Manual Bacnet
Manual Bacnet
A7
Document 51659
2/10/09 Rev:
P/N: 51659:A7 ECN: 08-717
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of smoke detec- bedrooms), smoking in bed, and violent explosions (caused by escap-
tors, heat detectors, manual pull stations, audible warning devices, ing gas, improper storage of flammable materials, etc.).
and a fire alarm control panel with remote notification capability—can Heat detectors do not sense particles of combustion and alarm only
provide early warning of a developing fire. Such a system, however, when heat on their sensors increases at a predetermined rate or
does not assure protection against property damage or loss of life reaches a predetermined level. Rate-of-rise heat detectors may be
resulting from a fire. subject to reduced sensitivity over time. For this reason, the rate-of-
The Manufacturer recommends that smoke and/or heat detectors be rise feature of each detector should be tested at least once per year
located throughout a protected premise following the recommenda- by a qualified fire protection specialist. Heat detectors are designed
tions of the current edition of the National Fire Protection Association to protect property, not life.
Standard 72 (NFPA 72), manufacturer's recommendations, State and IMPORTANT! Smoke detectors must be installed in the same room
local codes, and the recommendations contained in the Guide for as the control panel and in rooms used by the system for the connec-
Proper Use of System Smoke Detectors, which is made available at tion of alarm transmission wiring, communications, signaling, and/or
no charge to all installing dealers. These documents can be found at power. If detectors are not so located, a developing fire may damage
http://www.systemsensor.com/html/applicat.html. the alarm system, crippling its ability to report a fire.
A study by the Federal Emergency Management Agency (an agency Audible warning devices such as bells may not alert people if these
of the United States government) indicated that smoke detectors may devices are located on the other side of closed or partly open doors or
not go off in as many as 35% of all fires. While fire alarm systems are are located on another floor of a building. Any warning device may
designed to provide early warning against fire, they do not guarantee fail to alert people with a disability or those who have recently con-
warning or protection against fire. A fire alarm system may not pro- sumed drugs, alcohol or medication. Please note that:
vide timely or adequate warning, or simply may not function, for a
variety of reasons: • Strobes can, under certain circumstances, cause seizures in people
with conditions such as epilepsy.
Smoke detectors may not sense fire where smoke cannot reach the
• Studies have shown that certain people, even when they hear a fire
detectors such as in chimneys, in or behind walls, on roofs, or on the
alarm signal, do not respond or comprehend the meaning of the signal.
other side of closed doors. Smoke detectors also may not sense a
It is the property owner's responsibility to conduct fire drills and other
fire on another level or floor of a building. A second-floor detector, for training exercise to make people aware of fire alarm signals and
example, may not sense a first-floor or basement fire. instruct them on the proper reaction to alarm signals.
Particles of combustion or “smoke” from a developing fire may not • In rare instances, the sounding of a warning device can cause tempo-
reach the sensing chambers of smoke detectors because: rary or permanent hearing loss.
• Barriers such as closed or partially closed doors, walls, or chimneys A fire alarm system will not operate without any electrical power. If
may inhibit particle or smoke flow. AC power fails, the system will operate from standby batteries only for
• Smoke particles may become “cold,” stratify, and not reach the ceiling a specified time and only if the batteries have been properly main-
or upper walls where detectors are located. tained and replaced regularly.
• Smoke particles may be blown away from detectors by air outlets. Equipment used in the system may not be technically compatible
• Smoke particles may be drawn into air returns before reaching the with the control panel. It is essential to use only equipment listed for
detector. service with your control panel.
The amount of “smoke” present may be insufficient to alarm smoke Telephone lines needed to transmit alarm signals from a premise to a
detectors. Smoke detectors are designed to alarm at various levels of central monitoring station may be out of service or temporarily dis-
smoke density. If such density levels are not created by a developing abled. For added protection against telephone line failure, backup
fire at the location of detectors, the detectors will not go into alarm. radio transmission systems are recommended.
Smoke detectors, even when working properly, have sensing limita- The most common cause of fire alarm malfunction is inadequate
tions. Detectors that have photo-electronic sensing chambers tend to maintenance. To keep the entire fire alarm system in excellent work-
detect smoldering fires better than flaming fires, which have little visi- ing order, ongoing maintenance is required per the manufacturer's
ble smoke. Detectors that have ionizing-type sensing chambers tend recommendations, and UL and NFPA standards. At a minimum, the
to detect fast-flaming fires better than smoldering fires. Because fires requirements of NFPA 72 shall be followed. Environments with large
develop in different ways and are often unpredictable in their growth, amounts of dust, dirt or high air velocity require more frequent mainte-
neither type of detector is necessarily best and a given type of detec- nance. A maintenance agreement should be arranged through the
tor may not provide adequate warning of a fire. local manufacturer's representative. Maintenance should be sched-
uled monthly or as required by National and/or local fire codes and
Smoke detectors cannot be expected to provide adequate warning of should be performed by authorized professional fire alarm installers
fires caused by arson, children playing with matches (especially in
FCC Warning
WARNING: This equipment generates, uses, and can radi- likely to cause interference, in which case the user will be
ate radio frequency energy and if not installed and used in required to correct the interference at his own expense.
accordance with the instruction manual, may cause inter- Canadian Requirements: This digital apparatus does not
ference to radio communications. It has been tested and exceed the Class A limits for radiation noise emissions
found to comply with the limits for class A computing from digital apparatus set out in the Radio Interference
device pursuant to Subpart B of Part 15 of FCC Rules, Regulations of the Canadian Department of Communica-
which is designed to provide reasonable protection against tions.
such interference when operated in a commercial environ-
ment. Operation of this equipment in a residential area is Le present appareil numerique n'emet pas de bruits radio-
electriques depassant les limites applicables aux appareils
numeriques de la classe A prescrites dans le Reglement
Acclimate Plus™, HARSH™, NOTI•FIRE•NET™, VeriFire™, NION™, NOTIFER Intergrated Systems™ and ONYXWorks™ are trademarks, and
ONYX®, FlashScan®, UniNet®, VIEW®, NOTIFIER® are registered trademarks of Honeywell. Simplex® is registered trademark of Tyco
International Ltd. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint
Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of
General Electric Company.
©2006 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
NOTE: This manual is written with the understanding that its user is trained in BACnet operations
and services. The information provided here is solely for the configuration of the Gateway to
communicate event information to an existing BACnet network.
1.3.1 Compliance
This product has been investigated to, and found to be in compliance with the following standards.
National Fire Protection Association
• NFPA 72—National Fire Alarm Code
Underwriters Laboratories
• UL-864—Control Units for Fire Alarm Systems, Ninth Edition
• UL-2017—General-Purpose Signaling Devices and Systems, First Edition
1.3.2 Installation
This product is intended to be installed in accordance with the following regulatory agencies.
Local
• AHJ—Authority Having Jurisdiction
National Fire Protection Association
• NFPA 70—National Electrical Code
• NFPA 72—National Fire Alarm Code
• NFPA 101—Life Safety Code
Underwriters Laboratories
• UL-1076—In certified applications, the unit shall be installed in accordance with Proprietary
Burglar Alarm Units and Systems, Fifth Edition
Underwriters Laboratories Canada
• CAN/ULC-S524-06—Standard for the Installation of Fire Alarm Systems, Fifth Edition
• CAN/ULC-S561-03—Installation and Services for Fire Signal Receiving Centres and
Systems, First Edition
Canada
• CSA C22.1—Canadian Electrical Code, Part I, Safety Standard for Electrical Installations
WARNING: Installation
! Improper installation, maintenance, and lack of routine testing could result in system malfunction.
NOTE: Refer to Appendix B, “PIC Statement”, on page 39 for the BACnet PIC statement.
1.5 Compatibility
NOTE: The BACnet Gateway requires that at least one node on the NFN network be an ONYX
series panel. Running a BACnet Gateway on an NFN network with only classic panels will cause
events to be labeled with incorrect times and dates, and may cause other problems.
The BACnet Gateway behaves as any other node on a NFN network and is compatible with the
following.
AFP-1010 MIB-WPCC
†
AFP-2800 NCM-W/F
AM2020 SIB-NET
DVC NCM-W/F
NCS NCM-W/F
NCA NCM-W/F
NCA-2 NCM-W/F
NFS-320* NCM-W/F
NFS-640* NCM-W/F
NFS2-640* NCM-W/F
NFS-3030* NCM-W/F
NFS2-3030* NCM-W/F
NFS2-3030* NCM-W/F
1.7 Troubleshooting
Before calling technical support, please do the following:
Step 1. Log the entire discovery process from start to finish including the panel online message
from the Gateway Activity window and save the file. Please refer to, “Viewing BACnet
Gateway Activity with the BACnet Gateway Configuration Tool” on page 31.
Step 2. Make a backup file of your BACnet Gateway. Please refer to, “Back Up BACnet
Gateway” on page 33.
Ethernet
From PNET-1
EIA-232 Gateway
Ethernet
From PNET-1
EIA-232 Gateway
and NCM-W/F
OR
NOTI•FIRE•NET™
NOTE: No NCM W/F is required when the BACnet Gateway connects directly to a supported
NOTIFIER® panel or annunciator when it is a standalone panel or annunciator. Refer to Table 1.2
on page 10 for a list of supported panels and annunciators.
DB9-NUP Connector -
used for operation as
the network connection
to NFN
HDD Power
Connector (P1)
RJ45 Ethernet
Connector (CN2)
NOTE: The replacement of the lithium battery on the board is to be performed by a trained
technician.
+24VDC power
connection from
power supply to
POWER FIRE
ALARM
PREALARM SECURITY SUPERVISORY SYSTEM
TROUBLE
DISABLED
POINTS
ALARM
SILENCED Gateway board power
supply connector
ACKNOWLEDGE SILENCE DRILL RESET LAMP
STEP DISPLAY HOLD 2 SECONDS TEST
1
!
2@ 3
=
4, 5
%
6
:
7
/
8
.
9 0? DISABLE
ENABLE
*
NEXT
SELECTION +
Q W E R T Y U I O P # PREVIOUS
SELECTION
–
A S D F G H J K L Esc
&
RECALL
LAST (
ENTRY
Gateway
Board
PNET-1 connection
NOTE: All wiring from the power supply is power limited, and a separation of at least ¼” (6.35
mm) must be maintained between power limited and non-power limited wiring
NOTE: All BACnet Gateway circuits are power limited. Route wiring per the power limited and
non-power limited constraints defined in the pertinent Fire Alarm Control Panel manual.
Step 1. Install a new CAB-3/CAB-4 series cabinet according to the requirements of the local
authority having jurisdiction or prepare an existing CAB-3/CAB-4 series cabinet that
houses a supported NOTIFIER® panel or annunciator. Refer to Table 1.2 on page 10 for
list of supported panels and annunciators.
NOTE: The CAB3/CAB4 cabinet is ordered separately. For installation details, refer to the CAB-
3/CAB-4 Series Installation Document, 15330 and or the panel’s or annunciator’s documentation.
Step 2. After the CAB3/CAB4 cabinet is prepared with the CHS-4L chassis installed, perform the
“BACnet Gateway Assembly Installation” on page 18.
1 General
All cabinets are fabricated from 16 gauge steel. The cabinet consists of two basic components: a backbox and a locking
door.
The key-locked door is provided with a pin-type hinge, two keys, and the necessary hardware to mount the door to the
backbox. The backbox has been engineered to provide ease-of-entry for the installer. Knockouts are positioned at
numerous points to let the installer bring conduit into the enclosure easily. Doors can be mounted on the left or right-hand
side. The same hinge works in both configurations, so that this choice can be made in the field. The door opens 180°.
Cabinets are available in five sizes: A through D, and AA. The outside dimensions are noted on each enclosure diagram.
“A” size accommodates one chassis, a power supply, and two 26 AH batteries; “D” size accommodates four chassis, a
power supply, and two 26 AH batteries; “AA” size holds one chassis with no compartment for batteries. A trim ring
option is available for semi-flush mounting. The CAB-3/CAB-4 Series is compatible with multiple chassis including the
CHS-M2, CHS2-M2, CHS-M3, CHS-4, CHS-4L, CHS-4N, CHS-BH, CHS-PS, CA-1, and CA-2. Note: CAB-4 series
backboxes and doors are sold separately.
the doors can be opened “barn door” style, permitting an open work
space. Note that in this type of installation it is necessary to leave
enough space between cabinets to insert a key into the locks on the
door frames.
IMPORTANT: Attach the two hinges and two alignment tabs to the
backbox before any equipment is installed. With chassis installed,
space is very limited.
Display Interface Assembly Note: When the door is left-hand
mounted, the Display Interface Assembly (DIA) dress panel cannot be
opened when the door is at less than a 120° angle to the cabinet. If you are using the left-hand mounting option, be sure
that the door can open at least 120°. This is especially important if the cabinet is to be mounted in a closed area, such as a
closet or utility room.
Step 6. You are now ready to perform the “Network Communication Module Installation” on
page 20 if its use is applicable to your installation, if not perform the “BACnet Gateway
Configuration” on page 23.
2 1
3
4
6
Earth
+5VDC Output
5V REF Output
Red wire
NOTE: For installation details, refer to the NCM Installation Document (51533) or the supported
NOTIFIER® panel’s or annunciator’s documentation.
Use the Network Control Module board configuration that fits your installation needs.
• NCM-W with twisted pair wire.
• NCM-F with fiber-optic cable.
12 Clintonville Road
Northford, CT 06472-1653 USA
203-484-7161 • FAX 203-484-7118
www.notifier.com
Network Communications Module NCM-W/F
Product Installation Document
PN 51533:C 12/28/2006 06-069
1 UL 864 Compliance
1.1 Products Subject to AHJ Approval
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864 9th Edition.
The following products have not received UL 864 9th Edition certification and may only be used in retrofit applications.
Operation of the NCM-W, NCM-F with products not tested for UL 864 9th Edition has not been evaluated and may not
comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local
Authority Having Jurisdiction (AHJ).
• AM2020/AFP1010
• MIB
• NAM-232
2 Product Overview
The Network Communications Module (NCM) provides a means for connecting specific Notifier fire alarm control
products to NOTI•FIRE•NET™. There are two types of NCMs available: NCM-W for connecting nodes with twisted-
pair wire, and NCM-F for connecting nodes with fiber-optic cable.
In most applications, one NCM is required per NOTI•FIRE•NET™ node (including fire alarm control panels and
network annunciators) . Even though the NCM has two NUP ports, only one may be connected to a NOTI•FIRE•NET™.
node. Except in some DVC applications, do not connect two NCMs via NUP ports (aka “NUP to NUP”).
For instructions on the additional capabilities available with the DVC, refer to the DVC Manual.
• Input power requirements: 24 VDC , 0.11 amps, regulated, power-limited compatible power supply UL/ULC listed
for fire protective signalling use.
• Communications circuit requirements: Refer to the NOTI•FIRE•NET™ Manual (Network Version 4.0 and Higher)
for wiring length and threshold information.
Step 2. After the installation perform “BACnet Gateway Configuration” on page 23.
NOTE: For complete details on powering and connecting an NCM-W/F, refer to its Product
Installation Document P/N 51533.
Gateway Board
Gateway board to PNET-1
To Internet or Intranet
PNET-1 surge suppressor
Refer to Table 2.1, “46175 Power Supply Specifications” for power supply specifications.
Earth
+5VDC Output
5V REF Output Black wire
*The NCM-W/F cable (P/N 75583) is not required when directly connecting to a supported
NOTIFIER® panel or annunciator when they act as a standalone panel or annunciator.
Step 3. Follow the displayed instructions to install the BACnet Gateway Configuration Tool.
Step 4. Record your current Internet Protocol (TCP/IP) property settings so you can restore them
later.
Step 5. Click Use the following IP address, and then type 192.168.1.X into the IP address field.
NOTE: X can be any number between 0 and 255 except for 2 (since the BACnet Gateway
default IP address is 192.168.1.2).
Step 6. Click OK, and then close all remaining open windows.
Step 1. Launch the BACnet Gateway Configuration Tool by clicking Start Ö All Programs Ö
BACnet Gateway Config Tool from the Windows taskbar.
Step 2. Click the Address field, and then click the default gateway IP address 192.168.1.2 in the
menu that drops down.
Step 4. Type the default password, 00000000, and then click OK.
NOTE: By default, the BACnet Gateway synchronizes its internal clock with the NFN network
time, or with the Fire Alarm Control Panel in the case of a direct connection. Configuring the
SNTP server is only necessary if you want the gateway to synchronize with another server, such
as an ONYXWorks® Workstation or an SNTP time server.
Step 1. In the left pane of the BACnet Gateway Configuration Tool under the Gateway heading,
click SNTP Configuration.
Step 2. Click the SNTP Server Address field under the Value heading, and then type the address
of the SNTP server.
Step 2. Use the fields under the Value heading to enter your local Greenwich Mean Time offset
value as well as the appropriate information about the observance of Daylight Savings
Time.
Configure IP Settings
Step 1. In the left pane of the BACnet Gateway Configuration Tool under the Gateway heading,
click IP Configuration.
Step 2. Click the fields under the Value heading, and type the IP, Subnet Mask, and Gateway
(router) addresses this BACnet Gateway will use on your network.
Step 3. Click Apply to activate these settings.
Step 2. Right-click your LAN connection, and then click Properties in the menu that appears.
Step 4. Enter the settings you recorded earlier into the Internet Protocol (TCP/IP) Properties
dialogue, and then click OK to return your configuration computer to your IP network.
Finalize the BACnet Gateway Configuration
Log into the BACnet Gateway
Step 1. Click View Ö Refresh Gateway List to refresh the gateway address list.
Step 2. Click the Address field, and then, from the menu that drops down, click the IP address
you assigned this BACnet Gateway.
Step 4. Type the default password, 00000000, and then click OK.
The BACnet Gateway Configuration Tool now displays the remaining configurable
settings for the BACnet Gateway. Click the fields under the Value heading to enter
appropriate values, following the guidelines in the following steps.
Gateway Properties
• We recommend you select the Life Safety Notification Type if your system supports it.
Otherwise, virtually all clients support Multi State notification.
• If you are adding the BACnet Gateway to a network that already includes another gateway or
gateways, assign the Network Number based on the highest Network Number used by any
gateway already on the network. The Network Number for the new BACnet Gateway must be
greater than the highest Network Number by one thousand. For example, if the network
already includes a gateway with a Network Number of 1001, then the lowest Network Number
which can be assigned to the new BACnet Gateway is 2001.
BBMD Configuration
• If the BACnet Gateway and the Building Management System (BMS) are connected to the IP
network across different subnets, they must be connected through a BACnet Broadcast
Management Device (BBMD). When using a BBMD, set the Foreign Device value to True
and enter values for IP Address, Port and Register Time.
Multiple Gateways
• NFN networks with more than 15 nodes must be monitored using the Multiple Gateway
option.
• When using this Multiple Gateway option, set the Multiple Gateway value to True, and enter a
value for each network node to be monitored by this BACnet Gateway.
• You may enter up to 14 nodes for FACPs to be monitored, since the BACnet Gateway can
support 15 nodes including itself.
Apply Settings
Step 5. Once all BACnet Gateway settings have been properly configured, click Apply at the
bottom of the Value pane to apply the settings and reboot the gateway.
NOTE: If you are changing settings on a BACnet Gateway previously configured with monitored
nodes, this screen button will be labeled Apply And Delete Objects.
NOTE: The NFN network must be stable with very few events in order for the discovery process
to discover all objects upon initial configuration. After initial configuration, the BACnet Gateway
updates the network daily at its specified Network Update Time (the default time is 2:00:00).
It is helpful to launch the Gateway Activity window before connecting the BACnet Gateway to an
NFN network or directly to a Fire Alarm Control Panel, so you can monitor the messages the
BACnet Gateway generates in its initial Auto Discovery and Property Search routines. To open the
Gateway Activity window:
Step 1. Log into the BACnet Gateway (refer to “Log into the BACnet Gateway” on page 28).
Step 2. Click View Ö Gateway Activity.
The Gateway Activity window opens. Network traffic will affect the time required to populate the
Gateway Activity window.
Connect to an NCM-W/F or
a Supported NOTIFIER Panel
or Annunciator DB9 to NUP cable P/N 75554
Step 1. A DB9 to NUP cable is used to connect a DB9 to NUP cable between the gateway and
NFN network in one of these ways:
• Connect the cable between to the BACnet Gateway board’s DB9 connector and a
NCM W/F board NUP connector.xxx
• Use a NCM-W for a twisted pair wire connection.
• NCM-F for a fiber-optic cable connection.
• Connect the cable between to the BACnet Gateway board’s DB9 connector and a
supported NOTIFIER® panel’s and annunciator’s CPU NUP connector.
Refer to Table 1.2 on page 10 for supported NOTIFIER® panels and annunciators.
Step 2. After the cable connection is made the gateway configuration is complete.
Step 3. You should now configure your BACnet Client to communicate with the gateway.
The BACnet client workstation front end must conform to BACnet Standard Annex J for
IP and support Device Objects, Binary Output Objects, and Multi-state Input or Life
Safety Points/Zones. It is also required to write to Notification Objects and receive
confirmed/unconfirmed event notification messages. For details, refer to Appendix B,
“PIC Statement”, on page 39.
Step 1. Log into the BACnet Gateway (refer to “Log into the BACnet Gateway” on page 28).
Step 2. Click Tools Ö Backup Gateway.
Step 3. Navigate to where you want to store the backup file, type a name for the file, and then
click Save.
Step 3. Navigate to where the backup file (.bnk) was saved, click on the file name, and then click
Open.
(Detector) Loop 5, Detector 83: L005D083 (BACnet Life Safety Point or Multi-state Input Object)
(Zone) Zone 134: ZONE0134 (BACnet Life Safety Zone or Multi-state Input Object)
Any Node, Loop 5, Control Module 12: L005C012 (BACnet Binary Output Object)
An AM2020 as node 120: .Name = 120_AM2020 (_ denotes spaces) (BACnet Device Object)
An NCM as node 11 connected to BACnet GW: .Name = 011_ _ _ BACGW (BACnet Device Object)
(Module) Loop 9, Module 120: L009M120 (BACnet Life Safety Point or Multi-state Input Object)
(Zone) Zone 1003: ZONE1003 (BACnet Life Safety Zone or Multi-state Input Object)
(Panel Internal Devices)--LOOP 8, LOOP10, BATTERY, ANNUN021, ACPOWER, PANEL (BACnet Life Safety Point or
Multi-state Input Object)
DS-WP-B DS-WPM-B
AE-N-I-B AE-ACK-B
AE-ASUM-B AE-INFO-B
DM-DDB-B
DM-DOB-A DM-DOB-B
DM-LM-B
Segmentation Capability
• Segmented requests supported, Window Size 1024 max.
• Segmented responses supported, Window Size 1024 max.
Standard Object Types Supported - Life Safety Point/Life Safety Zone
2 IssA larm Fire A larm , S ecurity A larm (Life/P rope rty), C ritical P rocess A larm
(Life/P rope rty), M edical E m ergency
3 IssFault S ecurity Trouble, Fire Trouble, Non-Fire Trouble, Fire D evice or Zone
D isabled , Non-Fire D evice D isabled
2 IssA larm Fire A larm , S ecurity A larm (Life/P rope rty), C ritical P rocess A larm
(Life/P rope rty), M edical E m ergency
3 IssFault S ecurity Trouble, Fire Trouble, Non-Fire Trouble, Fire D evice or Zone
D isabled , Non-Fire D evice D isabled
7 IssA ctive Non-Fire A ctivation
1 E sFault S ecurity Trouble, Fire Trouble, Non-Fire Trouble, Fire D evice or Zone
D isabled , Non-Fire D evice D isabled
2 E sO ffNorm al A ll statuses other than norm al and fault.
10 Ism E nabled S et if point has bee n disabled and subsequently enabled since startup.
11 Ism D isabled Fire D evice or Zone D isab led , Non-Fire D evice D isabled
toFault
1,0,0,0 InA larm Fire A larm , S ecurity A larm (Life/P rope rty), C ritical P rocess A larm
(Life/P rope rty), M edical E m ergen , P reA larm
1,0,0,1 InA larm , O utO fService Fire D evice or Zone D isab led , Non-Fire D evice D isabled
2 IssAlarm Fire Alarm , Security Alarm (Life/Prope rty), C ritical Process A larm
(Life/P roperty), M edical E m ergency
3 IssFault S ecurity Trouble, Fire Trouble, Non-Fire Trouble, Fire D evice or Zone
D isabled, Non-Fire D evice D isabled
7 IssA ctive Non-Fire A ctivation
2 IssAlarm Fire Alarm , Security Alarm (Life/Prope rty), C ritical Process A larm
(Life/P roperty), M edical E m ergency
3 IssFault S ecurity Trouble, Fire Trouble, Non-Fire Trouble, Fire D evice or Zone
D isabled, Non-Fire D evice D isabled
7 IssA ctive Non-Fire A ctivation
1 EsFault S ecurity Trouble, Fire Trouble, Non-Fire Trouble, Fire D evice or Zone
D isabled, Non-Fire D evice D isabled
2 E sO ffNorm al All statuses other than norm al and fault.
10 Ism E nabled S et if point has been disabled and subsequently enabled since startup.
toFault
1,0,0,0 InA larm Fire Alarm , Security Alarm (Life/Prope rty), C ritical Process A larm
(Life/P rope rty), M edical E m ergen , PreA larm
1,1,0,0 InA larm , Fault S ecurity Trouble, Fire Trouble, Non-Fire Trouble
1,0,0,1 InA larm , O utO fS ervice Fire D evice or Zone D isabled, Non-Fire D evice D isabled
Networking Options:
• Select - Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-
MS/TP, etc. BACnet to Proprietary ARCnet Fire Network
• Annex H, BACnet Tunneling Router over IP
• BACnet/IP Broadcast Management Device (BBMD)
Does the BBMD support registrations by Foreign Devices?
• Yes
• Select - No
NOTE: This procedure is only necessary if you are configuring an BACnet Gateway using a
Configuration computer that is not already on the same IP network as the BACnet Gateway. Refer
to “IP and NFN Network Connections” on page 21.
NOTE: A direct connection requires that a cross over Ethernet cable to be made or purchased
by the customer.
Gateway Board
To Configuration Computer
1 White/Orange 1 White/Green
2 Orange 2 Green
3 White/Green 3 White/Orange
4 Blue 4 Blue
5 White/Blue 5 White/Blue
6 Green 6 Orange
7 White/Brown 7 White/Brown
8 Brown 8 Brown
G P
Gateway Panel Compatibility 10
configuration 45 PIC STATEMENT 39
features 7 PNET-1 15
gateway Power Connections 19, 21
configuration overview 23 power supply
example installation diagram 17 mounting plate 15
part number 15
Power Supply Connections 19, 21
R
Related Documentation 8
S
Segmentation Capability 39
Standard Object Types Supported 39
Supported - Binary Output 42
System Requirements 11
W
Wiring
Power 19
Notifier BACnet Gateway - Installation and Operation Manual - P/N: 51659:Rev: A7 2/10/09 51
World Headquarters
12 Clintonville Road
Northford, CT 06472-1610 USA
203-484-7161
fax 203-484-7118
www.notifier.com