Manual NEF160110VAC Overload Relay

This document provides information on the NEF Motor Protection Relay from Protek Electronics. It describes the key features and operation of the NEF-160 model. The NEF-160 is an electronic motor protection relay rated for currents from 33 to 160 amps with a 1000V AC rating. It has adjustable current and trip class settings via DIP switches to suit the protected motor. Standard features include options for automatic, manual, or remote reset as well as an input for motor thermistor protection.

Uploaded by

Long Pham
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views25 pages

Manual NEF160110VAC Overload Relay

This document provides information on the NEF Motor Protection Relay from Protek Electronics. It describes the key features and operation of the NEF-160 model. The NEF-160 is an electronic motor protection relay rated for currents from 33 to 160 amps with a 1000V AC rating. It has adjustable current and trip class settings via DIP switches to suit the protected motor. Standard features include options for automatic, manual, or remote reset as well as an input for motor thermistor protection.

Uploaded by

Long Pham
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 25

NEF Motor

Protection Relay

Product
Familiarisation
September 2017. V1.3
The range

2 Models
• NEF-40: 0.825…40A 1)
• NEF-160: 33…160A

Rated voltage
• 1000V AC

Control supply voltage options


• 24, 110 or 240V AC

Compliance
• IEC 60947-4-1
• RCM
1) Basic current setting NEF-40 = 8.25…40A – lower current ranges are possible by looping CT wires

NEF Product Familiarisation 2


Key Features

• Simple to use and setup. DIP switches allow for


quick, accurate and repeatable settings
• Rated up to 1000V AC. Well suited for underground
mining applications
• Remote reset as standard
• PTC thermistor input as standard
• Adjustable trip class (5-10-20-30) to suit application
requirements
• Optional adaptor plate for easy transition from
Sprecher+Schuh CEF1-11/12 overload

NEF Product Familiarisation 3


Compact dimensions

• One frame size

77

189
Pass-thru window allows for cables
up to 50mm2

Dimensions in mm 70

NEF Product Familiarisation 4


General Schematic

• Choice of control voltage 3 phase supply

• 24V, 110V or 240V AC


• Manual / remote / automatic reset
• Thermistor input
• Trip and alarm contacts

Motor thermistor

Control supply Trip & alarm contacts


Shown in powered state
Reset

NEF Product Familiarisation 5


Setting the current

• 7 setting DIP switches are provided in order to adjust the


NEF to the name plate full load current of the motor
• The current ranges are as follows:
• NEF-40 8.25 to 40 amps in 0.25 amp steps
• NEF-160 33 to 160 amps in 1 amp steps
• With all the switches off (to the right) the basic settings
are 8.25 and 33 amps respectively
• By switching the switches over to the left the current
setting is increased according to which switches are on

NEF-40 NEF-160

• In the example NEF-40, switches 1 (0.25A), 2 (0.5A) and 3 (1A) are to the left, therefore the
setting = 8.25 basic + 0.25 + 0.5 + 1, which is equal to 10 amps full load

• In the example NEF-160, switches 2 and 4 are added to the basic 33A setting = 33 + 2 + 8 = 43A

NEF Product Familiarisation 6


Current below 8.25 amps (1)

• With the NEF-40 it is possible to loop the 3 motor feed wires through the current transformer
which then allows lower currents to be set
• The current set on the switches is then divided by the number of CT loops
• Example 1; the current to be monitored is 5.0 amps. With 2 loops, the lowest current setting
becomes 8.25 / 2 = 4.125 amps
• If we multiply the current by 2 then 5.0 x 2 = 10. We therefore set the switches to 10 amps

No. of loops Effective setting range (A)

2 4.125…20

4 2.063…10
NEF

NEF

5 1.65….8

8 1.03…5

10 0.825…4

NEF Product Familiarisation 7


Current below 8.25 amps (2)

• Example: 5 loops of 2.5mm2 cable, which gives operation range of 1.65…8A.

NEF Product Familiarisation 8


Setting the trip class

• The NEF tripping curves can be adjusted to suit the application and to match the unit to the
motor’s thermal withstand capabilities. This is achieved by the use of 2 DIP switches on the
front panel. By adding the switch settings together, a range of tripping times can be set from 5
seconds to 30 seconds based on 6 times full load current (FLC)
• A standard setting of 10 seconds (switch 1 to the left), corresponds to that of a standard motor
and is equivalent to that of a normal thermal overload
• For motors with higher thermal capacity and for longer run-up times, a correspondingly higher setting
should be used
• For motors with lower thermal capacity and short run-up times, a lower setting should be used
• Refer to thermal withstand specifications made by motor manufacturers

NEF Product Familiarisation 9


Time Current Curves

Example: with trip class 20,


the NEF will trip within 20
seconds if the current is
600% of motor FLC

• Hot start and cold start refer to the temperature of the motor when starting
• A hot start is considered a time that a motor has been restarted in less than 30 minutes from the
previous start or after an overload condition has been experienced
• A cold start is an initial start or when a motor has not been ran for at least 30 minutes

NEF Product Familiarisation 10


Thermistor input

• The NEF incorporates a thermistor input


• If this function is not required a 1k resistor (supplied) must be installed across
terminals T1 and T2 of the NEF
• The NEF will trip if the thermistor chain is open, shorted or over temperature

• Technical data
• Max. resistance of thermistors 1500
• Max. no. of PTC sensors 6
• Overtemperature 3500
• Short circuit 50
• Indication LED

NEF Product Familiarisation 11


Choice of reset method

• Manual
• Reset is achieved by pressing the Reset pushbutton on the front of
the NEF after a suitable cool-down time 1)

• Automatic
• Short-circuit terminals 7 and 8
• The NEF will automatically reset after the minimum time depending
on alarm
• Manual reset pushbutton is disabled

• Remote
• Max. cable distance is 30 metres

1) Minimum cool-down time to reset in manual condition is 6x the selected trip class.

NEF Product Familiarisation 12


- -

- -
- -

- -

-
-
- -
· -

· -

-
-
- -

- -

W
W
W
· -

· -

·
-
-
-
-

- - - -

-
-

- -
- - - -

W
W
W
W
W

- -
Catalogue No: NEF-160-110VAC
OVERLOAD ELECTRONIC 33-160A 110V AC CONTROL
Motor Control and Drives > Motor Starting and Protection > Motor Protection > NHP Motor Protection Relays > NHP
Protek Electronic Motor Protection Relay

Electronic Overload 33-160A 110V AC Control Voltage.

· 1000V AC rated for suitability into underground mining 
applications
· To optimise inventory, three units over two sizes cover 0.825 to 
600 amps
· Adjustable current settings by DIP switches to suit protected 
motor
· As standard, choice of automatic or remote reset functionality to 
suit your requirements
· As standard, input for thermistor over protection adds 
convenience
· Trip curves can be selected to suit the application, for flexibility
· LED indication for immediate identification of cause of fault
· Rapid single-phasing detection keeps downtimes to a minimum
· Choice of control voltages 24, 110, 240V AC and 24V DC to suit 
installation
· Range of optional accessories available, including adaptor plate 
for CEF1-11/12 replacement NEF-40/160
 
Representative Photo Only
(actual product may vary based on configuration selections)

REFERENCES

IECEx Certificate -

Supplier Declaration of
-
Conformity:

Installation Guide: -

User Manual: -

Manufacturer Datasheet: -

Manufacturer Catalogue
-
& Product Selection:

NHP Electrical Engineering Products NEF160110VAC Datasheet
1300 NHP NHP | nhp.com.au     |     0800 NHP NHP | nhp-nz.com 14 August 2018, Page 2341 o
LED indication

PTC
• Blink LED: PTC short circuit trip 17 18 19 20 21
• Solid LED: PTC overtemperature trip

• Blink LED: current >110% Ie


• Solid LED: current overload trip

• Slow blink LED: increasing motor temperature


• Fast blink LED: decreasing motor temperature
• Solid LED: steady state motor temperature 98B

• Blink LED: phase imbalance trip


• Solid LED: phase failure trip • Solid LED: power on

NEF Product Familiarisation 13


Example power and control circuit
schematics

NEF Product Familiarisation 14


Adaptor plate for ease of installation

The adaptor plate adds an additional depth of 22mm to the footprint of the NEF.

NEF Product Familiarisation 15


NEF model description code

NEF Product Familiarisation 16