0% found this document useful (0 votes)
87 views

IT6500C - D Series Programming Guide

Uploaded by

Robert Seredenko
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
87 views

IT6500C - D Series Programming Guide

Uploaded by

Robert Seredenko
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 129

Highpowered and

programmable
Power supply
IT6500C/D Series Programming Guide

Model: IT6512C/IT6513C/IT6514C/IT6515C/IT6516C/IT6517C/
IT6522C/IT6523C/IT6524C/IT6525C/IT6526C/IT6527C/
IT6532C/IT6533C/IT6534C/IT6535C/IT6536C/IT6537C
/IT6542C/IT6543C/IT6544C/IT6545C/IT6546C/IT6547C
/IT6552C/IT6553C/IT6554C/IT6555C/IT6556C/IT6557C
/IT6562C/IT6563C/IT6564C/IT6565C/IT6566C/IT6567C
/IT6572C/IT6573C/IT6574C/IT6575C/IT6576C/IT6577C
/IT6582C/IT6583C/IT6584C/IT6585C/IT6586C/IT6587C/
IT6592C/IT6593C/IT6594C/IT6595C/IT6596C/IT6597C/
IT6512D/IT6513D/IT6514D/IT6515D/IT6516D/IT6517D/
IT6522D/IT6523D/IT6524D/IT6525D/IT6526D/IT6527D/
IT6532D/IT6533D/IT6534D/IT6535D/IT6536D/IT6537D
/IT6542D/IT6543D/IT6544D/IT6545D/IT6546D/IT6547D
/IT6552D/IT6553D/IT6554D/IT6555D/IT6556D/IT6557D
/IT6562D/IT6563D/IT6564D/IT6565D/IT6566D/IT6567D
/IT6572D/IT6573D/IT6574D/IT6575D/IT6576D/IT6577D
/IT6582D/IT6583D/IT6584D/IT6585D/IT6586D/IT6587D/
IT6592D/IT6593D/IT6594D/IT6595D/IT6596D/IT6597D
Version: 2.1
Notices Warranty Safety Notices
© Itech Electronic, Co., Ltd. 2018
No part of this manual may be The materials contained in this
reproduced in any form or by any means document are provided “ as is “,
(including electronic storage and and is subject to change, without
retrieval or translation into a foreign prior notice, in future editions. A CAUTION sign denotes a
language) without prior permission and Further, to the maximum extent hazard. It calls attention to an
written consent from Itech Electronics, permitted by applicable laws,
Co., Ltd. as governed by international operating procedure or practice
ITECH disclaims all warrants, either
copyright laws. express or implied, with regard to
that, if not correctly performed
this manual and any information or adhered to, could result in
Manual Part Number damage to the product or loss of
contained herein, including but not
IT6500C-402248 limited to the implied warranties of important data. Do not proceed
merchantability and fitness for a beyond a CAUTION sign until
Revision particular purpose. ITECH shall not the indicated conditions are fully
2nd Edition: MAR 12, 2018 be held liable for errors or for understood and met.
Itech Electronic, Co., Ltd. incidental or indirect damages in
connection with the furnishing, use
Trademarks or application of this document or of
any information contained herein.
Pentium is U.S. registered trademarks Should ITECH and the user enter
of Intel Corporation.
into a separate written agreement A WARNING sign denotes a
Microsoft, Visual Studio, Windows and with warranty terms covering the hazard. It calls attention to an
MS Windows are registered trademarks materials in this document that operating procedure or practice
of Microsoft Corporation in the United conflict with these terms, the that, if not correctly performed
States and/or other countries and warranty terms in the separate or adhered to, could result in
regions. agreement shall prevail. personal injury or death. Do not
Technology Licenses proceed beyond a WARNING
The hardware and/or software sign until the indicated
described herein are furnished under a conditions are fully understood
license and may be used or copied only and met.
in accordance with the terms of such
license.

Restricted Rights Legend NOTE


Restricted permissions of the U.S. A NOTE sign denotes important
government. Permissions for software hint. It calls attention to tips or
and technical data which are authorized supplementary information that
to the U.S. Government only include is essential for users to refer to.
those for custom provision to end users.
ITECH provides this customary
commercial license in software and
technical data pursuant to FAR 12.211
(Technical Data) and 12.212 (Computer
Software) and, for the Department of
Defense, DFARS 252.227-7015
(Technical Data – Commercial Items)
and DFARS 227.7202-3 (Rights in
Commercial Computer Software or
Computer Software Documentation).
IT6500C User Manual

Quality Certification and Assurance


We certify that IT6500C/D series power supply meets all the published
specifications at time of shipment from the factory.

Warranty
ITECH warrants that the product will be free from defects in material and
workmanship under normal use for a period of one (1) year from the date of
delivery (except those described in the Limitation of Warranty below).
For warranty service or repair, the product must be returned to a service center
designated by ITECH.
 The product returned to ITECH for warranty service must be shipped
PREPAID. And ITECH will pay for return of the product to customer.
 If the product is returned to ITECH for warranty service from overseas, all
the freights, duties and other taxes shall be on the account of customer.

Limitation of Warranty
This Warranty will be rendered invalid if the product is:
 Damaged resulting from customer-wired circuits or customer-supplied parts
or accessories;
 Modified or repaired by customer without authorization;
 Damaged resulting from customer-wired circuits or use in an environment
not designated by us;
 The product model or serial number is altered, deleted, removed or made
illegible by customer;
 Damaged as a result of accidents, including but not limited to lightning,
moisture, fire, improper use or negligence.

Safety Symbols
Direct current ON (power)

Alternating current OFF (power)

Both direct and alternating Power-on state


current
Chassis (earth ground) symbol. Power-off state

Earth (ground) terminal Reference


terminal

Caution Positive terminal

Warning (refer to this manual for Negative terminal


specific Warning or Caution
information)
A chassis terminal - -

Copyright© Itech Electronics Co., Ltd. i


IT6500C User Manual

Safety Precautions
The following safety precautions must be observed during all phases of
operation of this instrument. Failure to comply with these precautions or specific
warnings elsewhere in this manual will constitute a default under safety
standards of design, manufacture and intended use of the instrument. ITECH
assumes no liability for the customer’s failure to comply with these precautions.

 Do not use the instrument if it is damaged. Before operation, check


the casing to see whether it cracks. Do not operate the instrument in
the presence of inflammable gasses, vapors or dusts.
 The power supply is provided with a power line during delivery and
should be connected to junction box. Before operation, be sure that
the power supply is well grounded. Make sure to use the power cord
supplied by ITECH.
 Check all marks on the instrument before connecting the instrument
to power supply.
 Use electric wires of appropriate load. All loading wires should be
capable of bearing maximum short-circuit of electronic load without
overheating. If there are multiple loads, each pair of the load power
cord must be carry out the full rated short-circuit output current of the
power securely.
 Ensure the voltage fluctuation of mains supply is less than 10% of the
working voltage range in order to reduce risks of fire and electric
shock.
 Do not install alternative parts on the instrument or perform any
unauthorized modification.
 Do not use the instrument if the detachable cover is removed or
loosen.
 To prevent the possibility of accidental injuries, be sure to use the
power adapter supplied by the manufacturer only.
 We do not accept responsibility for any direct or indirect financial
damage or loss of profit that might occur when using the instrument.
 This instrument is used for industrial purposes. Do not apply this
product to IT power supply system.
 Never use the instrument with a life-support system or any other
equipment subject to safety requirements.

 Failure to use the instrument as directed by the manufacturer may


render its protective features void.
 Always clean the casing with a dry cloth. Do not clean the internals.
 Make sure the vent hole is always unblocked.

Environmental Conditions
The instrument is designed for indoor use and an area with low condensation.
The table below shows the general environmental requirements for the
instrument.
Environmental Conditions Requirements
Operating temperature 0°C to 40°C
Operating humidity 20%-80% (non-condensation)
Copyright© Itech Electronics Co., Ltd. ii
IT6500C User Manual
Storage temperature -10°C to 70 °C
Altitude Operating up to 2,000 meters
Installation category II
Pollution degree Pollution degree 2
Note
To make accurate measurements, allow the instrument to warm up for 30 min.

Regulatory Markings
The CE mark indicates that the product
complies with all the relevant European
legal directives. The specific year (if any)
affixed refers to the year when the design
was approved.
The instrument complies with the WEEE
Directive (2002/96/EC) marking
requirement. This affix product label
indicates that you must not discard the
electrical/electronic product in domestic
household waste.

This symbol indicates the time period


during which no hazardous or toxic
substances are expected to leak or
deteriorate during normal use. The
expected useful life of the product is 10
years. The product can be used safely
during the 10-year Environment Friendly
Use Period (EFUP). Upon expiration of
the EFUP, the product must be
immediately recycled.

Waste Electrical and Electronic Equiment (WEEE)


Directive
2002/96/EC Waste Electrical and Electronic Equipment
(WEEE) Directive
This product complies with the WEEE Directive (2002/96/EC)
marking requirement. This affix product label indicates that you
must not discard the electrical/electronic product in domestic
household waste.
Product Category
With reference to the equipment classifications described in the
Annex 1 of the WEEE Directive, this instrument is classified as
a “ Monitoring and Control Instrument “.
To return this unwanted instrument, contact your nearest ITECH
office.

Copyright© Itech Electronics Co., Ltd. iii


IT6500C/D Programming and Syntax Guide

Compliance Information
Complies with the essential requirements of the following applicable European
Directives, and carries the CE marking accordingly:
 Electromagnetic Compatibility (EMC) Directive 2014/30/EU
 Low-Voltage Directive (Safety) 2014/35/EU

Conforms with the following product standards:

EMC Standard
IEC 61326-1:2012/ EN 61326-1:2013 ¹²³
Reference Standards
CISPR 11:2009+A1:2010/ EN 55011:2009+A1:2010 (Group 1, Class A)
IEC 61000-4-2:2008/ EN 61000-4-2:2009
IEC 61000-4-3:2006+A1:2007+A2:2010/ EN 61000-4-3:2006+A1:2008+A2:2010
IEC 61000-4-4:2004+A1:2010/ EN 61000-4-4:2004+A1:2010
IEC 61000-4-5:2005/ EN 61000-4-5:2006
IEC 61000-4-6:2008/ EN 61000-4-6:2009
IEC 61000-4-11:2004/ EN 61000-4-11:2004

1. The product is intended for use in non-residential/non-domestic environments. Use of the


product in residential/domestic environments may cause electromagnetic interference.
2. Connection of the instrument to a test object may produce radiations beyond the specified
limit.
3. Use high-performance shielded interface cable to ensure conformity with the EMC standards
listed above.

Safety Standard
IEC 61010-1:2010/ EN 61010-1:2010

Copyright© Itech Electronics Co., Ltd. iv


IT6500C/D Programming and Syntax Guide

Content
Quality Certification and Assurance ...................................................................................................................... 1
Warranty............................................................................................................................................................... 1
Limitation of Warranty .......................................................................................................................................... 1
Safety Symbols ...................................................................................................................................................... 1
Safety Precautions ................................................................................................................................................ 2
Environmental Conditions ..................................................................................................................................... 2
Regulatory Markings ............................................................................................................................................. 3
Waste Electrical and Electronic Equiment (WEEE) Directive................................................................................... 3
Compliance Information ....................................................................................................................................... 4
Chapter1 Remote Control ................................................................................................................................ 1
1.1 Overview ......................................................................................................................................................... 1
1.2 SCPI Command Introduction ........................................................................................................................... 1
1.3 Command Type of SCPI ................................................................................................................................... 1
1.4 Message Typeof SCPI....................................................................................................................................... 3
1.5 Response Data Type ........................................................................................................................................ 5
1.6 Command Format ........................................................................................................................................... 6
1.7 Data Type ........................................................................................................................................................ 8
1.8 Communication Interface ................................................................................................................................ 9
1.8.4 LAN Interface ............................................................................................................................................. 11
Chapter2 SCPI status register ........................................................................................................................ 13
Chapter3 SCPI Command Description............................................................................................................ 15
STATus:QUEStionable[:EVENt]? ........................................................................................................................... 15
STATus:QUEStionable:CONDition? ....................................................................................................................... 15
STATus:QUEStionable:ENABle .............................................................................................................................. 15
STATus:QUEStionable:PTRansition ....................................................................................................................... 16
STATus:QUEStionable:NTRansition ...................................................................................................................... 16
STATus:OPERation[:EVENt]? ................................................................................................................................ 17
STATus:OPERation:CONDition? ............................................................................................................................ 17
STATus:OPERation:ENABle ................................................................................................................................... 17
STATus:OPERation:PTRansition ............................................................................................................................ 18
STATus:OPERation:NTRansition ........................................................................................................................... 18
SYSTem:BEEPer:IMMediate ................................................................................................................................. 19
SYSTem:BEEPer[:STATe] ....................................................................................................................................... 19
SYSTem:VERSion? ................................................................................................................................................ 19
SYSTem:ERRor? ................................................................................................................................................... 20
SYSTem:REMote .................................................................................................................................................. 20
SYSTem:LOCal...................................................................................................................................................... 20
SYSTem:RWLock .................................................................................................................................................. 21
SYSTem:COMMunicate:SELect............................................................................................................................. 21
SYSTem:COMMunicate:GPIB:ADDRess ................................................................................................................ 21
SYSTem:COMMunicate:SERial:BAUDrate ............................................................................................................. 22
SYSTem:COMMunicate:LAN:CURRent:ADDRess................................................................................................... 22
SYSTem:COMMunicate:LAN:CURRent:DGATeway ................................................................................................ 23
SYSTem:COMMunicate:LAN:CURRent:SMASk ...................................................................................................... 23
SYSTem:COMMunicate:LAN:DHCP[:STATe] .......................................................................................................... 24
SYSTem:COMMunicate:LAN:SOCKetport ............................................................................................................. 24
SYSTem:COMMunicate:LAN:MACaddress? .......................................................................................................... 25
Chapter4 Display Related Command ............................................................................................................. 26
DISPlay[:WINDow][:STATe] .................................................................................................................................. 26
DISPlay[:WINDow]:TEXT[:DATA] .......................................................................................................................... 26
DISPlay[:WINDOW]:TEXT:CLEar ........................................................................................................................... 26
Chapter5 Trigger Command ........................................................................................................................... 28
TRIGger[:IMMediate] .......................................................................................................................................... 28
TRIGger:SOURce ................................................................................................................................................. 28
Copyright© Itech Electronics Co., Ltd. v
IT6500C/D Programming and Syntax Guide
Chapter6 Input Measuring Commands .......................................................................................................... 29
MEASure[:SCALar]:VOLTage[:DC]? ....................................................................................................................... 29
FETCh[:SCALar]:VOLTage[:DC]? ............................................................................................................................ 29
MEASure[:SCALar]:CURRent[:DC]? ...................................................................................................................... 29
FETCh[:SCALar]:CURRent[:DC]? ........................................................................................................................... 30
MEASure[:SCALar]:POWer[:DC]? ......................................................................................................................... 30
FETCh[:SCALar]:POWer[:DC]? .............................................................................................................................. 30
FETCh? ................................................................................................................................................................ 30
MEASure? ........................................................................................................................................................... 31
Chapter7 Output Commands ......................................................................................................................... 32
[SOURce:]CURRent[:LEVel][:IMMediate][:AMPLitude]......................................................................................... 32
[SOURce:]CURRent:MINimum[:LEVel] ................................................................................................................. 32
[SOURce:]CURRent:MAXimum[:LEVel] ................................................................................................................ 33
[SOURce:]CURRent:RISE[:LEVel] .......................................................................................................................... 33
[SOURce:]CURRent:FALL[:LEVel] .......................................................................................................................... 34
[SOURce:]CURRent:PROTection:STATe ................................................................................................................. 34
[SOURce:]CURRent:PROTection[:LEVel] ............................................................................................................... 35
[SOURce:]CURRent:PROTection:DELay ................................................................................................................ 35
[SOURce:]VOLTage[:LEVel][:IMMediate][:AMPLitude] ......................................................................................... 36
[SOURce:]VOLTage:MINimum[:LEVel] .................................................................................................................. 36
[SOURce:]VOLTage:MAXimum[:LEVel] ................................................................................................................. 37
[SOURce:]VOLTage:RISE[:LEVel] ........................................................................................................................... 38
[SOURce:]VOLTage:FALL[:LEVel] ........................................................................................................................... 38
[SOURce:]VOLTage:PROTection:STATe .................................................................................................................. 39
[SOURce:]VOLTage:PROTection[:LEVel] ................................................................................................................ 39
[SOURce:]VOLTage:PROTection:DELay ................................................................................................................. 39
[SOURce:]POWer[:LEVel][:IMMediate][:AMPLitude] ........................................................................................... 40
[SOURce:]POWer:MINimum[:LEVel] .................................................................................................................... 40
[SOURce:]POWer:MAXimum[:LEVel] ................................................................................................................... 41
[SOURce:]POWer:RISE[:LEVel] ............................................................................................................................. 42
[SOURce:]POWer:FALL[:LEVel] ............................................................................................................................. 42
[SOURce:]POWer:PROTection:STATe .................................................................................................................... 43
[SOURce:]POWer:PROTection[:LEVel] .................................................................................................................. 43
[SOURce:]POWer:PROTection:DELay ................................................................................................................... 43
[SOURce:]RESistance[:LEVel][:IMMediate][:AMPLitude] ...................................................................................... 44
[SOURce:]PROTection:TRIGgered?....................................................................................................................... 45
[SOURce:]PROTection:CLEar ................................................................................................................................ 45
[SOURce:]APPLy .................................................................................................................................................. 45
[SOURce:]EXTern[:STATe] ..................................................................................................................................... 45
[SOURce:]EXTern:MONitor:RANGe ...................................................................................................................... 46
[SOURce:]EXTern:PROGram:MODE ..................................................................................................................... 46
[SOURce:]EXTern:PROGram:RANGe .................................................................................................................... 47
[SOURce:]OUTPut[:STATe] ................................................................................................................................... 47
[SOURce:]CV:PRIority .......................................................................................................................................... 48
[SOURce:]CC:PRIority .......................................................................................................................................... 48
[SOURce:]PRIority:TYPE ...................................................................................................................................... 49
[SOURce:]FILTer:LEVel ......................................................................................................................................... 49
[SOURce:]SENSe:RVERse:PROTect[:STATe] ........................................................................................................... 50
Chapter8 DCR Command ............................................................................................................................... 51
DCR[:STATe] ......................................................................................................................................................... 51
"DCR:DATA?", ...................................................................................................................................................... 51
DCR:BATTery:CAPAcity[:LEVel] ............................................................................................................................. 52
Chapter9 Load Related Command(IT6500C) ............................................................................................. 53
LOAD[:STATe]....................................................................................................................................................... 53
LOAD:SELection................................................................................................................................................... 53
LOAD:NUMBer[:EXTernal] ................................................................................................................................... 54
LOAD:CURRent[:LEVel][:IMMediate][:AMPLitude] ............................................................................................... 54
Copyright© Itech Electronics Co., Ltd. vi
IT6500C/D Programming and Syntax Guide
LOAD:CURRent:MINimum[:LEVel] ....................................................................................................................... 55
LOAD:CURRent:MAXimum[:LEVel]....................................................................................................................... 55
LOAD:CURRent:RISE[:LEVel] ................................................................................................................................ 56
LOAD:CURRent:FALL[:LEVel] ................................................................................................................................ 56
LOAD:CURRent:PROTection:STATe ....................................................................................................................... 57
LOAD:CURRent:PROTection[:LEVel] ..................................................................................................................... 57
LOAD:CURRent:PROTection:DELay....................................................................................................................... 58
LOAD:POWer[:LEVel][:IMMediate][:AMPLitude].................................................................................................. 58
LOAD:POWer:MINimum[:LEVel] .......................................................................................................................... 59
LOAD: POWer:MAXimum[:LEVel] ........................................................................................................................ 59
LOAD: POWer:RISE[:LEVel] .................................................................................................................................. 60
LOAD:POWer:FALL[:LEVel] ................................................................................................................................... 61
LOAD:POWer:PROTection:STATe .......................................................................................................................... 61
LOAD:POWer:PROTection[:LEVel] ........................................................................................................................ 62
LOAD:POWer:PROTection:DELay ......................................................................................................................... 62
Chapter10 List Operation Commands .............................................................................................................. 64
LIST[:STATe] ......................................................................................................................................................... 64
LIST:RECall ........................................................................................................................................................... 64
LIST:EDIT ............................................................................................................................................................. 65
LIST:REPeat ......................................................................................................................................................... 65
LIST:SEQuence:COUNt ......................................................................................................................................... 65
LIST:SEQuence:SELect ......................................................................................................................................... 66
LIST:SEQuence:REPeat ......................................................................................................................................... 66
LIST:SAVe............................................................................................................................................................. 67
LIST:PAUSe[:STATe] .............................................................................................................................................. 67
Chapter11 Wave Operation Command ........................................................................................................... 68
SEQuence:EDIT ................................................................................................................................................... 68
SEQuence:RECall ................................................................................................................................................. 68
SEQuence:STEP:COUNt ....................................................................................................................................... 68
SEQuence[:STEP]:VOLTage................................................................................................................................... 69
SEQuence[:STEP]:CURRent .................................................................................................................................. 69
SEQuence[:STEP]:LOAD:CURRent? ...................................................................................................................... 70
SEQuence[:STEP]:WIDTh ..................................................................................................................................... 70
SEQuence[:STEP]:SLOPe ...................................................................................................................................... 71
SEQuence:SAVe ................................................................................................................................................... 71
Chapter12 Car Wave Command(IT6500C) .................................................................................................. 72
CARWave:ISO16750:SHORt:DROP[:STATe] ........................................................................................................... 72
CARWave:ISO16750:SHORt:DROP:VOLTage[:LEVel] ............................................................................................. 72
CARWave:ISO16750:RESet[:STATe] ...................................................................................................................... 73
CARWave:ISO16750:RESet:VOLTage[:LEVel] ........................................................................................................ 73
CARWave:ISO16570:STARtup:PROFile[:STATe] ..................................................................................................... 74
CARWave:ISO16750:STARtup:PROFile:VOLTage[:LEVel] ....................................................................................... 74
CARWave:ISO16750:STARtup:PROFile:INDex ....................................................................................................... 74
CARWave:STARtup:DIN40839[:STATe].................................................................................................................. 75
CARWave:STARtup:DIN40839:VOLTage:STARt:LEVel ............................................................................................ 76
CARWave:ISO21848:Umaxdyn:TEST:PULSe[:STATe] ............................................................................................. 76
CARWave:ISO21848:MOMENTary:VOLTage:DROP[:STATe] ................................................................................... 77
CARWave:ISO21848:RESet[:STATe] ...................................................................................................................... 77
CARWave:ISO21848:RESet:VOLTage[:LEVel] ........................................................................................................ 78
CARWave:ISO21848:STARtup:PROFile[:STATe] ..................................................................................................... 78
CARWave:ISO16750:LOAD:DUMP[:STATe] ........................................................................................................... 79
CARWave:ISO16750:LOAD:DUMP:TEST[:MODe].................................................................................................. 79
CARWave:ISO16750:LOAD:DUMP[:VOLTage]:UN[:LEVel] ..................................................................................... 80
CARWave:ISO16750:LOAD:DUMP[:VOLTage]:US[:LEVel] ...................................................................................... 80
CARWave:ISO16750:LOAD:DUMP[:TIMe]:TD[:LEVel] ........................................................................................... 81
CARWave:ISO16750:LOAD:DUMP:VOLTage[:LEVel].............................................................................................. 81
CARWave:SAE[:TEST]:2B[:STATe] ......................................................................................................................... 82

Copyright© Itech Electronics Co., Ltd. vii


IT6500C/D Programming and Syntax Guide
CARWave:SAE[:TEST]:2B:VOLTage[:LEVel] ............................................................................................................ 82
CARWave:SAE[:TEST]:2B[:TIMe]:TD[:LEVel] ......................................................................................................... 82
CARWave:SAE[:TEST]:4[:STATe] ............................................................................................................................ 83
CARWave:SAE[:TEST]:4:VOLTage[:LEVel] .............................................................................................................. 83
CARWave:SAE[:TEST]:4[:VOLTage]:VS[:LEVel]....................................................................................................... 84
CARWave:SAE[:TEST]:4[:VOLTage]:VA[:LEVel] ...................................................................................................... 84
CARWave:SAE[:TEST]:4[:TIMe]:T7[:LEVel] ............................................................................................................ 85
CARWave:SAE[:TEST]:4[:TIMe]:T9[:LEVel] ............................................................................................................ 85
CARWave:SAE[:TEST]:4[:TIMe]:T11[:LEVel] .......................................................................................................... 86
CARWave:SAE[:TEST]:5[:STATe] ............................................................................................................................ 86
CARWave:SAE[:TEST]:5:TEST[:MODe] .................................................................................................................. 87
CARWave:SAE[:TEST]:5[:VOLTage]:UN[:LEVel] ..................................................................................................... 87
CARWave:SAE[:TEST]:5[:VOLTage]:US[:LEVel] ...................................................................................................... 88
CARWave:SAE[:TEST]:5[:TIMe]:TD[:LEVel] ........................................................................................................... 88
CARWave:SAE[:TEST]:5:VOLTage[:LEVel] .............................................................................................................. 89
CARWave:LV124:E02[:STATe] ............................................................................................................................... 89
CARWave:LV124:E04[:STATe] ............................................................................................................................... 89
CARWave:LV124:E05[:STATe] ............................................................................................................................... 90
CARWave:LV124:E07[:STATe] ............................................................................................................................... 90
CARWave:LV124:E07:UBMAX[:LEVel] .................................................................................................................. 91
CARWave:LV124:E07:UBMIN[:LEVel] ................................................................................................................... 91
CARWave:LV124:E07[:UBMIN]:TIMe ................................................................................................................... 92
CARWave:LV124:E08[:STATe] ............................................................................................................................... 92
CARWave:LV124:E08:UBMAX[:LEVel] .................................................................................................................. 93
CARWave:LV124:E08:UBMIN[:LEVel] ................................................................................................................... 93
CARWave:LV124:E08[:UBMIN]:TIMe ................................................................................................................... 94
CARWave:LV124:E09[:STATe] ............................................................................................................................... 94
CARWave:LV124:E09:UBMIN[:LEVel] ................................................................................................................... 95
CARWave:LV124:E11[:STATe] ............................................................................................................................... 95
CARWave:LV124:E11:TEST:MODE ........................................................................................................................ 96
CARWave:LV124:E11:PULSe:MODE ..................................................................................................................... 96
CARWave:LV124:E12[:STATe] ............................................................................................................................... 96
CARWave:LV124:E12:DELTAU[:LEVel]................................................................................................................... 97
Chapter13 Battery Charge and Discharge Statistic Command ......................................................................... 98
BATTery:CAPacity:CLEar ...................................................................................................................................... 98
FETCh:BATTery:CAPacity[:CHARge]? .................................................................................................................... 98
FETCh:BATTery:CAPacity:DISCharge? ................................................................................................................... 98
Chapter14 Calibration Command .................................................................................................................. 100
CALibrate:SECure[:STATe] .................................................................................................................................. 100
CALibrate:VOLTage:LEVel ................................................................................................................................... 100
CALibrate:VOLTage[:DATA] ................................................................................................................................. 100
CALibrate:CURRent:LEVel .................................................................................................................................. 101
CALibrate:CURRent[:DATA] ................................................................................................................................ 101
CALibrate:MONitor:VOLTage:LEVel .................................................................................................................... 101
CALibrate:MONitor:VOLTage[:DATA] .................................................................................................................. 101
CALibrate:MONitor:CURRent:LEVel ................................................................................................................... 102
CALibrate:MONitor:CURRent[:DATA] ................................................................................................................. 102
CALibrate:PROGram:VOLTage:LEVel................................................................................................................... 102
CALibrate:PROGram:VOLTage[:DATA] ................................................................................................................ 103
CALibrate:PROGram:CURRent:LEVel .................................................................................................................. 103
CALibrate:PROGram:CURRent[:DATA] ................................................................................................................ 103
CALibrate:EQUal:INPut:CURRent:LEVel .............................................................................................................. 104
CALibrate:EQUal:INPut:CURRent[:DATA]............................................................................................................ 104
CALibrate:EQUal:OUTPut:CURRent:LEVel .......................................................................................................... 104
CALibrate:EQUal:OUTPut:CURRent[:DATA] ........................................................................................................ 104
CALibrate:SUMMary:OUTPut:CURRent:LEVel .................................................................................................... 105
CALibrate:SUMMary:OUTPut:CURRent[:DATA] .................................................................................................. 105
CALibrate:SAVe ................................................................................................................................................. 105

Copyright© Itech Electronics Co., Ltd. viii


IT6500C/D Programming and Syntax Guide
CALibrate:INITialize ........................................................................................................................................... 106
Chapter15 Parallel Related Command ........................................................................................................... 107
LINK[:STATe] ...................................................................................................................................................... 107
LINK:ROLE ......................................................................................................................................................... 107
LINK:NUMBer.................................................................................................................................................... 107
Chapter16 TraceRelated Command(IT6500C) ................................................................................................ 109
TRACe:CLEar ..................................................................................................................................................... 109
TRACe:POINts ................................................................................................................................................... 109
TRACe:FEED:CONTrol ........................................................................................................................................ 109
TRACe:FEED:SELected ....................................................................................................................................... 110
TRACe:DELay ..................................................................................................................................................... 110
TRACe:TIMer ..................................................................................................................................................... 111
TRACe:POINts:ACTual? ...................................................................................................................................... 111
TRACe:CLEar:AUTO[:STATe] ............................................................................................................................... 111
TRACe:DATA? .................................................................................................................................................... 112
Chapter17 IEEE-488 Commands..................................................................................................................... 113
*CLS .................................................................................................................................................................. 113
*ESE .................................................................................................................................................................. 113
*ESR? ................................................................................................................................................................ 114
*IDN? ................................................................................................................................................................ 114
*OPC ................................................................................................................................................................. 114
*PSC.................................................................................................................................................................. 115
*RST .................................................................................................................................................................. 115
*SRE <n> ........................................................................................................................................................... 115
*STB.................................................................................................................................................................. 116
*SAV ................................................................................................................................................................. 116
*RCL:................................................................................................................................................................. 117
*TST? ................................................................................................................................................................ 117

Copyright© Itech Electronics Co., Ltd. ix


Remote Control

Chapter1 Remote Control


1.1 Overview
This chapter will provide following remote configuration introductions:
 SCPI Command Introduction
 Command type
 Command format
 Data format
 Remote Operation

1.2 SCPI Command Introduction


SCPI is short for Standard Commands for Programmable Instruments which
defines a communication method of bus controller and instrument. It is based
on ASCII and supply for testing and measuring instruments. SCPI command is
based on hierarchical architecture which also known as tree system. In this
system, Relevant Command is returned to a common node or root, so that a
subsystem is formed.
A part of OUTPut subsystem is listed below:
OUTPut:
SYNC {OFF|0|ON|1}
SYNC:
MODE {NORMal|CARRier}
POLarity {NORMal|INVerted}
OUTPut is the root class keyword, SYNC is the second keyword, MODE and
POLarity are the third keyword. Colon(:) is used for separating the command
keyword and the next level keyword.

1.3 Command Type of SCPI


SCPI has two types of commands, common and subsystem.
 Common commands generally are not related to specific operation but to
controlling overall.electronic load functions, such as reset, status, and
synchronization. All common commands consist of a three-letter mnemonic
preceded by an asterisk: *RST *IDN? *SRE 8.
 Subsystem commands perform specific electronic load functions. They are
organized into an inverted tree structure with the "root" at the top. The
following figure shows a portion of a subsyste command tree, from which
you access the commands located along the various paths.

Copyright© Itech Electronics Co., Ltd. 1


Remote Control

Multiple commands in a message


Multiple SCPI commands can be combined and sent as a single
message with one message terminator. There are two important
considerations when sending several commands within a single
message:
 Use a semicolon to separate commands within a message.
 Head paths influence how the instrument interprets commands.
We consider the head path as a string which will be inserted in front of
every command of a message. As for the first command of a message,
the head path is a null string; for each subsequent command, the head
path is a string which is defined to form the current command until and
including the head of the last colon separator. A message with two
combined commands: CURR:LEV 3;PROT:STAT OFF
The example indicates the effect of semicolon and explains the concept
of head path. Since the head path is defined to be "CURR" after "curr: lev
3", the head of the second command, "curr", is deleted and the
instrument explains the second command as: CURR:PROT:STAT OFF
If "curr" is explicitly included in the second command, it is semantically
wrong. Since combining it with the head path will become
"CURR:CURR:PROT:STAT OFF", resulting in wrong command.

Movement in the subsystem


In order to combine commands from different subsystems, you need to
be able to reset the header path to a null string within a message. You do
this by beginning the command with a colon (:), which discards any
previous header path. For example, you could clear the output protection
and check the status of the Operation Condition register in one message
by using a root specifier as follows:
PROTection:CLEAr;:STATus:OPERation:CONDition?
The following message shows how to combine commands from different
subsystems as well as within the same subsystem:
POWer:LEVel 200;PROTection 28; :CURRent:LEVel 3;PROTection:STATe ON
Note the use of the optional header LEVel to maintain the correct path
within the voltage and current subsystems, and the use of the root
specifier to move between subsystems.
Copyright© Itech Electronics Co., Ltd. 2
Remote Control

Including Common Commands


You can combine common commands with subsystem commands in the
same message. Treat the common command as a message unit by
separating it with a semicolon (the message unit separator). Common
commands do not affect the header path; you may insert them anywhere
in the message.
VOLTage:TRIGgered 17.5;:INITialize;*TRG
OUTPut OFF;*RCL 2;OUTPut ONIT872X-3X SCPI Communication protocol 17

Case sensitivity
Common commands and SCPI commands are not case sensitive. You
can use upper or lower, for example:

*RST = *rst
:DATA? = :data?
:SYSTem:PRESet = :system:preset

Long-form and short-form versions


A SCPI command word can be sent in its long-form or short-form version.
The command subsystem tables in Section 5 provide the in the
long-form version. However, the short-form version is indicated by upper
case characters. Examples:
:SYSTem:PRESet long-form
:SYST:PRES short form
:SYSTem:PRES long-form and short-form combination
Note that each command word must be in long-form or short-form, and
not something in between.
For example, :SYSTe:PRESe is illegal and will generate an error. The
command will not be executed.

Query
Observe the following precautions with queries:
 Set up the proper number of variables for the returned data. For example, if
you are reading back a measurement array, you must dimension the array
according to the number of measurements that you have placed in the
measurement buffer.
 Read back all the results of a query before sending another command to
the electronic load. Otherwise a Query Interrupted error will occur and the
unreturned data will be lost.

1.4 Message Typeof SCPI


There are two types of SCPI messages, program and response.
 program message: A program message consists of one or more properly
formatted SCPI commands sent from the controller to the electronic load.
The message, which may be sent at any time, requests the electronic load
to perform some action.
Copyright© Itech Electronics Co., Ltd. 3
Remote Control

 response message: A response message consists of data in a specific


SCPI format sent from the electronic load to the controller. The electronic
load sends the message only when commanded by a program message
called a "query."
The next figure illustrates SCPI message structure:

The Message Unit


The simplest SCPI command is a single message unit consisting of a command
header (or keyword) followed by a message terminator. The message unit may
include a parameter after the header. The parameter can be numeric or a
string.
VOLTage 20<NL>

Headers
Headers, also referred to as keywords, are instructions recognized by the
electronic load. Headers may be either in the long form or the short form. In the
long form, the header is completely spelled out, such as VOLTAGE, STATUS,
and DELAY. In the short form, the header has only the first three or four letters,
such as VOLT, STAT, and DEL.

Query Indicator
Following a header with a question mark turns it into a query (VOLTage?,
VOLTage:PROTection?). If a query contains a parameter, place the query
indicator at the end of the last header(VOLTage:PROTection?MAX).

Message Unit Separator


When two or more message units are combined into a compound message,
separate the units with a semicolon (STATus:OPERation?;QUEStionable?).

Root Specifier
When it precedes the first header of a message unit, the colon becomes the
root specifier. It tells the command parser that this is the root or the top node of
the command tree.

Message Terminator
A terminator informs SCPI that it has reached the end of a message. Three
permitted message terminators are:
Copyright© Itech Electronics Co., Ltd. 4
Remote Control

 newline (<NL>),decimal 10 or hexadecimal 0X0A in ASCII.


 end or identify (<END>)
 both of the above (<NL><END>).
In the examples of this guide, there is an assumed message terminator at the
end of each message.

Command execution rules


 Commands execute in the order that they are presented in the program
message.
 An invalid command generates an error and, of course, is not executed.
 Valid commands that precede an invalid command in a multiple command
program message are executed.
 Valid commands that follow an invalid command in a multiple command
program message are ignored.

1.5 Response Data Type


Character strings returned by query statements may take either of the following
forms, depending on the length of the returned string:
<CRD> Character Response Data. Permits the return of character strings.
<AARD> Arbitrary ASCII Response Data. Permits the return of undelimited 7-bit
ASCII. This data type has an implied message terminator.
<SRD> String Response Data. Returns string parameters enclosed in double
quotes

Response messages
A response message is the message sent by the instrument to the computer in
response to aquery command.

Sending a response message


Afte sending a query command, the response message is placed in the Output
Queue. When the IT8800 Series is then addressed to talk, the response
message is sent from the Output Queue to the computer.

Multiple response messages


If you send more than one query command in the same program message (see
the paragraph entitled, “ Multiple Command Messages “), the multiple response
messages for all the queries is sent to the computer when the IT8800 Series is
addressed to talk. The responses are sent in the order that the query
commands were sent and are separated by semicolons (;). Items within the
same query are separated by commas (,). The following example shows the
response message for a program message that contains four single item query
commands:
0; 1; 1; 0

Response message terminator (RMT)


Each response is terminated with an LF (line feed) and EOI (end or identify).
The following example shows how a multiple response message is terminated:
0; 1; 1; 0; <RMT>

Copyright© Itech Electronics Co., Ltd. 5


Remote Control

Message exchange protocol


Two rules summarize the message exchange protocol:
Rule 1.You must always tell the IT6500 Series what to send to the computer.
The following two steps must always be performed to send information from the
instrument other computer:
1. Send the appropriate query command(s) in a program message.1.
2. Address the IT6500 Series to talk.
Rule 2.The complete response message must be received by the computer
before another program message can be sent to the IT6500 Series.

1.6 Command Format


Formats for command display are as follows:
[SOURce[1|2]:]VOLTage:UNIT {VPP|VRMS|DBM}
[SOURce[1|2]:]FREQuency:CENTer
{<frequency>|MINimum|MAXimum|DEFault}
Based on the command syntax, most commands (and certain Parameter) are
expressed in both upper and lower cases. Upper case refers to abbreviation of
commands. Shorter program line may send commands in abbreviated format.
Long-format commands may be sent to ensure better program readability.
For example, both formats of VOLT and VOLTAGE are acceptable in the above
syntax statements. Upper or lower case may be used. Therefore, formats of
VOLTAGE, volt and Volt are all acceptable. Other formats (such as VOL and
VOLTAG) are invalid and will cause errors.
 Parameter options with given command strings are included in the brace
({ }). The brace is not sent along with command strings.
 Vertical stripes (|) separate several parameter options with given command
strings. For example, {VPP|VRMS|DBM} indicates that you may assign
"APP", "VRMS" or "DBM" in the above commands. Vertical stripes are not
sent along with command strings.
 Angle brackets (< >) in the second example indicates that a value must be
assigned to the parameter in the brace. For example, the parameter in the
angle bracket is <frequency> in the above syntax statements. Angle
brackets are not sent along with command strings. You must assign a
value (such as "FREQ:CENT 1000") to the parameter, unless you select
other options displayed in the syntax (such as "FREQ:CENT MIN").
 Some syntax elements (such as nodes and Parameter) are included in
square brackets ([ ]). It indicates that these elements can be selected and
omitted. Angle brackets are not sent along with command strings. If no
value is assigned to the optional Parameter, the instrument will select a
default value. In the above examples, "SOURce[1|2]" indicates that you
may refer to source channel 1 by "SOURce" or "SOURce1" or "SOUR1" or
"SOUR". In addition, since the whole SOURce node is optional (in the
square bracket), you can refer to the channel 1 by omitting the whole
SOURce node. It is because the channel 1 is the default channel for
SOURce language node. On the other hand, if you want to refer to channel
2, "SOURce2" or "SOUR2" must be used in the program line.

Colon (:)
It is used to separate key words of a command with the key words in next level.
Copyright© Itech Electronics Co., Ltd. 6
Remote Control

As shown below:
APPL:SIN 455E3,1.15,0.0
In this example, APPLy command assigns a sine wave with frequency of 455
KHz, amplitude of 1.15 V and DC offset of 0.0 V.

Semicolon (;)
It is used to separate several commands in the same subsystem and can also
minimize typing. For example, to send the following command string:
TRIG:SOUR EXT; COUNT 10
has the same effect as sending the following two commands:
TRIG:SOUR EXT
TRIG:COUNT 10

Question mark (?)


You can insert question marks into a command to query current values of most
Parameter. For example, the following commands will trigger to set the count as
10:
TRIG:COUN 10
Then, you may query count value by sending the following command:
TRIG:COUN?
You may also query the allowable minimum or maximum count as follows:
TRIG:COUN?MIN
TRIG:COUN?MAX

Comma (,)
If a command requires several Parameter, then a comma must be used to
separate adjacent Parameter.

Space
You must use blank characters, [TAB] or [Space] to separate Parameter with
key words of commands.

Generic commands (*)


Execute functions like reset, self inspection and status operation. Generic
commands always start with a asterisk (*) and occupy 3 character sizes,
including one or more Parameter. Key words of a command and the first
parameter are separated by a space. Semicolon (;) can separate several
commands as follows:
*RST; *CLS; *ESE 32; *OPC?

Command terminator
Command strings sent to the instrument must end with a <Newline> (<NL>)
character. IEEE-488 EOI (End or Identify) information can be used as <NL>
character to replace termination command string of <NL> character. It is
acceptable to place one <NL> after a <Enter>. Termination of command string
always resets current SCPI command path to root level.

Copyright© Itech Electronics Co., Ltd. 7


Remote Control

NOTE
As for every SCPI message with one query sent to the instrument, the
instrument will use a <NL> or newline sign (EOI) to terminate response of
return. For example, if "DISP:TEXT?" is sent, <NL> will be placed after
the returned data string to terminate response. If an SCPI message
includes several queries separated by semicolon (such as
"DISP?;DISP:TEXT?"), <NL> will terminate response returned after
response to the last query. In all cases, the program must read <NL> in
response before another command is sent to the instrument, otherwise
errors will be caused.

1.7 Data Type


SCPI language defines several data types used for program message and
response messages.
 Numerical parameter
Commands requiring numerical Parameter support the notations of all common
decimal notations, including optional signs, decimal points, scientific notation,
etc. Special values of numerical Parameter are also acceptable, such as MIN,
MAX and DEF. In addition, suffixes for engineering units can also be sent
together with numerical Parameter (including M, k, m or u). If the command
accepts only some specific values, the instrument will automatically round the
input Parameter to acceptable values. The following commands require
numerical Parameter of frequency value:
[SOURce[1|2]:]FREQuency:CENTer {<Frequency>|MINimum|MAXimum}
 <NR1>: There is an implicit decimal point in the last bit,such as 273
 <NR2>: There is an explicit decimal point,such as .273
 <NR3>: There are an explicit decimal point and exponential,such as
2.73E+22.73E+2
 <Nrf>:The extensible form includes <NR1>, <NR2> and <NR3>,such
as 273 273. 2.73E2273 273. 2.73E2
 <Nrf+>: The extensible decimal form includes <NRf> and MIN MAX
DEF, such as 273 273. 2.73E2 MAX. MIN and MAX are the minimum
and maximum finite number. Within the range of the parameter
definition, DEF is the default of the parameter.
 Discrete parameter
Discrete Parameter are used for settings with limited number of programming
values (such as IMMediate, EXTernal or BUS). They can use short and long
format like key words of commands. They may be expressed in both upper and
lower case. The query response always returns uppercase Parameter in short
format. The following commands require discrete Parameter in voltage unit:
[SOURce[1|2]:]VOLTage:UNIT {VPP|VRMS|DBM}
 Boolean parameter
Boolean Parameter refer to true or false binary conditions. In case of false
conditions, the instrument will accept "OFF" or "0". In case of true conditions,
the instrument will accept "ON" or "1". In query of Boolean settings, the
instrument will always return "0" or "1". Boolean Parameter are required by the
following commands:
DISPlay {OFF|0|ON|1}
 ASCII string Parameter
Copyright© Itech Electronics Co., Ltd. 8
Remote Control

String Parameter may actually include all ASCII character sets. Character
strings must start and end with paired quotation marks; and single quotation
marks or double quotation marks are both allowed. Quotation mark separators
may also act as one part of a string, they can be typed twice without any
character added between them. String parameter is used in the following
command:
DISPlay:TEXT <quoted string>
For example, the following commands display message of "WAITING..."
(without quotation marks) on the front panel of the instrument.
DISP:TEXT "WAITING..."
Single quotation marks may also be used to display the same message.
DISP:TEXT 'WAITING...'

1.8 Communication Interface


IT6500C have five standard communication interfaces: RS232, USB, GPIB,
LAN and CAN. The customer can choose any one according to his demands.

1.8.1 RS232 Interface


Using a cable with two COM ports to connect power supply and PC. Then
please press [Shift] +[P-set] (Menu) button to enter the menu to configure the
communication parameters. You could do the secondary development with all
SCPI commands.

Note
The setup about RS232 in the program should agree with the configuration in the system set.
If you want to change the communication parameters, please press [Shift] +[P-set] (Menu)
button to enter the system set.

RS-232 Data style


RS232 with start bit and stop bit. The start bit and stop bit cannot be edited.
While you could select the odd parity or even parity under the system set.
Odd or EVEN options have been saved in the nonvolatile memory.

Baudrate
Edit baudrate: press [Shift] +[P-set] (Menu) to enter the menu setup, you could
select the baudrate among the following options:
4800/ 9600/ 19200/ 38400/ 57600/ 115200

RS-232 connection
Please use a straight-through RS232 cable with DB9 interface and connect the
RS232 serial port with the controller’s serial port(for example. PC). Form 2-2
gives a detailed description for each pin.
RS-232 pins description
Pin description
1 connectionless
2 TXD, transmit data
3 RXD,receive data
4 connectionless
Copyright© Itech Electronics Co., Ltd. 9
Remote Control

5 GND
6 connectionless
7 connectionless
8 connectionless
9 connectionless

RS-232 Troubleshooting:
If you meet some problems when communicating with PC by RS232 interface,
please check the following items:
 Please check the parameters setting
PC and power supply must have the same configuration in the following
items: baudrate, parity bit, data bit and flow control. Please note that power
supply has been configured with a start bit and stop bit(the two values are
fixed).
 Check the cable
Ensure you have used the correct communication cable. Please pay
attention that some cable may not have a correct internal wiring even it is
with a appropriate DB9 interface.
The RS232 communication cable should have been connected to a correct
serial port of the PC.
Communication Setup
Please ensure the PC and power supply have the same configuration in the
following items.
baudrate: 9600(4800, 9600, 19200, 38400, 57600, 115200).You could enter the
system menu to set the baudrate.
Data bit: 8
Stop bit: 1
Parity bit: (none, even, odd)
EVEN 8 data bits have even parity
ODD 8 data bits have odd parity
NONE 8 data bits have no parity
Native machine address: (0 ~31, factory default is 0)
Parity=
Start Bit 8 Data Bits Stop Bit
None

1.8.2 USB Interface


Use a cable with two USB ports to connect power supply and PC. You can
program through USB interface to achieve all functions of power supply.
The functions of USB488 interface are as follows:
 Interface is 488.2 USB488 interface
 Receive the following request: REN_CONTROL, GO_TO_LOCAL, and
LOCAL_LOCKOUT
 When the interface receives MsgID = TRIGGER USBTMC command, it will
transmit the TRIGGER command to the function layer
The functions of power supply’s USB488 are as follows:
Copyright© Itech Electronics Co., Ltd. 10
Remote Control

 receive all SCPI commands


 device is SR1 enabled
 device is RL1 enabled
 device is DT1 enabled

1.8.3 GPIB Interface


Use a IEEE488 bus to connect GPIB interfaces of power supply and PC.
Please ensure that the screws have been screwed down in order to have a full
connection. Then press [Shift] +[P-set] (Menu) to enter the system menu to set
the address. The address range of power supply is 1-30. After you set the
address, please press [Enter] button to confirm. GPIB address is saved in
nonvolatile memory.

1.8.4 LAN Interface


Press [Shift] +[P-set] (Menu) button to enter the system set. Please select
“ LAN “ in the Communication from System and then configure Gateway, IP,
Mask and SocketPort in the LAN option.
Connect the LAN interface of power supply to the computer with a reticle
(crossed). The gateway address should be consistent with that of the PC, and
the IP address should be at the same network segment with the PC’s IP
address.

1.8.5 CAN Communication Port


There is one DB25 interface at the rear panel, and the pin definition is shown
below. The user can use this terminal for PC connection; to activate connection,
be sure that the values set in the System menu are same as the corresponding
values set in PC.
Note
CAN setting in the program shall be consistent with the one set in the System menu of front
panel. To query and change, press the composite key [Shift] + [P-set](Menu) to enter the
setting screen in System menu for query and change. For details, refer to 3.9 System Menu.

Baud Rate
In the front panel [Shift] + [P-set](Menu), under the System menu, the user can
select one Baud rate stored in NVM:
20K|40K|50k|80k|100k|125k|150k|200k|250k|400K|500K|1000K

CAN Pin Definition


Use DB25 interface for connection. CAN interface pin is as follows.
Pin No. Description
CAN interface pin 1 CANH
14 CANL

CAN Troubleshooting:
If CAN connection fails, check that:
1. The PC and power supply have same Baud rate.
2. Appropriate interface pin or adapter is used, as described in CAN
connector.
3. The interface cable is correctly connected (CAN_H to CAN_H, CAN_L to

Copyright© Itech Electronics Co., Ltd. 11


Remote Control

CAN_L).
Check whether 120 Ω terminal resistance is connected.

Setting Communication
Before running communication, please match the power supply parameters
with the PC parameters as shown below.
Baud rate: 10K(20K, 40K, 50K, 80K, 100K, 125K, 200K, 250K, 400K, 500K,
500K). You can enter the System menu through panel and set the
communication Baud rate
Addr.: 1-127
Prescale (Pres): Not settable. Change with Baud rate setting.
PTS (BS1): Not settable. Change with Baud rate setting.
PBS (BS2): Not settable. Change with Baud rate setting.
Baud rate (Prescale) PTS PBS
10k 300 1 6
20k 150 1 6
40K 75 1 6
50K 60 1 6
80K 75 1 1
100K 30 1 6
125K 30 0 5
200K 15 1 6
250K 15 1 5
400K 15 1 1
500K 6 1 6
1000K 3 1 6

Copyright© Itech Electronics Co., Ltd. 12


SCPI status register

Chapter2 SCPI status register


You can get the current status of the power supply by reading the operation
status registers. The power supply records the different status of the instrument
through the four status register group, the four status register group are: status
byte register, standard event register, query status register and operation
status register. Status byte register records the
information of the other status register
BIT Signal Meaning
Operation status register
0 CAL The power supply is calculating the new calibration
3 parameter.
4 TRIG The power supply is triggered.
5 CC The power supply is in constant current status.
6 CV The power supply is in constant voltage status.
7 CW The power supply is in constant power status.
EXT Ext-Ctrl is enabled.
Query status register
0 OV Over voltage
1 OC Over current
2 OP Over power
3 UV Under Voltage
4 OT Over temperature
5 PROT All of protect function status
6 SRVS Remote Sense Reverse
7 LINE Off Line
8 ORVS Output Reverse protect
9 ErrCal Calibration error
10 LOC The load over current
The load over power
11 LOP
Standard event register
0 OPC Operation completed. All the parallel operations are
2 completed.
3 QYE Query error. Output buffer data lost.
4 DDE Instrument memory data loss or self test error
5 EXE Execute error. Command parameter over flow or the
7 operation condition is not consistent
CME Command error. There is syntax or semantic error in
the command received.
PON Power on bit, this bit is set to 1 after power on
Status byte register
2 EAV Error buffer available
3 QUES This bit is set to 1 when any one status of enabled
query status register changes.
4 MAV Output buffer available
5 ESB Bit ESB is set to 1 when the status of a enabled
standard event status
6 RQS register changes
OPER If the status of enabled operation register

Copyright© Itech Electronics Co., Ltd. 13


SCPI status register

7 changes,then this bit is set to1.

The following chart is the Status register Structure of the power


supply:

Copyright© Itech Electronics Co., Ltd. 14


SCPI Command Description

Chapter3 SCPI Command Description


STATus:QUEStionable[:EVENt]?
This command can be used to read the value in query event register.The power
supply will return a decimal number corresponding to the binary weighted sum
of each unit digit of register. These digits will be latched. After executing this
command, the query event register will be cleared.

Query syntax
STATus:QUEStionable[:EVENt]?

Arguments
None

Returns
<NR1>

Related Command
STATus:QUEStionable:ENABle

STATus:QUEStionable:CONDition?
This command is used to read the value of query condition register and
gets the status of power supply.

Query syntax
STATus:QUEStionable:CONDition?

Arguments
None

Returns
<NR1>

STATus:QUEStionable:ENABle
This command edits the enable register value of query event. In query, the
power supply will return a decimal number representing the binary weighted
sum of the enable register.

Command syntax
STATus:QUEStionable:ENABle <NRf>

Arguments
<.NR1> 0~65535

Copyright© Itech Electronics Co., Ltd. 15


SCPI Command Description

Default set
Refer to *PSC command

Example
STATus:QUEStionable:ENABle 16

Query syntax
STATus:QUEStionable:ENABle?

Returns
<NR1>

Related Command
*PSC

STATus:QUEStionable:PTRansition
This command is used to edit the positive transition trigger register of
query event.

Command syntax
STATus:QUEStionable:PTRansition <NR1>

Arguments
0~65535

Example
STAT:QUES:PTR 2000

Query syntax
STATus:QUEStionable:PTRansition?

Returns:
NR1

STATus:QUEStionable:NTRansition
This command is used to edit the negative transition trigger register of
query event.

Command syntax
STATus:QUEStionable:NTRansition <NR1>

Arguments
0~65535

Example
STAT:QUES:NTR 1000
Copyright© Itech Electronics Co., Ltd. 16
SCPI Command Description

Query syntax
STATus:QUEStionable:NTRansition?

Returns
NR1

STATus:OPERation[:EVENt]?
This command can read the parameter from operation event register.
After executing this order, operation event register is reset.

Query syntax
STATus:OPERation[:EVENt]?

Arguments
None

Returns
<NR1>

Related Command
STATus:OPERation:ENABle

STATus:OPERation:CONDition?
This command can read the parameter from the operation condition register.
When the parameter of operation condition register changes, the bit
corresponding in operation event register is 1.

Query syntax
STATus:OPERation:CONDition?

Arguments
None

Returns
<NR1>

STATus:OPERation:ENABle
This command can set the parameter of operation event enable register.
Setting parameter can determine which bit value of operation event register is 1
and the bit will cause OPER of status byte register to be 1.

Command syntax
STATus:OPERation:ENABle <NR1>

Arguments
0~65535

Copyright© Itech Electronics Co., Ltd. 17


SCPI Command Description

Example
STATus:OPERation:ENABle 128

Query syntax
STATus:OPERation:ENABle?

Returns
<NR1>

STATus:OPERation:PTRansition
This command is used to edit the positive transition trigger register of
operation event.

Command syntax
STATus:OPERation:PTRansition <NR1>

Arguments
0~65535

Example
STATus:OPERation:PTRansition 1000

Query syntax
STATus:OPERation:PTRansition?

Returns
<NR1>

STATus:OPERation:NTRansition
This command is used to edit the negative transition trigger register of
operation event.

Command syntax
STATus:OPERation:NTRansition <NR1>

Arguments
0~65535

Example
STATus:OPERation:NTRansition 1000

Query syntax
STATus: OPERation:NTRansition?

Returns
<NR1>
Copyright© Itech Electronics Co., Ltd. 18
SCPI Command Description

SYSTem:BEEPer:IMMediate
This command is used to test the beeper. After executing this command, the
instrument will beeper immediately.

Command syntax
SYSTem:BEEPer:IMMediate

Arguments
None

Example
SYST:BEEP:IMM

Query syntax
None

SYSTem:BEEPer[:STATe]
This command is used to turn on/turn off the beeper, when the arguments is set
to 1/ON, the beeper is enabled and press keyboard will beeper, otherwise, it is
mute.

Command syntax
SYSTem:BEEPer <bool>

Arguments
OFF|ON|0|1

Example
SYSTem:BEEP 1

Query syntax
SYSTem:BEEPer[:STATe]?

Returns
0|1

SYSTem:VERSion?
This command is used to query the current SCPI version. The returned
parameter is a string like “YYYY.V “, in which the YYYY is the year of that
version, V is the software version of that year.

Command syntax
SYST:VERS?

Arguments
None

Copyright© Itech Electronics Co., Ltd. 19


SCPI Command Description

Returns
<NR2>

SYSTem:ERRor?
This command is used to read the error information.

Command syntax
SYSTem:ERRor?

Arguments
None

SYSTem:REMote
This command is used to switch to the remote control mode(PC control).
In this mode, the keys on front panel is invalid except [Shift]+Meter],
[On/Off] and [Meter].

Command syntax
SYSTem:REMote

Arguments
None

Query syntax
None

Example
SYST:REM

SYSTem:LOCal
This command is used to switch the instrument to local control
mode(control from panel). In this mode ,all of keys on front panel is valid.

Command syntax
SYSTem:LOCal

Arguments
None

Query syntax
None

Example
SYST:LOC

Copyright© Itech Electronics Co., Ltd. 20


SCPI Command Description

SYSTem:RWLock
This command is transmit through RS232 interface, the same function as
SYSTem:REMote, but the difference is: this command can lock “ LOCAL
“ button as well. When this command is executed, the “ Local “ button
can’t switch to local control mode.

Command syntax
SYSTem:RWLock

Arguments
None

Example:
SYST:RWL

SYSTem:COMMunicate:SELect
This command is used to select the communication interface.

Arguments
RS232|USB|GPIB|LAN

Example
SYST:COMM:SEL RS232

Query syntax
SYSTem:COMMunicate:SELect?

Returns
RS232|USB|GPIB|LAN

SYSTem:COMMunicate:GPIB:ADDRess
This command is used to set the address of GPIB interface.

Command syntax
SYSTem:COMMunicate:GPIB[:SELF]:ADDRess <NR1>

Arguments
<1-30>

Reset Value
15

Query syntax
SYSTem:COMMunicate:GPIB[:SELF]:ADDRess?

Copyright© Itech Electronics Co., Ltd. 21


SCPI Command Description

Returns
NR1

SYSTem:COMMunicate:SERial:BAUDrate
This command is used to set the baudrate of RS232.

Command syntax
SYSTem:COMMunicate:SERial:BAUDrate<4800|9600|19200|38400|57600|11
5200>

Arguments
4800|9600|19200|38400|57600|115200

Example
SYSTem:COMM:SER:BAUD 4800

Query syntax
SYSTem:COMMunicate:SERial:BAUDrate?

Returns
<NR1>

SYSTem:COMMunicate:LAN:CURRent:ADDRess
This command is used to set IP address of power supply.

Command syntax
SYSTem:COMMunicate:LAN:CURRent:ADDRess <STR>

Arguments
<STR>

Unit
None

*RST
192.168.0.200

Example
SYST:COMM:LAN:CURR:ADDR "192.168.0.200"

Query syntax
SYSTem:COMMunicate:LAN:CURRent:ADDRess?

Returns
<STR>

Copyright© Itech Electronics Co., Ltd. 22


SCPI Command Description

SYSTem:COMMunicate:LAN:CURRent:DGATeway
This command is used to set gateway of power supply.

Command syntax
SYSTem:COMMunicate:LAN:CURRent:DGATeway

Arguments
<STR>

Unit
None

*Reset Value
192.168.0.1

Example
SYST:COMM:LAN:CURR:DGAT "192.168.0.1"

Query syntax
SYSTem:COMMunicate:LAN:CURRent:DGATeway?

Returns
<STR>

SYSTem:COMMunicate:LAN:CURRent:SMASk
This command is used to set the subnet mask of power supply.

Command syntax
SYSTem:COMMunicate:LAN:CURRent:SMASk

Arguments
<STR>

Unit
None

*RST
255.255.255.0

Example
SYST:COMM:LAN:CURR:SMAS "255.255.255.0"

Query syntax
SYSTem:COMMunicate:LAN:CURRent:SMASk?

Copyright© Itech Electronics Co., Ltd. 23


SCPI Command Description

Returns
<STR>

SYSTem:COMMunicate:LAN:DHCP[:STATe]
This command is used to set Dynamic IP address of power supply.

Command syntax
SYSTem:COMMunicate:LAN:DHCP[:STATe] <bool>

Arguments
0|1|OFF|ON

Reset Value
0

Example
SYST:COMM:LAN:DHCP 1

Query syntax
SYSTem:COMMunicate:LAN:DHCP[:STATe]?

Returns
0|1

SYSTem:COMMunicate:LAN:SOCKetport
This command is used to set socket port of communication.

Command syntax
SYSTem:COMMunicate:LAN:SOCKetport <NR1>

Arguments
<NR1>

Unit
None

*RST 值
30000

Query syntax
SYSTem:COMMunicate:LAN:SOCKetport?

Returns
<NR1>

Copyright© Itech Electronics Co., Ltd. 24


SCPI Command Description

SYSTem:COMMunicate:LAN:MACaddress?
This command is used to return the MAC address of LAN communication.

Command syntax
SYSTem:COMMunicate:LAN:MACaddress?

Arguments
<STR>

Copyright© Itech Electronics Co., Ltd. 25


Display Related Command

Chapter4 Display Related Command


DISPlay[:WINDow][:STATe]
This command is used to set the screen state.

Command syntax
DISPlay[:WINDow][:STATe] <bool>

Arguments
0|1|OFF|ON

Example
DISP 1

Query syntax
DISPlay[:WINDow][:STATe]?

Returns
0|1

DISPlay[:WINDow]:TEXT[:DATA]
This command is used to display a character string on point area.

Command syntax
DISPlay[:WINDow]:TEXT[:DATA] <NR1>,<str>

Arguments
<NR1>,<str>

Example
DISP:TEXT 1, “HELL0 “

Query syntax
DISPlay[:WINDow]:TEXT[:DATA]?

Returns
<str>

DISPlay[:WINDOW]:TEXT:CLEar
This command is used to clean the screen.

Command syntax
DISPlay[:WINDOW]:TEXT:CLEar

Copyright© Itech Electronics Co., Ltd. 26


Display Related Command

Arguments
None

Example
DISP:TEXT:CLE

Copyright© Itech Electronics Co., Ltd. 27


Trigger Command

Chapter5 Trigger Command


TRIGger[:IMMediate]
This command is used to create a trigger signal.

Command syntax
TRIGger[:IMMediate]

Arguments
None

TRIGger:SOURce
This command is used to set the trigger source.

Command syntax
TRIGger:SOURce <MANUal|BUS|EXTernal>

Arguments
MANUal|BUS|EXTernal

Query syntax
TRIGger:SOURce?

Returns
<CRD>

Copyright© Itech Electronics Co., Ltd. 28


Input Measuring Commands

Chapter6 Input Measuring Commands


MEASure[:SCALar]:VOLTage[:DC]?
This command is used to enquire the actual output voltage.

Command syntax
MEASure[:SCALar]:VOLTage[:DC]?

Arguments
None

Returns
〈NRf〉

Unit
V

Example
MEAS:VOLT?

FETCh[:SCALar]:VOLTage[:DC]?
This command is used to fetch the DC voltage value in buffer.

Command syntax
FETCh[:SCALar]:VOLTage[:DC]?

Returns
<NRf>

Unit
V

MEASure[:SCALar]:CURRent[:DC]?
This command is used to enquire the latest DC current value.

Command syntax
MEASure[:SCALar]:CURRent[:DC]?

Arguments
None

Returns
<NRf>

Copyright© Itech Electronics Co., Ltd. 29


Input Measuring Commands

Unit
A

Example
MEAS:CURR?

FETCh[:SCALar]:CURRent[:DC]?
This command is used to fetch the DC current value in buffer.

Command syntax
FETCh[:SCALar]:CURRent[:DC]?

Returns
<NRf>

MEASure[:SCALar]:POWer[:DC]?
This command is used to enquire the latest output power .

Command syntax
MEASure[:SCALar]:POWer[:DC]?

Arguments
None

Returns
〈NRf〉

Returns Unit
W

Example
MEASure:SCALar:POWer:DC?

FETCh[:SCALar]:POWer[:DC]?
This command is used to fetch the power value in buffer.

Command syntax
FETCh:POWer?

Returns
<NRf>

FETCh?
This command is used to fetch the measurements of voltage, current and
power.

Copyright© Itech Electronics Co., Ltd. 30


Input Measuring Commands

Command syntax
FETCh?

Returns
<NRf>,<NRf>,<NRf>

MEASure?
This command is used to enquire the latest measurements of voltage, current
and power.

Command syntax
MEASure?

Returns
<NRf>,<NRf>,<NRf>

Copyright© Itech Electronics Co., Ltd. 31


Output Commands

Chapter7 Output Commands


[SOURce:]CURRent[:LEVel][:IMMediate][:AMPLitude]
This command is used to set the output current value.

Command syntax
[SOURce:]CURRent[:LEVel][:IMMediate][:AMPLitude]<MINimum|MAXimum|N
Rf>

Arguments
MINimum|MAXimum|NRf

Unit
A

Reset Value
0.5 (The reset value of different models are different)

Example
CURR 2.0

Query syntax
[SOURce:]CURRent[:LEVel][:IMMediate][:AMPLitude]? [MINimum|MAXimum]

Returns
NRf

[SOURce:]CURRent:MINimum[:LEVel]
This command is used to set the minimum value of current.

Command syntax
[SOURce:]CURRent:MINimum[:LEVel] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
A

Reset Value
0.0

Example
CURR:MIN 0.0

Copyright© Itech Electronics Co., Ltd. 32


Output Commands

Query syntax
[SOURce:]CURRent:MINimum[:LEVel]? [MINimum|MAXimum]

Returns
NRf

Related Command
CURR:MAX,CURR

[SOURce:]CURRent:MAXimum[:LEVel]
This command is used to set the maximum value of current.

Command syntax
[SOURce:]CURRent:MAXimum[:LEVel] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
A

Reset Value
MAXimum

Example
CURR:MAX 120.0

Query syntax
[SOURce:]CURRent:MAXimum[:LEVel]? [MINimum|MAXimum]

Returns
NRf

Related Command
CURR:MIN ,CURR

[SOURce:]CURRent:RISE[:LEVel]
This command is used to set rising time of current.

Command syntax
[SOURce:]CURRent:RISE[:LEVel] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Copyright© Itech Electronics Co., Ltd. 33


Output Commands

Unit
S

Reset Value
0.001

Example
CURR:RISE 10.0

Query syntax
[SOURce:]CURRent:RISE[:LEVel]? [MINimum|MAXimum]

Returns
NRf

[SOURce:]CURRent:FALL[:LEVel]
This command is used to set falling time of current.

Command syntax
[SOURce:]CURRent:FALL[:LEVel] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
S

Reset Value
0.001

Example
CURR:FALL 2.0

Query syntax
[SOURce:]CURRent:FALL[:LEVel]? [MINimum|MAXimum]

Returns
NRf

[SOURce:]CURRent:PROTection:STATe
This command is used to set over current protection state.

Command syntax
[SOURce:]CURRent:PROTection:STATe <bool>

Copyright© Itech Electronics Co., Ltd. 34


Output Commands

Command Arguments
ON|OFF|1|0

Example
CURR:PROT:STAT 1

Reset Value
1

Query syntax
[SOURce:]CURRent:PROTection:STATe?

Returns
0|1

[SOURce:]CURRent:PROTection[:LEVel]
This command is used to set current value for over current protection.

Command syntax
[SOURce:]CURRent:PROTection[:LEVel] <MINimum|MAXimum|DEFault|NRf>

Arguments
MINimum|MAXimum|DEFault|NRf

Unit
A

Reset Value
MAXimum

Example
CURR:PROT 10.0

Query syntax
[SOURce:]CURRent:PROTection[:LEVel]? [MINimum|MAXimum|DEFault]

Returns
NRf

[SOURce:]CURRent:PROTection:DELay
This command is used to set delay time for over current protection.

Command syntax
[SOURce:]CURRent:PROTection:DELay <MINimum|MAXimum|NRf>

Copyright© Itech Electronics Co., Ltd. 35


Output Commands

Arguments
MINimum|MAXimum|NRf

Unit
S

Reset Value
0.2

Example
CURR:PROT:DEL 6.0

Query syntax
[SOURce:]CURRent:PROTection:DELay? [MINimum|MAXimum]

Returns
NRf

[SOURce:]VOLTage[:LEVel][:IMMediate][:AMPLitude]
This command is used to set output Voltage value.

Command syntax
[SOURce:]VOLTage[:LEVel][:IMMediate][:AMPLitude]
<MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
V

Reset Value
0.0

Example
VOLT 60.0

Query syntax
[SOURce:]VOLTage[:LEVel][:IMMediate][:AMPLitude]? [MINimum|MAXimum]

Returns
NRf

[SOURce:]VOLTage:MINimum[:LEVel]
This command is used to set minimum value of voltage.

Copyright© Itech Electronics Co., Ltd. 36


Output Commands

Command syntax
[SOURce:]VOLTage:MINimum[:LEVel] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
V

Reset Value
MINimum

Example
VOLT:MIN 2.0

Query syntax
[SOURce:]VOLTage:MINimum[:LEVel]? [MINimum|MAXimum]

Returns
NRf

[SOURce:]VOLTage:MAXimum[:LEVel]
This command is used to set maximum value of voltage.

Command syntax
[SOURce:]VOLTage:MAXimum[:LEVel] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
V

Reset Value
MAXimum

Example
VOLT:MAX 24.0

Query syntax
[SOURce:]VOLTage:MAXimum[:LEVel]? [MINimum|MAXimum]

Returns
NRf

Copyright© Itech Electronics Co., Ltd. 37


Output Commands

[SOURce:]VOLTage:RISE[:LEVel]
This command is used to set rising time of voltage.

Command syntax
[SOURce:]VOLTage:RISE[:LEVel] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
S

Example
VOLT:RISE 5.0

Query syntax
[SOURce:]VOLTage:RISE[:LEVel]? [MINimum|MAXimum]

Returns
NRf

[SOURce:]VOLTage:FALL[:LEVel]
This command is used to set falling time of voltage.

Command syntax
[SOURce:]VOLTage:FALL[:LEVel] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
S

Reset Value
0.001

Example
VOLT:FALL 2.0

Query syntax
[SOURce:]VOLTage:FALL[:LEVel]? [MINimum|MAXimum]

Returns
NRf

Copyright© Itech Electronics Co., Ltd. 38


Output Commands

[SOURce:]VOLTage:PROTection:STATe
This command is used to set over voltage protection state.

Command syntax
[SOURce:]VOLTage:PROTection:STATe <bool>

Arguments
ON|OFF|1|0

Query syntax
[SOURce:]VOLTage:PROTection:STATe?

Returns
0|1

[SOURce:]VOLTage:PROTection[:LEVel]
This command is used to set voltage value of OVP.

Command syntax
[SOURce:]VOLTage:PROTection[:LEVel] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
V

Reset Value
MAXimum

Example
VOLT:PROT MAX

Query syntax
[SOURce:]VOLTage:PROTection[:LEVel]? [MINimum|MAXimum]

Returns
NRF

[SOURce:]VOLTage:PROTection:DELay
This command is used to set delay time for over voltage protection.

Command syntax
[SOURce:]VOLTage:PROTection:DELay <MINimum|MAXimum|NRf>

Copyright© Itech Electronics Co., Ltd. 39


Output Commands

Arguments
MINimum|MAXimum|NRf

Unit
S

Reset Value
0.02

Example
VOLT:PROT:DEL 0.4

Query syntax
[SOURce:]VOLTage:PROTection:DELay? [MINimum|MAXimum]

Returns
NRf

[SOURce:]POWer[:LEVel][:IMMediate][:AMPLitude]
This command is used to set output power.

Command syntax:
[SOURce:]POWer[:LEVel][:IMMediate][:AMPLitude]
<MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
W

Reset Value
MAXimum

Example
POW 5.0

Query syntax
[SOURce:]POWer[:LEVel][:IMMediate][:AMPLitude]? [MINimum|MAXimum]

Returns
NRf

[SOURce:]POWer:MINimum[:LEVel]
This command is used to set minimum value of power.
Copyright© Itech Electronics Co., Ltd. 40
Output Commands

Command syntax
[SOURce:]POWer:MINimum[:LEVel]

Arguments
MINimum|MAXimum|NRf

Unit
W

Reset Value
0.0

Example
POW:MIN 2.0

Query syntax
[SOURce:]POWer:MINimum[:LEVel]? [MINimum|MAXimum]

Returns
NRf

[SOURce:]POWer:MAXimum[:LEVel]
This command is used to set maximum value of power.

Command syntax
[SOURce:]POWer:MAXimum[:LEVel] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
W

Reset Value
MAXimum

Example
POW:MAX min

Query syntax
[SOURce:]POWer:MAXimum[:LEVel]? [MINimum|MAXimum]

Returns
NRf

Copyright© Itech Electronics Co., Ltd. 41


Output Commands

[SOURce:]POWer:RISE[:LEVel]
This command is used to set rising time of power.

Command syntax
[SOURce:]POWer:RISE[:LEVel] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
S

Example
POW:RISE 5.0

Query syntax
[SOURce:]POWer:RISE[:LEVel]? [MINimum|MAXimum]

Returns
NRf

[SOURce:]POWer:FALL[:LEVel]
This command is used to set falling time of power.

Command syntax
[SOURce:]POWer:FALL[:LEVel] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
S

Reset Value
0.001

Example
POW:FALL 3.0

Query syntax
[SOURce:]POWer:FALL[:LEVel]? [MINimum|MAXimum]

Returns
NRf

Copyright© Itech Electronics Co., Ltd. 42


Output Commands

[SOURce:]POWer:PROTection:STATe
This command is used to set over power protection state.

Command syntax
[SOURce:]POWer:PROTection:STATe<bool>

Arguments
ON|OFF|1|0

Reset Value
1

Example
POW:PROT:STAT 1

Query syntax
[SOURce:]POWer:PROTection:STATe?

Returns
0|1

[SOURce:]POWer:PROTection[:LEVel]
This command is used to set power value for over power protection.

Command syntax
[SOURce:]POWer:PROTection[:LEVel] <MINimum|MAXimum|DEFault|NRf>

Arguments
MINimum|MAXimum|DEFault|NRf

Unit
w

Query syntax
[SOURce:]POWer:PROTection[:LEVel]? [MINimum|MAXimum|DEFault]

Returns
NRf

[SOURce:]POWer:PROTection:DELay
This command is used to set delay time for over power protection.

Command syntax
[SOURce:]POWer:PROTection:DELay <MINimum|MAXimum|NRf>

Copyright© Itech Electronics Co., Ltd. 43


Output Commands

Arguments
MINimum|MAXimum|NRf

Unit
S

Reset Value
0.02

Example
POW: PROT: DEL 2.0

Query syntax
[SOURce:]POWer:PROTection:DELay? [MINimum|MAXimum]

Returns
NRf

[SOURce:]RESistance[:LEVel][:IMMediate][:AMPLitude
]
This command is used to set internal resistance.

Command syntax
[SOURce:]RESistance[:LEVel][:IMMediate][:AMPLitude]
<MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
Ohms

Reset Value
MINimum

Example
RES 3.0

Query syntax
[SOURce:]RESistance[:LEVel][:IMMediate][:AMPLitude]?
[MINimum|MAXimum]

Returns
NRf

Copyright© Itech Electronics Co., Ltd. 44


Output Commands

[SOURce:]PROTection:TRIGgered?
This command is used to query executing state of over voltage protection.

Command syntax
[SOURce:]PROTection:TRIGgered?

Arguments
None

Returns
NR1

[SOURce:]PROTection:CLEar
This command is used to clear the OVP state.

Command syntax
[SOURce:]PROTection:CLEar

Arguments
None

[SOURce:]APPLy
This command is used to set output voltage and current.

Command syntax
[SOURce:]APPly <NRf+>,<NRf+>

Arguments
<MINimum|MAXimum|NRf >,< MINimum|MAXimum|NRf >

Unit
V, A

Example
APPL 12.0V,24.0A

Query syntax
[SOURce:]APPLy?

Returns
NRf,NRf

[SOURce:]EXTern[:STATe]
This command is used to set external control state.

Copyright© Itech Electronics Co., Ltd. 45


Output Commands

Command syntax
[SOURce:]EXTern[:STATe] <bool>

Arguments
ON|OFF|1|0

Reset Value
0

Example
EXT 1

Query syntax
[SOURce:]EXTern[:STATe]?

Returns
0|1

[SOURce:]EXTern:MONitor:RANGe
This command is used to set output range of external monitor.

Command syntax
[SOURce:]EXTern:MONitor:RANGe <10V|5V>

Arguments
10V|5V

Reset Value
10V

Example
EXT:MON:RANG 5V

Query syntax
[SOURce:]EXTern:MONitor:RANGe?

Returns
10V|5V

[SOURce:]EXTern:PROGram:MODE
This command is used to set external program mode.

Command syntax
[SOURce:]EXTern:PROGram:MODE <VOLTage| RESistance>

Copyright© Itech Electronics Co., Ltd. 46


Output Commands

Arguments
VOLTage|RESistance

Reset Value
VOLTage

Example
EXT:PROG:MODE VOLT

Query syntax
[SOURce:]EXTern:PROGram:MODE?

Returns
VOLTage|RESistance

[SOURce:]EXTern:PROGram:RANGe
This command is used to set external program range.

Command syntax
[SOURce:]EXTern:PROGram:RANGe <10V/10K|5V/5K>

Arguments
10V/10K|5V/5K

Reset Value
10V/10K

Example
EXT:PROG:RANG 10V/10K

Query syntax
[SOURce:]EXTern:PROGram:RANGe?

Returns
[SOURce:]EXTern:PROGram:RANGe?

[SOURce:]OUTPut[:STATe]
This command is used to control the output switch state.

Command syntax
[SOURce:]OUTPut[:STATe] <bool>

Arguments
0|1|OFF|ON

Copyright© Itech Electronics Co., Ltd. 47


Output Commands

Reset Value
0

Example
OUTP 1

Query syntax
[SOURce:]OUTPut[:STATe]?

Returns
0|1

[SOURce:]CV:PRIority
This command is used to set the CV priority.

Command syntax
[SOURce:]CV:PRIority <HIGH|LOW>

Arguments
HIGH|LOW

Reset Value
HIGH

Example
CV:PRI HIGH

Query syntax
[SOURce:]CV:PRIority?

Returns
<CRD>

[SOURce:]CC:PRIority
This command is used to the CC priority.

Command syntax
[SOURce:]CC:PRIority <HIGH|LOW>

Arguments
HIGH|LOW

Reset
HIGH

Copyright© Itech Electronics Co., Ltd. 48


Output Commands

Example
CC:PRI HIGH

Query syntax
[SOURce:]CC:PRIority?

Returns
<CRD>

[SOURce:]PRIority:TYPE
This command is used to query type of priority.

Command syntax
[SOURce:]PRIority:TYPE <CV|CC>

Arguments
CV|CC

Reset Value
CV

Example
PRI:TYPE CV

Query syntax
[SOURce:]PRIority:TYPE?

Returns
<CRD>

[SOURce:]FILTer:LEVel
This command is used to set level of filter.

Command syntax
[SOURce:]FILTer:LEVel <LOW|MEDium|FAST>

Arguments
LOW|MEDium|FAST

Query syntax
[SOURce:]FILTer:LEVel?

Returns
<CRD>

Copyright© Itech Electronics Co., Ltd. 49


Output Commands

[SOURce:]SENSe:RVERse:PROTect[:STATe]
This command is used to set the status of sense reverse protection.

Command syntax
[SOURce:]SENSe:RVERse:PROTect[:STATe] <bool>

Arguments
0|1|OFF|ON

Query syntax
[SOURce]SENSe:RVERse:PROTect[:STATe]?

Returns
<0|1>

Copyright© Itech Electronics Co., Ltd. 50


DCR Command

Chapter8 DCR Command


DCR[:STATe]
This command is used to set state of DCR function.

Command syntax
DCR[:STATe] <bool>

Arguments
0|1|OFF|ON

Reset Value
OFF

Example
DCR 0

Query syntax
DCR[:STATe]?

Return Arguments
0|1

"DCR:DATA?",
This command is used to query DCR value.

Command syntax
DCR:DATA?

Arguments
None

Reset Value
0

Example
DCR:DATA?

Return Arguments
<NRf>

Copyright© Itech Electronics Co., Ltd. 51


DCR Command

DCR:BATTery:CAPAcity[:LEVel]
This command is used to enter capacity of under test battery.

Command syntax
DCR:BATTery:CAPAcity <NRf>

Arguments
<NRf>

Reset Value
0

Example
DCR:BATTery:CAPAcity 0.1

Query syntax
DCR:BATTery:CAPAcity?

Return Arguments
<NRf>

Copyright© Itech Electronics Co., Ltd. 52


Load Related Command(IT6500C)

Chapter9 Load Related Command(IT6500C)


Except LOAD[:STATe] command, other commands are specially for IT6500C,
which are not suitable for IT6500D series models.

LOAD[:STATe]
This command is used to set load state. When the load of IT6500C Series
power supply is on, you need to select internal load or external load. Default
load is internal load. IT6500D Series power supply only has internal load. This
command is used to turn on and off load function state.

Command syntax
LOAD[:STATe] <bool>

Arguments
0|1|OFF|ON

Reset Value
OFF

Example
LOAD 0

Query syntax
LOAD[:STATe]?

Returns
0|1

LOAD:SELection
This command is used to select internal load or external load, which is
applicable for IT6500C Series power supply.

Command syntax
LOAD:SELection <INTernal|EXTernal>
Arguments
INTernal|EXTernal

Reset Value
INTernal

Example
LOAD:SELection INT

Copyright© Itech Electronics Co., Ltd. 53


Load Related Command(IT6500C)

Query syntax
LOAD:SELection?

Returns
<CRD>

LOAD:NUMBer[:EXTernal]
This command is used to set the number of external loads. When IT6500C
Series power supply uses external load function, you need to set the number of
external loads.

Command syntax
LOAD:NUMBer[:EXTernal] <1~3>

Arguments
<1~3>

Reset Value
1

Example
LOAD:NUMB 1

Query syntax
LOAD:NUMBer[:EXTernal]?

Returns
NR1

LOAD:CURRent[:LEVel][:IMMediate][:AMPLitude]
This command is used to set current of load.

Command syntax
LOAD:CURRent[:LEVel][:IMMediate][:AMPLitude] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
A

Reset Value
5 (The reset value of different models are different)

Example
LOAD:CURR 2.0

Copyright© Itech Electronics Co., Ltd. 54


Load Related Command(IT6500C)

Query syntax
LOAD:CURRent[:LEVel][:IMMediate][:AMPLitude]? [MINimum|MAXimum]

Returns
NRf

LOAD:CURRent:MINimum[:LEVel]
This command is used to set minimum value of load current.

Command syntax
LOAD:CURRent:MINimum[:LEVel] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
A

Reset Value
0.0

Example
LOAD:CURR:MIN 2.0

Query syntax
LOAD:CURRent:MINimum[:LEVel]? [MINimum|MAXimum]

Returns
NRf

Related Command
LOAD:CURR:MAX,LOAD:CURR

LOAD:CURRent:MAXimum[:LEVel]
This command is used to set maximum value of load current.

Command syntax
LOAD:CURRent:MAXimum[:LEVel] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
A

Copyright© Itech Electronics Co., Ltd. 55


Load Related Command(IT6500C)

Example
LOAD:CURR:MAX 3.0

Query syntax
LOAD:CURRent:MAXimum[:LEVel]? [MINimum|MAXimum]

Returns
NRf

Related Command
LOAD:CURR:MIN,LOAD:CURR

LOAD:CURRent:RISE[:LEVel]
This command is used to set rising time for load current.

Command syntax
LOAD:CURRent:RISE[:LEVel] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
S

Reset Value
0.001

Example
LOAD:CURR:RISE 4.0

Query syntax
LOAD:CURRent:RISE[:LEVel]? [MINimum|MAXimum]

Returns
NRf

LOAD:CURRent:FALL[:LEVel]
This command is used to set falling time for load current.

Command syntax
LOAD:CURRent:FALL[:LEVel] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Copyright© Itech Electronics Co., Ltd. 56


Load Related Command(IT6500C)

Unit
S

Reset Value
0.001

Example
LOAD:CURR:FALL 1.0

Query syntax
LOAD:CURRent:FALL[:LEVel]? [MINinum|MAXimum]

Returns
NRf

LOAD:CURRent:PROTection:STATe
This command is used to set load OCP state.

Command syntax
LOAD:CURRent:PROTection:STATe <bool>

Arguments
ON|OFF|1|0

Reset Value
1

Example
LOAD:CURR:PROT:STAT 1

Query syntax
LOAD:CURRent:PROTection:STATe?

Returns
0|1

LOAD:CURRent:PROTection[:LEVel]
This command is used to set current value of load OCP.

Command syntax
LOAD:CURRent:PROTection[:LEVel] <MINimum|MAXimum|DEFault|NRf>

Arguments
MINimum|MAXimum|DEFault|NRf

Copyright© Itech Electronics Co., Ltd. 57


Load Related Command(IT6500C)

Unit
A

Reset Value
MAXimum

Example
LOAD:CURR:PROT 24.0

Query syntax
LOAD:CURRent:PROTection[:LEVel]? [MINimum|MAXimum]

Returns
NRf

LOAD:CURRent:PROTection:DELay
This command is used to set delay time for load OCP.

Command syntax
LOAD:CURRent:PROTection:DELay <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf
Unit
s
Reset Value
0.2
Example
LOAD:CURR:PROT:DEL 0.02

Query syntax
LOAD:CURRent:PROTection:DELay? [MINimum|MAXimum]

Returns
NRf

LOAD:POWer[:LEVel][:IMMediate][:AMPLitude]
This command is used to set the load power.

Command syntax
LOAD:POWer[:LEVel][:IMMediate][:AMPLitude] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Copyright© Itech Electronics Co., Ltd. 58


Load Related Command(IT6500C)

Unit
W

Reset Value
MAXimum

Example
LOAD:POW MIN

Query syntax
LOAD:POWer[:LEVel][:IMMediate][:AMPLitude]? [MINimum|MAXimum]

Returns
NRf

LOAD:POWer:MINimum[:LEVel]
This command is used to set minimum power of load.

Command syntax
LOAD:POWer:MINimum[:LEVel] [MINimum|MAXimum|NRf]

Arguments
MINimum|MAXimum|NRf

Unit
W

Reset Value
0.0

Example
LOAD:POW:MIN 2.0

Query syntax
LOAD:POWer:MINimum[:LEVel]? [MINimum|MAXimum]

Returns
NRf

Related Command
LOAD:POW:MAX,LOAD:POW

LOAD: POWer:MAXimum[:LEVel]
This command is used to set maximum value of power.

Copyright© Itech Electronics Co., Ltd. 59


Load Related Command(IT6500C)

Command syntax
LOAD:POWer:MAXimum[:LEVel] < MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
W

Reset Value
MAXimum

Example
LOAD:POW:MAX 3100

Query syntax
LOAD:POWer:MAXimum[:LEVel]? [MINimum|MAXimum]

Returns
NRf

Related Command
LOAD:POW:MIN,LOAD:POW

LOAD: POWer:RISE[:LEVel]
This command is used to set rising time for load power.

Command syntax
LOAD:POWer:RISE[:LEVel] <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
S

Reset Value
0.001

Example
LOAD:POWer:RISE[:LEVel] 200ms

Query syntax
LOAD:POWer:RISE[:LEVel]? [MINimum|MAXimum]

Copyright© Itech Electronics Co., Ltd. 60


Load Related Command(IT6500C)

Returns
NRf

LOAD:POWer:FALL[:LEVel]
This command is used to set falling time for load power.

Command syntax
LOAD:POWer:FALL[:LEVel]

Arguments
MINimum|MAXimum|NRf

Unit
S

Reset Value
0.001

Example
LOAD:POW:FALL 0.2

Query syntax
LOAD:POWer:FALL[:LEVel]? [MINimum|MAXimum]

Returns
NRf

LOAD:POWer:PROTection:STATe
This command is used to set over power protect state.

Command syntax
LOAD:POWer:PROTection:STATe <bool>

Arguments
ON|OFF|1|0

Reset Value
1

Example
LOAD:POW:PROT:STAT 1

Query syntax
[SOURce:]POWer:PROTection:STATe?

Copyright© Itech Electronics Co., Ltd. 61


Load Related Command(IT6500C)

Returns
0|1

LOAD:POWer:PROTection[:LEVel]
This command is used to set power value of load OPP.

Command syntax
LOAD:POWer:PROTection[:LEVel] <MINimum|MAXimum|DEFault|NRf>

Arguments
MINimum|MAXimum|DEFault|NRf

Unit
W

Reset Value
MAXimum

Example
LOAD:POW:PROT MAX

Query syntax
LOAD:POWer:PROTection[:LEVel]? [MINimum|MAXimum|DEFault]

Returns
NRf

LOAD:POWer:PROTection:DELay
This command is used to set delay time for load OPP.

Command syntax
LOAD:POWer:PROTection:DELay <MINimum|MAXimum|NRf>

Arguments
MINimum|MAXimum|NRf

Unit
S

Reset Value
0.5

Example
LOAD:POW:PROT:DEL 0.04

Copyright© Itech Electronics Co., Ltd. 62


Load Related Command(IT6500C)

Query syntax
LOAD:POWer:PROTection:DELay? [MINimum|MAXimum]

Returns
NRf

Copyright© Itech Electronics Co., Ltd. 63


List Operation Commands

Chapter10 List Operation Commands


LIST[:STATe]
This command is used to set the state of list mode. If the state is ON ( 1 ),
and the list file can not be edit.

Command syntax
LIST[:STATe ]<bool>

Arguments
0|1|OFF|ON

Reset Value
0

Example
LIST:STAT 1

Query syntax
LIST:STATe?

Returns
0|1

LIST:RECall
This command is used to recall a list file.

Command syntax
LIST:RECall <MINimum|MAXimum|<1~10>>

Arguments
MINimum|MAXimum|<1~10>

Example
LIST:REC 1

Query syntax
LIST:RECAll?

Returns
NR1

Copyright© Itech Electronics Co., Ltd. 64


List Operation Commands

LIST:EDIT
This command is used to select list file which has been edited.

Command syntax
LIST:EDIT <MINimum|MAXimum|1~10>

Arguments
MINimum|MAXimum|<1~10>

Example
LIST:EDIT 10

Query syntax
LIST:EDIT?

Returns
NR1

LIST:REPeat
This command is used to edit the running times of list file.

Command syntax
LIST:REPeat <MINimum|MAXimum|1~65535>

Arguments
MINimum|MAXimum|<1 to 65535>

Example
LIST:REP 2000

Query syntax
LIST:REPeat? [MINimum|MAXimum]

Returns
NR1

LIST:SEQuence:COUNt
This command is used to edit the wave count of list file.

Command syntax
LIST:SEQuence:COUNt <1-10>

Arguments
<1~10>

Copyright© Itech Electronics Co., Ltd. 65


List Operation Commands

Example
LIST:SEQ:COUN 1

Query syntax
LIST:SEQuence:COUNt?

Returns
<NR1>

LIST:SEQuence:SELect
This command is used to edit the selected wave sequence in LIST file. For
each List, you can select 1-10 wave files from 100 wave files and combine them
to a List file in sequence.

Command syntax
LIST:SEQuence:SELect<1~10>.<1~100>

Arguments
<1-10>,<1-100>

Example
LIST:SEQ:SEL 1,20

Query syntax
LIST:SEQuence:SELect? <NR1>

Returns
NR1

LIST:SEQuence:REPeat
This command is used to edit the running count of sequence which is
linked to the List file.

Command syntax
LIST:SEQuence:REPeat <1~10>,<MINimum|MAXimum|<NR1>

Arguments
<1~10>,MINimum|MAXimum|<1~65535>

Query syntax
LIST:SEQuence:REPeat? [MINimum|MAXimum]

Returns
NR1

Copyright© Itech Electronics Co., Ltd. 66


List Operation Commands

LIST:SAVe
This command is used to save the list file in a nonvolatile memory.

Command syntax
LIST:SAVe <1~10>

Arguments
<1-10>

Example
LIST:SAV 4

LIST:PAUSe[:STATe]
This command is used to pause the list and continue.

Command syntax
LIST:PAUSe[:STATe] <bool>

Arguments
0|1|OFF|ON

Example
LIST:PAUS 0

Query syntax
LIST:PAUSe[:STATe]?

Returns
0|1

Copyright© Itech Electronics Co., Ltd. 67


Wave Operation Command

Chapter11 Wave Operation Command


SEQuence:EDIT
This command is used to select the wave file to be edited.

Command syntax
SEQuence:EDIT <MINimum|MAXimum|1~100>

Arguments
MINimum|MAXimum|<1~100>

Example
SEQ:EDIT 3

Query syntax
SEQuence:EDIT? [MINimum|MAXimum]

Returns
NR1

SEQuence:RECall
This command is used to recall a wave file.

Command syntax
SEQuence:RECall <NR1>

Arguments
MINimum|MAXimum|<1-100>

Example
SEQ:REC 1

Query syntax
SEQ:REC?

Returns
NR1

SEQuence:STEP:COUNt
This command is used to edit the step count of wave file.

Command syntax
SEQuence:STEP:COUNt <1~10>

Copyright© Itech Electronics Co., Ltd. 68


Wave Operation Command

Arguments
<1-10>

Example
SEQ:STEP:COUN 5

Query syntax
SEQuence:STEP:COUNt?

Returns
NR1

SEQuence[:STEP]:VOLTage
This command is used to edit the voltage of specified step of the wave file.

Command syntax
SEQuence[:STEP]:VOLTage <NR1>,<MINimum|MAXimum|NRf>
Arguments
<1-10>,MINimum|MAXimum|NRf

Unit
V

Example
SEQ:VOLT 6,7.0V

Query syntax
SEQuence[:STEP]:VOLTage?<NR1>,[MINimum|MAXimum]
Returns
NRf

SEQuence[:STEP]:CURRent
This command is used to edit the current of specified step of a wave file.

Command syntax
SEQuence[:STEP]:CURRent <NR1>,<MINimum|MAXimum|NRf>

Arguments
<1~10>,MINimum|MAXimum|NRf

Unit
A

Example
SEQ:CURR 1,12.0
Copyright© Itech Electronics Co., Ltd. 69
Wave Operation Command

Query syntax
SEQuence[:STEP]:CURRent? <NR1>,[MINimum|MAXimum]

Returns
NRf

SEQuence[:STEP]:LOAD:CURRent?
This command is used to edit the load current of specified step of a
sequence file. This command is prepared for IT6500C model.

Arguments
<NR1>,MINimum|MAXimum|NRf

Unit
s

Example
SEQ:LOAD:CURR 1,0.5

Query syntax
SEQuence[:STEP]:LOAD:CURRent? <NR1>

Returns
<NRf>

SEQuence[:STEP]:WIDTh
This command is used to edit the width of specified step of the wavefile .

Command syntax
SEQuence[:STEP]:WIDth <NR1>,<MINimum|MAXimum|NRf>

Arguments
<1~10>,MINimum|MAXimum|NRf

Unit
s

Example
SEQ:WIDT 1,64

Query syntax
SEQuence[:STEP]:WIDTh? <NR1>,[MINimum|MAXimum]

Returns
NRf

Copyright© Itech Electronics Co., Ltd. 70


Wave Operation Command

SEQuence[:STEP]:SLOPe
This command is used to edit the slope of a specified step of the wave
file.

Command syntax
SEQuence[:STEP]:SLOPe <NR1>,MINimum|MAXimum|NRf

Arguments
<NR1>,MINimum|MAXimum|NRf

Unit
s

Example
SEQ:SLOP 1,4

Query syntax
SEQuence[:STEP]:SLOPe? <NR1>,[MINimum|MAXimum]

Returns
NRf

SEQuence:SAVe
This command is used to save the wave file.

Command syntax
SEQuence:SAVe <NR1>

Arguments
<1~100>

Example
SEQ:SAV 1

Copyright© Itech Electronics Co., Ltd. 71


Car Wave Command(IT6500C)

Chapter12 Car Wave Command(IT6500C)


The car wave command is a special command of IT6500C, but it’s not suitable
for IT6500D Series.

CARWave:ISO16750:SHORt:DROP[:STATe]
This command is used to analog ISO short drop wave of car.

Command syntax
CARWave:ISO16750:SHORt:DROP <bool>

Arguments
ON|OFF|1|0

Reset Value
0

Example
CARW:ISO16750:SHOR 1

Query syntax
CARWave:ISO16750:SHORt:DROP[:STATe]?

Returns
0|1

CARWave:ISO16750:SHORt:DROP:VOLTage[:LEVel]
This command is used to select ISO analog voltage of short drop wave of car.

Command syntax
CARWave:ISO16750:SHORt:DROP:VOLTage <12V|24V>

Arguments
12V|24V

Reset Value
12V

Example
CARW:ISO16750:SHOR:DROP:VOLT 24V

Query syntax
CARW:ISO16750:SHOR:DROP:VOLT?

Copyright© Itech Electronics Co., Ltd. 72


Car Wave Command(IT6500C)

Returns
<CRD>

CARWave:ISO16750:RESet[:STATe]
This command is used to analog ISO reset wave of car.

Command syntax
CARWave:ISO16750:RESet <bool>

Arguments
ON|OFF|1|0

Reset Value
0

Example
CARWave:ISO16750:RES 1

Query syntax
CARWave:ISO16750:RESet?

Returns
0|1

CARWave:ISO16750:RESet:VOLTage[:LEVel]
This command is used to set minimum supply voltage of ISO reset wave of car

Command syntax
CARWave:ISO16750:RESet:VOLTage <value>

Arguments
MINimum|MAXimum|NR3

Reset Value
12

Example
CARW:ISO16750:RES:VOLT 5.0 , CARW:ISO16750:RES:VOLT? MAX

Query syntax
CARWave:ISO16750:RESet:VOLTage? [MINimum|MAXimum]

Returns
NR3

Copyright© Itech Electronics Co., Ltd. 73


Car Wave Command(IT6500C)

CARWave:ISO16570:STARtup:PROFile[:STATe]
This command is used to analog ISO startup wave of car.

Command syntax
CARWave:ISO16750:STARtup:PROFile:STATe

Arguments
ON|OFF|1|0

Reset Value
0

Example
CARW:ISO16750:STAR:PROF 0

Query syntax
CARWave:ISO16750:STARtup:PROFile?

Returns
0|1

CARWave:ISO16750:STARtup:PROFile:VOLTage[:LEVel]
This command is used to select ISO startup wave voltage of car.

Command syntax
CARWave:ISO16750:STRTtup:PROFile:VOLTage <12V|24V>

Arguments
12V|24V

Reset Value
12V

Example
CARW:ISO16750:STAR:PROF:VOLT 12V

Query syntax
CARWave:ISO16750:STARtup:VOLTage?

Returns
<CRD>

CARWave:ISO16750:STARtup:PROFile:INDex
This command is used to select ISO startup wave level of car.

Copyright© Itech Electronics Co., Ltd. 74


Car Wave Command(IT6500C)

Command syntax
CARWave:ISO16750:STARtup:PROFile:INDex <1|2|3|4>

Arguments
1|2|3|4(12V), 1|2|3(24V)

Reset Value
1

Example
CARW:ISO16750:star:prof:ind 1

Query syntax
CARWave:ISO16750:STARtup:PROFile:INDex?

Returns
<CRD>

CARWave:STARtup:DIN40839[:STATe]
This command is used to analog DIN40839 startup wave of car.

Command syntax
CARWave:STARtup:DIN40839 <bool>

Arguments
0|1|OFF|ON

Reset Value
0

Example
CARW:STAR:DIN40839 1

Query syntax
CARWave:STARtup:DIN40839?

Returns
0|1

CARWave:STARtup:DIN40839:VOLTage[:SELect]
This command is used to select DIN40839 startup wave voltage of car.

Command syntax
CARWave:STARtup:DIN40839:VOLTage <12V|24V>

Copyright© Itech Electronics Co., Ltd. 75


Car Wave Command(IT6500C)

Arguments
12V|24V

Reset Value
12V

Example
CARW:STAR:DIN40839:VOLT 12V

Query syntax
CARWave:STARtup:DIN40839:VOLTage?

Returns
<CRD>

CARWave:STARtup:DIN40839:VOLTage:STARt:LEVel
This command is used to set user-defined DIN40839 start voltage level.

Command syntax
CARWave:STARtup:DIN40839:VOLTage:STARt:LEVel <Value>

Arguments
12V|24V

Reset Value
12V

Example
CARW:STAR:DIN40839:VOLT:STAR:LEV

Query syntax
CARWave:STARtup:DIN40839:VOLTage:STARt:LEVe?

Returns
<CRD>

CARWave:ISO21848:Umaxdyn:TEST:PULSe[:STATe]
This command is used to in ISO21848Umaxdyn test pulse.

Command syntax
CARWave:ISO21848:Umaxdyn:TEST:PULSe[:STATe] 0|1

Arguments
0|1|ON|OFF

Copyright© Itech Electronics Co., Ltd. 76


Car Wave Command(IT6500C)

Reset Value
0

Example
CARW:ISO21848:Umaxdyn:TEST:PULS 1

Query syntax
CARWave:ISO21848:Umaxdyn:TEST:PULSe[:STATe]?

Returns
<CRD>

CARWave:ISO21848:MOMENTary:VOLTage:DROP[:STA
Te]
This command is used to select ISO21848 analog voltage of short drop wave of
car.

Command syntax
CARWave:ISO21848:MOMENTary:VOLTage:DROP[:STATe] 0|1

Arguments
0|1|ON|OFF

Reset Value
0

Example
CARWave:ISO21848:MOMENTary:VOLTage:DROP 1

Query syntax
CARWave:ISO21848:MOMENTary:VOLTage:DROP[:STATe]?

Returns
<CRD>

CARWave:ISO21848:RESet[:STATe]
This command is used to analog ISO21848 reset wave of car.

Command syntax
CARWave:ISO21848:RESet[:STATe] <bool>

Arguments
ON|OFF|1|0

Reset Value
0
Copyright© Itech Electronics Co., Ltd. 77
Car Wave Command(IT6500C)

Example
CARWave:ISO21848:RES 1

Query syntax
CARWave:ISO21848:RESet[:STATe]?

Returns
0|1

CARWave:ISO21848:RESet:VOLTage[:LEVel]
This command is used to set minimum supply voltage of ISO21848 reset wave
of car

Command syntax
CARWave: ISO21848:RESet:VOLTage[:LEVel]

Arguments
MINimum|MAXimum|NR3

Reset Value
0.0

Example
CARW:ISO21848:RES:VOLT 5.0 , CARW:ISO21848:RES:VOLT? MAX

Query syntax
CARWave:ISO21848:RESet:VOLTage[:LEVel]? [MINimum|MAXimum]

Returns
NR3

CARWave:ISO21848:STARtup:PROFile[:STATe]
This command is used to analog ISO21848 startup wave of car.

Command syntax
CARWave:ISO21848:STARtup:PROFile[:STATe] 0|1

Arguments
0|1

Reset Value
0

Example
CARWave:ISO21848:STARtup:PROFile 1

Copyright© Itech Electronics Co., Ltd. 78


Car Wave Command(IT6500C)

Query syntax
CARWave:ISO21848:STARtup:PROFile[:STATe]?

Returns
<CRD>

CARWave:ISO16750:LOAD:DUMP[:STATe]
This command is used to simulate load dump wave of car.

Command syntax
CARWave:ISO16750:LOAD:DUMP <bool>

Arguments
ON|OFF|1|0

Reset Value
0

Example
CARW:ISO16750:LOAD:DUMP 1

Query syntax
CARWave:ISO16750:LOAD:DUMP?

Returns
0|1

CARWave:ISO16750:LOAD:DUMP:TEST[:MODe]
This command is used to select the test mode of load dump wave of car.

Command syntax
CARWave:ISO16750:LOAD:DUMP:TEST <AMODe|BMODe >

Arguments
AMODe|BMODe

Reset Value
AMODe

Example
CARW:ISO16750:LOAD:DUMP:TEST AMOD

Query syntax
CARWave:ISO16750:LOAD:DUMP:TEST?

Copyright© Itech Electronics Co., Ltd. 79


Car Wave Command(IT6500C)

Returns
<CRD>

CARWave:ISO16750:LOAD:DUMP[:VOLTage]:UN[:LEV
el]
This command is used to set peak voltage of load dump wave of car.

Command syntax
CARWave:ISO16750:LOAD:DUMP:UN <value>

Arguments
MINimum|MAXimum|NR3

Reset Value
MINimum

Example
CARW:ISO16750:LOAD:DUMP:UN 50

Query syntax
CARW:ISO16750:LOAD:DUMP:UN? [MINimum|MAXimum]

Returns
NR3

CARWave:ISO16750:LOAD:DUMP[:VOLTage]:US[:LEV
el]
This command is used to set the clamp voltage of load dump wave of car.

Command syntax
CARWave:ISO16750:LOAD:DUMP:US <value>

Arguments
MINimum|MAXimum|NR3

Reset Value
MINimum

Example
CARW:ISO16750:LOAD:DUMP:US 40

Query syntax
CARW:ISO16750:LOAD:DUMP:US? [MINimum|MAXimum]

Copyright© Itech Electronics Co., Ltd. 80


Car Wave Command(IT6500C)

Returns
NR3

CARWave:ISO16750:LOAD:DUMP[:TIMe]:TD[:LEVel]
This command is used to set pulse width of load dump.

Command syntax
CARWave:ISO16750:LOAD:DUMP:TD <value>

Arguments
MINimum|MAXimum|NR3

Reset Value
0.004

Example
CARW:ISO16750:LOAD:DUMP:TD 40

Query syntax
CARW:ISO16750:LOAD:DUMP:TD? [MINimum|MAXimum]

Returns
NR3

CARWave:ISO16750:LOAD:DUMP:VOLTage[:LEVel]
This command is used to set the voltage system of load dump.

Command syntax
CARWave:ISO16750:LOAD:DUMP:VOLT <12V|24V>

Arguments
12V|24V

Reset Value
12V

Example
CARW:ISO16750:LOAD:DUMP:VOLT 12V

Query syntax
CARW:ISO16750:LOAD:DUMP:VOLT?

Returns
<CRD>

Copyright© Itech Electronics Co., Ltd. 81


Car Wave Command(IT6500C)

CARWave:SAE[:TEST]:2B[:STATe]
This command is used to simulate the SAEJ1113-11 TEST 2B.

Command syntax
CARWave:SAE:2B <bool>

Arguments
ON|OFF|1|0

Reset Value
0

Example
CARWave:SAE:2B 1

Query syntax
CARWave:SAE:2B?

Returns
0|1

CARWave:SAE[:TEST]:2B:VOLTage[:LEVel]
This command is used to select voltage system of SAEJ1113-11 TEST 2B.

Command syntax
CARWave:SAE:2B:VOLT <12V|24V>

Arguments
12V|24V

Reset Value
12V

Example
CARWave:SAE:2B:VOLT 12V

Query syntax
CARWave:SAE:2B:VOLT?

Returns
<CRD>

CARWave:SAE[:TEST]:2B[:TIMe]:TD[:LEVel]
This command is used to set pulse width of SAEJ1113-11 TEST 2B

Copyright© Itech Electronics Co., Ltd. 82


Car Wave Command(IT6500C)

Command syntax
CARWave:SAE:2B:TD <value>

Arguments
MINimum|MAXimum|NR3

Reset Value
0.2

Example
CARWave:SAE:2B:TD 0.05

Query syntax
CARWave:SAE:2B:TD? [MINimum|MAXimum]

Returns
NR3

CARWave:SAE[:TEST]:4[:STATe]
This command is used to simulate SAEJ1113-11 TEST 4.

Command syntax
CARWave:SAE:4 <bool>

Arguments
ON|OFF|1|0

Reset Value
0

Example
CARWave:SAE:4 1

Query syntax
CARWave:SAE:4?

Returns
0|1

CARWave:SAE[:TEST]:4:VOLTage[:LEVel]
This command is used to select voltage system of SAEJ1113-11 TEST 4

Command syntax
CARWave:SAE:4:VOLT <12V|24V>

Copyright© Itech Electronics Co., Ltd. 83


Car Wave Command(IT6500C)

Arguments
12V|24V

Reset Value
12V

Example
CARWave:SAE:4:VOLT 12V

Query syntax
CARWave:SAE:4:VOLT?

Returns
<CRD>

CARWave:SAE[:TEST]:4[:VOLTage]:VS[:LEVel]
This command is used to set Vs of SAEJ1113-11 TEST 4.

Command syntax
CARWave:SAE:4:VS < value >

Arguments
MINimum|MAXimum|NR3

Reset Value
MINimum

Example
CARWave:SAE:4:VS 10

Query syntax
CARWave:SAE:4:VS?

Returns
NR3

CARWave:SAE[:TEST]:4[:VOLTage]:VA[:LEVel]
This command is used to set Va of SAEJ1113-11 TEST 4.

Command syntax
CARWave:SAE:4:VA < value >

Arguments
MINimum|MAXimum|NR3

Copyright© Itech Electronics Co., Ltd. 84


Car Wave Command(IT6500C)

Reset Value
MINimum

Example
CARWave:SAE:4:VA 10

Query syntax
CARWave:SAE:4:VA?

Returns
NR3

CARWave:SAE[:TEST]:4[:TIMe]:T7[:LEVel]
This command is used to set T7 of SAEJ1113-11 TEST 4

Command syntax
CARWave:SAE:4:T7 < value >

Arguments
MINimum|MAXimum|NR3

Reset Value
MINimum

Example
CARWave:SAE:4:T7 0.1

Query syntax
CARWave:SAE:4:T7?

Returns
NR3

CARWave:SAE[:TEST]:4[:TIMe]:T9[:LEVel]
This command is used to set T9 SAEJ1113-11 TEST 4.

Command syntax
CARWave:SAE:4:T9 < value >

Arguments
MINimum|MAXimum|NR3

Reset Value
MINimum

Copyright© Itech Electronics Co., Ltd. 85


Car Wave Command(IT6500C)

Example
CARWave:SAE:4:T9 0.1

Query syntax
CARWave:SAE:4:T9?

Returns
NR3

CARWave:SAE[:TEST]:4[:TIMe]:T11[:LEVel]
This command is used to set T11 of SAEJ1113-11 TEST 4

Command syntax
CARWave:SAE:4:T11 < value >

Arguments
MINimum|MAXimum|NR3

Reset Value
MINimum

Example
CARWave:SAE:4:T11 0.1

Query syntax
CARWave:SAE:4:T11?

Returns
NR3

CARWave:SAE[:TEST]:5[:STATe]
This command is used to simulate SAEJ1113-11 TEST 5.

Command syntax
CARWave:SAE:5 <bool>

Arguments
ON|OFF|1|0

Reset Value
0

Example
CARWave:SAE:5 1

Copyright© Itech Electronics Co., Ltd. 86


Car Wave Command(IT6500C)

Query syntax
CARWave:SAE:5?

Returns
0|1

CARWave:SAE[:TEST]:5:TEST[:MODe]
This command is used to select test mode of SAEJ1113-11 TEST 5.

Command syntax
CARWave:SAE:5:TEST <AMODe|BMODe>

Arguments
AMODe|BMODe

Reset Value
AMODe

Example
CARWave:SAE:5:TEST AMODe

Query syntax
CARWave:SAE:5:TEST?

Returns
<CRD>

CARWave:SAE[:TEST]:5[:VOLTage]:UN[:LEVel]
This command is used to set Un of SAEJ1113-11 TEST 5.

Command syntax
CARWave:SAE:5:UN < value >

Arguments
MINimum|MAXimum|NR3

Reset Value
MINimum

Example
CARWave:SAE:5:UN 70

Query syntax
CARWave:SAE:5:UN?

Copyright© Itech Electronics Co., Ltd. 87


Car Wave Command(IT6500C)

Returns
NR3

CARWave:SAE[:TEST]:5[:VOLTage]:US[:LEVel]
This command is used to set Us of SAEJ1113-11 TEST 5

Command syntax
CARWave:SAE:5:US < value >

Arguments
MINimum|MAXimum|NR3

Reset Value
MINimum

Example
CARWave:SAE:5:US 50

Query syntax
CARWave:SAE:5:US?

Returns
NR3

CARWave:SAE[:TEST]:5[:TIMe]:TD[:LEVel]
This command is used to set Td of SAEJ1113-11 TEST 5

Command syntax
CARWave:SAE:5:TD < value >

Arguments
MINimum|MAXimum|NR3

Reset Value
MINimum

Example
CARWave:SAE:5:TD 0.2

Query syntax
CARWave:SAE:5:TD?

Returns
NR3

Copyright© Itech Electronics Co., Ltd. 88


Car Wave Command(IT6500C)

CARWave:SAE[:TEST]:5:VOLTage[:LEVel]
This command is used to set voltage system of SAEJ1113-11 TEST 5

Command syntax
CARWave:SAE:5:VOLT < 12V|24V >

Arguments
12V|24V

Reset Value
12V

Example
CARWave:SAE:5:VOLT 12V

Query syntax
CARWave:SAE:5:VOLT?

Returns
<CRD>

CARWave:LV124:E02[:STATe]
This command is used to simulate LV124 E02 wave.

Command syntax
CARWave:LV124:E02 <bool>

Arguments
ON|OFF|1|0

Reset Value
0

Example
CARWave:LV124:E02 1

Query syntax
CARWave:LV124:E02?

Returns
0|1

CARWave:LV124:E04[:STATe]
This command is used to simulate LV124 E04.

Copyright© Itech Electronics Co., Ltd. 89


Car Wave Command(IT6500C)

Command syntax
CARWave:LV124:E04 <bool>

Arguments
ON|OFF|1|0

Reset Value
0

Example
CARWave:LV124:E04 1

Query syntax
CARWave:LV124:E04?

Returns
0|1

CARWave:LV124:E05[:STATe]
This command is used to simulate LV124 E05.

Command syntax
CARWave:LV124:E05 <bool>

Arguments
ON|OFF|1|0

Reset Value
0

Example
CARWave:LV124:E05 1

Query syntax
CARWave:LV124:E05?

Returns
0|1

CARWave:LV124:E07[:STATe]
This command is used to simulate LV124 E07.

Command syntax
CARWave:LV124:E07 <bool>

Copyright© Itech Electronics Co., Ltd. 90


Car Wave Command(IT6500C)

Arguments
ON|OFF|1|0

Reset Value
0

Example
CARWave:LV124:E07 1

Query syntax
CARWave:LV124:E07?

Returns
0|1

CARWave:LV124:E07:UBMAX[:LEVel]
This command is used to set starting voltage Ubmax of LV124 E07.

Command syntax
CARWave:LV124:E07:UBMAX < value >

Arguments
MINimum|MAXimum|NR3

Reset Value
0.0

Example
CARWave:LV124:E07:UBMAX 50

Query syntax
CARWave:LV124:E07:UBMAX?

Returns
NR3

CARWave:LV124:E07:UBMIN[:LEVel]
This command is used to set keeping voltage Ubmin of LV124 E07.

Command syntax
CARWave:LV124:E07:UBMIN < value >

Arguments
MINimum|MAXimum|NR3

Copyright© Itech Electronics Co., Ltd. 91


Car Wave Command(IT6500C)

Reset Value
MINimum

Example
CARWave:LV124:E07:UBMIN 20

Query syntax
CARWave:LV124:E07:UBMIN?

Returns
NR3

CARWave:LV124:E07[:UBMIN]:TIMe
This command is used to set keeping voltage duration of LV124 E07

Command syntax
CARWave:LV124:E07:TIM < value >

Arguments
MINimum|MAXimum|NR3

Reset Value
0.0

Example
CARWave:LV124:E07:TIM 1

Query syntax
CARWave:LV124:E07:TIM?

Returns
NR3

CARWave:LV124:E08[:STATe]
This command is used to simulate LV124 E08.

Command syntax
CARWave:LV124:E08 <bool>

Arguments
ON|OFF|1|0

Reset Value
0

Copyright© Itech Electronics Co., Ltd. 92


Car Wave Command(IT6500C)

Example
CARWave:LV124:E08 1

Query syntax
CARWave:LV124:E08?

Returns
0|1

CARWave:LV124:E08:UBMAX[:LEVel]
This command is used to set starting voltage Ubmax of LV124 E08.

Command syntax
CARWave:LV124:E08:UBMAX < value >

Arguments
MINimum|MAXimum|NR3

Reset Value
0.0

Example
CARWave:LV124:E08:UBMAX 50

Query syntax
CARWave:LV124:E08:UBMAX?

Returns
NR3

CARWave:LV124:E08:UBMIN[:LEVel]
This command is used to set keeping voltage Ubmin of LV124 E08.

Command syntax
CARWave:LV124:E08:UBMIN < value >

Arguments
MINimum|MAXimum|NR3

Reset Value
0.0

Example
CARWave:LV124:E08:UBMIN 20

Copyright© Itech Electronics Co., Ltd. 93


Car Wave Command(IT6500C)

Query syntax
CARWave:LV124:E08:UBMIN?

Returns
NR3

CARWave:LV124:E08[:UBMIN]:TIMe
This command is used to set keeping voltage duration of LV124 E08.

Command syntax
CARWave:LV124:E08:TIM < value >

Arguments
MINimum|MAXimum|NR3

Reset Value
0.0

Example
CARWave:LV124:E08:TIM 1

Query syntax
CARWave:LV124:E08:TIM?

Returns
NR3

CARWave:LV124:E09[:STATe]
This command is used to simulation LV124 E09.

Command syntax
CARWave:LV124:E09 <bool>

Arguments
ON|OFF|1|0

Reset Value
0

Example
CARWave:LV124:E09 1

Query syntax
CARWave:LV124:E09?

Copyright© Itech Electronics Co., Ltd. 94


Car Wave Command(IT6500C)

Returns
0|1

CARWave:LV124:E09:UBMIN[:LEVel]
This command is used to set keeping voltage Ubmin of LV124 E09.

Command syntax
CARWave:LV124:E09:UBMIN < value >

Arguments
MINimum|MAXimum|NR3

Reset Value
6.0

Example
CARWave:LV124:E09:UBMIN 20

Query syntax
CARWave:LV124:E09:UBMIN?

Returns
NR3

CARWave:LV124:E11[:STATe]
This command is used to simulate LV124 E11.

Command syntax
CARWave:LV124:E11 <bool>

Arguments
ON|OFF|1|0

Reset Value
0

Example
CARWave:LV124:E11 1

Query syntax
CARWave:LV124:E11?

Returns
0|1

Copyright© Itech Electronics Co., Ltd. 95


Car Wave Command(IT6500C)

CARWave:LV124:E11:TEST:MODE
This command is used to select test mode of LV124 E11.

Command syntax
CARWave:LV124:E11:TEST:MODE <COLD|WARM >

Arguments
COLD|WARM

Reset Value
COLD

Example
CARWave:LV124:E11:TEST:MODE COLD

Query syntax
CARWave:LV124:E11:TEST:MODE?

Returns
<CRD>

CARWave:LV124:E11:PULSe:MODE
This command is used to select pulse mode of LV124 E11.

Command syntax
CARWave:LV124:E11:PULS:MODE <NORMal|SEVEre >

Arguments
NORMal | SEVEre

Reset Value
NORMal

Example
CARWave:LV124:E1:PULS:MODE NORMal

Query syntax
CARWave:LV124:E1:PULS:MODE?

Returns
<CRD>

CARWave:LV124:E12[:STATe]
This command is simulate LV124 E12.

Copyright© Itech Electronics Co., Ltd. 96


Car Wave Command(IT6500C)

Command syntax
CARWave:LV124:E12 <bool>

Arguments
ON|OFF|1|0

Reset Value
0

Example
CARWave:LV124:E12 1

Query syntax
CARWave:LV124:E12?

Returns
0|1

CARWave:LV124:E12:DELTAU[:LEVel]
This command is used to set voltage drop ΔU value of LV124 E12.

Command syntax
CARWave:LV124:E12:DELTAU < value >

Arguments
MINimum|MAXimum|NR3

Reset Value
0.0

Example
CARWave:LV124:E12:DELTAU 2

Query syntax
CARWave:LV124:E12:DELTAU?

Returns
NR3

Copyright© Itech Electronics Co., Ltd. 97


Battery Charge and Discharge Statistic Command

Chapter13 Battery Charge and Discharge


Statistic Command
BATTery:CAPacity:CLEar
This command is used to clear battery charge and discharge capacity.

Command syntax
BATTery:CAPacity:CLEar

Arguments
NONE

Example
BATT:CAP:CLE

FETCh:BATTery:CAPacity[:CHARge]?
This command is used to obtain battery charge capacity.

Command syntax
FETCh:BATTery:CAPacity[:CHARge]?

ReturnsUnit
AH

Returns:
NRf

Example
FETC:BATT:CAP? ->3.00

FETCh:BATTery:CAPacity:DISCharge?
This command is used to obtain battery discharge capacity.

Command syntax
FETCh:BATTery:CAPacity:DISCharge?

ReturnsArguments
AH

Returns
NRf

Copyright© Itech Electronics Co., Ltd. 98


Battery Charge and Discharge Statistic Command

Example
FETC:BATT:CAP:DISC? ->4.0

Copyright© Itech Electronics Co., Ltd. 99


Calibration Command

Chapter14 Calibration Command


CALibrate:SECure[:STATe]
This command is used to set the calibration state.

Command syntax
CALibrate:SECure[:STATe] <bool>,<string>

Arguments
0|1|OFF|ON,<string>

Example
CAL:SEC 0, “ 6522 “

Query syntax
CALibrate:SECure[:STATe]?

Returns
0|1

CALibrate:VOLTage:LEVel
This command is used to define the voltage calibration point.

Command syntax
CALibrate:VOLTage:LEVel <P0|P1>

Arguments
P0|P1

Example
CAL:VOLT:LEV P0

CALibrate:VOLTage[:DATA]
This command is used to read the actual voltage of the present
calibration point.

Command syntax
CALibrate:VOLTage[:DATA] <NRf>

Arguments
NRf

Unit
V
Copyright© Itech Electronics Co., Ltd. 100
Calibration Command

Example
CAL:VOLT 12.0V

CALibrate:CURRent:LEVel
This command is used to define the current calibration points.

Command syntax
CALibrate:CURRent:LEVel <P0|P1>

Arguments
P0|P1

Example
CAL:CURR:LEV P0

CALibrate:CURRent[:DATA]
This command is used to read the actual current of the present
calibration point.

Command syntax
CALibrate:CURRent[:DATA] <NRf>

Arguments
NRf

Unit
A

Example
CAL:CURR 20.0

CALibrate:MONitor:VOLTage:LEVel
This command is used to set monitoring the voltage calibration point.

Command syntax
CALibrate:MONitor:VOLTage:LEVel <P0|P1>

Arguments
P0|P1

Example
CAL:MON:VOLT:LEV P0

CALibrate:MONitor:VOLTage[:DATA]
This command is used to set the voltage calibration point data for monitoring.

Copyright© Itech Electronics Co., Ltd. 101


Calibration Command

Command syntax
CALibrate:MONitor:VOLTage[:DATA] <NRf>

Arguments
NRf

Unit
V

Example
CAL:MON:VOLT 30.0V

CALibrate:MONitor:CURRent:LEVel
This command is used to set monitoring the current calibration point.

Command syntax
CALibrate:MONitor:CURRent:LEVel <P0|P1>

Arguments
P0|P1

Example
CAL:MON:CURR:LEV P0

CALibrate:MONitor:CURRent[:DATA]
This command is used to current calibration point data for monitoring.

Command syntax
CALibrate:MONitor:CURRent[:DATA] <NRf>
Arguments
NRf

Unit
A

Example
CAL:MON:CURR 15.0

CALibrate:PROGram:VOLTage:LEVel
This command is used to set voltage calibration point for programming.

Command syntax
CALibrate:PROGram:VOLTage:LEVel <P0|P1>

Copyright© Itech Electronics Co., Ltd. 102


Calibration Command

Arguments
P0|P1

Example
CAL:PROG:VOLT:LEV P0

CALibrate:PROGram:VOLTage[:DATA]
This command is used to set calibration data of program voltage.

Command syntax
CALibrate:PROGram:VOLTage[:DATA] <NRf>
Arguments
NRf

Unit
V

Example
CAL:PROG:VOLT 24.0V

CALibrate:PROGram:CURRent:LEVel
This command is used to set calibration point of program current.

Command syntax
CALibrate:PROGram:CURRent:LEVel <P0|P1>

Arguments
P0|P1

Example
CAL:PROG:CURR:LEV P0

CALibrate:PROGram:CURRent[:DATA]
This command is used to set calibration data of program current.

Command syntax
CALibrate:PROGram:CURRent[:DATA] <NRf>

Arguments
NRf

Unit
A

Copyright© Itech Electronics Co., Ltd. 103


Calibration Command

Example
CAL:PROG:CURR 15.0

CALibrate:EQUal:INPut:CURRent:LEVel
This command is used to set calibration point of current sharing input current.

Command syntax
CALibrate:EQUal:INPut:CURRent:LEVel <P0|P1>

Arguments
P0|P1

Example
CAL:EQU:INP:CURR P0

CALibrate:EQUal:INPut:CURRent[:DATA]
This command is used to set calibration data of current sharing input current.

Command syntax
CALibrate:EQUal:INPut:CURRent[:DATA

Arguments
NRf

Unit
A

Example
CAL:EQU:INP:CURR 12.0A

CALibrate:EQUal:OUTPut:CURRent:LEVel
This command is used to set calibration point of current sharing output current.

Command syntax
CALibrate:EQUal:OUTPut:CURRent:LEVel <P0|P1>

Arguments
P0|P1

Example
CAL:EQU:OUTP:CURR:LEV P0

CALibrate:EQUal:OUTPut:CURRent[:DATA]
This command is used to set calibration data of current sharing output current.

Copyright© Itech Electronics Co., Ltd. 104


Calibration Command

Command syntax
CALibrate:EQUal:OUTPut:CURRent[:DATA] <NRf>

Arguments
NRf

Unit
A

Example
CAL:EQU:OUTP:CURR 12.0

CALibrate:SUMMary:OUTPut:CURRent:LEVel
This command is used to set calibration point of summary current.

Command syntax:
CAL:SUMM:OUTPut:CURRent:LEVel <P0|P1>

Arguments
P0|P1

Example
CAL:SUMM:OUTP:CURR:LEV P0

CALibrate:SUMMary:OUTPut:CURRent[:DATA]
This command is used to set calibration data of summary current.

Command syntax
CALibrate:SUMMary:OUTPut:CURRent[:DATA] <NRf>

Arguments
NRf

Unit
A

Example
CAL:SUMM:OUTP:CURR 20.0

CALibrate:SAVe
This command is used to save the calibration parameters in a nonvolatile
memory.

Copyright© Itech Electronics Co., Ltd. 105


Calibration Command

Command syntax
CALibrate:SAVe

Example
CAL:SAV

CALibrate:INITialize
This command is used to initialize the calibration parameters.

Command syntax
CALibrate:INITialize

Example
CAL:INIT

Copyright© Itech Electronics Co., Ltd. 106


Parallel Related Command

Chapter15 Parallel Related Command


LINK[:STATe]
This command is used to set link state.

Command syntax
LINK[:STATe] <bool>

Arguments
0|1|OFF|ON

Example
LINK:STAT 1

Query syntax
LINK[:STATe]?

Returns
0|1

LINK:ROLE
This command is used to set link role.

Command syntax
LINK:ROLE <SLAVe|MASTer>

Arguments
SLAVe|MASTer

Example
LINK:ROLE slav

Query syntax
LINK:ROLE?

Returns
<CRD>

LINK:NUMBer
This command is used to set link number.

Command syntax
LINK:NUMBer <MINimum|MAXimum|NR1 >

Copyright© Itech Electronics Co., Ltd. 107


Parallel Related Command

Arguments
MINimum|MAXimum|<2-32>

Example
LINK:NUMB 1

Query syntax
LINK:NUMBer?

Returns
NR1

Copyright© Itech Electronics Co., Ltd. 108


TraceRelated Command(IT6500C)

Chapter16 TraceRelated Command(IT6500


C)
In the sub-system, this command is used to configure and control data save in
cache.

TRACe:CLEar
This command is used to clear reading cache. If cache is not cleared,
subsequent saving will overwrite the previous data.

Command syntax
TRACe:CLEar

Arguments
NONE

Example
TRAC:CLE

TRACe:POINts
This command is used to specify cache size.

Command syntax
TRACe:POINts <2 to 2500|MINimum|MAXimum|DEFault>

Arguments
2 to 2500|MINimum|MAXimum|DEFault

Returns
NR1

Example
TRAC:POIN 10

Query syntax
TRACe:POINts? [MINimum|MAXimum|DEFault]

Returns
<NR1>

TRACe:FEED:CONTrol
This command is used to select cache control. Select NEVer, Save to Cache is
disabled; select NEXT, save process starts and will stop when the cache is
filled in. Select ALWays. After cache is filled in, circulate the cache.

Copyright© Itech Electronics Co., Ltd. 109


TraceRelated Command(IT6500C)

Command syntax
TRACe:FEED:CONTrol <CRD>

Command Arguments
NEXT|ALWays|NEVer

Query syntax
TRACe:FEED:CONTrol?

Returns
<CRD>

TRACe:FEED:SELected
This command is used to select the reading source saved in the cache. If
VOLTage is selected, the voltage reading is saved in cache; if CURRent is
selected, the current reading is saved in cache. If VOLTage and CURRent are
simultaneously selected, both voltage and current are saved in cache when
saving is executed.

Command syntax
TRACe:FEED:SELected <CRD>

Command Arguments
VOLTage|CURRent|BOTH

Example
TRAC:FEED:SEL VOLT

Query syntax
TRACe:FEED:SELected?

Returns
<CRD>

TRACe:DELay
This command is used to select cache delay time.

Command syntax
TRACe:DELay<NRf>

Command Arguments
0 to3600s|MINimum|MAXimum|Default

Unit
s

Copyright© Itech Electronics Co., Ltd. 110


TraceRelated Command(IT6500C)

Query syntax
TRACe:DELay? [MINimum|MAXimum|DEFault]

Returns
<NR3>

TRACe:TIMer
This command is used to select cache time interval.

Command syntax
TRACe:TIMer < NRf>

Arguments
0.00002 to 3600s|MINimum|MAXimum|DEFault

Unit
s

Example
TRAC:TIM 0.1

Query syntax
TRACe:TIMer? [MINimum|MAXimum|DEFault]

Returns
<NR3>

TRACe:POINts:ACTual?
This command is used to select number of actual readings in the cache.

Command syntax
TRACe:POINts:ACTual?

Returns
<NR1>

TRACe:CLEar:AUTO[:STATe]
This command is used to select whether to automatically clear cache data.
When Auto Clear is enabled, when saving starts, buffer will be automatically
cleared; when it is disabled, the new reading will be saved to the buffer area
following the previous data till the buffer is full or when saving stops.

Command syntax
TRACe:CLEar:AUTO[:STATe] <bool>

Copyright© Itech Electronics Co., Ltd. 111


TraceRelated Command(IT6500C)

Arguments
0|1|OFF|ON

Query syntax
TRACe:CLEar:AUTO[:STATe]?

Returns
0|1

TRACe:DATA?
This command is used to read all values saved in the cache.

Command syntax
TRACe:DATA?

Returns
{ <NR3>,<NR3>,<NR3>…}

Copyright© Itech Electronics Co., Ltd. 112


IEEE-488 Commands

Chapter17 IEEE-488 Commands


This chapter introduced often-used IEEE-488 commands.

*CLS
This command clears the following registers:
 Standard event register
 Query event register
 Operation event register
 Status byte register

Command syntax
*CLS

Arguments
None

*ESE
This command can set the parameter of standard event enable register.
Setting parameter can determine which bit of standard event register is 1
and the byte will enable ESB of status byte register is 1.

Command syntax
*ESE <NR1>

Arguments
0~255

Default set
Refer to *PSC command

Example
*ESE 128

Query syntax
*ESE?

Returns
<NR1>

Related Command
*ESR? *PSC *STB?

Copyright© Itech Electronics Co., Ltd. 113


IEEE-488 Commands

*ESR?
This command can read the value of standard event status register. After
executing this command, standard event status register is reset. Bit
definition of standard event status register is as the same as the
standard event status enable register.

Query syntax
*ESR?

Arguments
None

Returns
<NR1>

Related Command
*CLS *ESE *ESE? *OPC

*IDN?
This command can read information about power supply. The returns
parameter contains 4 segments divided by comma.

Query syntax
*IDN?

Arguments
None

Returns
<AARD> segment description

Example
ITECH,IT6522C,601234567890123456,1.03-1.02

*OPC
When all commands before this command are executed, bit OPC in
standard event register will be set to 1.

Command syntax
*OPC

Arguments
None

Query syntax
*OPC?
Copyright© Itech Electronics Co., Ltd. 114
IEEE-488 Commands

Returns
<NR1>

*PSC
This command is used to control whether the power supply will generate a
service request when power on again.
 1 OR ON: When the power supply power on, status byte enable register,
operater event enable register, query event enable register and standard
event enable register will be cleared.
 0 OR OFF: When the power supply power on, The value of status byte
enable register, operater event enable register, query event enable register
and standard event enable register will be stored in the none-volatile
storage, which will be recalled when power on.

Command Syntax
*PSC <bool>

Parameters
0|1|ON|OFF

Query Syntax
*PSC?

Returned Parameters
0|1

*RST
This command reset the power supply to default settings.

Command syntax
*RST

Arguments
None

*SRE <n>
This command can set the parameter of state byte enable register.
Setting parameter can determine which byte value of state byte register
is 1 and the byte will set RQS of state byte register to 1. Bit definition of
state byte enable register is as the same as the state byte register.

Command syntax
*SRE <NRf>

Arguments
0~255

Copyright© Itech Electronics Co., Ltd. 115


IEEE-488 Commands

Default set
Refer to *PSC command

Example
*SRE 128

Query syntax
*SRE?

Returns
<NR1>

Related Command
*ESE *ESR? *PSC *STB?

*STB
This command can read the data from status byte register. After execute this
command, the value of bit6 in status byte register will be clean.
Bit 7 6 5 4 3 2 1 0
Position
Condition OPER RQS ESB MAV QUES EAV Not used Not Used

The Arguments description in table as follow:


 OPER: Operation status summary
 RQS: Request service
 ESB: Event status summary
 MAV: Message is enabled
 QUES: EQuery status register position.
 EAV: Error message is enabled.

Query syntax
*STB?

Arguments
None

Returns
<NR1>

Related Command
*CLS *ESE *ESR

*SAV
This command can save the current setups of power supply to specified
memory. These setups contains current setups, voltage setups, max voltage
Copyright© Itech Electronics Co., Ltd. 116
IEEE-488 Commands

set, min voltage set, OVP set, OVP timer, OPP set, voltage rise and fall time,
analog interface and series and parallel set.
The memory can divided into 10 groups, each contains 0~9 setups. So IT6512
can save 100 Setups in all.

Command syntax
*SAV<NRf>〉

Arguments
0~99

Example
*SAV 99

*RCL:
This command can recall the setups you saved before from the specified
memory.

Command syntax
*RCL<NRf>

Arguments
0~99

Example
*RCL 80

*TST?
This command is used to query the self-test by the instrument. 0 indicates that
self-test succeeds; other Arguments indicate self-test fails. In addition, in case
of failure, an error information will be generated to describe failure reason.

Command syntax
*TST?

Arguments
None

Returns
<NR1>

Copyright© Itech Electronics Co., Ltd. 117


Contact US
Thank you for purchasing ITECH products.If you have any doubt about this product,please
contact us as follow.
1. Please refer to the CD-ROM of related user’s manual in package.
2. Visit ITECH website www.itechate.com .
3. Select the most convenient contact for further consultation.

You might also like