc_rdparam.0.A1 – cnc_rdparam.32767.A8 Byte, Char, Word, Read
CNC Parameter
cnc_rdparam.0.0** – cnc_rdparam.32767.31** Short, DWord, Long, Only
cnc_rdparam.0.A1.0**-cnc_rdparam.32767.A8.31** Float, Double
*The correct data type for each parameter is dependent on which machine is being accessed. When cre-
ating a CNC Parameter tag, the data type must be manually assigned. Otherwise, the Default data type is
assigned. If Default is the assigned data type, then the data type of the tag is determined and set at runtime.

**Bit in parameter tags can only be assigned the Boolean data type.

www. ptc.com
Fanuc Focas Ethernet Driver 44

Alarm Values
Specific alarm information can be read using the cnc_alarm2 tag. Refer to the machine's manual for which
bits correspond with which alarms. When a bit is set to true it means there is one or more alarms of that
type present in the machine.

For bit access, append a dot (.) to the cnc_alarm2 tag. The range is 32-bits starting at bit 0 (0-31). All bit tags
can only be assigned the Boolean data type.

Address Type Range Data Type Access


cnc_alarm2
cnc_alarm2.0
Alarm Reporting DWord, Long, Boolean Read Only
through
cnc_alarm2.31

Diagnostic Values
The diagnostic values of the machine can be read with cnc_diagnoss tags. The user must provide a diagnosis
number and the desired axis. For values that do not have an axis, 0 must be used. An axis value of -1 (ALL_
AXES) is not supported.

The format for these tag addresses are in the form cnc_diagnoss: A:B.C where A is the diagnosis number, B
is the axis, and C is optional bit access. Tag address examples include:

l cnc_diagnoss:301:1
l cnc_diagnoss:301:2
l cnc_diagnoss:301:3
l cnc_diagnoss:1140:0 (as a Byte)
l cnc_diagnoss:1140:0.0 (as a Boolean)

For bit access, append a dot (.) to the cnc_diagnoss tag. The range is 8-bits starting at bit 0 (0-7). All bit tags
can only be assigned the Boolean data type.

Address
Range Data Type Access
Type
cnc_diagnoss:1:0
through
cnc_diagnoss:A:B Boolean, Byte,
where A is the maximum diagnosis number and B is the Char, Word,
maximum axis defined. Short, DWord,
Diagnostic Read
These maximums are machine dependent. Long,
Reporting Only
Float, Double
For bit access to values:
cnc_diagnoss:1:0.0 Boolean
through
cnc_diagnoss:A:B.7

www. ptc.com
45 Fanuc Focas Ethernet Driver

Path Values
The target_path tag can be used to get and set the current path for the controller. Writing a value to the tar-
get_path tag produces a cnc_setpath call to the machine. A read produces a cnc_getpath call.

Address Type Range Data Type Access


Path Control target_path Byte, Char, Word, Short, DWord, Long, Read / Write

Read Axis Data Values


The axis data values of the machine can be read with cnc_rdaxisdata tags. The user must provide a class,
type, axis, and whether they want the data or flag value. Please refer to the documentation of cnc_rdaxisdata
for the specific class, type combinations that will retrieve the information desired.

The format for these tag addresses are in the form cnc_rdaxisdata: A:B:C:data or cnc_rdaxisdata: A:B:C:-
flags.D where A is the class, B is the type, C is the axis, and D is optional bit access on the flags value.
Examples include:

l cnc_rdaxisdata:1:1:1:data (Machine position of the x axis)


l cnc_rdaxisdata:1:1:2:data (Machine position of the y axis)
l cnc_rdaxisdata:1:1:3:data (Machine position of the z axis)
l cnc_rdaxisdata:1:1:1:flags.0 (Whether the machine position of the x axis is displayed on the screen or
not)
l cnc_rdaxisdata:2:1:2:data (Load current as a percentage of the y axis)

For data that is not specific to an axis use an axis value of 1.

Address Type Range Data Type Access


cnc_rdaxisdata:1:0:1:data
through
cnc_diagnoss:5:9:4:data

cnc_rdaxisdata:1:0:1:flags
Boolean, Byte, Char,
through
Word,
cnc_diagnoss:5:9:4:flags
Axis Data Reporting Short, DWord, Long, Read Only
Float, Double
These maximums are device dependent.
Boolean

For bit access to flags value:


cnc_rdaxisdata:1:0:1:flags.0
through
cnc_diagnoss:5:9:4:flags.15

www. ptc.com
Fanuc Focas Ethernet Driver 46

Error Descriptions
The following categories of messages may be generated. Click the link for a list of the related messages.

Address Validation
Device Status Messages
General Driver Error Messages
Slave Device Driver Error Messages
Focas Data Window Library Error Codes

Address Validation
The following messages may be generated. Click the link for a description of the message.

Address <address> is out of range for the specified device or register.


Array size is out of range for address <address>.
Array support is not available for the specified address: <address>.
Data type <type> is not valid for device address <address>.
Device address <address> contains a syntax error.
Device address <address> is read only.
Missing address.

Address <address> is out of range for the specified device or register.


Error Type:
Warning

Possible Cause:
A tag address that has been specified statically references a location that is beyond the range of supported
locations for the device.

Solution:
Verify that the address is correct; if it is not, re-enter it in the client application.

Array size is out of range for address <address>.


Error Type:
Warning

Possible Cause:
A tag address that has been specified statically is requesting an array size that is too large for the address
type or block size of the driver.

Solution:
Re-enter the address in the client application to specify a smaller value for the array or a different starting
point.

www. ptc.com
47 Fanuc Focas Ethernet Driver

Array support is not available for the specified address: <address>.


Error Type:
Warning

Possible Cause:
A tag address that has been specified statically contains an array reference for an address type that doesn't
support arrays.

Solution:
Re-enter the address in the client application to remove the array reference or correct the address type.

Data Type <type> is not valid for device address <address>.


Error Type:
Warning

Possible Cause:
A tag address that has been specified statically has been assigned an invalid data type.

Solution:
Modify the requested data type in the client application.

Device address <address> contains a syntax error.


Error Type:
Warning

Possible Cause:
A tag address that has been specified statically contains one or more invalid characters.

Solution:
Re-enter the address in the client application.

Device address <address> is read only.


Error Type:
Warning

Possible Cause:
A tag address that has been specified statically has a requested access mode that is not compatible with
what the device supports for that address.

Solution:
Change the access mode in the client application.

Missing address.
Error Type:
Warning

www. ptc.com
Fanuc Focas Ethernet Driver 48

Possible Cause:
A tag address that has been specified statically has no length.

Solution:
Re-enter the address in the client application.

Device Status Messages


The following messages may be generated. Click the link for a description of the message.

Device <device name> is not responding.


Unable to write to <address> on device <device name>.

Device <device name> is not responding.


Error Type:
Serious

Possible Cause:
1. The connection between the device and the host PC is broken.

2. The IP address assigned to the device is incorrect.

3. The response from the device took longer to receive than the amount of time specified in the
"Request Timeout" device setting.

Solution:
1. Verify the cabling between the PC and the PLC device.

2. Verify that the IP address given to the named device matches that of the actual device.

3. Increase the Request Timeout setting so that the entire response can be handled.

Unable to write to <address> on device <device name>.


Error Type:
Serious

Possible Cause:
1. The connection between the device and the host PC is broken.

2. The named device may have been assigned an incorrect IP address.

Solution:
1. Verify the cabling between the PC and the PLC device.

2. Verify that the IP address given to the named device matches that of the actual device.

www. ptc.com
49 Fanuc Focas Ethernet Driver

General Driver Messages


The following messages may be generated. Click the link for a description of the message.

Could not acquire library handle for device <channel.device>. FWLIB error: <code>.
Could not read one or more vacant macros in range starting at <address> on device
<device>.
Could not set request timeout for device <channel.device>. FWLIB error: <code>.
Invalid XML document. Reason: Error loading Unsolicited Data Areas for device <device
name>. End address can not be less than start address for area area-number.
Invalid XML document. Reason: Error loading Unsolicited Data Areas for device device-
name. Invalid area order or duplicate area number.
Invalid XML document. Reason: Error loading Unsolicited Data Areas for device device-
name. Maximum size of area area-number is size bytes.
Read error occurred for address starting at <address> on device <channel.device>. FWLIB
error: <code>.
Unable to start the Fanuc Focas Data Window Library services.
Write error occurred for address <address> on device <channel.device>. FWLIB error:
<code>.

Could not acquire library handle for device <channel.device>. FWLIB error:
<code>.
Error Type:
Warning

Possible Cause:
1. Call to Focas 1 Data Window Library to connect to device failed.

2. Invalid device IP or port number.

3. The device may not be running.

4. The device may be busy processing other requests.

5. There may be a cabling problem.

Solution:
The error code provided by the library should help diagnose the problem. If the problem is transient, the
driver should be able to connect on a subsequent retry.

See Also:
Focas 1 Data Window Library Error Codes

Could not read one or more vacant macros in range starting at <address>
on device <device>.
Error Type:
Warning

www. ptc.com
Fanuc Focas Ethernet Driver 50

Possible Cause:
The macro number is not configured in the device.

Solution:
Check the tag address and device configuration.

Could not set request timeout for device <channel.device>. FWLIB error:
<code>.
Error Type:
Warning

Possible Cause:
1. Call to Focas 1 Data Window Library to set request timeout failed.

2. Invalid timeout.

3. The device may be busy processing other requests.

4. There may be a cabling problem.

Solution:
The error code provided by the library should help diagnose the problem. If the problem is transient, the
driver should be able to set the timeout on a subsequent retry.

See Also:
Focas 1 Data Window Library Error Codes

Invalid XML document. Reason: Error loading Unsolicited Data Areas for
device <device-name>. End address can not be less than start address for
area <area-number>.
Error Type:
Fatal

Possible Cause:
The end address for the given unsolicited data area is greater than the start address.

Solution:
Make the end address greater than or equal to the start address.

Invalid XML document. Reason: Error loading Unsolicited Data Areas for
device <device-name>. Invalid area order or duplicate area number.
Error Type:
Fatal

Possible Cause:

www. ptc.com
51 Fanuc Focas Ethernet Driver

1. The unsolicited data areas are not listed in the correct order.

2. There are duplicate area numbers.

Solution:
1. Correct the ordering of the unsolicited data areas to be in the increasing order starting at 1.

2. Renumber the duplicate area number.

See Also:
Unsolicited Data Areas

Invalid XML document. Reason: Error loading Unsolicited Data Areas for
device <device-name>. Maximum size of area <area-number> is <size>
bytes.
Error Type:
Fatal

Possible Cause:
The maximum number of bytes for areas 1, 2, or 3 are 1430, 1414, or 1398 respectively. The range that has
been defined for these areas is outside this limit.

Solution:
Correct the unsolicited data area size based on the limits above.

See Also:
Unsolicited Data Areas

Read error occurred for address starting at <address> on device <chan-


nel.device>. FWLIB error: <code>.
Error Type:
Warning

Possible Cause:
1. Call to Focas 1 Data Window Library to read data failed.

2. Invalid PMC type.

3. Invalid address.

4. Invalid request size.

5. The device may be busy processing other requests.

6. There may be a cabling problem.

Solution:
The error code provided by the library should help diagnose the problem. If the problem is transient, the
driver should be able to read the data on a subsequent retry.

www. ptc.com
Fanuc Focas Ethernet Driver 52

See Also:
Focas 1 Data Window Library Error Codes

Unable to start the Fanuc Focas Data Window Library services.


Error Type:
Fatal

Possible Cause:
The driver was unable to load the Fanuc Focas Data Window Library.

Solution:
Make sure that the library is installed on the computer. Contact this software's distributor.

Write error occurred for address <address> on device <channel.device>.


FWLIB error: <code>.
Error Type:
Warning

Possible Cause:
1. Call to Focas 1 Data Window Library to write data failed.

2. Invalid PMC type.

3. Invalid address.

4. Invalid request size.

5. The device may be busy processing other requests.

6. There may be a cabling problem.

Solution:
The error code provided by the library should help diagnose the problem. If the problem is transient, the
driver should be able to write the data on a subsequent retry.

See Also:
Focas 1 Data Window Library Error Codes

Slave Device Driver Messages


The following messages may be generated. Click the link for a description of the message.

Attempt to launch unsolicited message server failed.


Could not access necessary system resources for slave device: <channel.device>.
Failed to connect slave device <channel.device>. Could not acquire library handle. FWLIB
error: <code>.
Failed to connect slave device <channel.device>. Could not determine host IP address.
Failed to connect slave device <channel.device>. Could not set data area size.

www. ptc.com
53 Fanuc Focas Ethernet Driver

Failed to connect slave device <channel.device>. Could not set data area start address.
Failed to connect slave device <channel.device>. Could not set data area type.
Failed to connect slave device <channel.device>. Could not set host IP.
Failed to connect slave device <channel.device>. Could not set host port.
Failed to connect slave device <channel.device>. Could not set message alive time.
Failed to connect slave device <channel.device>. Could not set message retries.
Failed to connect slave device <channel.device>. Could not set message timeout.
Failed to connect slave device <channel.device>. Could not set messaging properties.
FWLIB data error <code>.
Failed to connect slave device <channel.device>. Could not set messaging properties.
FWLIB error: <code>.
Failed to connect slave device <channel.device>. Could not set number of data areas.
Failed to connect slave device <channel.device>. Could not set request timeout. FWLIB
error: <code>.
Failed to connect slave device <channel.device>. Could not set transmission control PMC
type.
Failed to connect slave device <channel.device>. Could not set transmission control start
address.
Failed to connect slave device <channel.device>. Could not start messaging session.
FWLIB error: <code>.
Installed version of Focas 1 Library does not support unsolicited communication. Device
<channel.device> deactivated.
Received CNC power down notification from unsolicited message server. Reconnecting
slave devices.
Received CNC power up notification from unsolicited message server.
Received socket error notification from unsolicited message server.
Received unsolicited message server shutdown notification.
Unsolicited message server does not seem to be running. Attempting to launch.

Attempt to launch unsolicited message server failed.


Error Type:
Warning

Possible Cause:
The driver was not able to start the Unsolicited Message Server.

Solution:
For the restart to succeed, the message server executable file "UMsgServ.ext" must be located in the host
computer’s system folder.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

www. ptc.com
Fanuc Focas Ethernet Driver 54

See Also:
Unsolicited Messaging

Could not access necessary system resources for slave device: <chan-
nel.device>.
Error Type:
Serious

Possible Cause:
The driver could not create data objects needed for unsolicited communications.

Solution:
Close down all unnecessary applications running on the host computer.

Failed to connect slave device <channel.device>. Could not acquire library


handle. FWLIB error: <code>.
Error Type:
Warning

Possible Cause:
1. Call to Focas 1 Data Window Library to connect to device failed.

2. Invalid device IP or port number.

3. The device may not be running.

4. The device may be busy processing other requests.

5. There may be a cabling problem.

Solution:
The error code provided by the library should help diagnose the problem. If the problem is transient, the
driver should be able to connect on a subsequent retry.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

See Also:
Focas 1 Data Window Library Error Codes

Failed to connect slave device <channel.device>. Could not determine host


IP address.
Error Type:
Warning

Possible Cause:

www. ptc.com
55 Fanuc Focas Ethernet Driver

Part of starting an unsolicited messaging session with a device includes informing the device of the IP of the
host computer. This message will be posted if the driver fails to determine the default IP of the host com-
puter.

Solution:
Make sure that an IP address is configured for the computer.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

Failed to connect slave device <channel.device>. Could not set data area
size.
Error Type:
Warning

Possible Cause:
Call to Focas 1 Data Window Library to set unsolicited message data area size failed.

Solution:
Ensure that the specified range of addresses is valid.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

See Also:
Unsolicited Data Areas

Failed to connect slave device <channel.device>. Could not set data area
start address.
Error Type:
Warning

Possible Cause:
Call to Focas 1 Data Window Library to set unsolicited message data area start address failed.

Solution:
Ensure that the specified start address is valid.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

See Also:

www. ptc.com
Fanuc Focas Ethernet Driver 56

Unsolicited Data Areas

Failed to connect slave device <channel.device>. Could not set data area
type.
Error Type:
Warning

Possible Cause:
Call to Focas 1 Data Window Library to set unsolicited message data area type failed.

Solution:
Ensure that the specified type is valid.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

See Also:
Unsolicited Data Areas

Failed to connect slave device <channel.device>. Could not set host IP.
Error Type:
Warning

Possible Cause:
Call to Focas 1 Data Window Library to set host IP of Unsolicited Message Server failed.

Solution:
Check the IP of the host computer.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

Failed to connect slave device <channel.device>. Could not set host port.
Error Type:
Warning

Possible Cause:
Call to Focas 1 Data Window Library to set host port of Unsolicited Message Server failed.

Solution:
Ensure that the specified port number is valid.

Note:

www. ptc.com
57 Fanuc Focas Ethernet Driver

The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

See Also:
Unsolicited Transfer Control

Failed to connect slave device <channel.device>. Could not set message


alive time.
Error Type:
Warning

Possible Cause:
Call to Focas 1 Data Window Library to set unsolicited message alive time failed.

Solution:
Ensure that the specified alive time value is valid.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

See Also:
Unsolicited Transfer Control

Failed to connect slave device <channel.device>. Could not set message


retries.
Error Type:
Warning

Possible Cause:
Call to Focas 1 Data Window Library to set transmission control message retries failed.

Solution:
Ensure that the specified retries value is valid.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

See Also:
Unsolicited Transfer Control

www. ptc.com
Fanuc Focas Ethernet Driver 58

Failed to connect slave device <channel.device>. Could not set message


timeout.
Error Type:
Warning

Possible Cause:
Call to Focas 1 Data Window Library to set unsolicited message timeout failed.

Solution:
Ensure that the specified timeout value is valid.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

See Also:
Unsolicited Transfer Control

Failed to connect slave device <channel.device>. Could not set messaging


properties. FWLIB data error <code>.
Error Type:
Warning

Possible Cause:
1. Call to Focas 1 Data Window Library to set unsolicited messaging properties failed due to a data
related error.

2. Invalid transfer control parameters.

3. The device may not be running.

4. The device may be busy processing other requests.

5. There may be a cabling problem.

Solution:
The error code provided by the library should help diagnose the problem. If the problem is transient, the
driver should be able to connect on a subsequent retry.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

See Also:
Focas 1 Data Window Library Error Codes
Unsolicited Transfer Control

www. ptc.com
59 Fanuc Focas Ethernet Driver

Failed to connect slave device <channel.device>. Could not set messaging


properties. FWLIB error: <code>.
Error Type:
Warning

Possible Cause:
1. Call to Focas 1 Data Window Library to set unsolicited messaging properties failed due to a non-data
related error.

2. Invalid transfer control properties.

3. The device may not be running.

4. The device may be busy processing other requests.

5. There may be a cabling problem.

Solution:
The error code provided by the library should help diagnose the problem. If the problem is transient, the
driver should be able to connect on a subsequent retry.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

See Also:
Focas 1 Data Window Library Error Codes
Unsolicited Transfer Control

Failed to connect slave device <channel.device>. Could not set number of


data areas.
Error Type:
Warning

Possible Cause:
Call to Focas 1 Data Window Library to set number of unsolicited message data areas failed.

Solution:
Ensure that the device supports the number of data areas configured.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

See Also:
Unsolicited Data Areas

www. ptc.com
Fanuc Focas Ethernet Driver 60

Failed to connect slave device <channel.device>. Could not set request


timeout. FWLIB error: <code>.
Error Type:
Warning

Possible Cause:
1. Call to Focas 1 Data Window Library to set request timeout failed.

2. Invalid timeout.

3. The device may be busy processing other requests.

4. There may be a cabling problem.

Solution:
The error code provided by the library should help diagnose the problem. If the problem is transient, the
driver should be able to set the timeout on a subsequent retry.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

See Also:
Focas 1 Data Window Library Error Codes

Failed to connect slave device <channel.device>. Could not set trans-


mission control PMC type.
Error Type:
Warning

Possible Cause:
Call to Focas 1 Data Window Library to set transmission control PMC type failed.

Solution:
Ensure that the specified PMC type is valid.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

See Also:
Unsolicited Transfer Control

Failed to connect slave device <channel.device>. Could not set trans-


mission control start address.
Error Type:

www. ptc.com
61 Fanuc Focas Ethernet Driver

Warning

Possible Cause:
Call to Focas 1 Data Window Library to set transmission control start address failed.

Solution:
Ensure that the specified start address is valid.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

See Also:
Unsolicited Transfer Control

Failed to connect slave device <channel.device>. Could not start mes-


saging session. FWLIB error: <code>.
Error Type:
Warning

Possible Cause:
1. Call to Focas 1 Data Window Library to start unsolicited messaging session failed.

2. Invalid transfer control parameters.

3. The device may not be running.

4. The device may be busy processing other requests.

5. There may be a cabling problem.

Solution:
The error code provided by the library should help diagnose the problem. If the problem is transient, the
driver should be able to connect on a subsequent retry.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

See Also:
Focas 1 Data Window Library Error Codes
Unsolicited Transfer Control

Installed version of Focas Data Window Library does not support unso-
licited communication. Device <device> deactivated.
Error Type:

www. ptc.com
Fanuc Focas Ethernet Driver 62

Serious

Possible Cause:
The server project includes slave devices, but the version of the Focas 1 Data Window Library software
installed on the system does not support unsolicited communication.

Solution:
Contact the distributor for library update. The device's firmware may also need to be upgraded.

See Also:
Additional Software Requirements

Received CNC power down notification from unsolicited message server.


Reconnecting slave devices.
Error Type:
Warning

Possible Cause:
The Unsolicited Message Server has notified the driver that with one of the devices it has started an unso-
licited messaging session with no longer appears to be running. The likely reason is that the CNC was
powered down. Network problems could also be responsible.

Solution:
Restart the CNC and check for networking problems such as cable breaks. The driver should automatically
resume communication with the device.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

Received CNC power up notification from unsolicited message server.


Error Type:
Warning

Possible Cause:
The Unsolicited Message Server has notified the driver that one of the devices it has started an unsolicited
messaging session with has been powered up. This message likely follows a "Received CNC power down
notification" message.

Solution:
This is for information only. The driver should automatically resume communication with the device.

Received socket error notification from unsolicited message server.


Error Type:
Warning

www. ptc.com
63 Fanuc Focas Ethernet Driver

Possible Cause:
The Unsolicited Message Server experienced a socket error for one or more of the connections to a device
on the network.

Solution:
If the problem is transient, the driver should recover from this error by restarting all unsolicited messaging
sessions. If not, investigate cabling, CNC power supply, and I/F board.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

Received unsolicited message server shutdown notification.


Error Type:
Warning

Possible Cause:
The Unsolicited Message Server was shutdown while the driver was using it.

Solution:
This is for information only. The driver automatically restarts the message server. For the restart to succeed,
the message server executable file "UMsgServ.exe" must be located in the host computer’s system dir-
ectory.

Note:
The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

See Also:
Unsolicited Messaging

Unsolicited message server does not seem to be running. Attempting to


launch.
Error Type:
Warning

Possible Cause:
The Unsolicited Message Server has stopped running, and was not shutdown normally.

Solution:
This is for information only. The driver automatically restarts the message server. For the restart to succeed,
the message server executable file "UMsgServ.exe" must be located in the host computer’s system folder.

Note:

www. ptc.com
Fanuc Focas Ethernet Driver 64

The device's _System._Error Tag is set if the driver fails to start an unsolicited messaging session, or restart
the session after detection of a communications problem. Tags belonging to a slave device in an error state
continue to show the last value received from the device or their initial value of zero.

See Also:
Unsolicited Messaging

Focas 1 Data Window Library Error Codes


The Fanuc Focas Ethernet Driver uses the Fanuc Focas 1 Data Window Library software to communicate with
devices on the network. When the library cannot complete a request made by this driver, it returns an error
code describing the reason. These error codes are included in the relevant driver error messages. This table
is provided to aid in diagnosing the hardware or software configuration problem causing these errors. For
more information, refer to Additional Software Requirements.

Error Error Meaning


Code Type
-17 Protocol Data from Ethernet board is incorrect.
-16 Socket Investigate CNC power supply, Ethernet cable, and I/F board.
-15 DLL There is no DLL file for CNC series.
-8 Handle Invalid connection handle.
The CNC / PMC version does not match that of the library. Replace the library or
-7 Version
the CNC / PMC control software.
-6 Unexpected An unanticipated error occurred.
-2 Reset The RESET or STOP button was pressed.
The CNC was busy processing another request. This commonly occurs during slave
-1 Busy
device connect attempts. The driver retries until a connection is made.
0 Normal Function was completed without error.
Function was not executed or is not available. This can occur if the Unsolicited Mes-
1
Function sage Server goes down while the driver is using it. The driver then attempts to
(CNC)
restart the message server.
1
No PMC The PMC does not exist.
(PMC)
2 Length Invalid data block length.
3
Number Invalid data number.
(CNC)
3
Range Invalid address range.
(PMC)
4 Invalid data attribute. This could result from a bad address type or range for data
Attribute
(CNC) Read/Write.
4
Type Invalid address type.
(PMC)
5 Data Invalid data.
6 No Option Invalid CNC option.
7 Protection Write operation is prohibited.

www. ptc.com
65 Fanuc Focas Ethernet Driver

Error Error Meaning


Code Type
8 Overflow CNC tape memory is overflowed.
9 Parameter CNC parameter is set incorrectly.
The buffer is empty or full. This can occur if there are more slave devices than the
10 Buffer
Unsolicited Message Server is configured to handle.
11 Path Invalid path number.
12 Mode Invalid CNC mode.
CNC rejected request. This can occur if an attempt is made to start multiple unso-
13 Reject
licited messaging sessions with the same device.
14 Data Server Data server error occurred.
15 Alarm Function cannot be executed due to an alarm in CNC.
16 Stop CNC status is stop or emergency.
17 Password Data is protected by the CNC data protection function.

www. ptc.com
Fanuc Focas Ethernet Driver 66

Index

Additional Software Requirements 6


Address <address> is out of range for the specified device or register. 46
Address Descriptions 22
Address Validation 46
Alarm Values 44
Array size is out of range for address <address>. 46
Array support is not available for the specified address:<address>. 47
Attempt to launch unsolicited message server failed. 53
Attempts Before Timeout 14
Auto-Demotion 15

Boolean 22

Channel Assignment 12
Communications Parameters 15
Communications Timeouts 14
Connect Timeout 14
Could not access necessary system resources for slave device: <channel.device>. 54
Could not acquire library handle for device <channel.device>. FWLIB error <code>. 49
Could not read one or more vacant macros in range starting at <address> on device <device>. 49
Could not set request timeout for device <channel.device>. FWLIB error <code>. 50

Data Collection 12
Data Type <type> is not valid for device address <address>. 47
Data Types Description 22
Demote on Failure 15
Demotion Period 15
Device <device name> is not responding. 48

www. ptc.com
67 Fanuc Focas Ethernet Driver

Device address <address> contains a syntax error. 47


Device address <address> is read only. 47
Device ID 8
Device Status Messages 48
Diagnostic Values 44
Discard Requests when Demoted 15
Do Not Scan, Demand Poll Only 13
Driver 12
Driver Error Messages 49
DWord 22

Error Descriptions 46
External Dependencies 5

Failed to connect slave device <channel.device>. Could not acquire library handle. FWLIB error
<code>. 54
Failed to connect slave device <channel.device>. Could not determine host IP address. 54
Failed to connect slave device <channel.device>. Could not set data area size. 55
Failed to connect slave device <channel.device>. Could not set data area start address. 55
Failed to connect slave device <channel.device>. Could not set data area type. 56
Failed to connect slave device <channel.device>. Could not set host IP. 56
Failed to connect slave device <channel.device>. Could not set host port. 56
Failed to connect slave device <channel.device>. Could not set message alive time. 57
Failed to connect slave device <channel.device>. Could not set message retries. 57
Failed to connect slave device <channel.device>. Could not set message timeout. 58
Failed to connect slave device <channel.device>. Could not set messaging parameters. FWLIB data error
<code>. 58
Failed to connect slave device <channel.device>. Could not set messaging parameters. FWLIB error:
<code>. 59
Failed to connect slave device <channel.device>. Could not set number of data areas. 59
Failed to connect slave device <channel.device>. Could not set request timeout. FWLIB error <code>. 60
Failed to connect slave device <channel.device>. Could not set transmission control PMC type. 60
Failed to connect slave device <channel.device>. Could not set transmission control start address. 60
Failed to connect slave device <channel.device>. Could not start messaging session. FWLIB error
<code>. 61

www. ptc.com
Fanuc Focas Ethernet Driver 68

Float 22
Focas1 Data Window Library Error Codes 64

General 11

ID 12
Identification 11
Initial Updates from Cache 14
Install a Focas Library 5
Installed version of Focas Data Window Library does not support unsolicited communication. Device
<device> deactivated. 61
Inter-Request Delay 14
Invalid XML document. Reason: Error loading Unsolicited Data Areas for device <device-name>. End
address can not be less than start address for area <area-number>. 50
Invalid XML document. Reason: Error loading Unsolicited Data Areas for device <device-name>. Invalid
area order or duplicate area number. 50
Invalid XML document. Reason: Error loading Unsolicited Data Areas for device <device-name>. Max-
imum size of area <area-number> is <size bytes>. 51

Long 22

Missing address. 47
Model 12

Name 12
Network 8

www. ptc.com
69 Fanuc Focas Ethernet Driver

Open 34
Operating Mode 12
Optimizing Fanuc Focas Ethernet Communications 21
Overview 5

Parameter Read Values 43


Path Values 45
Power Mate i 32

Read Axis Data Values 45


Read error occurred for address starting at <address> on device <channel.device>. FWLIB error:
<code>. 51
Received CNC power down notification from unsolicited message server. Reconnecting slave devices. 62
Received CNC power up notification from unsolicited message server. 62
Received socket error notification from unsolicited message server. 62
Received unsolicited message server shutdown notification. 63
Redundancy 18
Request Timeout 14
Respect Tag-Specified Scan Rate 13

Scan Mode 13
Series 15i 23
Series 16i 25
Series 18i 27
Series 21i 29
Setup 8
Short 22
Simulated 13
Slave Device Driver Error Messages 52
Status Info Tags 37

www. ptc.com
Fanuc Focas Ethernet Driver 70

Timeouts to Demote 15
Tool Offset Tags 41

Unable to start the Fanuc Focas Ethernet Data Window Library services. 52
Unable to write tag <address> on device <device name>. 48
Unsolicited Data Areas 17
Unsolicited message server does not seem to be running. Attempting to launch. 63
Unsolicited Messaging 18
Unsolicited Transfer Control 16

Word 22
Workpiece Zero Offset Tags 42
Write error occurred for address <address> on device <channel.device>. FWLIB error <code>. 52

www. ptc.com

You might also like