SK-HEAT-W Series

Intelligent Thermal (Heat) Detector


Honeywell Silent Knight SK-HEAT-W Series intelligent thermal detectors
are designed for both performance and aesthetics. A new modern, sleek,
contemporary design and advanced thermal technologies make the
SK-HEAT-W Series ideal for both system operation and building design.

The point ID address, set using rotary decimal switches, provide specific
detector locations. The series includes a 135°F/57°C fixed temperature,
rate-of-rise and a 190°F/88°C fixed high-temperature detectors. These
thermal detectors provide effective, intelligent property protection in a
variety of applications.

SK-HEAT-W

F E AT U R E S & B E N E F I T S
• Sleek and stylish • High temperature • 360°-field viewing • Built-in functional test • Sealed against back
contemporary design model (SK-HEAT- angle of the visual switch activated by pressure
W-HT) factory preset alarm indicators (two external magnet
• Advanced thermal • Plugs into separate
to 190°F (88°C) bi-color LEDs). LEDs
technology for fast • Walk test with address base for ease of
blink green in Normal
response • Addressable by device display (an address of installation and
condition and turn on
121 will blink the maintenance
• Fixed temperature • Two-wire SLC steady red in Alarm.
detector LED 12-
model (SK-HEAT-W) connection • SEMS screws for
• Integral (pause)-1)
factory preset to wiring of the separate
• Visible LEDs “blink” communications and
135°F (57°C) • Low standby current base
every time the unit is built-in device-type
• Rate-of-rise model addressed identification • Designed for • Optional remote,
(SK-HEAT-W-ROR), directsurface or single- gang LED
• Built-in tamper- • Remote test feature
15°F (8.3°C) per electrical box accessory
resistant feature from the panel
minute mounting
APPLICATIONS INTELLIGENT BASES ACCESSORIES
Use thermal detectors for protection of B300-6: White, standard flanged CK300: Color Kit (includes cover and
property. For further information, refer low-profile mounting base. trim ring), white, 10-Pack.
to manual I56-6541, Applications B300-6-BP: Bulk pack of B300-6, CK300-IV: Color Kit (includes cover
Manual for System Smoke Detectors, package contains 10. and trim ring), ivory, 10-Pack.
which provides detailed information on B300-6-IV: Ivory, standard flanged CK300-BL: Color Kit (includes cover
detector spacing, placement, zoning, low-profile mounting base. and trim ring), black, 10-Pack.
wiring, and special applications
B300A-6-IV: Ivory, standard flanged M02-04-01: Detector test magnet.
low-profile mounting base. UL listed. M02-09-00: Telescoping test magnet.
INSTALLATION
B501-WHITE: White, standard RA100Z: Remote LED annunciator
The SK-HEAT-W Series plug-in
European flangeless mounting base. UL SMB600: Surface Mounting Kit
intelligent thermal detectors use a
listed. (flanged).
separate base to simplify installation,
B501-BL: Black, standard European TR300: Replacement trim ring for
service, and maintenance. Installation
flangeless mounting base. UL listed. B300-6, white.
instructions are shipped with each
detector B501-IV: Ivory, standard European TR300-IV: Replacement trimring for
flangeless mounting base. UL listed. B300-6-IV, ivory..
Mount base (all base types) on an B200S-WH: White, Intelligent,
electrical backbox which is at least 1.5" programmable sounder base.
(3.81 cm) deep. B200S-IV: Ivory, Intelligent,
programmable sounder base.
NOTE:
B200SR-WH: White, Intelligent sounder
• Because of the inherent supervision
base for retrofit applications.
provided by the SLC loop, end-of-line
B200SR-IV: Ivory, Intelligent sounder
resistors are not required. Wiring
base for retrofit applications.
“T-taps” or branches are permitted for
B200S-LF-WH: White, Low Frequency
Style 4 (Class “B”) wiring.
Intelligent, programmable sounder
• When using relay or sounder bases, base.
consult the installation sheet for device B200S-LF-IV: Ivory, Low Frequency
limitations between isolator modules Intelligent, programmable sounder
and isolator bases. base.
NOTE: Detectors must be mounted to one B200SR-LF-WH: White, Low
of the Intelligent Bases listed below. Frequency Intelligent sounder base for

ORDERING INFORMATION
retrofit applications.

SK-HEAT-W: Thermal heat detector, B200SR-LF-IV: Ivory, Low Frequency

135°F fixed, white. Intelligent sounder base for retrofit


applications.
SK-HEAT-ROR-W: Thermal heat
detector, 135°F rate of rise, white. B224RB-WH: White, plug-in System
Sensor relay base.
SK-HEAT-HT-W: Thermal heat detector,
190°F high temp, white. B224RB-IV: Ivory, plug-in System
Sensor relay base.
B224BI-WH: White, plug-in System
Sensor isolator detector base.
B224BI-IV: Ivory, plug-in System
Sensor isolator detector base.
SK-HEAT-W Series Detector Technical Specifications
PHYSICAL COMPATIBILITY For a complete listing of all
compliance approvals and
Height: 2.0" (51mm) installed in B300-6 base The SK-HEAT-W series detectors are certifications, please visit
compatible with the following Honeywell Silent www.silentknight.com.
Diameter: 6.2" (156mm) installed in B300-6
base 4.1" (104 mm) installed in B501 base Knight fire alarm control panels: Microsoft, Windows, and
the Windows Logo are
Weight: 3.4 oz (95 g) 6820: Addressable fire alarm control panel registered trademarks
or trademarks of
6820EVS: Addressable fire alarm control panel Microsoft Corporation.
ENVIRONMENTAL
with an emergency voice system.
Operating Temperature range: Silent Knight®, System
6808: Addressable fire alarm control panel Sensor® and Honeywell®
Heat -Fixed temperature: -4°F to 100°F (-20°C are registered
6700: Addressable fire alarm control panel trademarks of Honeywell
to 38°C) International, Inc.
5700: Addressable fire alarm control panel
Heat -Rate of Rise (ROR): -4°F to 100°F (-20°C This document is not
to 38°C) 5808: Addressable fire alarm control panel intended to be used for
5820XL: Addressable fire alarm control panel installation purposes. We
Heat -High Temperature: -4°F to 150°F (-20°C try to keep our product
to 66°C) 5820XL-EVS: Addressable fire alarm control information up-to
date and accurate. We
Humidity: 10% to 93% non-condensing panel with an emergency voice system cannot cover all specific
applications or anticipate
Thermal Ratings: Fixed Temperature Set point: AGENCY LISTINGS AND APPROVALS all requirements. All
For exact certification listings for each model, specifications are subject
135°F (57°C)
please reference the respective agency Web site. to change without notice.
Rate-of-Rise Detection: 15°F/min. (8.3°C/min UL listed: S2101 For Technical Support,
High Temperature Heat: 190°F (88°C)Electrical FM Approved call 800-446-6444.

Ratings CSFM: 7270-0559:0511

ELECTRICAL RATINGS
Voltage Range: 15 to 32VDC peak
Standby current (max. avg.): 200uA @ 24 VDC
(one communication every 5 seconds with LED
enabled).
LED current (max.): 4.5mA @ 24 VDC (“ON”).

For more information


Learn more about Honeywell Silent Knight and other
products by visiting www.silentknight.com

Honeywell Silent Knight


12 Clintonville Road
Northford, CT 06472 Doc 351637 | Rev A | 04/18
800-328-0103 © 2018 Honeywell International Inc.