0% found this document useful (0 votes)
133 views144 pages

PowerTag Link User Manual

The document provides information about the Acti9 PowerTag Link device including its technical characteristics, installation, commissioning process using EcoStruxure Power Commission software or web pages, device settings, and security. It contains chapters covering an overview of the Acti9 PowerTag system, installation of the Acti9 PowerTag Link, commissioning wireless devices, accessing and navigating the web interface, configuring device and network settings, and security settings.

Uploaded by

Heri Munir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
133 views144 pages

PowerTag Link User Manual

The document provides information about the Acti9 PowerTag Link device including its technical characteristics, installation, commissioning process using EcoStruxure Power Commission software or web pages, device settings, and security. It contains chapters covering an overview of the Acti9 PowerTag system, installation of the Acti9 PowerTag Link, commissioning wireless devices, accessing and navigating the web interface, configuring device and network settings, and security settings.

Uploaded by

Heri Munir
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 144

Acti9 PowerTag Link

DOCA0157EN-01 07/2019

Acti9 PowerTag Link


User Manual
07/2019
DOCA0157EN-01

www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical character-
istics of the performance of the products contained herein. This documentation is not intended as a
substitute for and is not to be used for determining suitability or reliability of these products for specific user
applications. It is the duty of any such user or integrator to perform the appropriate and complete risk
analysis, evaluation and testing of the products with respect to the relevant specific application or use
thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for
misuse of the information contained herein. If you have any suggestions for improvements or amendments
or have found errors in this publication, please notify us.
You agree not to reproduce, other than for your own personal, noncommercial use, all or part of this
document on any medium whatsoever without permission of Schneider Electric, given in writing. You also
agree not to establish any hypertext links to this document or its content. Schneider Electric does not grant
any right or license for the personal and noncommercial use of the document or its content, except for a
non-exclusive license to consult it on an "as is" basis, at your own risk. All other rights are reserved.
All pertinent state, regional, and local safety regulations must be observed when installing and using this
product. For reasons of safety and to help ensure compliance with documented system data, only the
manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must
be followed.
Failure to use Schneider Electric software or approved software with our hardware products may result in
injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2019 Schneider Electric. All rights reserved.

2 DOCA0157EN-01 07/2019
Table of Contents

Safety Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Chapter 1 Acti9 PowerTag System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Acti9 PowerTag Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Wireless Communication Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 2 Technical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Technical Characteristics of the Acti9 PowerTag Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Chapter 3 Installation of the Acti9 PowerTag Link. . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Chapter 4 General Principle to Commission an Acti9 PowerTag System . . . . . . . . . . 23
4.1 Commissioning Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Ethernet Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4.2 Pre-Requisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Installation of EcoStruxure Power Commission Software . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Firmware Upgrade. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Chapter 5 Getting Started with EcoStruxure Power Commission Software . . . . . . . . 31
Basic Commissioning of Wireless Devices with EcoStruxure Power Commission Software 32
Advanced Commissioning of Wireless Devices with EcoStruxure Power Commission
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Wireless Devices Configuration with EcoStruxure Power Commission Software . . . . . . . . . 34
Chapter 6 Getting Started with Web Pages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Discovering Acti9 PowerTag Link through Web Browser . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Login into Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Web Pages Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Basic Commissioning of Wireless Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Advanced Commissioning of Wireless Devices with Web Pages . . . . . . . . . . . . . . . . . . . . . 44
Wireless Network Configuration with Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Wireless Device Configuration with Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Chapter 7 Acti9 PowerTag Link Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
7.1 Acti9 PowerTag Link General Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Date/Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Time Zone Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
7.2 Ethernet Communication of the Acti9 PowerTag Link with Web Pages . . . . . . . . . . . . . . . . 55
Ethernet Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
IP Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
IP Network Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
7.3 Email Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Chapter 8 Acti9 PowerTag Link Security. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Modbus TCP/IP Filtering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
User Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Chapter 9 Load Monitoring and Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Load Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Status Monitoring and Load Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Chapter 10 Energy Management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Energy Counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Active Power Demand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

DOCA0157EN-01 07/2019 3
Chapter 11 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
About Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Alarms Output Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Voltage Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Current Overload at Voltage Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Communication Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Overload 80% . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Overload 50% . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Overload 45% . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Zero Current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Under Voltage (80%) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Load Operating Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Over Voltage (120%) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Partial Active Energy Delivered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Current I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Voltage V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Total Active Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Power Factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Chapter 12 Modbus Registers Tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Modbus Table Format and Data Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
System Modbus Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Wireless Devices Modbus Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Chapter 13 Diagnostics and Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
13.1 Monitoring and Diagnostics Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
General Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Communication Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
13.2 Reset of Acti9 PowerTag Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
13.3 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Common Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Description of Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Description of Ethernet Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Description of Wireless Status LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Appendix A Appendix Details of Modbus Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Modbus TCP/IP Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Modbus TCP/IP Exception Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Function 8: Modbus Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Function 43-14: Read Device Identification (Basic) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Function 43–15: Read Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Function 43-16: Write Date and Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Function 100–4: Read Non-Adjacent Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139

4 DOCA0157EN-01 07/2019
Safety Information

Important Information

NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before
trying to install, operate, service, or maintain it. The following special messages may appear throughout
this documentation or on the equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.

PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this
material.
A qualified person is one who has skills and knowledge related to the construction and operation of
electrical equipment and its installation, and has received safety training to recognize and avoid the
hazards involved.

DOCA0157EN-01 07/2019 5
6 DOCA0157EN-01 07/2019
About the Book

At a Glance

Document Scope
The purpose of this manual is to provide users, installers, and maintenance personnel with the technical
information necessary to install and use the Acti9 PowerTag Link communication system.

Validity Note
The Acti9 PowerTag Link communication system can be easily integrated into any building management
architecture.
It combines monitoring and metering and protection functions designed for energy efficiency solutions.
Based on the Modbus protocol, the Acti9 PowerTag Link communication system allows switchboards and
busbar truncking systems data to be exchanged in real time with a supervision system or a PLC.
This system's pre-wired cables can save time and prevent wiring errors during installation.

Related Documents

Title of Documentation Reference Number


Instruction Sheet for the Acti9 PowerTag Link PHA81113
(English, Dutch, French, German, Italian, Portuguese, Spanish, Chinese, Russian)
Instruction Sheet for the PowerTag Acti9 M63 Wireless Communication Energy EAV31628_web
Sensors
(English, Dutch, French, German, Italian, Portuguese, Spanish, Chinese, Russian)
Instruction Sheet for the PowerTag Acti9 P63 Wireless Communication Energy QGH78639
Sensors
(Chinese, Dutch, English, French, German, Italian, Portuguese, Romanian,
Russian, Spanish)
Instruction Sheet for the PowerTag Acti9 F63 Wireless Communication Energy QGH78642
Sensors
(Chinese, Dutch, English, French, German, Italian, Portuguese, Romanian,
Russian, Spanish)
Instruction Sheet for the PowerTag NSX Wireless Communication Energy Sensor QGH46815
for Compact NSX100-250, Compact NS100-250, Compact INS250, Compact
INV100-250
(Chinese, English, French, German, Italian, Portuguese, Russian, Spanish)
Instruction Sheet for the PowerTag NSX Wireless Communication Energy Sensor QGH46820
for Compact NSX400-630, Compact NS400-630, Compact INS320-630, Compact
INV320-630
(Chinese, English, French, German, Italian, Portuguese, Russian, Spanish)
EcoStruxure Power Commission Installation Guide DOCA0134EN
(English)

You can download these technical publications and other technical information from our website at
https://www.schneider-electric.com/en/download

DOCA0157EN-01 07/2019 7
8 DOCA0157EN-01 07/2019
Acti9 PowerTag Link
Acti9 PowerTag System
DOCA0157EN-01 07/2019

Chapter 1
Acti9 PowerTag System

Acti9 PowerTag System

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Overview 10
Acti9 PowerTag Link 12
Wireless Communication Devices 13

DOCA0157EN-01 07/2019 9
Acti9 PowerTag System

Overview

Introduction
The Acti9 PowerTag system is used to monitor the electrical distribution installation through any
supervision system.
Wireless devices in the Acti9 PowerTag system are used to monitor, and measure the electrical
switchboards and busbar trunking systems via a Modbus TCP/IP communication network.
The Acti9 PowerTag system collects the data from electrical switchboards and busbar trunking systems in
real time, thus contributing to achieve energy efficiency targets or monitoring final loads.
This system consists of:
 Acti9 PowerTag Link
 PowerTag energy sensors (PowerTag Acti9 M63 (for iC60 offer), PowerTag Acti9 P63 (for DT40 and
iC40 offers), PowerTag Acti9 F63 (for other devices such as VigiBlock and specific installations).
 PowerTag NSX energy sensors (for Compact NSX, Compact INS, Compact INV).

This system offers the following advantages and services:


 Telemetering applications.
 Load unbalance monitoring.
 Power and voltage loss monitoring.

 Energy management and regulations.


Acti9 PowerTag Link is a wireless gateway that exposes over TCP/IP all the Modbus registers of metering
and monitoring data to any supervision system.

Acti9 PowerTag System Architecture Diagram

10 DOCA0157EN-01 07/2019
Acti9 PowerTag System

Acti9 PowerTag Link also manages web pages in order to configure settings or to monitor the wireless
devices.

WARNING
POTENTIAL COMPROMISE OF SYSTEM AVAILABILITY, INTEGRITY, AND CONFIDENTIALITY
 Change the default passwords to help prevent unauthorized access to device settings and information.
 Disable unused ports or services and default accounts to minimize pathways for malicious attackers.
 Place networked devices behind multiple layers of cyber defenses (such as firewalls, network
segmentation, and network intrusion detection and protection).
 Use cyber security best practices (for example, least privilege, separation of duties) to help prevent
unauthorized exposure, loss, or modification of data and logs, or interruption of services.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

DOCA0157EN-01 07/2019 11
Acti9 PowerTag System

Acti9 PowerTag Link

Acti9 PowerTag Link Acting as a Gateway


The wireless communication devices provide compact and high density metering solution with rich and
accurate data for building systems (that can send energy, power, current, voltage, temperature and power
factor to Acti9 PowerTag Link concentrator).
You can configure:
 up to 20 wireless communication devices with PowerTag Link reference A9XMWD20.
 up to 100 wireless communication devices with PowerTag Link reference A9XMWD100 and up to 20
PowerTag Control devices among them.
The Acti9 PowerTag Link provides monitoring of the switchboard and busbar trunking via embedded web
pages for local access.

Description

A Power supply connector 110-230 Vac


B Default IPv4 address
C Communication status indicators
D Reset button
E RJ45 Ethernet connection

12 DOCA0157EN-01 07/2019
Acti9 PowerTag System

Wireless Communication Devices

Description
Wireless communication devices that can be connected to the Acti9 PowerTag Link are listed as follows:
 A9MEM15xx
 LV43402x

Refer to the PowerTag Selection Guide:


https://www.schneider-electric.com/en/download/document/CA908058E

Principle of Wireless Device Installation


The Acti9 PowerTag Link is installed in such a manner that the Wireless communication devices are
distributed around the gateway. It is recommended to install the Acti9 PowerTag Link in the center of the
switchboard. The distance between the wireless communication devices and the gateway should be
smaller than 3 meters.
NOTE: There is a possibility of disruption in the RF signal quality if wireless communication devices are
installed in a different switchboard (particularly if the enclosure has metallic partitions and door).

Maximum Number of Wireless Communication Devices in an Electrical Room


The wireless network configuration is used for special applications like data centers and high density
metering applications. In standard building applications, use the default settings.
For high density applications, thousands of wireless communication devices are placed in the same
environment. Therefore, it is necessary to consider radio frequency plan and bandwidth. For an installation
with multiple gateways, it is recommended to assign a dedicated and different channel to each gateway.
To increase the radio quality, you can adjust the communication period from 5 seconds (default) to 60
seconds.
For any installation with more than 400 wireless devices, please consult us for a detailed study of the RF
plan.
Any modification to the communication period has to be done after the commissioning of the wireless
communication devices is completed to avoid slowdown of the commissioning process.
NOTE: Modification in communication period does not slowdown the alarms. The voltage loss is sent
immediately. The communication period is used to send regular metering data (P, U, I, E, PF), and alarms
are sent immediately.
NOTE:
 The radio channel is chosen in the wireless settings of Acti9 PowerTag Link via the web pages and is
applied to all the wireless communication devices that are commissioned with Acti9 PowerTag Link.
 An Acti9 PowerTag Link device can manage.
 up to 20 wireless communication devices with PowerTag Link reference A9XMWD20.
 up to 100 wireless communication devices with PowerTag Link reference A9XMWD100, and up to
20 PowerTag Control devices among them.
 A set of Acti9 PowerTag Link devices has to be installed and commissioned to concentrate all the
needed Wireless communication devices.

DOCA0157EN-01 07/2019 13
Acti9 PowerTag System

14 DOCA0157EN-01 07/2019
Acti9 PowerTag Link
Technical Characteristics
DOCA0157EN-01 07/2019

Chapter 2
Technical Characteristics

Technical Characteristics

Technical Characteristics of the Acti9 PowerTag Link

Main Characteristics

Characteristic Value
Supply voltage Us 110/230 V AC ± 20 %, 2 A
Frequency 50/60 Hz
Power consumption 5 VA
Communication interface Ethernet 10/100 BASE-T, Cable length ≤ 100 m Cat.6 STP
maximum number of wireless devices Up to 20 sensors for PowerTag Link
Up to 100 sensors for PowerTag Link HD
Automatic IP configuration DHCP client (Ethernet port)
Local indication Product state Green, orange and red LED
Ethernet state (LAN ST) Green, orange and red LED
Overvoltage category III
Radio-frequency communication ISM band 2.4 GHz 2.4 GHz to 2.4835 GHz
Degree of protection(IEC 60068-2-30) Device only IP20
Device in modular enclosure IP40
Insulation class II
Fire resistance 650°C, 30 s
Environment In compliance with the RoHS directive REACH Regulations

Additional Characteristics

Characteristic Value
Operating temperature -25°C to +60°C
Storage temperature -40°C to +85°C
Pollution degree 2
Tropicalization (IEC 60068-2-30) Treatment 2 (relative humidity of 93% at 40°C)
Operating altitude 0 to 2000 m
Electromagnetic compatibility Reference standards
Immunity EN 55035
Emissions EN 55032
Electromagnetic compatibility EN 300328
and Radio spectrum Matters EN 301489-1
(ERM) EN 301489-17

Mechanical Characteristics

Characteristic Value
Dimensions Length 359 mm
Height 22.5 mm
Depth 42 mm
Weight 180 g

DOCA0157EN-01 07/2019 15
Technical Characteristics

16 DOCA0157EN-01 07/2019
Acti9 PowerTag Link
Installation
DOCA0157EN-01 07/2019

Chapter 3
Installation of the Acti9 PowerTag Link

Installation of the Acti9 PowerTag Link

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Mounting 18
Wiring 20

DOCA0157EN-01 07/2019 17
Installation

Mounting

Introduction
The Acti9 PowerTag Link can be mounted on a DIN rail and can be also installed horizontally.
The ambient operating temperature is:
 Horizontal and vertical mounting: −25°...+60°C

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
 Turn off all power supply sources before installing and during maintenance of this equipment.
 This equipment is intended only for installation in a restricted access location.
 Always use a voltage detection device with an appropriate rated value to make sure that the power
supply is off
Failure to follow these instructions will result in death or serious injury.

18 DOCA0157EN-01 07/2019
Installation

DIN Rail Mounting

The following table describes the procedure for mounting the Acti9 PowerTag Link device on a DIN rail:

Step Action
1 Position the Acti9 PowerTag Link onto the DIN rail.
2 Slide the Acti9 PowerTag Link device until it clicks into place.

DOCA0157EN-01 07/2019 19
Installation

Wiring

Introduction
Protect Acti9 PowerTag Link with an Acti9 MCB rated 4A curve C with a cable length under 3 meters (in
accordance to IEC 60.364)

Safety Instructions

DANGER
RISK OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
 Wear suitable personal protective equipment and follow the currently applicable electrical safety
instructions.
 This equipment may only be installed by qualified electricians who have read all the relevant
information.
 NEVER work alone.
 Before performing visual inspections, tests, or maintenance on this equipment, disconnect all sources
of electric power. Assume that all circuits are live until they have been de-energized, tested, and
tagged. Pay particular attention to the design of the power system. Consider all power supply sources,
particularly the potential for backfeed.
 Before closing protective covers and doors, carefully inspect the work area to ensure that no tools or
objects have been left inside the equipment.
 Take care when removing or replacing panels. Take special care to ensure that they do not come into
contact with live Busbars. To minimize the risk of injuries, do not tamper with the panels.
 The successful operation of this equipment depends upon proper handling, installation, and operation.
Failure to follow basic installation procedures can lead to personal injury as well as damage to
electrical equipment or other property.
 NEVER shunt an external fuse/circuit breaker.
 This equipment must be installed inside a suitable electrical cabinet.
Failure to follow these instructions will result in death or serious injury.

Connecting the Power Supply Connector

The following table describes the procedure for connecting the power supply connector:

Step Action
1 Insert both stripped power supply wires in the connector.
2 Fix the wires in place using the connector tightening screws.

20 DOCA0157EN-01 07/2019
Installation

The following figure gives the characteristics of cables that can be used to connect the 230 Vac power
supply:

NOTICE
HAZARD OF EQUIPMENT DAMAGE
Plug the power-supply connector (Phase-Neutral) into the power-supply socket with marking N-L on the
Acti9 PowerTag Link product.
Failure to follow these instructions can result in equipment damage.

DOCA0157EN-01 07/2019 21
Installation

22 DOCA0157EN-01 07/2019
Acti9 PowerTag Link
Getting Started with Acti9 PowerTag Link
DOCA0157EN-01 07/2019

Chapter 4
General Principle to Commission an Acti9 PowerTag System

General Principle to Commission an Acti9 PowerTag System

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
4.1 Commissioning Overview 24
4.2 Pre-Requisites 27

DOCA0157EN-01 07/2019 23
Getting Started with Acti9 PowerTag Link

Section 4.1
Commissioning Overview

Commissioning Overview

What Is in This Section?


This section contains the following topics:
Topic Page
Overview 25
Ethernet Connection 26

24 DOCA0157EN-01 07/2019
Getting Started with Acti9 PowerTag Link

Overview

The commissioning of an Acti9 PowerTag Link system can be performed using:


 the EcoStruxure Power Commission (see Ecostruxure Power Commission Online Help).
 the Acti9 PowerTag Link web pages. The web pages are autonomous to configure any devices
connected or paired with Acti9 PowerTag Link.
NOTE:
 Before commissioning the Acti9 PowerTag Link device, update the firmware of the Acti9 PowerTag Link
device.
 The firmware upgrade of the Acti9 PowerTag Link device can only be done using the EcoStruxure
Power Commission. see Ecostruxure Power Commission Online Help.

DOCA0157EN-01 07/2019 25
Getting Started with Acti9 PowerTag Link

Ethernet Connection

Acti9 PowerTag Link has an embedded web server. A web server is used to set Ethernet parameters or to
display wireless devices configured with EcoStruxure Power Commission software or with webpages.

Step Action
1 Disconnect your computer from all your actions
2 Connect an Ethernet straight cable between your PC and the Ethernet port on the Acti9 PowerTag Link

26 DOCA0157EN-01 07/2019
Getting Started with Acti9 PowerTag Link

Section 4.2
Pre-Requisites

Pre-Requisites

What Is in This Section?


This section contains the following topics:
Topic Page
Installation of EcoStruxure Power Commission Software 28
Firmware Upgrade 29

DOCA0157EN-01 07/2019 27
Getting Started with Acti9 PowerTag Link

Installation of EcoStruxure Power Commission Software

Downloading and Installation


The EcoStruxure Power Commission software is available on www.se.com.

28 DOCA0157EN-01 07/2019
Getting Started with Acti9 PowerTag Link

Firmware Upgrade

Firmware Upgrade
The firmware upgrade of Acti9 PowerTag Link can only be done using the EcoStruxure Power Commission
software if the Acti9 PowerTag Link is not in the latest firmware version.

Firmware Compatibility
You can find a compatibility table Device Firmware Baseline in the Information menu of EcoStruxure Power
Commission software.

DOCA0157EN-01 07/2019 29
Getting Started with Acti9 PowerTag Link

30 DOCA0157EN-01 07/2019
Acti9 PowerTag Link
Getting Started with EcoStruxure Power Commission Software
DOCA0157EN-01 07/2019

Chapter 5
Getting Started with EcoStruxure Power Commission Software

Getting Started with EcoStruxure Power Commission Software

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Basic Commissioning of Wireless Devices with EcoStruxure Power Commission Software 32
Advanced Commissioning of Wireless Devices with EcoStruxure Power Commission Software 33
Wireless Devices Configuration with EcoStruxure Power Commission Software 34

DOCA0157EN-01 07/2019 31
Getting Started with EcoStruxure Power Commission Software

Basic Commissioning of Wireless Devices with EcoStruxure Power Commission Software

Overview
Follow the steps given in the table to commission the Acti9 PowerTag Link with EcoStruxure Power
Commission software:

Step Action
1 Connect the Acti9 PowerTag Link device to the PC.
2 Launch the EcoStruxure Power Commission software.
3 Click Launch Device Discovery in the welcome screen.
Result: Discover Device(s) window displays all the devices connected in the network.
4 Select the device in the list and click on Find Devices button on the bottom left hand corner to continue
Click on Add Devices button on the bottom left hand corner to add the Acti9 PowerTag Link to the new project.
Complete project details in next screens and finish by clicking on Continue button.
Result: A new project with the Acti9 PowerTag Link is created (switchboard view / communication view).
5 Click on Connect to Device button to connect. When connection is established, select the Configure option.
Result: Screen to discover wireless devices is displayed.
6 Click Scan to discover the PowerTag energy sensors.
Result: The discovered PowerTag energy sensor is displayed.
7 Click Locate to find the PowerTag energy sensor in an electrical panel
Result: The Locate Wireless Device dialog box is displayed and the associated PowerTag energy sensor on the electrical
panel continuously blinks green.
8 Click STOP BLINK to stop blinking of the device once it is identified.
9 Click the down arrow icon.
Result: The configuration parameters page is displayed.
10 Enter the label for the PowerTag energy sensor.
11 Enter the name of the asset (name of the load), where it is located in the building, in the Asset name field.
12 Select the usage of the load from the Usage list.
13 Select the circuit breaker rating from the Associate breaker rating (A) list to calculate the percentage of loads.
14 Select the phase sequence corresponding to the physical sequence wired in the panel from the Phase sequence list.
15 Load works when Power is >= (W) (kWh) by moving the slider left or right.
16 Download PowerTag pairing and filled information to Acti9 PowerTag Link by clicking on Write to Device button.
Result: Message “write to device successful” when finished.
17 Save Acti9 PowerTag Link settings in the project by clicking on Write to Device button.
Result: Message “write to project successful” when finished.

NOTE: In the EcoStruxure Power Commission software, any gateway such as Acti9 PowerTag Link is
defined as a "device".

32 DOCA0157EN-01 07/2019
Getting Started with EcoStruxure Power Commission Software

Advanced Commissioning of Wireless Devices with EcoStruxure Power Commission Software

It is possible to achieve an advanced commissioning using EcoStruxure Power Commission software. For
further details, refer Ecostruxure Power Commission Online Help.

DOCA0157EN-01 07/2019 33
Getting Started with EcoStruxure Power Commission Software

Wireless Devices Configuration with EcoStruxure Power Commission Software

Introduction
It is possible to configure the PowerTag energy sensors of Acti9 PowerTag Link using EcoStruxure Power
Commission software. For further details, refer Ecostruxure Power Commission Online Help.

34 DOCA0157EN-01 07/2019
Acti9 PowerTag Link
Getting Started with Web Pages
DOCA0157EN-01 07/2019

Chapter 6
Getting Started with Web Pages

Getting Started with Web Pages

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Discovering Acti9 PowerTag Link through Web Browser 36
Login into Web Pages 38
Web Pages Layout 39
Basic Commissioning of Wireless Devices 40
Advanced Commissioning of Wireless Devices with Web Pages 44
Wireless Network Configuration with Web Pages 45
Wireless Device Configuration with Web Pages 47

DOCA0157EN-01 07/2019 35
Getting Started with Web Pages

Discovering Acti9 PowerTag Link through Web Browser

Accessing Acti9 PowerTag Link from Windows Operating System


Follow the steps given in the table to access the web page of Acti9 PowerTag Link through Windows
Explorer from Windows operating system:

Step Action
1 Open the Windows Explorer and click Network to display the Acti9 PowerTag Link icon in the list of devices, this may take up
to 2 minutes after device power on. (if the Acti9 PowerTag Link icon does not appear, change the PC settings as given in the
note below).
2 Double-click the Acti9 PowerTag Link icon. This launches the login page automatically in the web browser.
3 Type the user name (“admin” by default) and password (“admin” by default).
NOTE: These identifiers are case-sensitive.
4 Click OK.

The following figure shows the Windows Explorer screen without the discovery of Acti9 PowerTag Link.

36 DOCA0157EN-01 07/2019
Getting Started with Web Pages

The following figure shows the Windows Explorer screen after the discovery of Acti9 PowerTag Link.

If Acti9 PowerTag Link IPV4 is in DHCP mode, the computer must also be in DHCP mode. If Acti9
PowerTag Link uses a static IP, the computer must also use a static IP and Network setting (Subnet mask),
and must be the same for both devices (for example, factory IP settings).
In the configuration panel of Windows, click the local network properties and change the IPv4 settings.

Step Action
1 Right-click the Network icon located at the bottom-right corner of the Desktop screen then click Open Network and Sharing
Center.
2 Click Change adapter settings, then right-click on the Local Area Connection icon and click Properties.
3 Select Internet Protocol Version 4 (TCP/IPv4) from the list and click Properties.
4 Select Obtain an IP address automatically and click OK.

Accessing Acti9 PowerTag Link from the Operating System other than Windows
Follow the steps given in the table to access the web page of Acti9 PowerTag Link from the operating
system other than Windows:

Step Action
1 Launch the Internet browser.
2 Type the IPv4 address (encoded into the data matrix on the upper side of Acti9 PowerTag Link) in the Address field of the web
browser and press Enter to access the login page.
3 Type the User name (“admin” by default) and Password (“admin” by default).
NOTE: These identifiers are case-sensitive.
4 Click OK.

DOCA0157EN-01 07/2019 37
Getting Started with Web Pages

Login into Web Pages

Login Page
The Login page is used to enter the user credentials and select the preferred language to access Acti9
PowerTag Link web pages. When the user connects to the Acti9 PowerTag Link through a web browser,
the Login page is displayed as shown in the following figure.

Enter the following details in the Login page:


 Language
 User name
 Password

Enter the user name and password to access the web pages related to Acti9 PowerTag Link. The default
user name and password is admin to access the web page for the first time. You can select the language
in the Login page so that all the pages are displayed in the selected language.
The top right corner of all the web pages displays the following information:
 User name
 Logout

The Logout link is used to logout of the Acti9 PowerTag Link web page.

38 DOCA0157EN-01 07/2019
Getting Started with Web Pages

Web Pages Layout

Description
The web pages can be used for two main operations:
 Monitoring page allows to check the health of the electrical devices (such as HVAC, lighting, pumps,
machines, and so on).
 Gateway settings allows
 setting of Ethernet parameters and wireless devices parameters.
 diagnosis of exchanges on Ethernet network.
 adding or removing wireless devices connected to the gateway.
 management of time setting and time zone selection.
 IP configuration and IP services
 IP filtering
 configuration of email accounts
 management of user accounts
 alarm configuration

The administration part of the web pages allows the system integrators commission the Acti9 Powertag
system.
Web pages are accessible to the following three categories of user:
 Administrator can access all information and modify the parameters in the Settings menu.
 Operator can access monitoring pages of the connected devices and get access to Diagnostic menu.
 Guest can access only Monitoring menu.

The scope of products supported in the web pages are:


 Acti9 PowerTag Link
 Wireless devices

Web Page Organization

1. Displays the measurements and alarms associated to the devices.


2. Communication diagnostics
3. Wireless network configuration
 concentrator settings
 wireless devices commissioning (pairing and configuration)
 alarm settings

DOCA0157EN-01 07/2019 39
Getting Started with Web Pages

Basic Commissioning of Wireless Devices

Principle of Wireless Device Commissioning


The principle of wireless device commissioning consists of two steps:
 Pairing the wireless devices withe the concentrator
 Configuring the wireless devices

Commissioning the Wireless Communication Devices


The configuration of the wireless communication devices is done with Acti9 PowerTag Link web page.

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Settings → Devices → Wireless Devices.
4 Pairing process principle: When the scanning process is running, the gateway discovers the wireless devices located in the
environment, in the order of their appearance in the RF network. The gateway assigns a virtual Modbus address respecting the
order of appearance. If you define and upload a white list, the gateway will only pair the wireless devices belonging to the
defined white list.
Pairing process options are:
a Free Pairing
Recommended when:
 no particular Modbus address plan is required.
 pairing a reduced number of wireless devices (up to 20).

Initial state: All devices are powered ON. Click Start Scanning.

Stop scanning when all devices are discovered, or click Start scanning again to complete the scanning process.
Result: A list of paired devices are displayed.

40 DOCA0157EN-01 07/2019
Getting Started with Web Pages

Step Action
b Controlled Pairing
Recommended when:
 a Modbus address plan shall be followed.
 pairing a large number of wireless devices (more than 20.)

Applicable when:
 the wireless devices can be individually powered.
 the wireless devices are installed downstream the related circuit breaker.

Initial state:
 All PowerTag are powered OFF

Click Start Scanning.

Power on the wireless devices, one by one, respecting the required order.

Stop scanning when all the devices are discovered, or click Start Scanning again to complete the scanning process.
A list of paired devices are displayed, according to the required order (Modbus address plan). Note: Modbus address
can be changed after pairing process is done.
NOTE: Modbus address can be changed after completing the of pairing process.
5 Select the wireless device to configure and click Locate to find the device in the panel.
Result: The associated device blinks in the panel.
6 If one of the located wireless device is not part of your selection, click Delete to reject the device.

DOCA0157EN-01 07/2019 41
Getting Started with Web Pages

Step Action
7 Configure the associated device as below:

NOTE: If you have multiple panels and if each panel has PowerTag energy sensors, then it is
recommended to switch on power and commission each Acti9 PowerTag Link one by one if possible. This
helps to discover only the required wireless communication devices specific to each Acti9 PowerTag Link
and avoids discovering the long list of devices.
If other Acti9 PowerTag Link devices are powered on while you commission a new Acti9 PowerTag Link,
the new Acti9 PowerTag Link automatically selects the less polluted radio channel, and creates its network
on a different channel than the previous Acti9 PowerTag Link devices. This avoids having all the PowerTag
energy sensors on the same radio channel.

42 DOCA0157EN-01 07/2019
Getting Started with Web Pages

However, if all panels are powered on and commissioned simultaneously, then locate only the required
PowerTag energy sensors in multiple panels and reject the ones you do not want to configure with the
panel currently commissioned. All the rejected PowerTag energy sensors can be auto-discovered again
from another Acti9 PowerTag Link without any issues.

DOCA0157EN-01 07/2019 43
Getting Started with Web Pages

Advanced Commissioning of Wireless Devices with Web Pages

Step Action
1 In excel, create a csv file with separators containing the RF-id of the wireless devices you want
to pair with the gateway. For example, as shown in the following excel screenshot, RF-id shall
be listed in the first column of the csv file, and the first row shall be dedicated to the description
of the column.

2 Login to the webpage (see page 38).


3 Navigate to Settings → Communication → Wireless Network Configuration.
4 If specified in the radio frequency plan, choose the right communication channel in the
Communication tab.
5 Navigate to Settings → Devices → Wireless Devices → Selective Wireless Device Scanning.
6 Import the csv file.

Result: A confirmation message is displayed.

7 Refer to step 4 in Commissioning the Wireless Communication Devices (see page 40).

44 DOCA0157EN-01 07/2019
Getting Started with Web Pages

Wireless Network Configuration with Web Pages

Overview
The wireless network configuration is used for special applications like data centers and high density
metering applications. In standard building applications, use the default settings.
For high density applications, thousands of wireless communication devices are placed in the same
environment. Therefore, it is necessary to consider the radio frequency plan and bandwidth. For an
installation with multiple gateways, it is recommended to assign a dedicated and different channel to each
gateway. To increase the radio quality, you can adjust the communication period from 5 seconds (default)
to 60 seconds. For any installation with more than 400 wireless devices, please consult us for a detailed
study of the radio frequency plan.
Any modification to the communication period has to be done after the commissioning of the wireless
communication devices is completed to avoid slowdown of the commissioning process.
NOTE: Modification in communication period does not slowdown the alarms. The voltage loss is sent
immediately on demand. The communication period is used to send regular metering data (P, U, I, E, PF),
not voltage loss alarms.
NOTE:
 The radio channel is chosen in the wireless settings of Acti9 PowerTag Link and is applied to all the
wireless communication devices that are commissioned with Acti9 PowerTag Link.
 A set of Acti9 PowerTag Link devices has to be installed and commissioned to concentrate all the
needed Wireless communication devices.
NOTE: The communication period of thermal sensors is different. Please contact Schneider Electric for
more information.

DOCA0157EN-01 07/2019 45
Getting Started with Web Pages

Wireless Network Configuration with Webpages


The Wireless Network Configuration web page is used to configure wireless parameters (only with
administrator credentials).

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Settings → Communication → Wireless Network Configuration.

This page allows you to:


 select the wireless channel either automatically or manually. Click Automatic Selection of the Best
Channel to select the channel automatically.
Follow the procedure to configure wireless parameters in the manual mode:

Step Action
1 Select the required channel from the Channel list. The default channel is Channel 11.
2 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.

 define the communication period which defines the amount of time each PowerTag sends its data to the
Acti9 PowerTag Link. This step has to be done after commissioning.
Follow the procedure to define the communication period:

Step Action
1 Select the required communication period from the Communication Period list.
Default period: 5 seconds
2 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.
3 define the communication period which defines the amount of time each PowerTag sends its data to the Acti9 PowerTag Link.
This step has to be done after commissioning.

46 DOCA0157EN-01 07/2019
Getting Started with Web Pages

Wireless Device Configuration with Web Pages

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Settings → Devices → Wireless Devices.

Step Action
1 Click Start Scanning to discover the wireless devices connected to the Acti9 PowerTag Link.
Result: Displays the discovered wireless devices and allocates Modbus address to each device.
2 Select any wireless device and click the pencil icon to modify the configuration of the selected wireless device.
3 Enter the Asset Name of a wireless device.
4 Enter the Label of a wireless device
5 Select the Usage from the drop-down list.
6 Select the phase sequence for the wireless device from the Phase Sequence. You can define 1, 2, or 3 phase sequence of the
meter depending on the way the physical panel is wired (from left to right).
7 Select the Mounting Position as either Up or Down when applicable.
8 Select the breaker rating from the Associate Breaker Rating (A) list to calculate the percentage of loads.
9 If requested, enter the value for the energy counter in the Partial Energy area. Click Reset or enter the value as 0 to reset the
partial energy counter.
10 Load Operating Time Counter (hours): The Load Operating Time counter indicates the running operating time of the load in hours.
The load is powered and power flows to/from the load above the set threshold. The default value in this field is 0. You can set this
between 0 to 1000000 hours.
11 Load work when Power is >=: The Load Operating Time counter increments only when this condition (the power is greater or
equal to (>/=)) is met. You can set the value between 10W to 15000W.
12 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.

NOTE: It is recommended to create a backup file saved on your laptop using the backup function available
in the Maintenance menu of the webpage. The file will be automatically saved under the name
“backup.dat”. It will be used in case of disfunction and replacement of the gateway.
NOTE: Thermal sensors are only proposed through Schneider Electric service offer.

DOCA0157EN-01 07/2019 47
Getting Started with Web Pages

48 DOCA0157EN-01 07/2019
Acti9 PowerTag Link
Acti9 PowerTag Link Settings
DOCA0157EN-01 07/2019

Chapter 7
Acti9 PowerTag Link Settings

Acti9 PowerTag Link Settings

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
7.1 Acti9 PowerTag Link General Settings 50
7.2 Ethernet Communication of the Acti9 PowerTag Link with Web Pages 55
7.3 Email Service 59

DOCA0157EN-01 07/2019 49
Acti9 PowerTag Link Settings

Section 7.1
Acti9 PowerTag Link General Settings

Acti9 PowerTag Link General Settings

What Is in This Section?


This section contains the following topics:
Topic Page
Identification 51
Date/Time 52
Time Zone Page 54

50 DOCA0157EN-01 07/2019
Acti9 PowerTag Link Settings

Identification

Identification

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Settings → General → Identification.

The Identification page is used to edit the gateway name and it displays the following parameters:

Parameters Description
Gateway Identification
User Application Name You can customize the name of the gateway used by communication services.
Product Range Displays the product range name of the gateway.
Product Model Displays the product model name of the gateway.
Serial Number Displays the serial number of the gateway.
Firmware Revision Displays the firmware version number of the gateway.
Unique identifier Displays the identifier used by communication protocols.
Webpage Version Displays the web page version of the gateway.

Building Information
Building Name You can customize the name of the gateway place inside the building.

The Device Name is same as the name displayed in Windows explorer.


NOTE: The Device Name should contain only alphanumeric characters and a hyphen (-) character. The ‘-
’ character cannot be the last character.
Click Apply Changes to save the changes. Click Cancel Changes to revert the settings.

DOCA0157EN-01 07/2019 51
Acti9 PowerTag Link Settings

Date/Time

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Settings → General → Date/Time.

Manual mode
The Date/time page is used to set date and time and SNTP parameters as shown in the following figure:

NOTE: After any gateway power shut down, the gateway will reset to a default value of date and time. The
default date and time value is 2000/1/1, 00:00:00.
You can reset the date and time manually or automatically.
Follow the procedure to reset the date and time in Manual mode:

Step Action
1 Select Manual.
2 Enter the Date to be set in the format yyyy-mm-dd.
3 Enter the Time in the format hh:mm:sec.
4 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.

Follow the procedure to reset the date and time in Automatic mode:

Step Action
1 Select Network Synchronization via SNTP/NTP to configure the date and time automatically via SNTP/NTP.
Or
Select Network Synchronization via Modbus TCP to configure the date and time via Modbus TCP.
2 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.

SNTP Mode
Network Time Protocol (NTP) is a networking protocol for clock synchronization between computer
systems over packet-switched, variable-latency data networks.
A less complex implementation of NTP, using the same protocol without the storage of state over extended
periods of time is known as the Simple Network Time Protocol. It is used in embedded devices and in
applications where high accuracy timing is not required.
When automatic time configuration is selected and NTP servers are configured, the Acti9 PowerTag Link
can communicate with NTP and server to synchronizes its time.
The Acti9 PowerTag Link supports time synchronization with remote server using SNTP. When SNTP is
activated, time synchronization from one of the selected time servers can be achieved at every configured
interval and also supports Modbus time services Get Date-Time (function code 43-15) and Set Date-Time
(function code 43-16). The time is configured in 24-hour format.

52 DOCA0157EN-01 07/2019
Acti9 PowerTag Link Settings

Automatic Mode with SNTP Service


The Acti9 PowerTag Link receives date and time from SNTP server after every poll interval time. Follow
the procedure to configure date and time using SNTP/NTP parameters:

Step Action
1 Enter the value for Poll Interval in hours that ranges from 1 through 63. The default value of poll interval is 1.
2 Select Obtain SNTP/NTP Servers Automatically via DHCP/BOOTP to obtain the server address automatically from SNTP or NTP
servers.
3 Select Manual.
4 Enter the primary server name or IP address for Primary SNTP/NTP Server parameter.
The primary server can be:
 IPv4 address
 IPv6 address
 Domain name

5 Enter the secondary server name or IP address for Secondary SNTP/NTP server parameter. This is an optional parameter.
6 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.

DOCA0157EN-01 07/2019 53
Acti9 PowerTag Link Settings

Time Zone Page

Time Zone

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Settings → General → Time Zone.

The Time Zone page is used to configure the offset and daylight saving time for the selected time zone.

Follow the procedure to configure time zone settings:

Step Action
1 Click the offset value used by the local time zone from the Time Zone Offset list.
2 Select the Enable check box to configure the daylight time saving settings. The Enable check box is not selected by default.
3 Select the day, month, and time to configure the start time of daylight saving time from the respective Daylight Saving Time Begins
list.
4 Select the day, month, and time to configure the end time of daylight saving time from the Daylight Saving Time Ends list.
5 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.

54 DOCA0157EN-01 07/2019
Acti9 PowerTag Link Settings

Section 7.2
Ethernet Communication of the Acti9 PowerTag Link with Web Pages

Ethernet Communication of the Acti9 PowerTag Link with Web


Pages

What Is in This Section?


This section contains the following topics:
Topic Page
Ethernet Settings 56
IP Configuration 57
IP Network Services 58

DOCA0157EN-01 07/2019 55
Acti9 PowerTag Link Settings

Ethernet Settings

Description
The Ethernet page is used to configure the frame format and speed and mode of the Ethernet port. This
page also displays the MAC address of the Ethernet network.

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Settings → Communication → Ethernet.

Follow the procedure to configure Ethernet parameters:

Step Action
1 Select the type of Ethernet frame format from the Frame Format list. It can be Ethernet II, 802.3, or Auto. The default value of the
frame format is Auto.
2 Select the value for speed and mode of the Ethernet port from the Speed and Mode list.
The value of speed and mode can be one of the following:
 10 Mbps - Half duplex
 10 Mbps - Full duplex
 100 Mbps - Half duplex
 100 Mbps - Full duplex
 Auto-negotiation

The default value is Auto-negotiation.


3 Click Apply Changes and then click Reboot to automatically restart the device to save the settings. Click Cancel Changes to revert
the settings.

56 DOCA0157EN-01 07/2019
Acti9 PowerTag Link Settings

IP Configuration

Description
The IP Configuration page is used to configure IPv4, IPv6, and DNS parameters.

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Settings → Communication → IP Configuration.

IPv4 parameters can be set either in manual mode or in automatic mode. To configure IPv4 parameter in
automatic mode, click Automatic and select the type of protocol (DHCP or BOOTP) from the list. The
default type is DHCP protocol.
DHCP mode is used to acquire the IPv4 address from the DHCP server in the network to which Acti9
PowerTag Link is connected. BOOTP mode is used to acquire the IPv4 address if DHCP server is not
present in the network. A BOOTP server is configured in the network to assign the IPv4 address.
Follow the procedure to configure IPv4 parameters in the manual mode:

Step Action
1 Select Manual.
2 Enter the IPv4 Address of the device.
3 Enter the Subnet Mask of the device.
4 Enter the address of the Default Gateway.
5 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.

Follow the procedure below to configure IPv6 parameters:

Step Action
1 Select the Enable check box to enable the IPv6 service. The Enable check box is selected by default.
2 Display the value of the IPv6 Link Local Address. You cannot modify this parameter.
3 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.

The Acti9 PowerTag Link can acquire the domain name automatically or you can set the DNS server
address manually. Click Obtain DNS Servers Automatically via DHCP/BOOTP to acquire the DNS server
automatically from the network.
Follow the procedure below to configure DNS parameters in manual mode:

Step Action
1 Select Manual.
2 Enter the Primary DNS Server of the device.
3 Enter the Secondary DNS Server of the device.
4 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.

DOCA0157EN-01 07/2019 57
Acti9 PowerTag Link Settings

IP Network Services

Description
The IP Network Services page is used to configure the network protocols and discovery services.

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Settings → Communication → IP Network Services.

The Acti9 PowerTag Link supports HTTP, Modbus/TCP, DNS, SNTP, and discovery services.
The default value of the HTTP port number is 80.
Follow the procedure to configure Modbus/TCP parameters:

Step Action
1 Select the Enable check box to enable the Modbus/TCP service. The Enable check box is selected by default.
2 Display the port number of the Modbus/TCP network. The default value is 502.
3 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.

Follow the procedure to configure discovery services:

Step Action
1 Select the Enable check box to enable the discovery service. The Enable check box is selected by default.
2 Select the Silent Mode check box. The Silent Mode check box is selected by default.
3 Display the port number of the discovery network. The default value is 5357.
4 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.

Display the port value of the DNS and SNTP network. The default value of the port number is 53 and 123
respectively.

58 DOCA0157EN-01 07/2019
Acti9 PowerTag Link Settings

Section 7.3
Email Service

Email Service

Description

The event notification is used to send emails when the wireless devices trigger an alarm. The alarms are
configured by the administrator and can be sent to many users.
NOTE: Check your IT policies/administrator to get the right IT connection (port, LAN connection to Internet,
and email server to use).
The event notifications should not be used if email services are managed internally by a customer IT
domain administrator.
The Email Service page is used to configure the email server settings.

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Settings → Communication → Email Service.

Click the Enable check box to configure the email server settings (enabled by default). Acti9 PowerTag
Link allows you to define your own SMTP server.
Follow the steps given in the table to configure the email server settings:

Step Action
1 Enter the email server name or IP address in the SMTP Server Address area.
2 Select the type of security mode from the Connection Security Mode list.
The following are the available connection security modes:
 None
 TLS/SSL
 STARTTLS

3 Enter the server port value in the SMTP Server Port area. The value ranges from 1 to 65535.
4 Select Authentication if the server requires login information. This option is disabled by default.
5 Enter the user name in the SMTP Account Login area.
6 Enter the password to authenticate the SMTP login in the SMTP Account Password area.

DOCA0157EN-01 07/2019 59
Acti9 PowerTag Link Settings

Step Action
7 Enter the email address of the administrator who is administering the gateway in the From Address area.
The From Address can be used in different ways:
 Use the From Address as a context provider: If you want to notify and does not want to receive a reply, use a From Address
as contextual information. The From Address syntax includes “no-reply”, “gateway name”, “site name”, @a validated domain
.com, .net, and so on.
 Create an alias in the From Address to allow replies to be sent to the person in charge of an alarm: An email can be sent to
multiple people who are responsible for a specific appliance. This feature allows the receivers to reply to follow up with the
responsible person.
For example, if the facility manager receives an email from an alarm, the facility manager can send a reply email to the
Maintenance Contractor to follow up on the action.
8 Select the language of the email body from the Language list: French or English
9 Click Apply Changes to save the settings. If you do not want to save the changes, click Cancel Changes.
10 Enter the email address of the recipient to test the delivery of the email in the Recipient Address for Test area.
The test email feature enables connection from the gateway to the service. If the test emails are not received, the Internet
connection needs to enable the email ports (port 25 or 587). The port settings are configured in accordance between the gateway
that sends the email and the site router settings.
11 Click Test to deliver the email to the added recipient.

60 DOCA0157EN-01 07/2019
Acti9 PowerTag Link
Acti9 PowerTag Link Security
DOCA0157EN-01 07/2019

Chapter 8
Acti9 PowerTag Link Security

Acti9 PowerTag Link Security

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Modbus TCP/IP Filtering 62
User Management 63

DOCA0157EN-01 07/2019 61
Acti9 PowerTag Link Security

Modbus TCP/IP Filtering

Description
The Modbus TCP/IP filtering is a security feature that lists the IP addresses that the gateway can accept.
This function is used only with Ethernet static addressing mode. This page is used to configure the IP
address in order to enable write access.

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Settings → Communication → Modbus TCP/IP Filtering.

Follow the procedure to configure the IP address to enable write access:

Step Action
1 Select the Enable Modbus TCP/IP Filtering check box.
2 Click Add exception to add the IP address and access level. A maximum of 10 IP address can be added. The IP address added
has a write access.
3 Enter the IP address in the IP Address/Range area and select the Access level for the entered IP address.
4 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.

NOTE: You can only edit the global IP address range, but you cannot delete the global IP address range.
You can edit and delete the added exceptions.

62 DOCA0157EN-01 07/2019
Acti9 PowerTag Link Security

User Management

Users Accounts Page


The User Management is used to manage the user profiles. The Users Accounts page displays the existing
user accounts. This page is used to add a new user account and edit the password of the existing user
account.
NOTE: The email associated to each declared user is significant, as it is used during an alarm creation to
send an email if there is an occurrence of an alarm.
The following table lists the three types of user account supported by Acti9 PowerTag Link and their access
rights:

User Accounts Access


Administrator Access all information and modify the parameters in the Settings menu.
Operator Access monitoring pages of the connected devices and get access to diagnostic menu.
Guest Access only monitoring pages

One administrator account and one guest account are the first level of access to the web page by default.
The number of user accounts at administrator level is up to XX, at operator level is up to YY, and at guest
level is up to ZZ.
Follow the steps given in the table to create more accounts:

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Settings → User Management → User Accounts.

Follow the procedure to add a new user profile:

Step Action
1 Click Add User.
2 Enter the authentication information in the Username and Password area for a user.
3 Select the type of user from the Role list.
4 Enter the email of the user in the Email area.
5 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.

The Username and Password must meet the following criteria:


 The Username must have minimum of four characters.
 The Username must not exceed 16 characters.
 The Password must contain minimum of eight characters with one special character, one number, and
one alphabet in upper case.
 The Password must not exceed 16 characters.

DOCA0157EN-01 07/2019 63
Acti9 PowerTag Link Security

Follow the procedure to edit the details of an existing user profile:

Step Action
1 Select the user account from the User Accounts list and click the edit icon.
2 Select the type of user from the Role list.
3 Modify the Password for the selected user account, if required.
4 Enter the email of the user in the Email area.
5 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.

Click the delete icon to delete the user profile from web page. The user profile with Admin account cannot
be deleted.

64 DOCA0157EN-01 07/2019
Acti9 PowerTag Link
Load Monitoring and Control
DOCA0157EN-01 07/2019

Chapter 9
Load Monitoring and Control

Load Monitoring and Control

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Load Monitoring 66
Status Monitoring and Load Control 68

DOCA0157EN-01 07/2019 65
Load Monitoring and Control

Load Monitoring

Description
The Monitoring page is used to monitor the electrical loads. The facility managers can check the health of
the electrical loads like HVAC, lighting, pumps, machines, and so on.

General Page
The General page displays the status of the load.

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Monitoring → General.

The following information is displayed for the load:

Parameter Description
Asset Name Displays the name of the equipment or load name that the PowerTag tracks.
Usage Displays the usage of the energy of the equipment or load (for example, cooling, lighting, IT loads, and so on.)
Product Displays the type of PowerTag device associated to a circuit breaker.
Gateway Displays the gateway connected to the PowerTag.
Partial Energy Displays the partial counter of energy for the given electrical asset.
Load by Phase Displays the percentage of the load of the feeder connected to the PowerTag. The percentage indicates how
far an user is away from the tripping of a breaker. It is the ratio of the actual current to breaker rating.
Green: Indicates the circuit is loaded up to 50% in regards to circuit breaker rating.
Orange: Indicates the circuit is loaded between 50% and 80%.
Red: Indicates the circuit is loaded above 80% versus circuit breaker rating.

Click the expand button to see the real-time data for each device.

66 DOCA0157EN-01 07/2019
Load Monitoring and Control

As an example, the following screenshot shows all the real-time data available for each PowerTag sensor:

DOCA0157EN-01 07/2019 67
Load Monitoring and Control

Status Monitoring and Load Control

PowerTag C IO 230V
Load control with feedback loop can be achieved with PowerTag Control IO 230V module (reference
A9XMC1D3).

With this solution, you can easily control remotely a contractor (CT) or an impulse relay (TL) with or without
the information of the load circuit contact using the associated input.
Local Output Control
During commissioning phase, you will select if the output order should be a pulse (for “Impulse Relay”) or
a latch order (for “Contactor”). Once the IO Module has been commissioned, the front face push button
allows you to change the status of output control circuit.

Commissioning and decommissioning are done through web pages.


NOTE: The push button is not active when the LED is yellow or “Off”.
The push button can also be used for decommissioning in case of communication loss (>240 s)
To commission or decommission PowerTag C IO 230V, please refer to chapter “Wireless Device
Commissioning with Web Pages” or refer to EcoStruxure Power Commission Online Help.

68 DOCA0157EN-01 07/2019
Load Monitoring and Control

To configure PowerTag C IO 230V, you can refer to the following or to EcoStruxure Power Commission
Online Help

Step Action
1 Click Start Scanning to discover the wireless devices connected to the Acti9 PowerTag Link:
Result: Displays the discovered wireless devices and allocates Modbus address to each device.
2 Select any wireless device and click the pencil icon to modify the configuration of the selected wireless device.
3 Enter the Asset Name of a wireless device.
4 Enter the Label of a wireless device.
5 Enter the Usage from the drop-down list.
6 Enter the Configuration Type from the drop-down list.
7 Enter the Output Contact type from the drop-down list.
8 Check the Feedback Loop box if necessary.
9 Enter the Feedback Loop Contract type from the drop-down list.
10 If necessary, enable the Local Control by ticking the associated box.
11 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.

PowerTag C 2DI 230V


Status monitoring alone is achieved with PowerTag Control 2DI 230V module (reference A9XMC2D3).

With this solution, you can easily know the status of two contacts or achieve OF/SD daisy chain.
Commissioning and decommissioning are done through web pages.

DOCA0157EN-01 07/2019 69
Load Monitoring and Control

NOTE: The push button is used for decommissioning in case of communication loss (>240 s).

To commission or decommission PowerTag C 2DI 230V, please refer to chapter Wireless Device
Commissioning with Web Pages or refer to EcoStruxure Power Commission Online Help.
To configure PowerTag C 2DI 230V, you can refer to the following or to EcoStruxure Power Commission
Online Help.

Step Action
1 Click Start Scanning to discover the wireless devices connected to the Acti9 PowerTag Link:
Result: Displays the discovered wireless devices and allocates Modbus address to each device.
2 Select any wireless device and click the pencil icon to modify the configuration of the selected wireless device.
3 Enter the Asset Name of the Input 1.
4 Enter the Label of the Input 1.
5 Select the Usage from the drop-down list.
6 Select the Configuration Type from the drop-down list.
7 Select the Contact type from the drop-down list.
8 Repeat thse actions for the Input 2.
9 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.

70 DOCA0157EN-01 07/2019
Acti9 PowerTag Link
Energy Management
DOCA0157EN-01 07/2019

Chapter 10
Energy Management

Energy Management

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Energy Counter 72
Active Power Demand 73

DOCA0157EN-01 07/2019 71
Energy Management

Energy Counter

Total Active Energy Delivered


Displays the total counter of energy for the given electrical asset. It is not possible to reset this value.

Partial Active Energy Delivered


Displays the partial counter of energy for the given electrical asset. It is possible to clear all active energy
accumulated since the last reset. This does not reset the total active energy accumulation.

72 DOCA0157EN-01 07/2019
Energy Management

Active Power Demand

Power Demand
PowerTag Link/PowerTag Link HD provides:
 Total active power demand calculated on a sliding block interval.
 Maximum of the total active power demand.
 Date and time of occurrence of that maximum.

Power Demand Calculation


Power demand is calculated using arithmetical integration of the power value during a period of time
(interval) divided by the length of the interval. The result is equivalent to the energy accumulated during
the interval divided by the length of the interval.

Interval for Power Demand Calculation


Power demand is calculated over a sliding block interval. Navigate to Settings → Devices → Demand to
set the interval duration from 1 to 60 minutes. The default value is 10 mn.

Maximum Power Demand


The maximum power demand is the highest value calculated since the beginning of the measurement or
the last reset. PowerTag Link/PowerTag Link HD time stamps (date and time) the maximum power
demand occurrence.
PowerTag Link/PowerTag Link HD stores the maximum power demand and the associated date and time.

Resetting the Maximum Power Demand


Navigate to Settings → Devices → Demand and, click Reset all Max Demands to reset the maximum
power demand.

DOCA0157EN-01 07/2019 73
Energy Management

74 DOCA0157EN-01 07/2019
Acti9 PowerTag Link
Alarms
DOCA0157EN-01 07/2019

Chapter 11
Alarms

Alarms

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
About Alarms 76
Alarms Output Table 78
Voltage Loss 79
Current Overload at Voltage Loss 80
Communication Loss 81
Overload 80% 82
Overload 50% 83
Overload 45% 84
Zero Current 85
Under Voltage (80%) 86
Load Operating Time 87
Over Voltage (120%) 88
Partial Active Energy Delivered 89
Current I 90
Voltage V 91
Total Active Power 92
Power Factor 93

DOCA0157EN-01 07/2019 75
Alarms

About Alarms

Description
The Alarms page displays the active alarms. When an alarm is displayed, a notification is sent to the user
either by email (if the email service is enabled). An active alarm disappears when an issue is resolved.

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Monitoring → Alarms.

Parameter Description
Alarm Type Displays the type of an alarm when an alarm is occurred.
Alarm Value Displays the threshold value of an alarm.
Asset Name Displays the user-defined name of the alarm.
Usage Displays the type of the usage.
Product Displays the device type for which an alarm is configured.
Gateway Displays the user-configured gateway of the device.
Email Content Click Email to view the custom text of the email defined during an alarm configuration.
Date & Time Displays the date and time of the configured alarm in yyyy/mm/dd hh:mm:sec format.

Click Change date & time to modify the date and time parameters in the Settings → General → Date &
Time page.
Click Change alarm configuration to modify an existing alarm or to configure a new alarm in the Settings
→ Alarms → Alarm Configuration page.

Alarm Configuration Page


The Alarm Configuration page is used to configure alarms when there is an electrical event and
communication loss.

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Settings → Alarms → Alarm Configuration.

This page allows you to add a new alarm and edit the selected alarm from the list of events.

76 DOCA0157EN-01 07/2019
Alarms

Follow the steps given in the table to add a new alarm:

Step Action
1 Click Add Alarm to add a new event. You can create either generic alarm for the whole system or specific alarms to a selected
device.
2 a Select Generic Alarms for the Whole System, select when an alarm to occur, and then select the users to whom an alarm
notification to be sent through email (optional).

b Select Specific Alarms, select the required parameters, enter the threshold value that indicates for an alarm to occur,
and then select the users to whom an alarm notification to be sent through email (optional). It is possible to add up to 25
specific alarms maximum.

3 Enter the Subject and Message of the email event (if necessary).
4 Click Apply Changes to save the settings. Click Cancel Changes to revert the settings.

NOTE: The email with custom text that uses characters such as à, è, ù, é, â, ê, î, ô, û , ë, ï, ü, ÿ, and ç are
not shown correctly in the email but the generic text message is shown correctly.

DOCA0157EN-01 07/2019 77
Alarms

Alarms Output Table

Alarms Alarms Output


Modbus Registers Email Notifications
Generic Generic Specific
Voltage Loss x x
Current Overload at Voltage Loss x x
Communication Loss x
Overload 80% x
Overload 50% x
Overload 45% x
Zero Current x
Under Voltage (80%) x
Over Voltage (120%) x
Partial Active Energy Delivered x
Current I x
Voltage V x
Total Active Power x
Power Factor x
Load Operating Time Counter x

78 DOCA0157EN-01 07/2019
Alarms

Voltage Loss

This alarm indicates that the circuit on which PowerTag is installed is no longer under voltage. The cause
of the voltage loss can be a manual opening of the circuit, a mains power outage, a circuit breaker tripping.
PowerTag sends the Voltage Loss alarm to the gateway as soon as it happens, and before being fully de-
energized, i.e the alarm response-time does not depend on the wireless communication period.The alarm
will automatically disappear as soon as the PowerTag E is powered again.

DOCA0157EN-01 07/2019 79
Alarms

Current Overload at Voltage Loss

This alarm indicates that, there will be overcurrent during the time of voltage loss. This alarm occurs only
if the option is activated. The alarm is managed only if the nominal current or the breaker rating (Ir) of the
associated protection device has been set.
NOTE: RMS value of the current during the voltage loss, are available in the Modbus table. (See Modbus
Registers section for more details). These measurements help to diagnose the root cause of the
overcurrent.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Make sure the cause of the overcurrent is identified and fixed before closing the circuit.
Failure to follow these instructions will result in death or serious injury.

80 DOCA0157EN-01 07/2019
Alarms

Communication Loss

This alarm indicates that the gateway has lost the communication with a wireless device.
The communication loss happens if the gateway has not received packets for a period of time:
 PowerTag: 44 wireless communication periods
 PowerTag C: 3 minutes and 40 seconds
The alarm will automatically disappear as soon as the wireless device is back in the RF network

DOCA0157EN-01 07/2019 81
Alarms

Overload 80%

This alarm indicates that the load current exceeded 80% of the nominal current or the breaker rating (Ir) of
the associated protection device. On polyphase circuits, the alarm happens if the current of one of the
phases meets the above conditions. The gateway manages the alarms based on the values of the currents
sent by the PowerTag E. The response time of the alarm depends on the communication period set into
the Acti9 PowerTag system wireless network (default = 5s). The alarm automatically disappears when the
load current remains below the threshold for 15 minutes. Note that a hysteresis of 10% is applied on the
threshold.

82 DOCA0157EN-01 07/2019
Alarms

Overload 50%

This alarm indicates that the load current exceeded 50% of the nominal current or the breaker rating (Ir) of
the associated protection device.On polyphase circuits, the alarm happens if the current of one of the
phases meets the above conditions.The gateway manages the alarms based on the values of the currents
sent by the PowerTag E. The response time of the alarm depends on the communication period set into
the Acti9 PowerTag system wireless network (default = 5s)The alarm automatically disappears when the
load current remains below the threshold for 15 minutes.
NOTE: Note that a hysteresis of 10% is applied on the threshold.

DOCA0157EN-01 07/2019 83
Alarms

Overload 45%

This alarm indicates that the load current exceeded 45% of the nominal current or the breaker rating (Ir) of
the associated protection device.On polyphase circuits, the alarm happens if the current of one of the
phases meets the above conditions.The gateway manages the alarms based on the values of the currents
sent by the PowerTag E. The response time of the alarm depends on the communication period set into
the Acti9 PowerTag wireless network (default = 5s)The alarm automatically disappears when the load
current remains below the threshold for 15 minutes. Note that a hysteresis of 10% is applied on the
threshold.

84 DOCA0157EN-01 07/2019
Alarms

Zero Current

This alarm indicates that the load current value is 0 A.On polyphase circuits, the alarm happens if the
current of one of the phases meets the above conditions.The gateway manages the alarms based on the
values of the currents sent by the PowerTag E. The response time of the alarm depends on the
communication period set into the Acti9 PowerTag system wireless network (default = 5s)Zero current
alarm allow the monitoring of full time running loads. The alarm automatically disappears when the load
current is greater than 0 A on all phases.

DOCA0157EN-01 07/2019 85
Alarms

Under Voltage (80%)

This alarms triggers when voltage in a phase falls below 80% of the nominal value. The alarm automatically
disappears when the voltage remains greater than 88% of the nominal value (a hysteresis of 10% is
applied) for 15 minutes.

86 DOCA0157EN-01 07/2019
Alarms

Load Operating Time

This alarm indicates that the load operating time counter has reached the configured threshold value. The
alarm can be set with the following conditions: Every:
 Greater than: The alarm is triggered when the Load Operating Time counter exceed the configured
threshold.
 Every: The alarm is triggered every time the Load Operating Time counter has reached the time
configured in the threshold value.

DOCA0157EN-01 07/2019 87
Alarms

Over Voltage (120%)

This alarms triggers when voltage in a phase exceeds 120% of the nominal value. The alarm automatically
disappears when the voltage remains lower than 108% of the nominal value (a hysteresis of 10% is
applied) for 15 minutes.

88 DOCA0157EN-01 07/2019
Alarms

Partial Active Energy Delivered

This alarm indicates that the “Partial Active Energy Delivered” has reached the configured threshold value.
The alarm can be set with the following conditions:
 Greater than: The alarm is triggered when the “Partial Active Energy Delivered” exceeds the configured
threshold.
 Every: The alarm is triggered every time the “Partial Active Energy Delivered” has reached the time
configured in the threshold value.

DOCA0157EN-01 07/2019 89
Alarms

Current I

This alarm indicates that the Current I is greater or lower than the configured threshold value. The alarm
will become inactive if the Current I remains 15 minutes under or over (as defined by the comparator) 90%
of the threshold value.

90 DOCA0157EN-01 07/2019
Alarms

Voltage V

This alarm indicates that the Voltage V is greater or lower than the configured threshold value. The alarm
will become inactive if the Voltage V remains 15 minutes under or over (as defined by the comparator) 90%
of the threshold value.

DOCA0157EN-01 07/2019 91
Alarms

Total Active Power

This alarm indicates that the Total Active Power is greater or lower than the configured threshold value.
The alarm will become inactive if the Total Active Power remains 15 minutes under or over (as defined by
the comparator) 90% of the threshold value.

92 DOCA0157EN-01 07/2019
Alarms

Power Factor

This alarm indicates that the Power Factor is greater or lower than the configured threshold value. The
alarm will become inactive if the Power Factor remains 15 minutes under or over (as defined by the
comparator) 90% of the threshold value.

DOCA0157EN-01 07/2019 93
Alarms

94 DOCA0157EN-01 07/2019
Acti9 PowerTag Link
Modbus Registers Tables
DOCA0157EN-01 07/2019

Chapter 12
Modbus Registers Tables

Modbus Registers Tables

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Modbus Table Format and Data Types 96
System Modbus Table 99
Wireless Devices Modbus Tables 100

DOCA0157EN-01 07/2019 95
Modbus Registers Tables

Modbus Table Format and Data Types

Table Formats
Register tables have the following columns:

Address Register No. RW X Unit Type Range Default Svd Function Description
Value Code

Designation Description
Address 16-bit register address in hexadecimal. The address is the data used in the Modbus frame.
Register 16-bit register number in decimal. Register = Address + 1
No Number of 16-bit registers that need to be read/written to access the complete information
R/RW Whether the register is read only (R) or read-write (RW).
X Scale factor:
 Scale “X1” means that the value of the register is the right one with the unit indicated.
 A scale of 10 means that the register contains the value multiplied by 10. The actual value is therefore the value of the
register divided by 10.
 A scale of 0.1 means that the register contains the value multiplied by 0.1. The actual value is therefore the value of the
register multiplied by 10.
Unit Information unit of measurement:
 “–”: no unit corresponding to the value expressed.
 “h”: hours
 “D”: the unit depends on the connected device.

Type Coding data type (see Data type table below).


Range Range of permitted values for the variable, usually a subset of what the format allows. For BITMAP type data, the content
of this domain is “–”.
Default Value Default value for the variable
Svd Saving the value in the event of a power failure:
 “Y”: the value of the register is saved in the event of a power failure.
 “N”: the value is lost in the event of a power failure.

NOTE: On start-up or reset, the available values are retrieved.


Function code Code of functions that can be used in the register.
Applicable Availability of the data depending on the associated device:
Devices  “Y”: the associated device provides the information.
 “N”: the associated device provides the information.

Description Information about the register and the restrictions that apply.

Data Types
The following data types appear in the tables of Modbus registers:

Name Description Range


UINT 16-bit unsigned integer (1 word) 0...65535
INT 16-bit signed integer (1 word) -32768...+32767
UINT32 32-bit unsigned integer (2 words) 0...4 294 967 295
INT32 32-bit signed integer (2 words) -2 147 483 648...+2 147 483 647
INT64 64-bit signed integer (4 words) -9 223 372 036 854 775 808...9 223 372 036 854 775
807
Float32 32-bit value (2 words) -3.4028E+38... +3.4028E+38
ASCII 8-bit alphanumeric character Table of ASCII Characters
BITMAP 16-bit field (1 word) –
DATE See below –

NOTE:
Float32 type data: Single precision float with sign bit, 8 bits exponent, 23 bits mantissa (positive and
negative normalized real)

96 DOCA0157EN-01 07/2019
Modbus Registers Tables

For ASCII type data, the order of transmission of characters in words (16-bit registers) is as follows:
 Character n as least significant
 Character n + 1 as most significant

All registers (16-bit or 2 bytes) are transmitted with Big Endian coding:
 The most significant byte is transmitted first.
 The least significant byte is transmitted second.

32-bit variables saved on two 16-bit words (e.g. consumption meters) are in Big Endian format:
 The most significant word is transmitted first, then the least significant.
64-bit variables saved on four 16-bit words (e.g. dates) are in Big Endian format:
 The most significant word is transmitted first, and so on.

DATE
DATE format in accordance with TI081 standard:

Word Bits
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
1 Reserved (0) R4 (0) Year (0...127)
2 0 Month (1...12) WD (0) Day (1...31)
3 SU (0) 0 Hour (0...23) iV 0 Minute (0...59)
4 Millisecond (0...59,999)
R4: Bit reserved
Year: 7 bits (year starting at 2000)
Month: 4 bits
Day: 5 bits
Hour: 5 bits
Minute: 6 bits
Millisecond: 16 bits
WD (day of the week) : Bit at 0 if this parameter is not used.
SU (summertime): Bit at 1 for summertime, bit at 0 if this parameter is not used.
iV (validity of the information received): Bit at 1 if the information is not valid, bit at 0 if this parameter is not used.

Direct Bit Addressing


Addressing is permitted for BITMAP type zones with functions 1, 2, 5, and 15.
The address of the first bit is constructed as follows: (register address x 16) + bit number.
This addressing mode is specific to Schneider Electric.
Example: For functions 1, 2, 5, and 15, bit 3 of register 0x0078 should be addressed; the bit address is
therefore 0x0783.
NOTE: The register whose bit needs to be addressed should have an address ≤ 0x0FFF.

Example of Modbus Frames


Request

Definition Number of Bytes Value Comment


Slave number 1 byte 0x05 Acti9 PowerTag Link Modbus Address
Function code 1 byte 0x03 Reads n output or internal words
Address 2 bytes 0x36E2 Address of a consumption meter whose address is 14050 in decimal notation.
Number of words 2 bytes 0x002C Reads 44 16-bit registers.
CRC 2 bytes xxxx Value of CRC16.

Response

Definition Number of Bytes Value Comment


Slave number 1 byte 0x05 Acti9 PowerTag Link Modbus Address
Function code 1 byte 0x03 Reads n output or internal words
Number of Bytes 2 bytes 0x0058 Number of bytes read
Value of words read 88 bytes – Reads 44 16-bit registers
CRC 2 bytes xxxx Value of CRC16.

DOCA0157EN-01 07/2019 97
Modbus Registers Tables

Modbus Register
The address of register number n is n-1. The tables detailed in the following parts of this document provides
both register numbers (in decimal format) and corresponding addresses (in hexadecimal format). For
example, the address of register number 3000 is 0x0BB7 (2999).
NOTE: How to use registers:
To know the description of the registers of each associated device (how to use them), print the PDF report
of Modbus registers using EcoStruxure Power Commission software, see Ecostruxure Power Commission
Online Help. This report gives a dynamic knowledge of all the registers potentially to be integrated into the
supervision systems including, a description of each register.

98 DOCA0157EN-01 07/2019
Modbus Registers Tables

System Modbus Table

Identification
The Modbus slave ID of Acti9 PowerTag Link to read Identification Modbus table is 255.

Address Register No. RW X Unit Type Range Invalid Svd Function Description
Value Code
0x64 101 6 R – – ASCII – N/A Y 03, Serial number on
100–4 12 ASCII characters;
11 alphanumeric digits maximum
[SN] or [S/N]:
PP YY WW [D[nnnn]]
 PP: Plant
 YY: Year in decimal notation
[05...99]
 WW: Week in decimal notation
[1...53]
 D: Day of the week in decimal
notation [1...7]
 nnnn: Sequence of numbers
[0001...10.000–1]
0x6A 107 3 R – – ASCII – N/A Y 03, Hardware version on 6 ASCII
100–4 characters
0x6D 110 3 R – – ASCII – N/A Y 03, Software version on 6 ASCII
100–4 characters.
Example: “V0.0.1”

Status

Address Register No. RW X Unit Type Range Invalid Svd Function Description
Value Code
0x70 113 1 R – – BITMAP – 0x0000 N 01, 02, 03, Acti9 PowerTag Link device status
100–4 and diagnostic register
Bit 0 = 1: start-up phase
Bit 1 = 1: operating phase
Bit 2 = 1: downgraded mode
Bit 3 = 1: Failure mode
Bit 12: not used
Bit 13: E2PROM error
Bit 14: RAM error
Bit 15: FLASH error
NOTE: Bits 0 to 3 are exclusive: only
one mode is used at any given time.

Date and Time

Address Register No. RW X Unit Type Range Invalid Svd Function Description
Value Code
0x73 116 4 RW – – DATE (1) N/A N 03, 16 Indicates the year, month, day,
100–4 hour, minute and millisecond on
the Acti9 PowerTag Link device.

(1) See description of the DATE type (see page 97).

DOCA0157EN-01 07/2019 99
Modbus Registers Tables

Wireless Devices Modbus Tables

Description
Acti9 PowerTag Link dynamically allocates a Modbus slave address to each of the wireless devices paired
with it. Addresses range from 1 to 247.
The following table lists the Modbus registers that applies to all wireless paired devices.
To read a value from a particular wireless device, the supervision system uses its dynamically allocated
Modbus address.

Modbus Table Common to Power Tag Energy Sensors

Address Register No. RW X Unit Type Range Invalid Svd Function Applicable Description
Value Code Devices

Energy 250/630 A
Energy 63 A
PowerTag

PowerTag
Current - Metering Data
0xBB7 3000 2 R – A Float32 – 0xFFC N 03, Y Y RMS Current on phase A.
00000 100–4
0xBB9 3002 2 R – A Float32 – 0xFFC N 03, Y Y RMS Current on phase B.
00000 100–4
0xBBB 3004 2 R – A Float32 – 0xFFC N 03, Y Y RMS Current on phase C.
00000 100–4
Voltage -Metering Data
0xBCB 3020 2 R – V Float32 – 0xFFC N 03, Y Y RMS Phase-to-phase voltage
00000 100–4 A-B.
0xBCD 3022 2 R – V Float32 – 0xFFC N 03, Y Y RMS Phase-to-phase voltage
00000 100–4 B-C.
0xBCF 3024 2 R – V Float32 – 0xFFC N 03, Y Y RMS Phase-to-phase voltage
00000 100–4 C-A.
0xBD3 3028 2 R – V Float32 – 0xFFC N 03, Y Y RMS Phase-to-neutral voltage
00000 100–4 A-N.
0xBD5 3030 2 R – V Float32 – 0xFFC N 03, Y Y RMS Phase-to-neutral voltage
00000 100–4 B-N.
0xBD7 3032 2 R – V Float32 – 0xFFC N 03, Y Y RMS Phase-to-neutral voltage
00000 100–4 C-N.
Power - Metering Data
0xBED 3054 2 R – W Float32 – 0xFFC N 03, Y Y Active power on phase A.
00000 100–4
0xBEF 3056 2 R – W Float32 – 0xFFC N 03, Y Y Active power on phase B.
00000 100–4
0xBF1 3058 2 R – W Float32 – 0xFFC N 03, Y Y Active power on phase C.
00000 100–4
0xBF3 3060 2 R – W Float32 – 0xFFC N 03, Y Y Total active power.
00000 100–4
0xBFB 3068 2 R - Var Float32 - 0xFFC N 03, N Y Total reactive power
00000 100–4
0xC03 3076 2 R - VA Float32 - 0xFFC N 03, Y Y Total apparent power
00000 100–4 (arithmetric)
Power Factor - Metering Data
0xC0B 3084 2 R – – Float32 – 0xFFC N 03, Y Y Total power factor.
00000 100–4
Frequency -Metering Data
0xC25 3110 2 R – Hz Float32 – 0xFFC N 03, N Y AC Frequency
00000 100–4

100 DOCA0157EN-01 07/2019


Modbus Registers Tables

Address Register No. RW X Unit Type Range Invalid Svd Function Applicable Description
Value Code Devices

Energy 250/630 A
Energy 63 A
PowerTag

PowerTag
Device temperature - Metering Data
0xC3B 3131 2 R – °C Float32 – 0xFFC N 03, N Y Device internal temperature
00000 100–4
Energy - Metering Data
0xC83 3204 4 R - Wh INT64 - 0x8000 Y 03 Y N Total active energydelivered +
000000 received, non resettable
000000
0xC87 3208 4 R – Wh INT64 – 0x8000 Y 03 N Y Active energy delivered count
000000 positively non resettable (Total
000000 Energy)
0xC8B 3212 4 R – Wh INT64 – 0x8000 Y 03 N Y Total active energy received,
000000 non resettable
000000
0xC8F 3216 4 R – Wh INT64 – 0x8000 Y 03 N Y Active energy on phase A
000000 delivered - received, non
000000 resettable
0xC93 3220 4 R – Wh INT64 – 0x8000 Y 03 N Y Active energy on phase B
000000 delivered - received, non
000000 resettable
0xC97 3224 4 R – Wh INT64 – 0x8000 Y 03 N Y Active energy on phase C
000000 delivered - received, non
000000 resettable
0xCB7 3256 4 R - Wh INT64 - 0x8000 Y 03 N Y Partial active energy delivered
000000 + received, resettable
000000
0xCBB 3260 4 RW - Wh INT64 - 0x8000 Y 03, 16 N Y Set partial active
000000 energycounter. The
000000 valuereturns to zero by Acti9
PowerTag Link
0xCBF 3264 4 R – Wh INT64 – 0x8000 Y 03 N Y Partial active energy delivered,
000000 resettable
000000
0xCC3 3268 4 RW – Wh INT64 – 0x8000 N 03, 16 N Y Set partial active energy
000000 delivered counter. The value
000000 returns to zero by Acti9
PowerTag Link.
0xCC7 3272 4 R – Wh INT64 – 0x8000 N 03 N Y Partial active energyreceived,
000000 resettable
000000
0xCCB 3276 4 RW – Wh INT64 – 0x8000 N 03, 16 N Y Set partial active energy
000000 received counter. The value
000000 returns to zero by Acti9
PowerTag Link.
0xCCF 3280 4 R – VAR INT64 – 0x8000 Y 03 N Y Partial reactive energy
h 000000 delivered, resettable
000000
0xCD3 3284 4 RW – VAR INT64 – 0x8000 N 03, 16 N Y Set partial reactive energy
h 000000 delivered counter. The value
000000 returns to zero by Acti9
PowerTag Link.
0xCD7 3288 4 R – VAR INT64 – 0x8000 N 03 N Y Partial reactive energy
h 000000 received, resettable
000000

DOCA0157EN-01 07/2019 101


Modbus Registers Tables

Address Register No. RW X Unit Type Range Invalid Svd Function Applicable Description
Value Code Devices

Energy 250/630 A
Energy 63 A
PowerTag

PowerTag
0xCDB 3292 4 RW – VAR INT64 – 0x8000 N 03, 16 N Y Set partial reactive energy
h 000000 received counter. The value
000000 returns to zero by Acti9
PowerTag Link.

Modbus Table to PowerTag Control Devices

Address Register No. RW XR Unit Type Range Invalid Svd Function Applicable Description
Value Code Devices

Control 2DI

Control IO
PowerTag

PowerTag
0X84D0 34001 10 R NA NA ASCII NA 0X00 Y 03 Y Y Digital input 1 name
100-4
0X84E7 34024 3 R NA NA ASCII NA 0X00 Y 03 Y Y Digital input 1 circuit identifier
100-4
0X84EA 34027 1 R NA NA ENUM NA 0xFFF Y 03 Y Y Digital input 1 product usage
F 100-4  1 = Main/Incomer
 2 = Sub/Head of group
 3 = Heating
 4 = Cooling
 5 = HVAC
 6 = Ventilation
 7 = Lighting
 8 = Office Equipment
 9 = Cooking
 10 = Food refrigeration
 11 = Elevators
 12 = Computers
 13 = Renewable Energy
Production
 14 = Genset
 15 = Compressed air
 16 = Vapor
 17 = Machine
 18 = Process
 19 = Water
 20 = Other sockets
 21 = Other

102 DOCA0157EN-01 07/2019


Modbus Registers Tables

Address Register No. RW XR Unit Type Range Invalid Svd Function Applicable Description
Value Code Devices

Control 2DI
PowerTag

PowerTag
Control IO
0X84EC 34029 1 R NA NA ENUM NA 0x800 Y 03 Y Y Digital input 1 assignment
0 100-4 reference
 0 = None
 1 = Standard input
 2 = Breaker position
 3 = Trip indicator (SD)
 4 = Chained trip indicator
 5 = Electrical trip signal contact
 6 = Thermal trip signal contact
 7 = Earth leakage trip signal
contact (SDV)
 8 = Groud fault trip signal
contact
 9 = Surge failure contact
 15 = Switchboard board door
contact
 16 = Feedback loop

Register is forced to 'Feedback


loop' (16), when Digital output 1
Feedback loop is configured to
'Enabled'. (See register 37036)
0X84ED 34030 1 R NA NA ENUM NA 0xFFF Y 03 Y Y Digital input 1 contact type
F 100-4  0 = Normally open
 1 = Normally close

0X84F8 34041 1 R NA NA ENUM NA 0xFFF Y 03 Y Y Digital input 1 electrical status


F 100-4 Indicates the electrical status of the
input regardless of the assignment
reference.
 0 = Low level
 1 = High level

0X84FE 34047 1 R NA NA ENUM NA 0xFFF Y 03 Y Y Digital input 1 breaker position


F 100-4 Indicates the breaker position -
Only available if input 1 assignment
reference is 'Breaker position' (case
= 2)
 0 = Open
 1 = Close

0X8508 34057 1 R NA NA ENUM NA 0xFFF Y 03 Y Y Digital input 1 trip indicator


F 100-4 Indicates the trip status- Only
available if input 1 assignment
reference is one of the trip cause
(case = 3 to 8)
 0 = Tripped
 1 = Not tripped

0X8510 34065 1 R NA NA ENUM NA 0xFFF Y 03 Y Y Digital input 1 status Indicates the


F 100-4 status of the Digital Input 1 - Only
available if input 1 assignment
reference is not 'Breaker position'
or none of the trip causes. (Cases
1, 9, 15, 16)
 0 = On
 1 = Off

0X8534 34101 10 R NA NA ASCII NA 0X00 Y 03 Y N Digital input 2 name


100-4
0X854B 34124 3 R NA NA ASCII NA 0X00 Y 03 Y N Digital input 2 circuit identifier
100-4

DOCA0157EN-01 07/2019 103


Modbus Registers Tables

Address Register No. RW XR Unit Type Range Invalid Svd Function Applicable Description
Value Code Devices

Control 2DI
PowerTag

PowerTag
Control IO
0X854E 34127 1 R NA NA ENUM NA 0xFFF Y 03 Y N Digital input 2 product usage
F 100-4  1 = Main/Incomer
 2 = Sub/Head of group
 3 = Heating
 4 = Cooling
 5 = HVAC
 6 = Ventilation
 7 = Lighting
 8 = Office Equipment
 9 = Cooking
 10 = Food refrigeration
 11 = Elevators
 12 = Computers
 13 = Renewable Energy
Production
 14 = Genset
 15 = Compressed air
 16 = Vapor
 17 = Machine
 18 = Process
 19 = Water
 20 = Other sockets
 21 = Other

0X8550 34129 1 R NA NA ENUM NA 0xFFF Y 03 Y N Digital input 2 assignment


F 100-4 reference
 0 = None
 1 = Standard input
 2 = Breaker position
 3 = Trip indicator (SD)
 4 = Chained trip indicator
 5 = Electrical trip signal contact
 6 = Thermal trip signal contact
 7 = Earth leakage trip signal
contact (SDV)
 8 = Groud fault trip signal
contact
 9 = Surge failure contact
 15 = Switchboard door contact
 16 = Feedback loop

0X8551 34130 1 R NA NA ENUM NA 0xFFF Y 03 v N Digital input 2 contact type


F 100-4  0 = Normally open
 1 = Normally close

0X855C 34141 1 R NA NA ENUM NA 0xFFF Y 03 Y N Digital input 2 electrical status


F 100-4 Indicates the electrical status of the
input regardless of the assignment
reference.
 0 = Low level
 1 = High level

0X8562 34147 1 R NA NA ENUM NA 0xFFF Y 03 Y N Digital input 2 breaker position


F 100-4 Indicates the breaker position -
Only available if input 2 assignment
reference is 'Breaker position' (case
= 2)
 0 = Open
 1 = Close

104 DOCA0157EN-01 07/2019


Modbus Registers Tables

Address Register No. RW XR Unit Type Range Invalid Svd Function Applicable Description
Value Code Devices

Control 2DI
PowerTag

PowerTag
Control IO
0X856C 34157 1 R NA NA ENUM NA 0xFFF Y 03 Y N Digital input 2 trip indicator
F 100-4 Indicates the trip status- Only
available if input 2 assignment
reference is one of the trip cause
(case = 3 to 8)
 0 = Tripped
 1 = Not tripped

0X8574 34165 1 R NA NA ENUM NA 0xFFF Y 03 Y N Digital input 2 status Indicates the


F 100-4 status of the Digital Input 2 - Only
available if input 2 assignment
reference is not 'Breaker position'
or none of the trip causes. (Cases
1, 9, 15, 16)
 0 = On
 1 = Off

0X9088 37001 10 R NA NA ASCII NA 0x00 Y 03 N Y Digital output 1 name


100-4
0X909F 37024 3 R NA NA ASCII NA 0x00 Y 03 N Y Digital output 1 circuit identifier
100-4
0X90A2 37027 1 R NA NA ENUM NA 0xFFF Y 03 N Y Digital output 1 product usage
F 100-4  1 = Main/Incomer
 2 = Sub/Head of group
 3 = Heating
 4 = Cooling
 5 = HVAC
 6 = Ventilation
 7 = Lighting
 8 = Office Equipment
 9 = Cooking
 10 = Food refrigeration
 11 = Elevators
 12 = Computers
 13 = Renewable Energy
Production
 14 = Genset
 15 = Compressed air
 16 = Vapor
 17 = Machine
 18 = Process
 19 = Water
 20 = Other sockets
 21 = Other

0X90A4 37029 1 R NA NA ENUM NA 0xFFF Y 03 N Y Digital output 1 behavior


F 100-4  0 = Normal
 1 = Latched

0X90A7 37032 1 R NA NA ENUM NA 0xFFF Y 03 N Y Digital output 1 contact type


F 100-4  0 = Normally open
 1 = Normally close

0X90A9 37034 1 R NA NA ENUM NA 0xFFF Y 03 N Y Digital output 1 local control enable


F 100-4  0 = Disable
 1 = Enabled

DOCA0157EN-01 07/2019 105


Modbus Registers Tables

Address Register No. RW XR Unit Type Range Invalid Svd Function Applicable Description
Value Code Devices

Control 2DI
PowerTag

PowerTag
Control IO
0X90AB 37036 1 R NA NA ENUM NA 0xFFF Y 03 N Y Digital output 1 feedback loop
F 100-4 enable. Register is forced to
'enabled' when Output is configured
to 'Latched' behavior. (See register
37029) When enabled, feedback
data are available in Input 1
registers (starting from register
34001)
 0 = Disable
 1 = Enabled

0X90BA 37051 1 RW NA NA UINT1 NA 0xFFF N 03,06, N Y Digital output 1 command


6 F 16,  0 = No command
100-4  1 = Off command
 2 = On command
 3 = Toggle command

0X90BB 37052 1 R NA NA UINT1 NA 0xFFF N 03 N Y Digital output 1 status Only


6 F 100-4 significant if Output is configured to
'Normal' behavior. (See register
37029). Otherwise is set to invalid
value.
 0 = Off
 1 = On

Load Monitoring Registers


The Modbus Registers of the PowerTag energy sensor allows you to monitor the following status in any
supervision system.
Alarms with two Types
 The voltage loss of the load.
 If an overload has occurred at the voltage loss event.

Load Operating Time: The duration of how long the load worked effectively (above a certain power, this
avoiding idle/standby times to be counted), to optimize the maintenance times.

106 DOCA0157EN-01 07/2019


Modbus Registers Tables

Address Register No. RW X Unit Type Range Invalid Svd Function Applicable Devices Description
Value Code

PowerTag Energy 63 A

PowerTag Control 2DI

PowerTag Control IO
PowerTag Energy
250/630 A
0xCE1 3298 2 R – – UINT – 0xFFF N 03, Y Y N N Validity of the Alarm
FFFFF 100–4 bitmap (register 3300)
 0 = Invalid.
 1 = Valid.

0xCE3 3300 2 R – – UINT – 0xFFF N 03, Y Y N N Alarms bitmap


FFFFF 100–4 0 = Alarm OFF.
1 = Alarm ON.
Bit 0 = Voltage loss
Bit 1 = Current Overload
at Voltage Loss
Bit 2 = Reserved
Bit 3 = Overload 45%
Bit 4 = Load current loss
Bit 5 = Overvoltage
120%
Bit 6 = Undervoltage
Alarm

80%
Bit 7 = Battery Low
0xCE5 3302 2 R NA A Float NA 0xFFC N 03, Y Y N N RMS Current on Phase A
32 00000 100–4 at Voltage Loss (Last
RMS current measured
when voltage loss
occurred)
0xCE7 3304 2 R NA A Float NA 0xFFC N 03, Y Y N N RMS Current on Phase B
32 00000 100–4 at Voltage Loss (Last
RMS current measured
when voltage loss
occurred)
0xCE9 3306 2 R NA A Float NA 0xFFC N 03, Y Y N N RMS Current on Phase C
32 00000 100–4 at Voltage Loss (Last
RMS current measured
when voltage loss
occurred)
0xCEB 3308 2 RW – Sec UINT – 0xFFF Y 03, Y Y N N Load Operating Time
32 FFFFF 100–4 counter.
0xCED 3310 2 RW – W Float – 0xFFC Y 03, Y Y N N Active Power Threshold
32 00000 100–4 for Load Operating Time
Operating Time

counter. Counter starts


above the threshold.
0xCEF 3312 4 R – – D/T – 0x0000 Y 03, Y Y N N Date and time stamp of
IEC 0000 100–4 last Set or reset of Load
870- Operating Time counter.
5-4
(T08
1)

DOCA0157EN-01 07/2019 107


Modbus Registers Tables

Configuration Registers
The detailed information for all the wireless devices has the same structure as given in the following table.

Address Register No. RW X Unit Type Range Invalid Svd Function Applicable Devices Description
Value Code

PowerTag Control 2DI

PowerTag Control IO
PowerTag Energy

PowerTag Energy
250/630 A
63 A
0x7918 31001 10 RW – – ASCII – 0x000 Y 03, 06, Y Y N N User application name of
0 16, the wireless device. The
100–4 user can enter maximum
20 characters.
0x7922 31011 3 RW – – ASCII – 0x000 Y 03, 06, Y Y N N Circuit identifier of the
0 16, wireless device. The user
100–4 can enter maximum five
characters.
0x7925 31014 1 RW – – ENU – 0xFFF Y 03, 06, Y Y N N Indicates the usageof the
M F 16, wireless device.
100–4  1 = Main/Incomer
 2 = Sub/Head of group
 3 = Heating
 4 = Cooling
 5 = HVAC
 6 = Ventilation
 7 = Lighting
 8 = Office Equipment
 9 = Cooking
 10 = Food refrigeration
 11 = Elevators
 12 = Computers
 13 = Renewable
Energy Production
 14 = Genset
 15 = Compressed air
 16 = Vapor
 17 = Machine
 18 = Process
 19 = Water
 20 = Other Sockets
 21 = Other

0x7926 31015 1 RW – – ENU – 0xFFF Y 03, 06, Y Y N N Phase sequence.


M F 16,  1 = Phase A
100–4  2 = Phase B
 3 = Phase C
 4 = Phase sequence
ABC
 5 = Phase sequence
ACB
 6 = Phase sequence
BCA
 7 = Phase sequence
BAC
 8 = Phase sequence
CAB
 9 = Phase sequence
CBA
0x7927 31016 1 RW – – ENU – 0xFFF Y 03, 06, Y N N N Mounting position.
M F 16,  0 = Not configured
100–4  1 = Top
 2 = Bottom

108 DOCA0157EN-01 07/2019


Modbus Registers Tables

Address Register No. RW X Unit Type Range Invalid Svd Function Applicable Devices Description
Value Code

PowerTag Control 2DI

PowerTag Control IO
PowerTag Energy

PowerTag Energy
250/630 A
63 A
0x7928 31017 1 RW – – ENU – 0xFFF Y 03, 06, Y Y N N Circuit diagnostic.
M F 16,  0 = Not configured
100–4  1 = Top
 2 = Bottom

0x7929 31018 1 RW – A UINT – 0xFFF Y 03, 06, Y Y N N Rated current of the


F 16, protective device to the
100–4 wireless device.
0x792A 31019 1 R – – BITM – 0xFFF Y 03 N Y N N Electrical network System
AP F Type (Only for PowerTag
NSX)
 0 = Unknown system
type
 3 = 3PH3W
 11= 3PH4W

0x792B 31020 2 R – V Float – 0xFFC Y 03 N Y N N Rated voltage


32 00000  LN rated voltage for
single phase wiring
systems
 LL rated voltage for 2
or 3 phases wiring
systems

DOCA0157EN-01 07/2019 109


Modbus Registers Tables

Device Identification

Address Register No. RW X Unit Type Range Invalid Svd Functi Applicable Description
Value on Devices
Code

PowerTag 2DI 230 V


PowerTag IO 230 V
PowerTag En erg y

PowerTag NSX
0x7930 31025 1 R – – ENUM – 0x800 Y 03 Y Y Y Y Indicates the product type of
0 100–4 wireless devices.
41 = PowerTag Acti9 M631P
(A9MEM1520)
42 = PowerTag Acti9 M631P+N
Top (A9MEM1521)
43 = PowerTag Acti9 M631P+N
Bottom (A9MEM1522)
44 = PowerTag Acti9 M633P
(A9MEM1540)
45 = PowerTag Acti9 M633P+N
Top (A9MEM1541)
46 = PowerTag Acti9 M633P+N
Bottom(A9MEM1542)
81 = PowerTag Acti9 F631P+N
(A9MEM1560)
82 = PowerTag Acti9 P631P+N
Top (A9MEM1561)
83 = PowerTag Acti9 P631P+N
Bottom(A9MEM1562)
84 = PowerTag Acti9 P631P+N
Bottom(A9MEM1563)
85 = PowerTag Acti9 F633P+N
(A9MEM1570)
86 = PowerTag Acti9 P633P+N
Top (A9MEM1571)
87 = PowerTag Acti9 P633P+N
Bottom(A9MEM1572)
88 = 3P-250A (LVSMC13)
89 = 3P-630A (LVSMC23)
92 = PowerTag NSX 3P-250 A
(LV434020)
93 = PowerTag NSX 4P-250 A
(LV434021)
94 = PowerTag NSX 3P-630 A
(LV434022)
95 = PowerTag NSX 4P-630 A
(LV434023)
96 = PowerTag Acti9 M633P
230V (A9MEM1543)
97 = PowerTag Acti9 C 2DI
230V (A9XMC2D3)
98 = PowerTag Acti9 C IO 230V
(A9XMC1D3)
101 = PowerTag Acti9 F63
1P+N 110V (A9MEM1564)
102 = PowerTag Acti9 F63
3P (A9MEM1573)
103 =PowerTag Acti9 F63
3P+N 110/230V (A9MEM1574)
0X7931 31026 1 NA NA UINT NA 0xFFF Y 03 Y Y Y Y Y Virtual Modbus slave address
F 100
-4
0X7932 31027 4 NA NA UINT NA 0x8000 Y 03 Y Y Y Y Y Wireless device Radio
64 00000 100 Frequency Identifier (RF-Id)
00000 -4
00

110 DOCA0157EN-01 07/2019


Modbus Registers Tables

Address Register No. RW X Unit Type Range Invalid Svd Functi Applicable Description
Value on Devices
Code

PowerTag 2DI 230 V


PowerTag IO 230 V
PowerTag En erg y

PowerTag NSX
0X7944 31045 16 NA NA ASCII NA 0x00 Y 03 Y Y Y Y Y Vendor name
100
-4
0X7954 31061 16 NA NA ASCII NA 0x00 Y 03 Y Y Y Y Y Product Code (Commercial
100 reference)
-4
0X7964 31077 6 NA NA ASCII NA 0x00 Y 03 Y Y Y Y Y Firmware revision
100
-4
0X796A 31083 6 NA NA ASCII NA 0x00 Y 03 Y Y Y Y Y Hardware revision
100
-4
0X7970 31089 10 NA NA ASCII NA 0x00 Y 03 Y Y Y Y Y Serial Number
100
-4
0X797A 31099 8 NA NA ASCII NA 0x00 Y 03 Y Y Y Y Y Product range
100
-4
0X7982 31107 8 NA NA ASCII NA 0x00 Y 03 Y Y Y Y Y Product model
100
-4
0X798A 31115 8 NA NA ASCII NA 0x00 Y 03 Y Y Y Y Y Product family
100
-4

DOCA0157EN-01 07/2019 111


Modbus Registers Tables

Diagnostic Data Registers

Address Register No. RW X Unit Type Range Invalid Svd Function Applicable Devices Description
Value Code

Energy 250/630A
Energy 63A

Control 2DI
PowerTag

PowerTag

PowerTag

PowerTag
Control IO
0x79A8 31145 1 R – – BITMAP – 0xFFF N 03, Y Y Y Y Validity of the RF
F 100–4 communication
between PowerTag
and PowerTag Link
status.
 0 = Invalid.
 1 = Valid.

0x79A9 31146 1 R – – BITMAP – 0xFFF N 03, Y Y Y Y Communication status


F 100–4 between Acti9
PowerTag Link and
wireless devices.
 0 = Communication
loss.
 1 = Communication
OK.
0x79B4 31157 2 R N NA Float32 NA 0xFFC N 03, Y Y Y Y Packet Error Rate
A 00000 100–4 (PER)
0x79B6 31159 2 R N NA Float32 NA 0xFFC N 03, Y Y Y Y Radio Signal Strength
A 00000 100–4 Indicator (RSSI) link
0x79B8 31161 1 R N NA UINT16 NA 0xFFF N 03, Y Y Y Y Link Quality Indicator
A F 100–4 (LQI) link
0x79C5 31174 2 R – – BITMAP – – N 03 Y Y N N Alarm status
value = 0: PowerTag
Link is operational
value different than 0:
PowerTag Link is non
operational

112 DOCA0157EN-01 07/2019


Acti9 PowerTag Link
Diagnostics and Troubleshooting
DOCA0157EN-01 07/2019

Chapter 13
Diagnostics and Troubleshooting

Diagnostics and Troubleshooting

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
13.1 Monitoring and Diagnostics Display 114
13.2 Reset of Acti9 PowerTag Link 119
13.3 Troubleshooting 120

DOCA0157EN-01 07/2019 113


Diagnostics and Troubleshooting

Section 13.1
Monitoring and Diagnostics Display

Monitoring and Diagnostics Display

What Is in This Section?


This section contains the following topics:
Topic Page
General Diagnostics 115
Communication Diagnostics 116

114 DOCA0157EN-01 07/2019


Diagnostics and Troubleshooting

General Diagnostics

Date/Time

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Diagnostics → General → Date/Time.

The Date/Time page displays the following information:

Parameters Description
Date/Time
Date Displays the current date in the format YYYY-MM-DD.
Time Displays the current in the local time zone in the format hh:mm:ss.
Uptime Displays the elapsed time since the last restart of the device.
Last Date/Time Synchronization
Last Synchronization Displays when the last synchronization happened.
Last Synchronization Time Displays the time source of the last synchronization.
Source
Last Synchronized Date Displays the last synchronized date in the format YYYY-MM-DD.
Last Synchronized Time Displays the last synchronized time in the format hh:mm:ss.

DOCA0157EN-01 07/2019 115


Diagnostics and Troubleshooting

Communication Diagnostics

Ethernet

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Diagnostics → Communication → Ethernet.

The Ethernet page displays the global and port statistics of the Ethernet network.

Function Name Description


Ethernet Global Statistics Frames Received OK Displays the number of frames received from all the Ethernet ports.
Frames Transmitted OK Displays the number of frames transmitted from all the Ethernet ports.
Reception Errors Displays the number of errors during reception of the frames.
Ethernet Port Statistics Link speed Displays link speed on Ethernet port.
Duplex mode Displays the communication mode of the Ethernet port. It can be half
duplex or full duplex.

Click Reset to clear the Ethernet frame counters.

IP Network Services

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Diagnostics → Communication → IP Network Services.

116 DOCA0157EN-01 07/2019


Diagnostics and Troubleshooting

Function Name Description


Modbus TCP Port Port status Displays the current status of the Modbus/TCP port.
Opened TCP connections Displays the number of established Modbus/TCP connections.
Received messages Displays the counter of received Modbus/TCP messages.
Transmitted messages Displays the counter of transmitted Modbus/TCP messages.
Modbus TCP Port Connections Displays the statistics of open Modbus/TCP connections.

Click Reset to clear the Modbus/TCP counter.

Wireless Network Quality Indicators

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Diagnostics → Communication → Wireless Network Quality Indicators.

The Wireless Network Quality Indicators page displays wireless network quality information such as Link
Quality Indicator (LQI), Received Signal Strength Indicator (RSSI), and Packet Error Rate (PER).

Parameter Description
Modbus Address Displays the Modbus address of the wireless device.
Asset Name Displays the user-defined asset name of the wireless device.
Usage Displays the user-defined usage of the wireless device.
Product Displays the type of wireless sensor.
LQI Displays the measurement of the strength and / or quality of the received frames.
The following values of LQI indicates the quality of the received frames:
 The value from 0...29 indicates that the RF communication is bad. In this case, check whether the rules of
installation are respected. You can also change the location of the Acti9 PowerTag Link inside the panel to be
closer to the PowerTag energy sensors.
 The values from 29...59 indicates that the RF communication is average. In this case, look at the RSSI value
whether to accept the level of quality or not. If the RSSI is above limit, consider the value of LQI as acceptable.
 The value greater than 59 indicates that the RF communication is OK.

NOTE: It is recommended to use this indicator as the main indicator of acceptance.


Radio Quality Displays the quality of the frames. When the LQI value is greater then 59, it indicates with green light and when LQI
value is lesser than 29, it indicates with red light. When the LQI value is between 30 and 59, it indicates with orange
light.
RSSI Displays the measurement of the power level (in dBm) that an RF device is exchanging from the remote radio nodes.
This indicator is used if the LQI is not acceptable.
 The value < -95 dBm is not good.
 The value > -95 dBm is acceptable.

PER Displays the ratio of the packet that does not reach a destination over the total expected number of packets and is
expressed as percentage. For Acti9 PowerTag Link system, the ratio is calculated over a fixed window of five minutes.

DOCA0157EN-01 07/2019 117


Diagnostics and Troubleshooting

Email Service

Step Action
1 Launch the Acti9 PowerTag Link web page in the web browser.
2 Login with user name and password.
3 Click Diagnostics → Communication → Email Service.

The Email Service page displays the information such as number of emails sent and emails not sent. This
page also displays the error count, if any, for connection errors, authentication errors, internal errors, and
sending errors as shown in the following figure:

Parameter Description
Email Sent successfully Displays the total number of successfully sent emails.
Emails Not Sent Displays the total number of emails not delivered to the recipients.
Connection Errors Displays the total number of connection errors if a connection is lost during an email delivery.
Authentication Errors Displays the total number of authentication errors.
Internal Errors Displays the total number of internal errors during the email service.
Sending Errors Displays the total number of sending errors.

Click Reset to clear the Email counter.

118 DOCA0157EN-01 07/2019


Diagnostics and Troubleshooting

Section 13.2
Reset of Acti9 PowerTag Link

Reset of Acti9 PowerTag Link

Description

Resetting Acti9 PowerTag Link


There are two levels of reset:
 Level 1: Press and hold the Reset button between 5 to 10 seconds to retain all the configurations of the
product. However, the mode of IP acquisition is set to DHCP mode, that is if you had set up a static IP
address and lost your IP address, you can still retrieve your product using DHCP.
 Level 2: Press and hold the Reset button for more than 10 seconds, the Acti9 PowerTag Link is reset
to the factory parameter settings.
The reset data is as follows:
 The user application name is set to myPowerTagLink-xxxx (IP address).
 The building name becomes default.
 The mode of IP acquisition is set to DHCP.
 The password is set to the default value.
 The panel information saved in Acti9 PowerTag Link is erased.
 The user accounts are erased (only default user accounts are retained).
 The wireless device configurations are deleted.
 The IP related settings are set to default value (date/time, DNS, IP filter, and email service).
 Generic events are set to default configurations.
 Specific alarm is deleted.

NOTICE
HAZARD OF EQUIPMENT DAMAGE
Do not switch off the power supply until the LED status stops blinking in RED, as the reboot is still in
progress.
Failure to follow these instructions can result in equipment damage.

DOCA0157EN-01 07/2019 119


Diagnostics and Troubleshooting

Section 13.3
Troubleshooting

Troubleshooting

What Is in This Section?


This section contains the following topics:
Topic Page
Common Problems 121
Description of Status LED 123
Description of Ethernet Status LED 124
Description of Wireless Status LED 125

120 DOCA0157EN-01 07/2019


Diagnostics and Troubleshooting

Common Problems

Description
The following table describes the abnormal behavior and diagnostics, and provides some corrective
actions:

Problem Diagnostics Action


Web page is displayed only with texts The text and graphics in the web page is loaded Refresh the browser.
without graphics. based on the traffic and disruptions on the IT
network.
IP setting changes are not effected. IP settings not applied Reboot the device if the changes do not take
effect within two minutes.
Firmware upgrade is not succeeded. PowerTag Link is disconnected from the Follow the below steps to recover the PowerTag
network Link:
1. Disconnect PowerTag Link from the network.
2. Power cycle the PowerTag Link.
3. Connect your PC or laptop directly to the
PowerTag Link.
4. Use Automatic Discovery from the
EcoStruxure Power Commission software to
connect Acti9 PowerTag Link, see
Ecostruxure Power Commission Online
Help.
5. Launch firmware upgrade.
Acti9 PowerTag Link has lost the Pollution on the radio frequency channel Change the radio frequency channel that
communication with wireless devices. communicates between wireless devices and
Acti9 PowerTag Link in the Settings →
Communication → Wireless Network
Configuration page.
A wireless device is not Acti9 Powertag Link does not recognize this Upgrade the firmware of Acti9 PowerTag Link
detected/discovered by Acti9 PowerTag type of wireless devices. with EcoStruxure Power Commission software,
Link. see Ecostruxure Power Commission Online
Help.

DOCA0157EN-01 07/2019 121


Diagnostics and Troubleshooting

Problem Diagnostics Action


You have detected a dysfunction of the Lost data, problem of data display on webpage Pre-requisite:
gateway. or on Modbus registers, lost connexion with the You should have a backup file saved on your
wireless devices. laptop by using the backup function available in
the Maintenance menu of the webpage. The file
will be automatically saved under the name
“backup.dat”

1. Apply reset to factory settings (reset level 2):


Fast red blink (2 blinks / sec) while pressing
the reset button for more than 10 seconds.
The LED stops after the product is restarting,
do not switch off until the LED stops blinking.
If step 1 is not successful, apply step 2.
2. Replace the default gateway by a new one
(with the same commercial reference).
Power ON the new PowerTag Link and
connect to the webpage (see page 36).
Go to Maintenance → Backup & Restore,
click Browse and open the backup file (.dat)
from the previous gateway. Then, click
Restore.

NOTE: If you have communication issues (Wireless LED not OK or communication loss), please refer to
the recommendations made in Chapter 1 - Acti9 PowerTag System --> Wireless Comunication Devices.

122 DOCA0157EN-01 07/2019


Diagnostics and Troubleshooting

Description of Status LED

Status LED
The following table lists the Status LED according to the operating mode:

Mode Status LED Status


Initialization / Green light: Product operates normally.
Operation
Start-up Alternate green and red light every second: Device is starting.

Factory Settings Orange light: The PowerTag Link is


 in DHCP client mode
 DHCP server has not assigned IP address

Reset (level 1) Green blink: Reset button acknowledgment (pressed between 5 to 10 seconds). IP settings are
reconfigured to DHCP mode.
Reset (level 2) Red blink (Fast, 2 blinks/sec): while pressing the reset button for more than10 seconds. The LED stops
blinking after the reset button is released: do not switch off the product until the LED stops blinking in
RED for at least 30 seconds, as the product restarts.
Duplicate IP Red blink (1 blink per second): System has detected duplicate IP address. Check and change the IP
address address of the PowerTag Link.
Degraded Orange blink: Power supply of the product is degraded.

Failure Red light: Out of service or hardware failure.

DOCA0157EN-01 07/2019 123


Diagnostics and Troubleshooting

Description of Ethernet Status LED

Ethernet Status LED

Mode LK/10-100/ACT LED Status


Ethernet communication Activity at 10 Mbps: alternate yellow and white

Activity at 100 Mbps: alternate green and white

124 DOCA0157EN-01 07/2019


Diagnostics and Troubleshooting

Description of Wireless Status LED

Wireless Status LED


The following table lists the Wireless Status LED according to the operating mode:

Mode Wireless Status LED Status


Initialization Amber light: not configured

Startup Amber blink: looking for wireless device

Operation Flash green every five seconds: networking complete (normal operation)

Degraded Green blink (1 blink per 5 seconds): downgraded while boot mode

Disabled No light: wireless disabled

DOCA0157EN-01 07/2019 125


Diagnostics and Troubleshooting

126 DOCA0157EN-01 07/2019


Acti9 PowerTag Link

DOCA0157EN-01 07/2019

Appendices

DOCA0157EN-01 07/2019 127


128 DOCA0157EN-01 07/2019
Acti9 PowerTag Link
Abbreviated title of Chapter
DOCA0157EN-01 07/2019

Appendix A
Appendix Details of Modbus Functions

Appendix Details of Modbus Functions

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Modbus TCP/IP Functions 130
Modbus TCP/IP Exception Codes 132
Function 8: Modbus Diagnostics 133
Function 43-14: Read Device Identification (Basic) 135
Function 43–15: Read Date and Time 137
Function 43-16: Write Date and Time 138
Function 100–4: Read Non-Adjacent Registers 139

DOCA0157EN-01 07/2019 129


Abbreviated title of Chapter

Modbus TCP/IP Functions

General Description
The Modbus messaging service provides a client/server communication between devices connected on
an Ethernet TCP/IP network.
The client/server model is based on four type of messages:
 Modbus Request, the message sent on the network by the client to initiate a transaction.
 Modbus Indication, the request message received on the server side.
 Modbus Response, the response message sent by the server.
 Modbus Confirmation, the response message received on the client side.

The Modbus messaging services (client/server model) are used for real time information exchange
between:
 Two device applications.
 Device application and other device.
 HMI/SCADA applications and devices.
 A PC and a device program providing on line services.

A dedicated header is used on TCP/IP to identify the Modbus Application Data Unit. It is called the MBAP
header (Modbus Application Protocol header).

The MBAP header contains the following fields:

Fields Length Description Client Server


Transaction Identifier 2 bytes Identification of a Modbus Initialized by the client Recopied by the server from the
Request/Response transaction received request
Protocol Identifier 2 bytes 0 = Modbus protocol Initialized by the client Recopied by the server from the
received request
Length 2 bytes Number of following bytes Initialized by the client Initialized by the server (Response)
(Request)
Unit Identifier 1 byte Identification of a remote slave Initialized by the client Recopied by the server from the
connected on a serial line or on received request
other buses

Table of Modbus Functions


The following table describes in detail the functions supported by Acti9 PowerTag Link devices:

Function Code Function Name


01 Read n output or internal bits
02 Read n input bits
03 Read n output or internal bits
05 Write 1 bit
06 Write 1 word

08 (1) Modbus diagnostic data


15 Write n bits
16 Write n words
43-14 (2) Read identification

130 DOCA0157EN-01 07/2019


Abbreviated title of Chapter

Function Code Function Name


43-15(3) Read the date and time

43-16(4) Write the date and time

100-4(5) Read non-adjacent words where n ≤ 100

(1)
For more details, see the appendix describing function 8 (see page 133)
(2)
For more details, see the appendix describing function 43-14 (see page 135)
(3)
For more details, see the appendix describing function 43-15 (see page 137)
(4)
For more details, see the appendix describing function 43-16 (see page 138)
(5)For more details, see the appendix describing function 100-4 (see page 139)

DOCA0157EN-01 07/2019 131


Abbreviated title of Chapter

Modbus TCP/IP Exception Codes

Exception Responses
Exception responses issued by the master or a slave can be the result of data processing errors. One of
the following events can occur after a request from the master:
 If the slave receives the request from the master without a communication error and manages the
request correctly, it sends back a normal response.
 If the slave does not receive the request from the master due to a communication error, it does not send
back a response. The master program ends by applying a time delay condition to the request.
 If the slave receives the request from the master but detects a communication error, it does not send
back a response. The master program ends by applying a time delay condition to the request.
 If the slave receives the request from the master without a communication error but cannot manage it
(for example, the request consists of reading a register that does not exist), the slave sends back an
exception response to inform the master of the nature of the error.

Exception Frame
The slave sends an exception frame to the master to indicate an exception response. An exception
response consists of four fields:

Field Definition Size


1 Slave number 1 byte
2 Exception function code 1 byte
3 Exception code n bytes
4 Check 2 bytes

Managing Modbus Exceptions


The exception response frame consists of two fields that distinguish it from a normal response frame:
 The exception response's exception function code is the same as the original request function code plus
128 (0x80).
 The exception code depends on the communication error detected by the slave.
The following table describes the exception codes managed by the Acti9 PowerTag Link device:

Exception Code Name Description


01 Illegal function The function code received in the request is not a permitted action for the slave. It
is possible that the slave is in an unsuitable state to process a specific request.
02 Illegal data address The data address received by the slave is not a permitted address for the slave.
03 Illegal data value The value of the request data field is not a permitted value for the slave.
04 Slave device failure The slave is unable to perform a required action due to an unrecoverable error.
06 Slave device busy The slave is busy processing another command. The master should send the
request once the slave is free.

NOTE: For more information, a detailed description of the Modbus protocol is available on
www.modbus.org.

Access to Variables
A Modbus variable can have the following attributes:
 Read-only
 Read/write
 Write-only

NOTE: An attempt to write to a read-only variable generates an exception response.

132 DOCA0157EN-01 07/2019


Abbreviated title of Chapter

Function 8: Modbus Diagnostics

Structure of Modbus Messages Concerning Acti9 PowerTag Link Diagnostic Counter Management
Request

Definition Number of Bytes Value


Slave number 1 byte 0xFF
Function code 2 bytes 08 (0x08)
Sub-function code 2 bytes 22 (0x0016)
Operation code 2 bytes 1 ((0x0001) see below list for operation code)
Diagnostic control 2 bytes 0x0100 (see below list for diagnostic control)
Starting entry index 1 byte 0x00 (0 to 255)

The operation code field is used to select the diagnostic and the statistic data to be read from the device.

Most Significant Byte Least Significant Byte


15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Reserved Protocol Version Operation Code

Bit assignments are included in the table below:

Bit Field Description


15...12 Reserved Must be zero
11...8 Protocol Version (PV) Indicates version of the protocol of the client (requestor)
Values are: 0x00 (initial version)
7...0 Operation Code Indicates function to be performed by the command
Values are:
 0x01 = Read diagnostic data
 0x02 = Clear diagnostic data
 0x03 = Clear all diagnostic data
 0x04 = List ports

The diagnostic control field provides the data selection information for this protocol as well as specifies the
logical port from which, the data is to be retrieved (if applicable). The diagnostic control field is defined as
shown in the following table:

Most Significant Byte Least Significant Byte


15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Data Selection Code Port Select

Bit assignments are included in the following table:

Bit Field Description


15...8 Data Selection Code (DS) Indicates the diagnostic data to retrieve or to clear from the logical port. See the table
below for valid values.
7...0 Port Select (PS) Indicates the logical port number to retrieve the selected data from
 0x00 = the internal port of a device that supports an embedded switch or any
single port not accessible externally
 0x01 to 0xFE = logical number of the desired port
 0xFF = the port the current request came in

This value should be 0xFF if the requested data is not port specific. See the Port
Select Needed column in the table below for which Data Selection Code requires a
valid port select value.

DOCA0157EN-01 07/2019 133


Abbreviated title of Chapter

Data selection code

Data Selection Code Diagnostic Data Retrieved Port Select Needed Type
0x00 Reserved Public
0x01 Basic network diagnostics Public
0x02 Ethernet port diagnostics Yes Public
0x03 Modbus TCP port 502 diagnostics Public
0x04 Modbus TCP port 502 connection table Public
0x05 to 0x7E Reserved for other public codes Public
0x7F Data structure offsets Public
0x80 to 0xFF Reserved Reserved

Response

Definition Number of Bytes Value


Slave number 1 byte 0xFF
Function code 2 bytes 08 (0x08)
Sub-function code 2 bytes 22 (0x0016)
Operation code 2 bytes 1 ((0x0001) see the above list for operation code)
Diagnostic control 2 bytes 0x0100 (see the above list for diagnostic control)
Starting entry index 1 byte 0x00 (0 to 255)

Resetting Counters
The counters are reset to 0:
 When they reach the maximum value 65535.
 When they are reset by a Modbus command (function code 8, sub-function code 10).
 When the power is cut off, or
 When the communication parameters are modified.

134 DOCA0157EN-01 07/2019


Abbreviated title of Chapter

Function 43-14: Read Device Identification (Basic)

Structure of Modbus Read Device Identification Messages


The ID consists of ASCII characters called objects.
Request for basic information

Definition Number of Bytes Value


Slave number 1 byte 0xFF
Function code 1 byte 0x2B
Sub-function code 1 byte 0x0E
Product ID 1 byte 0x01
Object identifier 1 byte 0x00

Response with basic information

Definition Number of Value


Bytes
Slave number 1 byte 0xFF
Function code 1 byte 0x2B
Sub-function code 1 byte 0x0E
Product ID 1 byte 0x01
Conformity level 1 byte 0x01
Reserved 1 byte 0x00
Reserved 1 byte 0x00
Number of objects 1 byte 0x03
Object 0: manufacturer name Object number 1 byte 0x00
Object length 1 byte 0x12
Object content 18 bytes Schneider Electric
Object 1: product code Object number 1 byte 0x01
Object length 1 byte 0x08
Object content 8 bytes A9XMWD20/A9XMWD100
Object 2: version number Object number 1 byte 0x02
Object length 1 byte 0x06 (minimum)
Object content 6 bytes Vx.y.z
minimum

Request for complete information

Definition Number of Bytes Value


Slave number 1 byte 0xFF
Function code 1 byte 0x2B
Sub-function code 1 byte 0x0E
Product ID 1 byte 0x02
Object identifier 1 byte 0x00

Response with complete information

Definition Number of Value


Bytes
Slave number 1 byte 0xFF
Function code 1 byte 0x2B
Sub-function code 1 byte 0x0E
Product ID 1 byte 0x02
Conformity level 1 byte 0x02
Reserved 1 byte 0x00

DOCA0157EN-01 07/2019 135


Abbreviated title of Chapter

Definition Number of Value


Bytes
Reserved 1 byte 0x00
Number of objects 1 byte 0x05
Object 0: manufacturer name Object number 1 byte 0x00
Object length 1 byte 0x12
Object content 18 bytes Schneider Electric
Object 1: product code Object number 1 byte 0x01
Object length 1 byte 0x08
Object content 8 bytes A9XMWD20/A9XMWD100
Object 2: version number Object number 1 byte 0x02
Object length 1 byte 0x06 (minimum)
Object content 6 bytes Vx.y.z
minimum

NOTE: The above table describes how to read the ID of a Acti9 PowerTag Link.

136 DOCA0157EN-01 07/2019


Abbreviated title of Chapter

Function 43–15: Read Date and Time

Structure of Modbus Read Date and Time Messages


Request

Definition Number of Bytes Value Example


Slave number 1 byte 0x2F 47
Function code 1 byte 0x2B 43
Sub-function code 1 byte 0x0F 15
Reserved 1 byte 0x00 Reserved

Response

Definition Number of Bytes Value Example


Slave number 1 byte 0x2F 47
Function code 1 byte 0x2B 43
Sub-function code 1 byte 0x0F 15
Reserved 1 byte 0x00 Reserved
Date and time(1) byte 1 Not used 1 byte 0x00 Not used
byte 2 Year 1 byte 0x0A Year 2010
byte 3 Month 1 byte 0x0B Month of November
byte 4 Day of the month 1 byte 0x02 Second day of the month
byte 5 Hour 1 byte 0x0E 14 hours
byte 6 Minute 1 byte 0x20 32 minutes
byte 7 and byte 8 Millisecond 2 bytes 0x0DAC 3.5 seconds
(1) See description of the DATE type (see page 97).

DOCA0157EN-01 07/2019 137


Abbreviated title of Chapter

Function 43-16: Write Date and Time

Structure of Modbus Write Date and Time Messages


Request

Definition Number of Value Example


Bytes
Slave number 1 byte 0x2F 47
Function code 1 byte 0x2B 43
Sub-function code 1 byte 0x10 16
Reserved 1 byte 0x00 Reserved
Date and time(1) byte 1 not used 1 byte 0x00 Not used
byte 2 Year 1 byte 0x0A Year 2010
byte 3 Month 1 byte 0x0B Month of November
byte 4 Day of the month 1 byte 0x02 Second day of the month
byte 5 Hour 1 byte 0x0E 14 hours
byte 6 Minute 1 byte 0x20 32 minutes
byte 7 and byte 8 Millisecond 2 bytes 0x0DAC 3.5 seconds
(1)
See description of the DATE type (see page 97).

Response

Definition Number of Value Example


Bytes
Slave number 1 byte 0x2F 47
Function code 1 byte 0x2B 43
Sub-function code 1 byte 0x10 15
Reserved 1 byte 0x00 Reserved
Date and time(1) byte 1 Not used 1 byte 0x00 Not used
byte 2 Year 1 byte 0x0A Year 2010
byte 3 Month 1 byte 0x0B Month of November
byte 4 Day of the month 1 byte 0x02 Second day of the month
byte 5 Hour 1 byte 0x0E 14 hours
byte 6 Minute 1 byte 0x20 32 minutes
byte 7 and byte 8 Millisecond 2 bytes 0x0DAE 3.502 seconds
(1)
See description of the DATE type (see page 97).

138 DOCA0157EN-01 07/2019


Abbreviated title of Chapter

Function 100–4: Read Non-Adjacent Registers

Structure of Modbus Read n Non-Adjacent Registers Messages Where n ≤ 100


The example below is the case of reading of 2 non-adjacent registers.
Request

Definition Number of Bytes Value


Modbus slave number 1 byte 0x2F
Function code 1 byte 0x64
Length of data in bytes 1 byte 0x06
Sub-function code 1 byte 0x04
Transmission number(1) 1 byte 0xXX

Address of the first word to be read (MSB) 1 byte 0x00


Address of the first word to be read (LSB) 1 byte 0x65
Address of the second word to be read (MSB) 1 byte 0x00
Address of the second word to be read (LSB) 1 byte 0x67
(1) The master gives the transmission number in the request.

NOTE: The above table describes how to read addresses 101 = 0x65 and 103 = 0x67 of a Modbus slave.
The Modbus slave number is 47 = 0x2F.
Response

Definition Number of Bytes Value


Modbus slave number 1 byte 0x2F
Function code 1 byte 0x64
Length of data in bytes 1 byte 0x06
Sub-function code 1 byte 0x04
Transmission number(1) 1 byte 0xXX
First word read (MSB) 1 byte 0x12
First word read (LSB) 1 byte 0x0A
Second word read (MSB) 1 byte 0x74
Second word read (LSB) 1 byte 0x0C
(1) The slave sends back the same number in the response.

NOTE: The above table describes how to read addresses 101 = 0x65 and 103 = 0x67 of a Modbus slave.
The Modbus slave number is 47 = 0x2F.

DOCA0157EN-01 07/2019 139


Abbreviated title of Chapter

140 DOCA0157EN-01 07/2019


DOCA0157EN-01

Schneider Electric Industries SAS As standards, specifications and designs change from time to time, please ask for confirmation
35, rue Joseph Monier of the information given in this publication.
CS30323
F - 92506 Rueil Malmaison Cedex

www.se.com 07/2019

You might also like