0% found this document useful (0 votes)
200 views93 pages

Power System Protection For ESE Propose

This document provides an overview of overcurrent protection for phase and earth faults in power systems. It discusses differential relay and overcurrent relay as the main and backup protection for power transformers. It covers discrimination methods using time, current, and time and current coordination. It also addresses fault calculation, CT polarity and star points, setting guidelines for distribution lines and power transformers, a case study, and practical testing of protection relays. The key topics are overcurrent protection concepts and their application in substation equipment protection.

Uploaded by

Ye Gyiii
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
200 views93 pages

Power System Protection For ESE Propose

This document provides an overview of overcurrent protection for phase and earth faults in power systems. It discusses differential relay and overcurrent relay as the main and backup protection for power transformers. It covers discrimination methods using time, current, and time and current coordination. It also addresses fault calculation, CT polarity and star points, setting guidelines for distribution lines and power transformers, a case study, and practical testing of protection relays. The key topics are overcurrent protection concepts and their application in substation equipment protection.

Uploaded by

Ye Gyiii
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 93

POWER 

SYSTEM PROTECTION TRAINNING

AUNG KO HTAY
TEST LAB((MEPE)
POWER TRANSFORMER PROTECTION

 DIFFERENTIAL RELAY ( MAIN PROTECTION )
 OVER CURRENT RELAY ( BACK UP PROTECTION )
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

1. Discrimination
2. Fault Calculation
3. CT’s Polarity & Star points
4. Setting Guide Line
5. Case Study
6. Practical Testing on Micom P122 relay with Omicron CMC‐356
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
1. Discrimination

Correct discrimination, each relay must isolate only the faulty section of the power system 
network, leaving the rest of the system undisturbed.

TIME
CURRENT
BOTH TIME & CURRENT
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
1. Discrimination by TIME

Disadvantage 

The longest fault clearance time occurs for faults in the section closest 
to the power source, where the fault level is high.
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

1. Discrimination by CURRENT

Disadvantage 

It is not practical to distinguish between a fault at FAULT‐1 and FAULT‐2, since the 
distance between these point may be only a few meters (i.e Z is not significantly change).
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

1. Discrimination by both TIME & CURRENT
STANDARD I.D.M.T OVERCURRENT RELAY CHARACTERISTIC
I.D.M.T – Inverse Definite Minimum Time
The time of operation is inversely proportional to the fault current level.
Faster operating times can be achieved by the relays nearest to fault.
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

1. Discrimination by Both TIME & CURRENT
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

1. Discrimination by Both TIME & CURRENT
GRADING MARGIN
General rule of thumb‐ 0.4 sec between the up‐stream and down‐stream relays
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
1. Discrimination by Both TIME & CURRENT

GRADING MARGIN
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
1. Discrimination by Both TIME & CURRENT

GRADING MARGIN
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

1. Discrimination by both TIME & CURRENT

COMBINED  I.D.M.T AND  HIGH SET INSTANTANEOUS OVERCURRENT RELAY CHARACTERISTIC


OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
1. Discrimination by both TIME & CURRENT

Nominal Current, In (pu, per unit )
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
1. Discrimination by both TIME & CURRENT

Secondary Current magnitude (A )
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
1. Discrimination by both TIME & CURRENT

Primary Percentage value, %
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
2. Fault Calculation
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
2. Fault Calculation

Fault Current & Load Flow in Distribution Line 

Distribution Line is Radial System

Load Current flows from Power System Network to load 
by only one direction.

Even if fault occurs, Fault Current also flows from 
Power System Network to fault point by only one direction.

Non‐Directional Over current Relay can be used.
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
2. Fault Calculation

Useful formulae
Following are the methods adopted to calculate fault currents in a power 
system.
• Ohmic method: All the impedances are expressed in Ω.
• Percentage impedance methods: The impedances are expressed in percentage  
with respect to a base MVA.
• Per unit method: Is similar to the percentage impedance method except that 
the percentages  are converted to equivalent decimals and again expressed to a
common base MVA. For example, 10% impedance on 1 MVA is expressed as 0.1 
pu on the same base.
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
2. Fault Calculation
MAXIMUM 3‐PHASE FAULT CALCULATION
(ONLY TRANSFORMER IMPEDANCE, Zt / WITHOUT SYSTEM IMPEDANCE, Zs) 
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
2. Fault Calculation
MAXIMUM 3‐PHASE FAULT 
( WITH SYSTEM IMPEDANCE, Zs)
System Fault level datas by using from software application :
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
2. Fault Calculation
MAXIMUM 3‐PHASE FAULT 
( WITH SYSTEM IMPEDANCE, Zs) 
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
2. Fault Calculation
Three Phase Fault & Single Line to Ground Fault 
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
3. CT’s Polarity & Star points
P2 P1

A
N
SHORT CUT
Choose Bus Side P1

So, now it become easy, choose S2 star points
for OC/EF relays and Meters of all the CTs,
except for the X’mer secondary main CT.

X’mer secondary main CT, choose S1 star point for 
OC/EF relay and Meter according to load flow.
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
3. CT’s Polarity & Star points
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

4. Setting Guide Line

 Distribution Line Protection
 Power Transformer Protection
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
4. Setting Guide Line

Distribution Line Protection

Over current Relay (50/51)

1‐Time over current relay (51)

Purpose ‐ Over load protection
Phase fault protection

I max (load)  <  OC tap  < Min fault current
I >, OCR tap = 120% or 150% of maximum load current.
Tms =    Coordinating time margin between upstream OCR and down  Stream OCR,
0.4 sec recommended.  
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
4. Setting Guide Line
Distribution Line Protection

2‐ Instantaneous over current relay 

‐ Only phase fault protection 
‐ Action instantaneously on an excessive rate of current rise ,thus indicating a fault.          

I>>, OCR tap =  4  or 5  times of maximum load current  or
minimum fault current of opposite bus fault.
Definite Time = 0 sec
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
4. Setting Guide Line
Distribution Line Protection

Over current ground  Relay (50G/51G)

1‐Time over current ground relay (51G)
Purpose ‐ Unbalanced load protection
Phase to ground fault protection

30% of I max (load)  <  OCRG tap  < Min fault current
Ie>, OCR tap = 30% of maximum load current.
Tms =   Coordinating time margin between upstream OCR and down  Stream OCR,
0.4 sec recommended. 
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
4. Setting Guide Line
Distribution Line Protection

2‐Instantaneous over current ground  relay (50G)

‐ Only phase to ground  fault protection  
‐ Action instantaneously on an excessive rate of current rise , thus indicating a fault .

OCR tap =  4  or 5  times of maximum load current  or
minimum fault current of opposite bus fault.
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
4. Setting Guide Line
Power Transformer Protection

Over Current Relay    ( 50/51 )

Purpose :  ‐ Back up protection for short circuit fault & over load.
Setting:     ‐ I>   = 100%  ~  150% of maximum rated current.
Instant element, I>>  ‐ 250% of fault current in the other side bus.

Tms ‐ Coordinated with upper level relay, lower than 1.2sec 
‐ Omit instant element of low voltage side relay for coordination  with other 
level relay.

‐ Remark:
Attention, grading time  ( 0.4  ≈  0.5sec ) for coordination And Zone‐3 Time  
(1.67sec ) of transmission line relay. 
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
4. Setting Guide Line
Power Transformer Protection

Over current ground relay  ( 50N/51N )

Purpose : ‐ Back up protection for ground fault setting;
Setting: ‐ 30% of maximum rated current.
Tms:
‐ Coordinated with upper / Lower level relay :
* The high voltage side:
Upper than ( 2sec ) at maximum fault of the high 
voltage side:
* The Low voltage side:
Coordinated ( 0.4  ~  0.5sec ) with the related 
transmission / distribution  line relay.
Remark:
* The high voltage side relay  ( 50N/51N )
Alarm when it operates, omitted the instant element for coordination.
(auto reclosing relay, give enough time for down stream fuse.)
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
5. Case Study
NAYPYIDAW SUBSTATION NO‐1
133/11 kV , 10 MVA , %Z‐ 7.5

Some of the data required for a relay setting:

One‐line diagram
Impedances of Transformer and System
Fault level
Maximum load current  through each protective device
CT ratio
Transformer Inrush characteristics
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
5. Case Study
NAYPYIDAW SUBSTATION NO‐1
133/11 kV , 10 MVA , %Z‐ 7.5
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
5. Case Study
NAYPYIDAW SUBSTATION NO‐1
133/11 kV , 10 MVA , %Z‐ 7.5
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS
5. Case Study
NAYPYIDAW SUBSTATION NO‐1
133/11 kV , 10 MVA , %Z‐ 7.5
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

6. Practical Testing on Micom P122 relay with Omicron CMC‐356 
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

6. Practical Testing on Micom P122 relay with Omicron CMC‐356 
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

6. Practical Testing on Micom P122 relay with Omicron CMC‐356 
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

6. Practical Testing on Micom P122 relay with Omicron CMC‐356 

What should be tested  ?

Relay and its Curve Characteristics

Pick up
Trip
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

6. Practical Testing on Micom P122 relay with Omicron CMC‐356 
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

6. Practical Testing on Micom P122 relay with Omicron CMC‐356 
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

6. Practical Testing on Micom P122 relay with Omicron CMC‐356 
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

6. Practical Testing on Micom P122 relay with Omicron CMC‐356 
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

6. Practical Testing on Micom P122 relay with Omicron CMC‐356 
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

6. Practical Testing on Micom P122 relay with Omicron CMC‐356 
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

6. Practical Testing on Micom P122 relay with Omicron CMC‐356 
OVER CURRENT PROTECTION FOR PHASE AND EARTH FAULTS

6. Practical Testing on Micom P122 relay with Omicron CMC‐356 
QUESTIONS  ???
THANKS FOR YOUR ATTENTION
POWER TRANSFORMER PROTECTION

DIFFERENTIAL RELAY ( MAIN PROTECTION )

1. DIFFERENIAL PROTECTION CONCEPTS
2. PRACTICAL TESTING ON MICOM P 633
1.DIFFERENIAL PROTECTION CONCEPTS

Fundamental of Differential Protection

Kirchhoff’s Current Law is the main concept of this protection, the summation of currents flowing in
and out at one node will be zero.

2A IZ
5 A
IX
3A IY

IX = IY  IZ or IX  IY  IZ = 0
1.DIFFERENIAL PROTECTION CONCEPTS

Fundamental of Differential Protection

1000A 1000A 1000A 1000A

1200/5 1500/5 1200/5 1500/5

10 MVA
33/11 kV
DYn11
100 Amp 300 Amp
1000A 1000A Ip Is
200/5 500/5
1200/5 1500/5

87T
1.DIFFERENIAL PROTECTION CONCEPTS

Fundamental of Differential Protection

STAR POINT
 The differential protection need to know the direction of the currents flowing in or out 
from the protected object, thus a star point of its connection is important.

I1 5 0 = I2 5 180 I1 5 180 = I2 5 0


1.DIFFERENIAL PROTECTION CONCEPTS

Fundamental of Differential Protection

STAR POINT
P2 P1

P2 P1
N
A
A
N
P1 P2

N
A
1.DIFFERENIAL PROTECTION CONCEPTS

10 MVA
33/11 kV
DYn11
100 Amp 300 Amp
Ip Is
200/5 800/5

2.5 Amp 1.875 Amp


87T

 Differential protected zone

Magnitude Correction
Phase Correction
Zero sequence Eliminating
Operating Characteristics
1.DIFFERENIAL PROTECTION CONCEPTS

Magnitude Correction

10 MVA
33/11 kV
DYn11
100 Amp 300 Amp
Ip Is
200/5 800/5

2.5 Amp 1.875 Amp


87T

Using Interposing Transformer
Using Protected Object for Reference (Numerical Relay)
Using CT for Reference (Numerical Relay)
Changing both sides

1.DIFFERENIAL PROTECTION CONCEPTS

10 MVA 33/11 kV
Magnitude Correction DYn11
100 Amp 300 Amp
Using Interposing Transformer
Ip Is

2.5 Amp 200/5 800/5 1.875 Amp

4.375 / 1 3.281 / 1

87T
0.571 Amp
0.571 Amp

IBase Primary = MVA/3kVPrimary = 10 MVA/ 3 33 kV = 175 A


IBase Secondary = MVA/3kVsecondary = 10 MVA/ 3 11 kV = 525 A

matching ratioAux#1 = IBase,Primary /CT RatioPrimary = 175 A / (200/5) = 4.375 ... (4.375/1) 


matching ratioAux#2 = IBase,Second /CT RatioSecond =  525 A / (800/5) = 3.281 ... (3.281/1)

IDiff = 0A 
1.DIFFERENIAL PROTECTION CONCEPTS

Magnitude Correction Changing secondary sides

Using Interposing Transformer 10 MVA 33/11 kV


DYn11
300 Amp
100 Amp
Changing primary sides
I Is
10 MVA 33/11 kV
100 Amp
DYn11
300 Amp
p 200/5 1.875
800/5
Amp
Ip Is
ICT
1 / 1.333
2.5 200/5 800/5
Amp
87T
2.5Amp
1 / 0.75 ICT 2.5Amp

87T ICT ratio = 2.5 / 1.875 = 1.333 ( 1 / 1.333 )
1.875 Amp Is  ( 1/ ICT ratio)  1.875  1.333  = 2.50 A 
1.875 Amp
(changing only secondary side)

ICT ratio = 1.875 / 2.5 = 0.75 ( 1 / 0.75 )
Ip  ( 1/ ICT ratio)  2.50 A  0.75 = 1.875 A (changing only primary side)
1.DIFFERENIAL PROTECTION CONCEPTS

Magnitude Correction
Using Protected Object for Reference ( Numerical Relay)

100 Amp 300 Amp


Ip Is
200/5 800/5

10 MVA
2.500 33/11 kV 1.875
Dyn11
Amp Amp

Setting  10 MVA
Parameters 33/11 kV
200/5 800/5

Ibase = Ibase =
0.5715
10/333 = 10/311 =
175 A 525 A
Matching Factor = CTratio/Ibase 0.5715 Matching Factor = CTratio/Ibase
= 0.2286 = 0.3048

2.5 A x 0.2286 = 0.5715
1.875 A x 0.3048 = 0.5715
1.DIFFERENIAL PROTECTION CONCEPTS

Phase Correction Numerical Relay

100 Amp 300 Amp


Ip Is
200/5 600/5

2.500 Amp 10 MVA Dyn11


2.5 Amp
33/11 kV

reference Rotate clockwise 30°

0.3465 0.5195

I1 2.5 180 = I2 2.5 0


1.DIFFERENIAL PROTECTION CONCEPTS

Phase Correction Numerical Relay

100 Amp 300 Amp


Ip Is
200/5 600/5

2.500 Amp 10 MVA Dyn11


2.5 Amp
33/11 kV

Rotate counter clockwise 30° reference

I1 2.5 180 = I2 2.5 0


1.DIFFERENIAL PROTECTION CONCEPTS

Phase Correction Numerical Relay
1.DIFFERENIAL PROTECTION CONCEPTS

Phase Correction Conventional Relay

Yy0‐ in phase (no phase shift)
‐30 30
1.DIFFERENIAL PROTECTION CONCEPTS

Zero sequence Eliminating Conventional Relay

Yy0‐ in phase (no phase shift)
‐30 30

Zero sequence can filter by connecting like this.
1.DIFFERENIAL PROTECTION CONCEPTS
Zero sequence Eliminating

Zero sequence filtering in Micom P 633
1.DIFFERENIAL PROTECTION CONCEPTS

Operating Characteristics

Diff/Restraint(bias) Characteristic
In‐rush Current
1.DIFFERENIAL PROTECTION CONCEPTS

Operating Characteristics
Diff/Restraint(bias) Characteristic

Minimum Pick up ( Id> )
Slope 1
Slope 2
High set of differential current
I different

I restrain
1.DIFFERENIAL PROTECTION CONCEPTS

Operating Characteristics
Diff/Restraint(bias) Characteristic
Minimum Pick up ( Id> )

Excitation Current of Transformer  0.02%
Tap position ( nominal tap ) 0.05%
Tap position ( maximum tap ) 0.13%

Idiff

Tripping Area

Id> 0.2
Non Tripping Area

I restrain
1.DIFFERENIAL PROTECTION CONCEPTS

Operating Characteristics
Diff/Restraint(bias) Characteristic

Slope 1

 CT Current Error 5% on Secondary Side (Current 87% of rated)
 CT Current Error 5% on Secondary Side (Current 150% of rated)
 CT Current Error 5% on Secondary Side (Current 1500% of rated)

Idiff Idiff
Id>> 2.5 Id>> 2.5
Tripping Area 
Tripping Area 
Slope1
Id> 0.2 Non Tripping Area 
Id> 0.2

Irestraint Irestraint
1.DIFFERENIAL PROTECTION CONCEPTS

Operating Characteristics
Diff/Restraint(bias) Characteristic

Slope 2

Id>> 2.5
o Using CT Saturation

Slope1

Id> 0.2

CT Saturation

In case the performance of CTs are not the same, then with the high through 
fault current , a CT might saturate on one side and the result to increasing the 
differential current which caused un‐wanted trip command. The differential 
protection must protect such this case.    
1.DIFFERENIAL PROTECTION CONCEPTS

Operating Characteristics
Diff/Restraint(bias) Characteristic

Slope 2

Correction

o Increasing slope 1 o using 2nd slope ( suitable)

Id>> 2.5 Id>> 2.5


Slope2
Slope1
Slope1

Id> 0.2 Id> 0.2


1.DIFFERENIAL PROTECTION CONCEPTS

Operating Characteristics
Diff/Restraint(bias) Characteristic

Slope 2

Now become

Id>> 2.5

Slope2

Slope1

Id> 0.2
1.DIFFERENIAL PROTECTION CONCEPTS

Operating Characteristics
Diff/Restraint(bias) Characteristic

High set of differential current

High Set

Id>> 2.5

Slope2

Slope1

Id> 0.2

I restrain

Slope = I diff / I restrain


1.DIFFERENIAL PROTECTION CONCEPTS

Operating Characteristics

Diff/Restraint(bias) Characteristic in Micom P633

High Set

Id>> 2.5

Slope2

Slope1

Id> 0.2

I restrain
Slope = I diff / I restrain

Slope1
0.5 In < slope < 4 In

Slope 2
4 In < slope 2 < IH
1.DIFFERENIAL PROTECTION CONCEPTS
Operating Characteristics
Diff/Restraint(bias) Characteristic in Micom P633

Minimum Pick up ( Id> )
Slope 1
Slope 2
High set of differential current
1.DIFFERENIAL PROTECTION CONCEPTS

Operating Characteristics

In‐rush Current (2nd harmonic)

Under normal steady‐state conditions, the magnetizing current required to produce 
the necessary flux is relatively small, usually less than 1% of full load current.
1.DIFFERENIAL PROTECTION CONCEPTS

Operating Characteristics

In‐rush Current (2nd harmonic)

However, if the transformer is energized at a voltage zero then the flux demand during 
the first half voltage cycle can be as high as twice the normal maximum flux.
The magnetizing in‐rush current may 8 to 12 times steady‐state magnetizing current.

 That can cause Differential relay instability.
1.DIFFERENIAL PROTECTION CONCEPTS
Operating Characteristics
In‐rush Current (2nd harmonic)

2nd harmonics filtering in Micom P633


2. PRACTICAL TESTING ON MICOM P 633

With OMICRON CMC ‐356
2. PRACTICAL TESTING ON MICOM P 633

CT RATIO
2. PRACTICAL TESTING ON MICOM P 633

CAPACITY‐MVA
2. PRACTICAL TESTING ON MICOM P 633

VOLTAGE LEVLE
2. PRACTICAL TESTING ON MICOM P 633

OPERATING CHARACTERISTICS

Minimum Pick up ( Id> )
Slope 1
Slope 2
High set of differential current
2. PRACTICAL TESTING ON MICOM P 633

OPERATING CHARACTERISTICS
2. PRACTICAL TESTING ON MICOM P 633

OPERATING CHARACTERISTICS
HOW TO DO SLOPE ( SLOPE = I different / I restrain ) IN CMC‐356

The first section (Area I)
2. PRACTICAL TESTING ON MICOM P 633

OPERATING CHARACTERISTICS
HOW TO DO SLOPE ( SLOPE = I different / I restrain ) IN CMC‐356

The first section (Area II)
2. PRACTICAL TESTING ON MICOM P 633

OPERATING CHARACTERISTICS
HOW TO DO SLOPE ( SLOPE = I different / I restrain ) IN CMC‐356

The first section (Area III)
2. PRACTICAL TESTING ON MICOM P 633

OPERATING CHARACTERISTICS
HOW TO DO SLOPE ( SLOPE = I different / I restrain ) IN CMC‐356

I diff = 2.5 , I restrain = 6.2

Slope‐2
0.7

I diff = 0.9 , I restrain = 4
Slope‐1
0.3
I diff = 0.2 , I restrain = 1.5
2. PRACTICAL TESTING ON MICOM P 633

What should be tested?

What should be tested at the secondary injection test?

#  the relay must not operate for normal load and external through fault condition.

#  the relay must operate for internal fault condition
2. PRACTICAL TESTING ON MICOM P 633
What should be tested?

Trip

Block
References :
# Areva Network Protection & Automation Guide
# Protective Relay Principal And Application by J Lewis Blackburn
# The Art and Science Of The Protective Relaying by C Russell Mason 
# Practical Power System Protection By L G Hewitson
# Micom Differential Relay Manual
# Micom Over current  Relay Manual
# Omicron CMC‐365 Over current protection Example
# Omicron CMC‐365 Advanced Protection Manual
# Omicron Transformer Differential & Testing Solution Presentation
QUESTIONS  ???
THANKS FOR YOUR ATTENTION

You might also like