Temperature Controller 2
Temperature Controller 2
RoHS
INDEX:
1. CATALOG DESCRIPTION-----------------------------------------------------------04
2. FEATURES--------------------------------------------------------------------------------05
3. FRONT FASCIA-------------------------------------------------------------------------06
4. PRODUCT DESCRIPTION------------------------------------------------------------07
5. DIMENSIONS----------------------------------------------------------------------------07
6. TECHNICAL SPECIFICATIONS-----------------------------------------------------09
8. MEASUREMENT------------------------------------------------------------------------16
9. DISPLAY----------------------------------------------------------------------------------18
15BL003-02
1
CAUTION: 3.0 FRONT FASCIA:
1. Always follow instructions stated in this product booklet.
2. Before installation, check to ensure that specications agree with
intended application.
3. Installation must be done by skilled technician. GIC PR-
4. Automation and controlled devices must be properly “installed” so
that they are protected against any risk of involuntary actuations.
5. Suitable dampers should be provided in event of excessive vibrations.
NOTE: 8888
21 PV
TM
1
14
AT
2
13
8
The example above explains that the feature is applicable only for 11
7 12
151F43B1,151G43B1,151H43B1,151J43B1, 151F43B, 151G43B, 151H43B,
151J43B.
#Symbols appear where description vary based on models. If the #
does not appear, then it indicates that the feature is applicable to all
the models. 3 4 5 6
Note: This type of control is applicable for double acting cat ids only.
Menu Sub menu Options “Pb" - Proportional Band
rEg "Int" - Integral Time
cont nr
"dEr" - derivative time
OP oPcF h1c2 "hct" - Heat cycle time
"cct” - cool cycle time
Condition Heater Cooler "rS" - Manual Reset (if "Int=0 only)
PV < [SP-hEST] ON OFF "coEF" - Coefcient Relation between power heating and cooling
element. Range between 0.1 to 10.
PV = SP OFF OFF
“coEF” > 1: represents that the cooling element is stronger than
PV >[SP+hEST] OFF ON heating element.
PV = SP OFF OFF “coEF” = 1: represents that the heating and cooling element are
equally strong.
“coEF” < 1: represents that the heating element is stronger than
cooling element.
Op2=trAt
34 OFF
(Set time)
Note:
1) When ever the Set Timer time is competed then “OVER” message
will display on lower display.
17.0 ALARMS: 5. Deviation high(“dEhi” on display): Alarm is activated when PV goes
above Effective Set Point(ESP)+A1th) and is deactivated When it goes
1. Absolute low (“AbLO” on display): Alarm is activated if PV goes below (Effective Set Point(ESP)+A1th-A1hy).
below A1th and is deactivated if PV goes above (A1th+A1hY).
Menu Sub menu Options Menu Sub menu Options
AL1/AL2 A1tY AbLo AL1/AL2 A1tY dEhi
PV ESP+A1th
PV A1th+A1hY
A1hY ESP+A1th-A1hy
Time
ON OFF ON OFF ON OFF ON OFF ON OFF Time
2. Absolute high (“AbhI” on display): Alarm is activated if PV goes 6. Deviation band (“dEbA” on display): Alarm is activated when PV
above A1th and is deactivated if PV goes below (A1th-A1hy). goes above(Effective Set Point (ESP)+A1hi) or below(Effective Set
Point(ESP) - A1Lo) and is Deactivated when PV goes below (Effective
Menu Sub menu Options Set Point(ESP)+ A1hi - A1hy) or above (Effective Set Point(ESP) - A1Lo
AL1/AL2 A1tY Abhi + A1hy).
Menu Sub menu Options
AL1/AL2 A1tY dEbA
PV
A1th
PV
A1th-A1hY ESP+A1hi
A1hY
A1hY
ESP+A1hi-A1hy
ESP
ESP-A1Lo+A1hy
A1hy
Time ESP-A1Lo
OFF ON OFF ON OFF
ON O ON O ON O ON O
Time
F F F F
F F F F
PV
COP o1LV+o1hs
A1hi
A1hY o1hs
A1hi-A1hy o1LV
A1L0+A1hy
A1hy
A1Lo
Time
ON OFF ON OFF ON
ON O ON O ON O ON O ON
F F F Time 8. Output high(“OPhi” on display): Alarm is activated if output goes
F
F F F F above o1hv and deactivated when output goes below (o1hv-o1hs).
Menu Sub menu Options
4. Deviation low ( “dELo” on display): Alarm is activated if PV goes
below (Effective Set Point(ESP) - A1th) and is deactivated when it goes AL1/AL2 A1tY oPhI
above (Effective Set Point(ESP)–A1th + A1hy).
o1hs o1hv-o1hs
ESP
PV
Time
ESP-A1th+A1hy OFF ON OFF ON OFF
A1hy
ESP-A1th
OFF ON Time
ON OFF ON
ALARM FUNCTIONALITY
ALARM FUNCTIONALITY
Note:
Alarm types and functions are explained for alarm
1. The explanation is same for alarm
2. Binary addition of alarm function allows Combination of different function.
Eg. If it is required to have no alarm at power On [8] and no alarm at sP change [16], set function as 24.
Main Menu: conF (Conguration) These functions allow the supervisory program to read and modify any
data of the controller.
Parameter Description
1 KEY Congurable key: The communication is based on messages sent by the master station
Range: (host) to the slave stations (PR-69) and vice versa. Every a message
1. stAt: Start tuning manually. Starts auto tuning manually contains four elds:
if Au To parameter is congured as 3. a) Slave address (from 1 to 99)
2. oPLP: Open loop. Switches controller to manual mode b) Function code: contains 3, 6 or 16 for specied functions.
if it is in auto mode and cont parameter is congured c) Information eld: contains data like word addresses and word
as PId or changes it to auto mode if it is in manual values as required by function in use.
mode. d) Control word: a cyclic redundancy check (CRC) performed with
3. Ack: Acknowledge. Used to acknowledge alarm if particular rules for CRC.
A1Fn is in alarm acknowledge mode. Also release the
alarm if it is in latched mode. Note: For function 16 - Preset Multiple Register ,We can only write one
4. oFF: Switch off the control action parameter at a time.
5. SPSL: Select active set point
6. chSP: Change set point when on main screen 3.1 Function 3 - Read n Word
7. rSEt #5,6,7,8,9,10,11,12 : To Reset and restart the ramp prole The request has the following frame:
8. noFc: No function, default: chSP Filed Name Byte Position
Slave MODBUS ID Byte 0
2 dISP Display congure:
Function Code(3) Byte 1
Range:
1. SP: Displays active set point on the lower display. First word Address MSB Byte 2
2. co: Displays controller output on the lower display First word Address LSB Byte 3
3. EFSP#5,6,7,8,9,10,11,12: Displays the set point which is set by Number of words MSB Byte 4
EFSP Number of wordsLSB Byte 5
4. A1th: Alarm1 threshold
5. A2th: Alarm2 threshold CRC MSB Byte 6
6.Unit : C/F CRC LSB Byte 7
7.timr: Displays Timer set time on lower display, default: sP
The normal reply(as opposed to exception reply)has the following frame:
3 LEd Led shift index
Filed Name Byte Position
Range : 0 (Off) to 9999 units, default: 2
Slave MODBUS ID Byte 0
MAIN MENU: PWD (Password Enable /Disable) Function Code(3) Byte 1
NB Number of Read bytes Byte 2
Parameter Description Value of first word MSB Byte 3
PWD Enable or Disable the Password
Value of first word LSB Byte 4
En : Enable the Password
dIS: Disable the Password Following Words Byte 5
CRC Error Check MSB Byte NB+2
CRC Error Check LSB Byte NB+3
3.2 Function 6 - One word write. The request has the following frame: 22. MODBUS QUERIES:
Filed Name Byte Position
1. Variable - Pv
Slave MODBUS ID Byte 0 Description: Process Variable
Function Code(6) Byte 1 Data type: Signed short
Word Address MSB Byte 2 Range: -1999 to 9999
Word Address LSB Byte 3 Decimal dependence: dP
READ/WRITE: Read
Value of first word MSB Byte 4 Address (in HEX) : 1001
Value of first word LSB Byte 5
2. Variable - coP
CRC Error Check MSB Byte 6 Description: Control Output
CRC Error Check LSB Byte 7 Data type: Signed short
Range: -100 to 100
3.3 The exception reply Decimal dependence: 0
An exception reply is given when the request is formally correct, but READ/WRITE: Read
cannot be satised standing particular situations; the reply contains a Address (in HEX): 1002
code indicating the cause of the missing regular reply. The frame is: 3. Variable - AL1
Description: Alarm 1 Status
Filed Name Byte Position
Data type: Unsigned short
Slave MODBUS ID Byte 0 Range: OFF-xxxx xxx0, ON- xxxx xxx1
Function Code(3) Byte 1 Decimal dependence: NA
First Word Address MSB Byte 2 READ/WRITE: Read
Byte 3 Address (in HEX): 1003
First Word Address LSB
Number of Word MSB Byte 4 4. Variable - AL2
Description: Alarm 2 Status
Number of Word LSB Byte 5
Data type: Unsigned short
CRC Error Check LSB Byte 6 Range: OFF-xxxx xx0x, ON- xxxx xx1x
CRC Error Check MSB Byte 7 Decimal dependence: NA
READ/WRITE: Read
3.4 Function 16 - Preset Multiple Register, one word write. Address (in HEX): 1003
The request has the following frame: 5. Variable - sEnb
Description: Sensor break alarm status
Filed Name Byte Position
Data type: Unsigned short
Slave MODBUS ID Byte 0 Range: OFF-xxxx x0xx, ON- xxxx x1xx
Function Code(0X10) Byte 1 Decimal dependence: NA
Start register no,(high byte) Byte 2 READ/WRITE: Read
Address (in HEX): 1003
Start register no,(Low byte) Byte 3
No. of register to write(High byte) Byte 4 6. Variable - LbA
Description: Loop break alarm status
No. of register to write(Low byte) Byte 5 Data type: Unsigned short
No. of data bytes Byte 6 Range: OFF-xxxx 0xxx, ON- xxxx 1xxx
Data 0 MSB Byte 7 Decimal dependence: NA
Data 0 LSB Byte 8 READ/WRITE: Read
Data 1 MSB Address (in HEX): 1003
Byte 9
Data 1 LSB Byte 10 7. Variable - SP
Description: Effective set point
Data 2 MSB Byte 11
Data type: Signed short
Data 2 LSB Byte 12 Range: sPLL to sPHL
CRC bytes of 1 to 6 (LSB) Byte 13 Decimal dependence: dP
CRC bytes of 1 to 6 (MSB) Byte 14 READ/WRITE: Read
Address (in HEX): 1004
Note: Number Of data bytes that follows 3 registers X 2 Bytes each = 6
8. Variable - stAt
Description: Regulator status
The normal reply(as opposed to exception reply) has the following frame: Data type: Unsigned short
Filed Name Byte Position Range: OFF - 0, Manual - 1,
Slave MODBUS ID Byte 0 AUTO SYM ON/OFF-2, AUTO ASYM ON/OFF-3,
AUTO N ZONE ON/OFF-4,
Function Code(0X10) Byte 1
AUTO PID TUNE ON-5, AUTO PID TUNE OFF-6
Start register no,(high byte) Byte 2 READ/WRITE: Read
Start register no,(Low byte) Byte 3 Decimal dependence: NA, Address (in HEX): 1005
No. of register written(High byte) Byte 4 9. Variable - MvEr
No. of register written(Low byte) Byte 5 Description: Model Version
CRC bytes of 1 to 6 (LSB) Byte 6 Data type: Unsigned short
Range: 105:Pr05, 106:PR06, 107: Pr07, 108: PR08
CRC bytes of 1 to 6 (MSB) Byte 7
Decimal dependence: NA
1) Illegal Function code -1 READ/WRITE: Read
2) Illegal data address-2 Address (in HEX): 1006
3) Illegal data value eld-3
10. Variable - cvEr
4) Slave device busy-6
Description: Code Version
Address 0 used for broadcasting messages has not been implemented Data type: Unsigned short
in Pr69. Decimal dependence: NA
READ/WRITE: Read
Address (in HEX): 1007
11. Variable - rFLg 5. Variable - SP1
Description: Ramp Soak Flg status Description: Set point 1
Data type: Unsigned short Data type: Signed short
Range: Range: spLL to sphL
NO RAMP SOAK ON: 0 Decimal dependence: dP
RAMP1 STAGE: 1 READ/WRITE: Read/Write, Address (in HEX): 2005
SOAK1 STAGE: 2 6. Variable - SP2
RAMP2 STAGE: 3 Description: Set point 2
SOAK2 STAGE: 4 Data type: Signed short
RAMP3 STAGE: 5 Range: spLL to sphL
SOAK3 STAGE: 6 Decimal dependence: dP
RAMP SOAK END: 7 READ/WRITE: Read/Write, Address (in HEX): 2006
Decimal dependence: NA 7. Variable - SP3
READ/WRITE: Read, Address (in HEX): 1008 Description: Set point 3
12. Variable - Aout#6,8 Data type: Signed short
Description: Value Transmitted on Analog output Range: spLL to sphL
Data type: Unsigned short Decimal dependence: dP
Range: 3 to 21 or 0-10 READ/WRITE: Read/Write, Address (in HEX): 2007
Decimal dependence: NA 8. Variable - SP4
READ/WRITE: Read , Address (in HEX): 1009 Description: Set point 4
13. Variable - Output 1 status (ON/OFF)#5,6,7,8 Data type: Signed short
Description :This is for indication of OP1 Range: spLL to spHL,
Data type: Unsigned short Decimal dependence: dP,
Range: 0 : OFF , 1 : ON READ/WRITE: Read/Write, Address (in HEX): 2008
Decimal dependence: NA InP
READ/WRITE: Read , Address (in HEX): 1009
1. Variable - SEns
14. Variable - Output 2 status (ON/OFF)#5,6,7,8 Description: Sensor select
Description: This is for indication of OP2 Data type: Unsigned short
Data type: Unsigned short Range:
Range: 0 : OFF - 1 : ON 0 = J thermocouple, 1 = K thermocouple, 2 = E thermocouple
Decimal dependence: NA 3 = S thermocouple, 4 = B thermocouple, 5 = Pt100 RTD
READ/WRITE: Read , Address (in HEX): 100A 6 = 0-50 mV signal, 7 = 0-60 mV signal, 8 = 12-60 mV,
15. Variable - Output 3 status (ON/OFF)#5,6,7,8 9 = R thermocouple,10 = 4-20mA, 11 = 0-10V, 12 = 0-5V, 13 = 1-5V
Description: This is for indication of OP3 Decimal dependence: NA
Data type: Unsigned short READ/WRITE: Read/Write, Address (in HEX): 2009
Range:0 : OFF - 1 : ON
2. Variable - IScL
Decimal dependence: NA
Description: Analog input low
READ/WRITE: Read , Address (in HEX): 100B
Data type: Signed short
16. Variable - Status OF PV w.r.t SP#5,6,7,8 Range: -1999 to Isch
Description: This is for relation between PV & SP Decimal dependence: dP
Data type: Unsigned short READ/WRITE: Read/Write, Address (in HEX): 200A
Range: 0 - 3 3. Variable - ISch
In case of sensor break : 0 Description: Analog input high
“-” (PV<SP): 1 Data type: Signed short
“=” (PV=SP):2 Range: IscL to 9999
“+” (PV>SP):3 Decimal dependence: dP
Decimal dependence: NA READ/WRITE: Read/Write
READ/WRITE: Read , Address (in HEX): 100C Address (in HEX): 200B
SP 4. Variable - rAtE
1. Variable - SPLL Description: Measurment Rate
Description: Set point low Data type: Signed short
Data type: Signed short Range: 0.001 to 2.000
Range: -1999 to setpoint as selected by EFSP Decimal dependence: 3
Decimal dependence: dP READ/WRITE: Read/Write
READ/WRITE: Read/Write Address (in HEX): 200C
Address (in HEX): 2001 5. Variable - oFSt
2. Variable - SPhL Description: Measurement Offset
Description: Set point high Data type: Signed short
Data type: Signed short Range: -1999 to 9999
Range: Setpoint as selected by EFsP to 9999 Decimal dependence: dP
Decimal dependence: dP READ/WRITE: Read/Write
READ/WRITE: Read/Write, Address (in HEX): 2002 Address (in HEX) : 200D
3. Variable - nSP 6. Variable - oPP
Description: Number of set point Description: Output power in case of error
Data type: Unsigned short Data type: Signed short
Range: 1 to 4 Range: -100.0 to 100.0
Decimal dependence: NA Decimal dependence: 1
READ/WRITE: Read/Write, Address (in HEX): 2003 READ/WRITE: Read/Write, Address (in HEX): 200E
RTD2
RTD3
RTD1
DC Analog I/P
Range: 0 to 99.99
Decimal dependence: 2 Pt-100
READ/WRITE: Read/Write, Address (in HEX): 2040
OP3
OP1 OP2 N L
17. Variable - soK1 + SSR -
Description: Soak 1
Data type: Unsigned short
Range: 0 to 99.59(hour:min)
11 12 13 14 15 16 17 18 19 20
Decimal dependence: 2
READ/WRITE: Read/Write, Address (in HEX): 2041
18. Variable - soK2 151G42B / 151G43B
Description: Soak 2
Data type: Unsigned short 1 2 3 4 5 6 7 8 9 10
Range: 0 to 99.59(hour:min) - +
+ TC/mV - + -
Decimal dependence: 2 RTD2 V mA
RTD1
V mA
RTD3
RTD1
DC Analog I/P
Range: -100 to 100
Decimal dependence: 1 Pt-100
READ/WRITE: Read/Write, Address (in HEX): 2045 OP1
}
OP2 OP3
22. Variable - SST 0-10V 4-20mA N L
+ -
Description: Soft start time
Data type: Unsigned short
Range: 0 to 7:59 (hh:mm) 11 12 13 14 15 16 17 18 19 20
Decimal dependence: 2
READ/WRITE: Read/Write, Address (in HEX): 2046
23. Variable - SSTH 151J42B /151J43B
Description: Soft start threshold
Data type: Signed short
Range: -1999 to 9999
1 2 3 4 5 6 7 8 9 10
Decimal dependence: dp + TC/mV - + V - mA
- +
READ/WRITE: Read/Write, Address (in HEX): 2047
RTD3
RTD2
RTD1
DC Analog I/P
Conf
Pt-100
1. Variable - Key
Description: Congure Key OP1 OP2 OP3 N L
Data type: Unsigned short
Range: 0: StAt, 1: oPLP, 2: Ack, 3: oFF,
4: SPSL, 5: ChSP, 6: rSEt, 7: noFc 11 12 13 14 15 16 17 18 19 20
Decimal dependence: NA
READ/WRITE: Read/Write, Address (in HEX): 2048
151F43B1 151K42B
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
+ -
+ TC/mV - - + D+ D- - +
+ V - mA TC/mV + -
RS485 V mA
RTD3
RTD2
RTD3
RTD2
RTD1
RTD1
DC Analog I/P
DC Analog I/P
Pt-100 Pt-100
OP3 OP1
OP1 OP2 N L OP2
+ SSR - SSR N L
+ -
11 12 13 14 15 16 17 18 19 20
11 12 13 14 15 16 17 18 19 20
151G43B1 151L42B
1
1 2 3 4 5 6 7 8 9 10
2 3 4 5 6 7 8 9 10 + -
+ - D+ D- TC
TC/mV + V-
-
mA
+
RTD3
RTD2
RTD1
RTD3
RTD2
RS485
RTD1
DC Analog I/P
Pt-100 Pt-100
OP1
OP1 OP2 OP3
}
OP3 N L
0-10V
OP2 SSR + SSR -
4-20mA N L
+ - + -
11 12 13 14 15 16 17 18 19 20
11 12 13 14 15 16 17 18 19 20
24. FAQs:
151H43B1
1. How to change effective set point selection using key ‘C’?
1 2 3 4 5 6 7 8 9 10 A.“SLSP” (select effective set point) must be programmed on “kEy”
parameter in the “conf” menu. If ‘C’ key is pressed and held for 2 sec
+ -
TC/mV +
- + D+ D- while on main screen “EFsP” is displayed on the upper display and
V - mA
RS485 currently effective set point (1 if sP1 is effective and 2 if sP2 is effective)
RTD1
RTD3
RTD2
DC Analog I/P
is displayed on the lower display. The upper display starts blinking.
Pt-100 Using ‘UP’ /‘DN’ key the value can be changed. Press ‘E’ to activate
OP1 the set point.Upper display stps blinking. Press ‘C’ key to exit from menu
}
0-10V 4-20mA
OP2 OP3 to main screen.
+ - N L
Menu Sub menu Options
conf kEy 'C'
11 12 13 14 15 16 17 18 19 20
2.What is ‘rAtE’ and ‘oFst’ parameter in the ‘InP’ menu?’
A. If it is required to apply slope and/or offset to the temperature
measured by the instrument, it can be done by using the above
151J43B1 parameters. Any value set on above a parameter allows the device to
see temperature as below:
Display temp. = rAtE* Measured Temp + oFst
1 2 3 4 5 6 7 8 9 10 This helps to re-calibrate the instrument.
+ - - +
TC/mV + - D+ D- 3. What is “Sens” Break alarm and break loop alarm?
V mA
RS485
RTD3
RTD2
RTD1
DC Analog I/P
A. To select sensor break alarm set “sEnb” on the desired output.
Pt-100 Whenever sensor break error occurs, the corresponding relay is set.
To select break loop alarm, break loop alarm time i.e. “Brkt ” is to be
OP1 OP2 OP3
N L set. If the controller output remains at 100% for the above time, then
loop break alarm is given. If any relay output is set for the alarm, the
given relay is switched on. Break loop alarm works only in PID mode.
11 12 13 14 15 16 17 18 19 20 Break loop alarm can be turned off by moving the controller to OFF
mode and then back to auto mode by pressing properly programmed
'C' key.
A. Soft start time is the time for which the soft power is provided after A. The query structure of read query is explained earlier. Assume that
On. Soft start threshold is the absolute temperature upto which soft Salve address is 01.
power is provided. While in soft start, if any of the above value is
reached, the soft start ends. Filed Name Byte Position
Even if the value on parameter “EFSP” in the “SP” menu is changed 10.Can we Autotune the device below ambient temperature in double
and the values parameter “SP1” and “SP2” in the menu are different, acting mode?
the auto tuning is started. Following condition must be satised to start A. Yes, but if SP > PV; then Auto tuning should be done only above
auto tune: ambient temperature. And if SP < PV, Autotuning should be done only
Controller should be in PID mode. below ambient temperature.
If Soft start is congured and auto tune is on 1 or 2 or 4:
“sP” be set the on PV <(SP-|SP/5|) for HEAT action. Ex 1.
or PV >(SP+|SP/5|) for COOL action. If Auto tuning is desired for a Set Point of 60°C (i.e. SP = 60) & device is
In all other conditions: congured in Dual Acting mode or Single Acting mode (Func = HEAT),
PV <(SP-|SP/3|) for HEAT action or then auto tuning will start only if PV< [ 60 - | 60/3 | ] = 40°C, if soft start
PV >(SP+|SP/3|) for COOL action. is not congured.
6. What value will be returned by the device if a read query for the PV Ex 2.
is sent and the device has Sensor/Over/Under range error? If Auto tuning is desired for a Set Point of 75°C (i.e. SP = 75) & device is
congured in Dual Acting mode or Single Acting mode(Func = HEAT),
A. Following values will be sent as reply for the modbus query to read then auto tuning will start only if PV< [ 75 - | 75/5 | ] = 60°C, if soft start
temperature if device is in error mode. is congured.
11.How to see CJC tempareture in device?
Error displyed Value returned
A. Press "UP" and "DOWN" key simultaneously. CJC value will appear
SEnb (sensor open) 0xC000 on lower display. To remove CJC value Press "EXIT" key. Device will
show value for which lower display is congured.
ovrg (over range error) 0xC001
12. How to reset device ?
unrg (under range error) 0xC002
A. On main screen when you press the enter key, you will get the
7.How to restart ramp and soak prole? option for reset the device ”rset”. When you press the reset you will
get option as “yes” or “ No” to reset device. If press “Yes” you will
A. To restart the ramp soak prole program “C” key as “rsEt”, then while get option to conrm the reset device. If again press “Yes” then
on the main screen press and hold the key for about 2 s. When reset, device will be reset and back to main screen .
the lower display alternates between a message “rsEt” and value If press “No” after conrming to reset then you get back to main
congured on it by the user. This message disappears after a time of screen.
about 1 min.
Menu Sub menu Options 13.What happen if Sens, ourg , unrg or control action off condition
occurs when timer is ON?
conf kEy rSEt
A. If the timer is started and any of the condition occurs then the timer
8. How to change Set point while on main Screen? time will get pause and resume again from the pause time when the
condition vanish.
A. It is possible to change the set point while on main screen. For this
set “kEy” parameter in “conF” menu as “chsP”. Then any time when Note: For Cat_ID :151K42B only output 2 can be assign as Timer
on main screen if the “C” key is pressed for more than 2 sec currently alarm (trAL).
effective set point appears on the screen. The upper display start
blinking. By using “UP” key or “DOWN” key the value can be changed.
Press “E” key to save the value. To discard the value press “C” key.
To exit to main screen, press “C” key.
Menu Sub menu Options
conf kEy chsp
25. Error Occurred in Device:
PASSWORD = 69