RE/RL XE/XL : 0,014 F/KM 0,009 F/KM
RE/RL XE/XL : 0,014 F/KM 0,009 F/KM
BÖLGE MÜDÜRLÜĞÜ
RÖLE MARKA VE TİPİ SIEMENS 7SA87 TARİH MERKEZ ADI YUSUFELİ HES GİS TM
Cap 0 257,8170 C0 0,009 µF/km Kr= RE/RL Kx= XE/XL RR1E= [R0PE1 + kz * (RarcFT + Rd) ] F-T arıza için
C=1/(18x10^6xln(GMD/r)) (F/km); GMD: İletkenler arası ort. mesafe (m), r: İletken yarıçapı (m) RR1= R1 + kz * (RarcFF / 2 ) F-F arıza için
7SA87
SETTING: 21 DISTANCE PROTECTIN1 GENERAL
Line1 / Proses Monitor / Closure detec. / Operating Mod Man Cl Operate&fault rec. blocked (Tüm Kademeler)= no Z. start= on dist. pick up
Circuit break. / General / Breaker Sett. / Current Thr. CB Open (A) 0,03 Zone-inc. Angle(Tüm Kademeler)= 0,00 derece D. Angle 86,51 derece
G.F.det.= 3I0 or V0
Z1 (İLERİ) = 0,85 x ZL1 R1(ph-g)= 38,57 ohmLV 3I0>tre.= 0,107 A (LV)
R1= 1,01 ohmLV R0PE1= 14,88 ohmLV R1(ph-ph)= 8,91 ohmLV V0>tre.= 1,66 V (LV)
X1reach= 16,57 ohmLV X0PE1= 52,90 ohmLV delay = 0,00 sn 3I0 p.s.= 0,10
Loop S.= block leading ph.
Z2 (İLERİ) = 1,00 x ZL1 + 0,5 x ZL2 R2(ph-g)= 43,78 ohmLV
R2= 1,42 ohmLV R0PE2= 20,10 ohmLV R2(ph-ph)= 9,31 ohmLV Z< BAŞLATMA
X2reach= 22,36 ohmLV X0PE2= 71,35 ohmLV delay= 0,40 sn M.P.C.tres.= 0,107 A (LV)
D. Angle= 0,00 derece
Z3 (İLERİ) = 1,00 x ZL1 + 0 x ZL2 1,2 x ZL3 R3(ph-g)= 75,40 ohmLV Cut out(ph-gr)= yes
R3= 4,21 ohmLV R0PE3= 51,71 ohmLV R3(ph-ph)= 12,11 ohmLV Cut out(ph-ph)= yes
X3reach= 57,48 ohmLV X0PE3= 181,24 ohmLV delay= 0,80 sn R.c.out= 35,00 ohmLV
R.c.out Angle= 40,00 derece
Z4 (İLERİ) = 1,20 x ZL1 + 0 x ZL2 + 1,44 x ZL3 R4(ph-g)= 85,74 ohmLV
R4= 5,05 ohmLV R0PE4= 62,06 ohmLV R4(ph-ph)= 12,95 ohmLV PICKUP I
X4reach= 68,97 ohmLV X0PE4= 217,49 ohmLV delay= 1,20 sn Mode= off
O/C Iph>> 7,00 A (LV)
Z5 (GERİ) = 0,10 x ZL4 X5(forward)= 68,97 ohmLV R5(ph-g)= 24,18 ohmLV Loop 1ph= ph-ph or ph-gr
R5= 0,03 ohmLV R0PE5= 0,50 ohmLV R5(ph-ph)= 7,93 ohmLV O. del. fw.= 1,00 sn
X5reach= 0,55 ohmLV X0PE5= 1,77 ohmLV delay= 0,35 sn O. del. n.d.= 1,80 sn
AR ZONE 1
Operate with= Z1, Z1B
Mode= on
1 pole op.= yes
68 POWER SWING SWITCH ONTO FAULT Op. Delay 1p= 1,00 sn
RL= 30,83 ohmLV Configüration= Z1,Z1B,Z2 Op. Delay mp= 0,50 sn
DR= 4,93 ohmLV Op. delay= 0 sn Ef. By AR cy.= 1
Blocking= Z1,2,3,4,5,1B Bl. İf 85-21 a.= yes
Pow. Sw. Band Setting: DR=0.16 * RL 79 AUTO RECLOSING
Min. Load Imp.:Rload= 0.8* Un /(√3*1.5*In) Mode= 1 Pole
25 SENKRONİZASYON CB ready check= No 85-21 TELEPROTECTION
T.K. El+Scada Max Num. of Shots= 1 Mode= POTT
67N GFPgnd sys1 (Yön. Toprak) Açı farkı= 10 30 derece Close time BKR1= 0.1 sn Send with= Z1,Z1B,Z2
Blocking by= Z1,2,3,4,5,1B Gerilim farkı= 10 20 voltLV Block Time Upon Man Cls= 60 sn Operate with= Z1B,Z2
Threshold= 0,107 xIn Frekans farkı= 0.1 0.2 Hz Reclaim time= 60 sn Send Prol.= 0,05 sn
Typ of Car. Curve= IECNI Min. Op. Limit= 80 80 voltLV 3 pole operate by 79= No Send Delay= 0 sn
Time dial= 0,30 Min. Op. Limit= 120 120 voltLV 1P Dead time= 1,5 sn Oper. Delay = 0 sn(1ph-3ph)
NOT: Yönlü Toprak: Ie> : 320 A - 0,3 (IEC Standart Inverse) (NOT: LP1 ve/veya LP2 röleleri başlatma aldığında blokaja geçirilecektir.)
Aşırı Gerilim: U> : 456 kV - 2,5 sn (100 km' den uzun havai iletim hatlarında kullanılır.)