Voltage Grade

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 1

AC cables are designed to be suitable for specific design voltages, which is called the "Voltage

Grade" (or "Voltage Designation", "Voltage Class" or "Voltage Rating") of the cable. The
voltage grade is commonly expressed in the following form:

Where is the power frequency voltage between phase and earth (V rms)

is the power frequency voltage between two phase conductors (V rms)


For example, some standard IEC voltage grades are 0.6/1kV, 1.9/3.3kV, 3.8/6.6kV,
6.35/11kV, 12.7/22kV, 19/33kV, etc.

The manufacturer designs the cable (i.e. insulation, bedding, sheaths, etc) for the specified
voltage grade. A cable can therefore be operated at voltages that do not exceed the voltage grade,
e.g. a 0.6/1kV cable can be operated for any phase-to-earth and phase-to-phase voltages not
exceeding 0.6kV and 1kV respectively. You may notice that LV cables are mainly specified to
0.6/1kV cables even though they are operated are much lower voltages (e.g. 240/415V,
220/380V, etc). This is due to the fact that the mechanical requirements of the insulation
thickness are greater than the electrical requirements.

Neutral Earthing Considerations For MV and HV cables (>1kV), some


consideration must be given to the neutral earthing arrangements of the system when specifying
a voltage grade. In the US, the Association of Edison Illuminating Companies (AEIC) has the
following specifications depending on the neutral earthing arrangements and clearing time of the
protective device:

 100% insulation level


 133% insulation level
 173% insulation level

The insulation levels above refer to the nominal phase-to-phase voltages. For example, a cable
with a 133% insulation level on a 33kV system is rated for 133% the nominal phase-to-phase
system voltage, i.e. 133% x 33kV = 43.89kV.

100% Insulation Level The 100% is the insulation level normally used for cables on solidly
earthed systems, or on any system where the protective device will clear earth faults within 1
minute.

133% Insulation Level The 133% insulation level is specified for systems where the
protective device is expected to clear earth faults within 1 hour, and is typically specified for
high impedance earthed or unearthed systems.

173% Insulation Level

The 173% insulation level is specified for systems where the time to clear an earth fault is
indefinite. This is typically recommended for unearthed or resonant earthed systems.

You might also like