INVB4000 LED Eng
INVB4000 LED Eng
INVB4000 LED Eng
Efficiency > 88 %
Without 50 Hz transformer
Specifications
General Housing 19''- plug-in case
Electrical safety EN 60950, VDE 0805 Size 3 U / 84 HP, 360 mm depth
Efficiency > 88 % at nominal load Weight approx. 13.5 kg
Galvanic isolation 3.75 kVDC Classification IP 20
EMC (emission) EN 50081-1 Cooling 2 internal, regulated fans
curve EN 55022A
EMC (immunity) EN 50082-2 Electrical connections
Operating temperature -5°C to +50°C, non condensing Input DC 3 high current terminal blocks
+50°C to +70°C, 2%/K derating Phoenix HDFK 16 mm2
Input AC Phoenix Power-Combicon plug
Input DC Output AC Phoenix Power-Combicon plug
INVB4000-48/60 48/60 VDC (38 – 72 VDC) Alarm Binder round connector
INVB4000-110 110 VDC (88 – 132 VDC)
INVB4000-125 125 VDC (88 – 148 VDC) All electrical connections are located on the front.
INVB4000-220 220 VDC (178 – 264 VDC)
Special features
Output AC Inverter with integrated static bypass for automatic load
Voltage 230 VAC switch from mains to inverter or vice versa (with voltage
failure tolerance +/-5% synchronization).
Frequency 50 Hz (60 Hz),
sinewave processor controlled Switching time: typically 4 ms
Output power 4 kVA / 3200 W
Power factor 0.8 The LED bar on the front panel displays the output power
Load range 0 – 100 % of the inverter. Each LED signals 25 % of the nominal
Crestfactor > 2.5 load.
Harmonic distortion <2%
Signals
Visual LEDs for load display, bypass Warranty 24 months
status and “Power Good”/ON
Electrical potential-free alarm contacts for Order code INVB4000-48/60-230
“Power Good” and bypass status INVB4000-110-230
INVB4000-125-230
Operation battery switch, INVB4000-220-230
push button for setup
Power Innovation GmbH Telefon: +49 (0) 4202 5117-0 Amtsgericht Walsrode Geschäftsführer:
Rehland 2 Fax: +49 (0) 4202 5117-70 HRB 121695 Dipl.-Ing. Bernhard Böden
28832 Achim eMail: [email protected] Steuer Nr. 48-201-24705
Internet: www.powerinnovation.com UST-ID DE 114 426 732