Job Name: CNCH Rionegro Unit Tag: CGAM-1

Prepared For: Airenet Quantity: 1

Unit Overview
Chiller Model CGAM
Unit Nominal Tonnage 20 tons
Unit Type High efficiency
Refrigeration Capacity 8.617 tons
Cooling Efficiency 6.577 EER (Btu/W-h)
IPLV.IP 14.15 EER (Btu/W-h)
NPLV.IP 7.103 EER (Btu/W-h)
Elevation 2130 m
Unit Frequency 60. hertz
Unit Voltage 460. volt 3 phases
Refrigerant Type R410A
Number of compressor 2
Number of circuits 1
Number of capacity steps 2
Agency Listing UL/CUL
CGAM020F2**2AXD2A1A1D1AX*
Model Number
A1A1A4AXAXXXA1A3X1D1XXC* X

Evaporator Information
Evaporator Application
Low temp below 10F
Fluid Temperatures Flow Rate
Evaporator Leaving -17.70 C Design Flow 24.37 gpm Freeze protection With freeze protection
Evaporator Entering -12.23 C Fluid Pressure Drop 0.0001000 hr-sq ft-deg
Fouling factor
F/ Btu
Fluid Properties Total PD evap+strainer 5.48 ft H2O
Flow switch set point 15
Fluid Type Ethylene glycol Design Evap PD 4.27 ft H2O Flow switch set point
cm/sec
Fluid Concentration 42.00 % Water connection size 2.000 in
Freeze Point -11.85 F

Condenser Information
Unit Application Wide ambient Fin Material Lanced aluminum
Ambient Air Temp. 75.0 F Total airflow 18666 cfm Number of Fans 2

Unit Electrical
Unit RLA LRA
Compressor Starter Across the line Incoming Power Line Conn. Type Single point Compressor A 18.60 A 142.00 A
Total Power 15.72 kW Terminal Compressor B 18.60 A 142.00 A
Power Line Conn. Type
block
Compressor Power 13.52 kW
Short Circuit Current Option Default
Fan Power 1.974 kW
Short Circuit Current Rating 5000 A
Fan FLA 3.20 A
Single Point Power MCA 50 A
Single Point Power MOP 60 A

Physical Information
Dimensions Weights Refrigerant Charge Oil Charge
Length 114 in Operating Weight 2208 lb Circuit 1 32.0 lb 1.74 gal
Width 50 in Shipping Weight 2185 lb
Height 85 in

Unit Acoustics (A-Weighted)


A-Weighted Sound Power Sound Pressure* Unit Sound Package
100% 86 dBA 61 dBA Super quiet
Note: In Accordance with AHRI 370 *Note: at 30 feet in free field

2022/06/24 14:08:41 Page 1 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

Partload Information
NPLV.IP 0.0000 EER (Btu/W-h)
Flow Evap WPD Evap ft Eff. EER
Load % Cap. tons LWT Evap C EWT Evap C Amb F Power kW
gpm H2O (Btu/W-h)
100 8.617 -17.70 -12.23 24.37 5.48 75.0 15.72 6.577

Warranty
Standard Warranty

Regulatory Compliance
Outside the scope of AHRI Air-Cooled Water-Chilling Packages
Certification Program or not optionally certified, but is rated in accordance
with AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).

Trane Select Assist


260
Version Number:
Data Generation Date: 6/24/2022

2022/06/24 14:08:41 Page 2 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

2022/06/24 14:08:41 Page 3 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

2022/06/24 14:08:41 Page 4 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

2022/06/24 14:08:41 Page 5 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

2022/06/24 14:08:41 Page 6 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

2022/06/24 14:08:41 Page 7 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

2022/06/24 14:08:41 Page 8 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

2022/06/24 14:08:41 Page 9 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

2022/06/24 14:08:41 Page 10 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

2022/06/24 14:08:41 Page 11 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

2022/06/24 14:08:41 Page 12 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

2022/06/24 14:08:41 Page 13 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

2022/06/24 14:08:41 Page 14 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

2022/06/24 14:08:41 Page 15 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

2022/06/24 14:08:41 Page 16 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

2022/06/24 14:08:41 Page 17 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

Foundation
Provide rigid, non-warping mounting pads or a concrete foundation of sufficient strength and mass to
support the applicable operating weight (i.e. including completed piping, and full operating charges of
refrigerant, oil and water). The expectation of Trane equipment is that piping is fully supported by an
independent structure/system, without being connected to the waterbox. Once in place, the unit must
be level within 1/2" across the length and width of the unit. The Trane Company is not responsible for
equipment problems resulting from an improperly designed or constructed foundation.

Center Of Gravity

Different unit configurations and options may cause a variation in the center of gravity from what is
listed in the submittal.. Refer to the Installation, Operating and Maintenance manual for specific lifting
instructions.

General
Units are constructed of a galvanized steel frame with galvanized steel panels and access doors.
Component surfaces are finished with a powder-coated paint.

Each unit ships with full operating charges of refrigerant and oil.

Compressor and Motor


The unit is equipped with two hermetic, direct-drive, 3600 rpm 60 Hz suction gas-cooled scroll
compressors. The simple design has only three major moving parts and a completely enclosed
compression chamber which leads to increased efficiency. Overload protection is internal to the
compressors. The compressor includes: centrifugal oil pump, oil level sight glass and oil charging
valve. Each compressor will have compressor heaters installed and properly sized to minimize the
amount of liquid refrigerant present in the oil sump during off cycles.

Unit-Mounted Starter
The control panel is designed per UL 1995. The starter is in an across-the-line configuration, factory-
mounted and fully pre-wired to the compressor motor and control panel. Typically, Trane scroll
compressors are up to full speed in one second when started across-the-line.

A factory-installed, factory-wired 820 VA control power transformer provides all unit control power (120
Vac secondary) and Trane CH530 module power (24 Vac secondary).

Power line connection type is standard with a terminal block.

Power Connection
Power connections include main three-phase power and two separate 115V, 20 amp customer
provided single phase power connections are required to power the heaters (if used for freeze
protection) as well as the programmable relays.

Short circuit current rating of 5 kA is provided.

Evaporator
Braze plate evaporator is made of stainless steel with copper as the braze material. It is designed to
withstand a refrigerant side working pressure of 430 psig (29.6 bars) and a waterside working pressure
of 150 psig (10.5 bars). Evaporator is tested at 1.1 times maximum allowable refrigerant side working
pressure and 1.5 times maximum allowable water side working pressure. It has one water pass. A
water strainer and a flow switch are factory installed.

Immersion heaters protect the evaporator to an ambient of -20°F (-29°C).

All evaporators have grooved pipe connections.

Note: An additional 115V, 20 amp field provided single phase power connection is required to power
the heaters (if used for freeze protection).

2022/06/24 14:08:41 Page 18 of 19


Job Name: CNCH Rionegro Unit Tag: CGAM-1
Prepared For: Airenet Quantity: 1

Condenser
Air-cooled condenser coils have lanced aluminum fins mechanically bonded to internally-finned copper
tubing.

The condenser coil has an integral sub-cooling circuit. The maximum allowable working pressure of
the condenser is 650 psig (44.8 bars). Condensers are factory proof tested at 650 psig (44.8 bars).

Direct-drive vertical discharge condenser fans are balanced and individually protected. Three-phase
condenser fan motors with permanently lubricated ball bearings and external thermal overload
protection are provided.

A variable speed drive on the first fan of each circuit allows the unit to start and operate with ambient
temperatures between 0.0 F and 125.0 F.

Refrigerant Circuits
The unit has a single refrigerant circuit. The circuit has Trane scroll compressors piped in parallel with
a passive oil management system. A passive oil management system maintains proper oil levels
within compressors and has no moving parts. Each refrigerant circuit includes filter drier, electronic
expansion valve, liquid line and discharge service valves. Capacity modulation is achieved by turning
compressors on and off. The unit has two capacity stages.

Data contained in available reports includes: water and air temperatures, refrigerant pressures and
temperatures, flow switch status, EXV position, and compressor starts and run-time. All necessary
settings and setpoints are programmed into the microprocessor-based controller via the operator
interface. The controller is capable of receiving signals simultaneously from a variety of control
sources, in any combination, and priority order of control sources can be programmed.

Communications
BACNet Interface allows the user to easily interface using BACNet MS/TP via a single twisted-pair
wiring to a factory-installed and tested communication board.

External Chilled Water and Demand Limit Setpoint


Controls, sensors, and safeties allow reset of chilled water temperature, based on temperature signal,
during periods of low outdoor air temperature (chilled water reset based on return chilled water
temperature is standard). The demand limit setpoint is communicated to a factory-installed and tested
communication board through a 2-10 Vdc or 4-20 mA signal.

Programmable Relays
Predefined, factory-installed, programmable relays allow the user to select four relay outputs. Available
outputs are: Alarm-Latching, Alarm-Auto Reset, General Alarm, Warning, Chiller Limit Mode,
Compressor Running, and Tracer Control.

Note: An additional 115V, 20 amp field provided power connection is required to power the
programmable relays.

Isolators
Molded elastomeric isolators, sized to reduce vibration transmission to the supporting structure when
the unit is installed, ship with the chiller.

2022/06/24 14:08:41 Page 19 of 19