D000011316 E850 Tech Data Sheet

The document provides technical specifications for Landis+Gyr electricity meters, models ZMQ202, ZFQ202, and ZCQ202. The meters can measure voltages from 100-230V and currents from 1-5A, with measurement accuracy of ±0.28% for active energy. Environmental conditions the meters are designed to withstand include temperatures from -25-55°C, humidity up to 95%, vibrations, electromagnetic interference, and surge voltages. Power consumption is less than 1.4VA when connected to voltage circuits and up to 4.5VA when also connected to additional power supplies and communication units.

Uploaded by

strahinja
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
866 views10 pages

D000011316 E850 Tech Data Sheet

The document provides technical specifications for Landis+Gyr electricity meters, models ZMQ202, ZFQ202, and ZCQ202. The meters can measure voltages from 100-230V and currents from 1-5A, with measurement accuracy of ±0.28% for active energy. Environmental conditions the meters are designed to withstand include temperatures from -25-55°C, humidity up to 95%, vibrations, electromagnetic interference, and surge voltages. Power consumption is less than 1.4VA when connected to voltage circuits and up to 4.5VA when also connected to additional power supplies and communication units.

Uploaded by

strahinja
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

Elektrizitätszähler

Electricity Meters IEC


IEC/MID
Industrie
High Precision
und Gewerbe
Metering

Landis+Gyr Qualigrid

ZMQ202, ZFQ202, ZCQ202


Technical data

Date: 19.08.2011
Filename: D000011316 E850 ZXQ202 Technical Data EN.docx
© 2010 Landis+Gyr AG

D000011316 f
2/10

ZMQ202, ZFQ202, ZCQ202 Technical Specifications

Voltage Measuring Accuracy


Nominal Voltage Un Load Dependency Class 0.2 S Active
100 110 115 200 1 % In, cos  = 1  0.28 %
3x V,3x V,3x V,3x V,
3 3 3 3 5 % In to Imax, cos  = 1  0.14 %
2 % In, cos  = 0.5  0.40 %
190 230
3x  V (user defined) 10 % In to Imax, cos  = 0.5  0.24 %
3 3 deviations between the individual phases
at 100 % In < 0.10 %
Voltage Range losses <1%
measurement 70 to 115 % Un
functional 65 to 130 % Un Additional Power Supply
measurement shut down 45% Un for ZMQ nominal voltage ranges Un
lower thresholds possible 100 to 230 V AC/DC
24 to 125 V AC/DC
Current functional range 70 to 115 % Un
Nominal Current 1 A, 5 A frequency 50 or 60 Hz
max. power consumption 6 VA
Maximum Current Imax
standard 120 % In Operating Behaviour
metrological up to 170 % In Voltage Failure (Power Down)
for -1/2, -5/10 200 % In block inputs and outputs immediate
metrological up to 240 % In transmitting contacts after 100 ms
thermal 12 A (at least 1.5 x Imax) standby operation after 0.5 s
data storage after a further 0.2 s
Influence of short-time overcurrents switch off after approx. 2.5 s
20 Imax during 0.5 s according IEC < 0.05 %
typical 100 A during 1 s possible Voltage Restoration (Power Up) 3 phase
function standby after 1 to 3 s
Starting Load (standard) detection of
120 % / 150 % Imax active energy < 0.05 % Pn energy direction + phase voltage after 1 s
reactive energy < 0.1 % Qn
200 % Imax active energy < 0.1 % Pn Power Consumption
reactive energy < 0.2 % Qn General
On request the starting threshold can be multiplied 100
by 2, 4 or 8 but may not exceed 0.4 %. all values are typical values at 3x V
3
Frequency maximum values 1.5 x typical values
nominal frequency fn 50 or 60 Hz (selectable) all values are voltage dependant
range 90 to 110 % fn
range for primary values: (50) 100 to 40’000 A Current Circuit (only for measurement) < 0.1 VA
400 V to 1000 kV 1A 0.004 VA
5A 0.09 VA

© Landis+Gyr AG D000011316 f — ZMQ202, ZFQ202, ZCQ202 — Technical data


3/10

Power Consumption Environmental Influences


Power supply connected to the voltage circuits Impermeability according to IEC 60529
voltage circuit without f6 and f9 housing IP51
transmitting contacts and (0.5 W) 0.9 VA
communication unit Flammability according to IEC 695-2-1
(f6 housing only)
additional power supply contact force of heating wire 1N
with transmitting contacts (0.8 W) 1.4 VA
duration 30 s
and communication unit
test temperature = 960°C (terminal block)
test temperature = 650°C (housing)
Power supply not connected to the voltage circuits
voltage circuit 0.05 VA
Electromagnetic Compatibility
additional power supply type 0.1 VA Electrostatic Discharges acc. to IEC 61000-4-2
additional power supply contact discharge 8 kV
without transmitting module 3 VA
and communication unit Immunity to Electromagnetic RF Fields
according to IEC 61000-4-3
additional power supply
80 to 2000 MHz 10 V/m
with transmitting module 4.5 VA
and communication unit measuring deviation <1%

Radio Interference Suppression according to


Environmental Influences IEC/CISPR 22 class B
Temperature Range according to IEC 62052-11
metrological –10 °C to 45 °C Fast Transient Burst Test to IEC 61000-4-4
operation –25 °C to 55 °C current and voltage circuits not under load 4 kV
storage and transportation current and voltage circuits under load 2 kV
with battery –25 °C to 55 °C auxiliary circuits > 40 V 2 kV
storage and transportation
without battery –25 °C to 70 °C
Insulation Strength
Insulation Test (Security)
Temperature Coefficient
all circuits to earth 4 kV 50 Hz
range –10 °C to 45 °C
measurement circuits against
at cos = 1 (5 % In to Imax) < 75 ppm/K
all other circuits 4 kV 50 Hz
at cos = 0.5 (10 % In to Imax) < 150 ppm/K outputs against all other circuits 2 kV 50 Hz
tariff inputs against all other circuits 2 kV 50 Hz
Relative Humidity according to IEC 62052-11
annual average < 75 % Impulse Voltage (Surge)
for 30 days in year 95 % surge 1.2 / 50s – 8 / 20s differential mode
on other days 85 % - current and voltage circuits 4 kV @ 2 
with the exception of condensation and formation of ice - auxiliary circuits > 40 V 1 kV @ 42 
surge 1.2 / 50s – 8 / 20s common mode
Vibration according to IEC 68-2-6
- current and voltage circuits 4 kV @ 12 9F
frequency 10 to 500 Hz
frequency < 60 Hz hconst = 0.375 mm For f6: Protection Class ll acc. to IEC 62052-11
frequency > 60 Hz aconst = 5 g
velocity 1 octave/min
Calendar Clock
duration 10 cycles
Accuracy at 23 °C < 5 ppm
Half-wave sinusoidal shock acc. to IEC 68-2-27 Backup Time (Power Reserve)
Three shocks in six directions with supercap > 20 days
amax 80 g loading time for max. backup time 300 h
ti 11 ms with battery (optional) 10 years
battery type CR-P2

D000011316 f – ZMQ202, ZFQ202, ZCQ202 – Technical data© Landis+Gyr AG


4/10

Display Communication Interfaces


Characteristics Optical Interface for Automatic Meter Reading
type LCD liquid crystal display Standard IEC62056-21
digit size in value field 8 mm status binary 1 IR LED off
number of positions in value field up to 8 status binary 0 IR LED on
digit size in index field 6 mm max. bit rate 9600 bps
number of positions in index field up to 8 transmission mode serial, half duplex,
asynchronous start/stop
protocol dlms (IEC 62056-42/46/53/61/62)
Inputs and Outputs
Optical Test Output Active and Reactive Energy RS485 Interface to Other Meters (Daisy Chain)
pulse width 40 ms standard ISO 8482
maximum pulse frequency 12 Hz max. current consumption
(with 1 transmitter and 8 receivers) 15 mA
Control Inputs max. current per unit 0.8 mA to 1 mA
100 to 125 V AC/DC status binary 1 differential voltage < -0.2 V
200 to 230 V AC/DC status binary 0 differential voltage > -0.2 V
voltage ranges
24 V DC Max. bus length bit rate no. of meters
48 to 60 V DC
1200 m 19.2 kbps 16 meters
The control voltage range is set by jumpers in the 550 m 38.4 kbps 32 meters
hardware. 250 m 57.6 kbps 32 meters
input current  3 mA
insulation 4 kV AC
Transmitting Contacts transmission mode serial, bidirectional,
asynchronous start/stop
type solid state relay
protocol dlms (IEC 62056-42/46/53/61/62)
max. switching voltage 125 V AC/230 V DC
connections 2-wire, not exchangeable
min. switching voltage 24 V DC
(twisted pair shielded cable)
max. continuous switching current 55 mA AC/DC
No termination resistor is needed for the described
min. switching current 0.1 mA line data. If required by the system, an external load
9
electrical lifetime > 15 x 10 pole changes of 1.2 k can be used.
contact resistance  50 
insulation between the contacts
and other current circuits 3.75 kV AC/1 min
insulation between contact groups 2 kV AC/1 min
pulse length r4 20, 40, 80 ms

Alarm Contacts
type monostable with switchover contact
max. switching voltage 250 V AC/DC
normal switching voltage 24 V DC
min. switching voltage 5 V DC at min. 10 mA
max. switching current 100 mA AC/DC at 250 V
min. switching current 5 mA DC
5
electrical lifetime 10 switching operations
with ohmic load
insulation 4 kV AC/1 min

© Landis+Gyr AG D000011316 f – ZMQ202, ZFQ202, ZCQ202 – Technical data


5/10

Connections Housing Material


Current and Voltage Connections f6 f6
type screw type terminals The meter housing is made of polycarbonate which
diameter 5.2 mm is partly glass-fibre reinforced.
2
recommended conductor cross-section 4 to 6 mm
screw type Pozidriv Kombi No. 1
screw dimensions M4 X 8 f9
max. head diameter 5.8 mm The meter housing is made of lacquered sheet steel.
The transparent meter cover is made of
tightening torque ≤ 1.7 Nm polycarbonate.

Input and Output Connections f6


auxiliary power supply, tariff inputs, alarm output,
synchronisation input and transmitting contacts
type spring type terminal

RS485-Interface Connections f6
type RJ-12

Pin allocation RS485:


RS485 RS485 1 GND
2 UP (Data a)
3 UN (Data b)
4 UN (Data b)
5 UP (Data a)
6 GND

The two RJ12 jacks of the RS485-interface are looped


internally to permit a connection of several meters.

Connections f9
direct plug-in Essaillec connectors with automatic
short circuit for current transformers

Standard data

Un 3x…/3 In Load Pmax R r4 Pulse value Energy register


[imp/ kWh/kvarh] [Wh, varh / imp] kWh, kvarh, kVA
100 V 1A 120 % 208 W 100 000 0.02 0,0000
100 V 1 (2) A 200 % 346 W 50 000 0.02
100 V 5A 120 % 1039 W 20 000 0.1
100 V 5 (7,5) A 150 % 1299 W 50 000 0.1
100 V 5 (10) A 200 % 1732 W 50 000 0.1 0,000
200 V 1A 120 % 416 W 25 000 0.05
200 V 1 (2) A 200 % 693 W 10 000 0.05
200 V 5A 120 % 2078 W 25 000 0.2

Memory capacity
per profile for profile 1 and profile 2

for tm = 15 min 4 register e.g. ±A, ±R 681 days


10 register e.g. ±A, ±R, 3x U, 3x I 336 days
36 register 100 days

D000011316 f – ZMQ202, ZFQ202, ZCQ202 – Technical data© Landis+Gyr AG


6/10

Weight and Dimensions f6


Weight 1.6 kg

Terminal Cover
short no free space
standard 40 mm free space
long 60 mm free space
special 110 mm free space

Meter Dimensions (Standard Terminal Cover)

173 75

6.2

14
206

239

281.6
6

30
26

140
40

40
7.4 20.4

16 19.1
150

© Landis+Gyr AG D000011316 f – ZMQ202, ZFQ202, ZCQ202 – Technical data


7/10

Weight and Dimensions f9


Weight 4.4 kg

Rack Mounting
202.6

13
2.4

4.6 4.6
5 5

190.5

200

9.5

28 25
0 25 9.5
0

34
6

earth screw for cable connection; earth pin for chassis f9.11 and f9.12

Chassis f9.10 (meter with cable connections)


ca. 384,5
254,5

445
2,5
27

D000011316 f – ZMQ202, ZFQ202, ZCQ202 – Technical data© Landis+Gyr AG


8/10

Chassis 30 f9.11 (direct plug-in meter) Chassis f9.12 (two direct plug-in meters)

30
291

291
445 445

2,5
2,5

27
27

Front
482 (19")
8,5 465 8,5
37,7

g
n
i
t
n
132,5
57,1

u
o
m
h
37,7

s
u
l
f
r

Flush Mounting for f9


o
f

465
t

201 7 4
51 7
e
k
c
113

133
57.1
M6

a
r
B
37.95

Cut-out for panel-flush mounting Cut-outfor1


9 "Chassis

© Landis+Gyr AG D000011316 f – ZMQ202, ZFQ202, ZCQ202 – Technical data


9/10

ZMQ 2 02 C.8 r4 f6

Network type

ZMQ 3-phase 4-wire network (M-circuit)


ZFQ 3-phase 3-wire network (F-circuit)
ZCQ 1-phase 2-wire network (C-circuit)

Accuracy class

02 Class 0.2 S for active energy according to IEC


05 Class 0.5 S for active energy according to IEC

Software configuration

C.4 basic measurement functions


C.6 additionally losses, harmonic distortion and CT/VT correction
C.8 additionally apparent energy and single phase measurement, max. demand, power
factor, monthly billing values

Transmitting contacts

r4 4 changeover contacts for +A, –A, +R, –R with fixed pulse width (4 x u)
r4a 8 normally open contacts with fixed pulse width (8 x u)
r4aa 4 normally open contacts for +A, –A, +R, –R in 2 groups with fixed pulse width (2 x 4 x u)
r3 4 changeover contacts for +A, –A, +R, –R with symmetric mark/space ratio (4 x u) and
storage of contact position in case of power outage

Casing

f6 Wall mounted housing (Plastic housing for wall mounting)


f9 Rack mounted housing (Metal housing equipped with ESSAILEC connectors)
– for flush mounting in 19" rack with counter connectors
– for flush mounting in 19" rack with cable connectors
– for switchboard mounting with cable connectors

Customer specific versions


– C.2: for serial connection to FAG/FBC (only with H90 and former hardware)
– C.7: specific functionality for India with Availability Based Tariff
– 16.7 Hz version
– Current ranges 1 (4) A; 1.5 (6) A; 2 A, 120% I n
– 3 x 400/230 V for direct connection to low voltage network

D000011316 f – ZMQ202, ZFQ202, ZCQ202 – Technical data© Landis+Gyr AG


10/10

Revision History

Version Date Comments


e 22.02.2010 Amendment of revision history

Copyright © 2010, Landis+Gyr. All rights reserved. Subject to change without notice.

Landis+Gyr AG
Feldstrasse 1
CH-6301 Zug
Switzerland
Phone: +41 41 935 6000
www.landisgyr.com

© Landis+Gyr AG D000011316 f – ZMQ202, ZFQ202, ZCQ202 – Technical data

You might also like