0% found this document useful (0 votes)
69 views72 pages

Anybus Ethernet Ip To Modbus TCP Linking Device Hms En2mb R User Manual

Uploaded by

ozeias ferreira
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
69 views72 pages

Anybus Ethernet Ip To Modbus TCP Linking Device Hms En2mb R User Manual

Uploaded by

ozeias ferreira
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 72

User Manual

EtherNet/IP to Modbus-TCP
Linking Device

Doc.Id. SCM-1202-008
Rev. 1.1

Connecting DevicesTM

+$/067$'‡&+,&$*2‡.$5/658+(‡72.<2‡%(,-,1*‡0,/$12‡08/+286(‡&29(175<‡381(‡&23(1+$*(1

HMS Industrial Networks


Mailing address: Box 4126, 300 04 Halmstad, Sweden E-mail: [email protected]
Visiting address: Stationsgatan 37, Halmstad, Sweden Web: www.anybus.com
Important User Information 2-1

Important User Information


This document is intended to provide a good understanding of the functionality offered by the EtherNet/IP to Mod-
bus-TCP linking device. The reader of this document is expected to be familiar with high level software design,
and communication systems in general.

Liability

Every care has been taken in the preparation of this manual. Please inform HMS Industrial Networks AB of any
inaccuracies or omissions. The data and illustrations found in this document are not binding. We, HMS Industrial
Networks AB, reserve the right to modify our products in line with our policy of continuous product development.
The information in this document is subject to change without notice and should not be considered as a commit-
ment by HMS Industrial Networks AB. HMS Industrial Networks AB assumes no responsibility for any errors that
may appear in this document.
There are many applications of this product. Those responsible for the use of this device must ensure that all the
necessary steps have been taken to verify that the applications meet all performance and safety requirements in-
cluding any applicable laws, regulations, codes, and standards.
HMS Industrial Networks AB will under no circumstances assume liability or responsibility for any problems that
may arise as a result from the use of undocumented features, timing, or functional side effects found outside the
documented scope of this product. The effects caused by any direct or indirect use of such aspects of the product
are undefined, and may include e.g. compatibility issues and stability issues.
The examples and illustrations in this document are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular implementation, HMS Industrial Networks AB cannot
assume responsibility for actual use based on these examples and illustrations.

Intellectual Property Rights

HMS Industrial Networks AB has intellectual property rights relating to technology embodied in the product de-
scribed in this document. These intellectual property rights may include patents and pending patent applications
in the US and other countries.

Trademark Acknowledgements

Anybus ® is a registered trademark of HMS Industrial Networks AB. All other trademarks are the property of their
respective holders.

Warning: This is a class A product. in a domestic environment this product may cause radio interference in
which case the user may be required to take adequate measures.
ESD Note: This product contains ESD (Electrostatic Discharge) sensitive parts that may be damaged if ESD
control procedures are not followed. Static control precautions are required when handling the prod-
uct. Failure to observe this may cause damage to the product.
Warning: DO NOT USE SD CARD OR USB CONNECTOR WHILE CIRCUIT IS LIVE UNLESS THE AREA IS
KNOWN TO BE FREE OF IGNITABLE CONCENTRATIONS OF FLAMMABLE GAS OR VAPORS.

EtherNet/IP to Modbus-TCP Linking Device User Manual


Rev 1.1
Copyright© HMS Industrial Networks AB
Nov 2016 Doc Id SCM-1202-008

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Table of Contents

Preface About This Document ..................................................................... 6


Related Documents..................................................................................................................... 6
Document History ...................................................................................................................... 6
Conventions & Terminology..................................................................................................... 6

Chapter 1 EtherNet/IP to Modbus-TCP Linking Device............................... 7


Introduction ................................................................................................................................. 7
Unique Integration into Studio 5000 .................................................................................. 7
Configuring the EtherNet/IP Network .................................................................................. 7
Functional Overview .................................................................................................................. 8
Data Exchange............................................................................................................................. 9
I/O Mapped Data ..................................................................................................................... 10
Parameter Data .......................................................................................................................... 10
Control/Status Word................................................................................................................ 10
Live List ...................................................................................................................................... 11
Transaction Status List ............................................................................................................. 12
Exception Code List ................................................................................................................. 13

Chapter 2 About the HMS-EN2MB-R Linking Device..................................14


External View ............................................................................................................................ 14
Mounting the Linking Device ................................................................................................. 15
DIN-rail Mounting .......................................................................................................... 15
Wall Mounting................................................................................................................. 16
Status LEDs ............................................................................................................................... 17
EtherNet/IP Connectors......................................................................................................... 18
USB Connector.......................................................................................................................... 18
Modbus-TCP Connectors........................................................................................................ 18
Power Connector ...................................................................................................................... 19

Chapter 3 Studio 5000 Implementation Example ...........................................20


Step by Step Guide.................................................................................................................... 20

Chapter 4 SD Card Functionality ....................................................................27


General Advice and Guidelines .............................................................................................. 27
Starting Up ................................................................................................................................. 28
Easy Backup ............................................................................................................................... 28
Simple Configuration Copy ..................................................................................................... 28
Easy Replacement ..................................................................................................................... 29
SD Card Synchronization Failure ........................................................................................... 30

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Chapter 5 Modbus-TCP Functions................................................................. 31

Chapter 6 Tag Editor ...................................................................................... 32


Tag Editor Overview ................................................................................................................ 32
Menu Choices.................................................................................................................... 33
Tag Editor Basics....................................................................................................................... 34
Tag Arrays ....................................................................................................................... 36
Tag Rule Definitions................................................................................................................. 37

Chapter 7 Modbus Configuration Manager.................................................... 38


General Information ................................................................................................................. 38
Overview..................................................................................................................................... 39
Home................................................................................................................................ 40
Configuration ............................................................................................................................. 41
Authentication .................................................................................................................. 41
Modbus Client .................................................................................................................. 42
Modbus Servers................................................................................................................. 43
EtherNet/IP (Adapter Interface)...................................................................................... 46
Tools........................................................................................................................................... 47
HMS-EN2MB-R Management ...................................................................................... 47
Backup and Restore .......................................................................................................... 47
Mapping Overview ............................................................................................................ 48
Transaction Monitor ......................................................................................................... 49

Chapter 8 CIP Objects .................................................................................... 50


General Information ................................................................................................................. 50
Identity Object (01h)................................................................................................................. 51
Message Router (02h) ............................................................................................................... 53
Assembly Object (04h) ............................................................................................................. 54
Connection Manager (06h) ...................................................................................................... 56
DLR Object (47h) ..................................................................................................................... 59
QoS Object (48h) ...................................................................................................................... 60
ADI Object (A2h) ..................................................................................................................... 61
Port Object (F4h) ...................................................................................................................... 63
TCP/IP Interface Object (F5h) .............................................................................................. 64
Ethernet Link Object (F6h) ..................................................................................................... 67

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
V

Appendix A Technical Specification .................................................................. 69


Protective Earth (PE) Requirements...................................................................................... 69
Power Supply ............................................................................................................................. 69
Environmental Specification ................................................................................................... 69
Temperature...................................................................................................................... 69
Relative Humidity............................................................................................................. 69
EMC (CE) Compliance ............................................................................................................ 70

Appendix B Copyright Notices .......................................................................... 71

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Preface

P. About This Document


For more information, documentation etc., please visit the HMS website, www.anybus.com.

P.1 Related Documents


Document Author
Modbus Application Protocol Specification V1.1B Modbus Organization
CIP Specification, Vol 1 (CIP Common) & 2 (EtherNet/IP) ODVA

P.2 Document History

Summary of Recent Changes (1.0... 1.1)

Change Page(s)
Corrected Product Code in Identity Object (01h) to 57h 51

Revision List

Revision Date Author(s) Chapter(s) Description


1.0 2016-10-27 KaD All First release
1.1 2016-11-15 KaD 8 Minor correction

P.3 Conventions & Terminology


The following conventions are used throughout this manual:
• Numbered lists provide sequential steps
• Bulleted lists provide information, not procedural steps
• The term ‘linking device’ refers to the EtherNet/IP to Modbus-TCP linking device
• Hexadecimal values are written in the format NNNNh, where NNNN is the hexadecimal value
• A byte always consists of 8 bits
• The terms ‘master’, ‘scanner’, ‘client’ and ‘controller’ will be used interchangeably to describe a
controlling unit on the network
• The terms ‘slave’, ‘adapter’, ‘server’ and ‘device’ will be used interchangeably to describe units
that are controlled by controlling units on the network

Linking Device
Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Chapter 1

1. EtherNet/IP to Modbus-TCP Linking Device

1.1 Introduction
The EtherNet/IP to Modbus-TCP Linking Device is used to provide a seamless connection between a
Modbus-TCP network and an EtherNet/IP network. The linking device enables the master of the Eth-
erNet/IP network to control the Modbus-TCP network, and data can be transmitted transparently be-
tween the two networks.

1.1.1 Unique Integration into Studio 5000

The EtherNet/IP to Modbus-TCP linking device features a custom add-on profile (AOP) for easy in-
tegration with Studio 5000. Within this add-on profile (AOP), the HMS configuration tool can be
launched. When the configuration is ready, it can automatically be translated to structured Studio 5000
controller tags.
All network and device level configuration is done within Studio 5000.
IMPORTANT:
The add-on profile is supported by RSLogix 5000, v20 and later.

1.2 Configuring the EtherNet/IP Network


The Linking Device is an EtherNet/IP adapter (slave) on the EtherNet/IP network. The general set-
tings for the adapter interface are configured using the configuration pages. All data transfers must be
configured in Studio 5000. Please note that the size of the I/O data that can be read from and written
to the module is defined when configuring the linking device using the configuration pages.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
EtherNet/IP to Modbus-TCP Linking Device 8

1.3 Functional Overview


Internally, the linking device consists of an intelligent gateway platform, a Modbus-TCP interface and
an EtherNet/IP (slave) interface. The Modbus-TCP interface and the EtherNet/IP (slave) interface are
interconnected through the intelligent gateway platform, which basically forwards data from one net-
work to the other and vice versa as shown below.
Modbus-TCP network

Anybus Modbus-TCP

Industrial network
Master Interface

Anybus network
slave interface

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
EtherNet/IP to Modbus-TCP Linking Device 9

1.4 Data Exchange


Each of the two network interfaces exchanges data on its network through two buffers. The linking de-
vice forwards the data between these buffers as shown below. Note that this process is separated from
the network data exchange. While the linking device ensures data consistency (where applicable), it does
not feature any built-in mechanisms for synchronization between the Modbus-TCP network and the
EtherNet/IP network.

Status Word
Data To
the Modbus-TCP Data From
Modbus-TCP network

Network the Modbus-TCP

Industrial network
Network

Modbus-TCP Network Interface Industrial Network Interface


Control Word
Data From
the Modbus-TCP Data to
Network the Modbus-TCP
Network

Each buffer holds a maximum of 4096 bytes of data. The first two I/O mapped bytes in either direction
can be dedicated for control/status information, and another eight bytes of data coming from the Mod-
bus-TCP network can feature a live list. Please note that the actual number of bytes that can be ex-
changed is highly network dependent.
Through the dedicated control word, the scanner on the EtherNet/IP network starts/stops the ex-
change of data on the Modbus-TCP network, and also resets the linking device if needed. The scanner
on the EtherNet/IP network can see the status of the Modbus-TCP network in the corresponding status
word. The live list feature gives the scanner on the EtherNet/IP network the opportunity to continu-
ously see and monitor the status of each individual transaction on the Modbus-TCP network.
Two additional lists, transaction status and exception codes, retrievable from the module by the scanner
on the EtherNet/IP network, provides detailed error information about all transactions.
The amount of data that shall be exchanged, and the use of the control/status word and the live list, is
specified separately for each application. This means that even though up to 4096 bytes of data can be
potentially forwarded to an interface, the amount of data that will actually be exchanged on that network
is determined by the Modbus-TCP settings and the limitations of the master side fieldbus.
The available control/status functionality is described below, as well as the live list and the transaction
status and exception code lists. Also note that the terminology and definitions used for different types
of data vary greatly between different networking systems.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
EtherNet/IP to Modbus-TCP Linking Device 10

1.5 I/O Mapped Data


I/O mapped data is cyclic data, exchanged between the networks and/or devices at a high transfer rate.
It is associated with implicit messaging, where data is continuously sent on the network.

1.6 Parameter Data


Parameter data is usually exchanged acyclically to set or change parameters in devices before or during
normal process. Acyclical data is set up as explicit messages using CIP message instructions in Studio
5000.
Typical explicit messages that can be retrieved from the module by the scanner of the EtherNet/IP net-
work includes the transaction status list and the exception code list.

1.7 Control/Status Word


The Control/Status word is always retrievable using acyclical access. Optionally, the Control/Status
word can also be I/O mapped. If so, it is disabled by default. It can be enabled/disabled when config-
uring the EtherNet/IP network via the configuration web pages. See “EtherNet/IP (Adapter Inter-
face)” on page 46.
The Control word is a 16-bit word (uint16) used by the EtherNet/IP network to control the linking de-
vice and subsequently also the Modbus-TCP network.

Bit Value Description


0 (Least signifi- 0 Puts the linking device in idle state
cant bit) 1 Puts the linking device in run state
1 - A reboot of the linking device is triggered by a rising edge, i.e. a transition from 0
to 1
2-7 Set to zero Unused
8-15 Set to zero Unused

The Status word is a 16-bit word used by the linking device to report its current actual status to the Eth-
erNet/IP network.

Bit Value Description


0 (Least signifi- 0 The linking device is in idle state
cant bit) 1 The linking device is in run state
1 - This bit is reflecting the state of bit 1 in the control word
Either 0 or 1
2-7 (reserved) Unused
8-15 (reserved) Unused

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
EtherNet/IP to Modbus-TCP Linking Device 11

1.8 Live List


The live list features the possibility for the EtherNet/IP network to retrieve a list containing the status
of every transaction on the Modbus-TCP network.
It is accessible using parameter access, and also I/O mapped by default. The I/O mapped live list can
be enabled/disabled when configuring the EtherNet/IP network settings. See “EtherNet/IP (Adapter
Interface)” on page 46. If the I/O mapped live list is enabled, it will occupy either byte 0-7 (control/
status word not enabled) or byte 2-9 (control/status word enabled and mapped to the first two bytes) in
the input data area.
All transactions and their places in the live list are also visible in the Transaction Monitor on the config-
uration web pages.
The live list consists of a bit array with 64 elements, where each bit corresponds to a transaction on the
Modbus-TCP network as in the table below.

Byte 7 Byte 6-1 Byte 0


Bit 63 Bit 62-56 Bit 55-8 Bit 7 Bit 6 - 2 Bit 1 Bit 0
Status of trans- Status of trans- ... Status of trans- Status of trans- Status of trans- Status of trans-
action no 63 action no 62-56 action no 7 action no 6 - 2 action no 1 action no 0

• Bit set to 1
Transaction successful.

• Bit set to 0
Transaction not successful.
Note: the reason for the unsuccessful transaction can be found on the corresponding index in
the transaction status list.
The order of the transactions in the live list conforms to the order in which they are stored in the Mod-
bus Server list.

Example
Consider the following configuration:
• Server 1 : a total of 2 transactions
• Server 2 : a total of 3 transactions
• Server 3 : a total of 1 transaction
This scenario will produce a live list as follows (assuming that the transactions are successful):

Bit 63 Bit 62 - 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0


- - Server 3, Server 2, Server 2, Server 2, Server 1, Server 1,
transaction 1 transaction 3 transaction 2 transaction 1 transaction 2 transaction 1
0 0 1 1 1 1 1 1

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
EtherNet/IP to Modbus-TCP Linking Device 12

1.9 Transaction Status List


This list holds information about the transactions between the Modbus network and the linking device,
from the perspective of the linking device.
It is a list available from the module, which is possibl3e to be retrieved acyclically (using parameter ac-
cess) by the EtherNet/IP network. It contains a byte array with 64 elements, where each byte contains
a transaction status code as in the table below.
The indexes in the transaction status list correspond completely to the indexes in the transaction live list.

Byte 0 Byte 1 Byte 2-6 Byte 7 Byte 8 - 55 Byte 56-62 Byte 63


Status of trans- Status of trans- Status of trans- Status of trans- ... Status of trans- Status of trans-
action no 0 action no 1 action no 2-6 action no 7 action no 56-62 action no 63

Transaction status codes

Transaction Status
Description
Code
0 Running ok
1 Gateway idle
2 No link
3 Modbus exception
4 Timeout
5 Linking device disconnect
6 Server disconnect
7 Cannot connect
8 Modbus header error
9 Internal device error
10 No valid data
11 Stop sending data to Modbus server
12 Unconfigured transaction

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
EtherNet/IP to Modbus-TCP Linking Device 13

1.10 Exception Code List


If Modbus transactions fail, the slaves can respond with an exception code. These can be found in the
exception code list available from the module, possible to be retrieved acyclically (using parameter ac-
cess) by the EtherNet/IP network. It contains a byte array with 64 elements, where each byte contains
an transaction exception code as in the table below. The indexes in the exception code list correspond
completely to the indexes in the transaction live list.

Byte 0 Byte 1 Byte 2-6 Byte 7 Byte 8-55 Byte 56-62 Byte 63
Exception code Exception code Exception code Exception code Exception code Exception code Exception code
for transaction for transaction for transaction for transaction for transaction for transaction for transaction
no 0 no 1 no 2 - 6 no 7 no 8 - 55 no 56 - 62 no 63

Standard Modbus exception codes

Exception Code Description


00 No error
01 Illegal function
02 Illegal data address
03 Illegal data value
04 Slave device failure
05 Acknowledge
06 Slave device busy
08 Memory parity error
0A Gateway path unavailable
0B Gateway target device failed to respond

Note: The exception codes found in the exception code list are only relevant if the corresponding trans-
action status codes equals 3: “Modbus exception”. See “Transaction Status List” on page 12 for more
information.
Note: If the slave responds with an exception code not in the list, refer to the documentation of the
slave for details.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Chapter 2

2. About the HMS-EN2MB-R Linking Device

2.1 External View


• A: Power Connector
This connector is used to apply power to the linking A
device. It is also possible to connect protective earth B
(PE) to the power connector. See “Power Connec-
tor” on page 19.

• B: SD Card Slot
This slot adds the possibility to store and load con-
C
figurations from an SD card. See “SD Card Func-
tionality” on page 27.
D E

• C: USB Port
This port adds the possibility to connect a PC to the
linking device to perform firmware upgrades. See
“USB Connector” on page 18.

• D: Status LEDs
See “Status LEDs” on page 17.

• E: DIN-rail Connector
The DIN-rail mechanism fastens the linking device
to a DIN-rail and connects the module to protective
earth (PE). See “Mounting the Linking Device” on
F
page 15.

• F: EtherNet/IP Connectors
See “EtherNet/IP Connectors” on page 18.
G

• G: Modbus-TCP Connectors
2-port switch with daisy-chain functionality. See
“Modbus-TCP Connectors” on page 18.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
About the HMS-EN2MB-R Linking Device 15

2.2 Mounting the Linking Device


The EtherNet/IP to Modbus-TCP Linking Device can be physically installed either by mounting it onto
a DIN-rail or, if installed in areas exposed to vibration, by mounting it on a wall for more stability.

2.2.1 DIN-rail Mounting

Make sure the DIN-rail fastening mechanism on the back of


the module is in a fixed and closed position, i. e. pushed all the
way up.

To mount the module, first hook it on to the DIN-rail (1),


then push it against the DIN-rail to make it snap on (2).

To unmount the module, a screwdriver is needed. Use the


screwdriver to push the DIN-rail fastening mechanism on the
back of the module down until it locks in a fixed and open po-
sition (1). Then unhook the module from the DIN-rail (2).

Note: Do not leave the module with the DIN-rail fastening


mechanism in a fixed and open position. This may eventually
wear the fastening mechanism out so it cannot be used effi-
ciently. Be sure to push the DIN-rail fastening mechanism
back into the fixed and closed position after demounting the
module.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
About the HMS-EN2MB-R Linking Device 16

2.2.2 Wall Mounting

Use the wall mounting option if there is a need to place the linking device in an environment exposed
to vibration. This way of mounting the module offers more stability than the traditional DIN-rail mount-
ing.
Note: The device should be fastened in a standing-up position, to ensure a constant air flow.
Note: When mounting the device to a wall using the wall mount option, do not forget to connect the
module to protective earth (PE) via the power connector. See “Power Connector” on page 19.

Mounting Instructions
Step Description Visual description
Open up the package containing the wall
1 mounting accessories.

- One metal frame


- Industrial velcro
- Four plastic vibration dampers

Remove the plastic protection from one


2 side of the velcro.

Attach the velcro to the metal frame.

Attach the four plastic vibration dampers


to the linking device, on the side that will
face the wall.

Remove the plastic protection from the


3 other side of the velcro.

Turn the device around, so that the plastic


4 vibration dampers face downwards.

Fasten the metal frame to the device by


pressing the frame firmly against the
device, making the two velcro parts attach
to each other.

Attach the metal frame and the device to a


5 wall using screws and washers (not
enclosed).

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
About the HMS-EN2MB-R Linking Device 17

2.3 Status LEDs


Note: A test sequence is performed on all LEDs during startup.
Note: An identification LED sequence can be performed on LEDs 1, 5 and 6 by clicking the “Wink
device” button in the linking device management section in the web configuration interface.

Linking Device and Modbus-TCP Network LEDs

LED no State Status


1 - Module Status Off Power off
EtherNet/IP Alternating red/green Boot sequence
Flashing green Idle
Green Running
Flashing red Major or minor recoverable error
Red Major or minor unrecoverable error
(Exception state or fatal)
2 - Network Status Off Power off or no IP address
EtherNet/IP Green Online, one or more connection estab-
lished (CIP Class 1 or 3)
Flashing green Online, no connections established
Red Duplicate IP address, fatal error
Flashing red One or more connections timed out (CIP
Class 1 or 3)
3, 4 - EtherNet/IP Off No link
Ethernet Link 1 and 2 Flashing green Receiving/transmitting Ethernet packets
at 100 Mbit
Flashing yellow Activity, receiving/transmitting Ethernet
packets at 10 Mbit
5 - SD card Green Accessing SD card
(SD) Red Failure
6 - Modbus-TCP Status Off Power off
(MTCP) Green Communicating with Modbus-TCP net-
work
Flashing green Idle
Flashing red Transaction error or timeout
Red Fatal error
7, 8 - Modbus-TCP Off No link
Ethernet Link 1 and 2 Flashing green Receiving/transmitting Ethernet packets
at 100 Mbit
Flashing yellow Activity, receiving/transmitting Ethernet
packets at 10 Mbit

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
About the HMS-EN2MB-R Linking Device 18

2.4 EtherNet/IP Connectors


Connectors for the EtherNet/IP network are found at the lower front of the module.

Pin no Description
1 TX+
2 TX-
3 RX+
6 RX- 1 8
4, 5, 7, 8 Not connected
Housing Shield

2.5 USB Connector


At the upper front of the module there is a USB connector used for firmware upgrades.

Pin no. Description


1 +5V Input
2 USBDM (USB communication signals) 2 1

3 USBDP (USB communication signals)


4 Signal GND
3 4
Housing Cable Shield

2.6 Modbus-TCP Connectors


The Modbus-TCP connectors are found at the bottom of the module.

Pin no. Description


1 TX+
2 TX-
3 RX+
4 Not connected
5 Not connected
6 RX- 1 8

7 Not connected
8 Not connected
Housing Shield

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
About the HMS-EN2MB-R Linking Device 19

2.7 Power Connector


Pin no. Description
1 +24V DC
2 GND
3 PE (Protective Earth)
1 2 3

Notes:
• Use 60/75 or 75×C copper (CU) wire only.
• The terminal tightening torque must be between 5... 7 lbs-in (0.5... 0.8 Nm)
See also...
- “Power Supply” on page 69.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Chapter 3

3. Studio 5000 Implementation Example


This section will guide you through all steps necessary to create a basic configuration for the
HMS-EN2MB-R Linking Device.

3.1 Step by Step Guide


1. Start the Studio 5000 software. Expand the “I/O Configuration” folder in the tree view.
Right-click “Ethernet” and select “New Module”.

2. Select the HMS-EN2MB-R Linking Device (catalogue number: HMS-EN2MB-R) and click
“Create”.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Studio 5000 Implementation Example 21

3. In the “New Module” window, assign a name to the module. The IP address should be set via
the BOOTP-DHCP server and entered in the IP address field. Click “Change” in the
“Module Definition” section.

4. In the “Module Definition” window, launch the configuration manager for the
HMS-EN2MB-R linking device.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Studio 5000 Implementation Example 22

5. This part of the configuration manager is called the tag editor. Since this is a new configuration,
the editor is empty. To proceed, open the HMS-EN2MB-R configuration pages by clicking the left-
most icon in the tool bar.

6. The introductory page of the HMS-EN2MB-R configuration pages presents useful information
about the Linking Device. In the menu to the left, choose “Modbus Servers”.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Studio 5000 Implementation Example 23

7. Create a server by clicking “Add new server”. Name it “My_Server” and click “Ok”. Click
“Transactions” to create transactions for this server.

8. To create a new transaction:


- Add a new transaction, and click “Edit”.
- Name it “MyTrans1”.
- Choose Modbus function code 23 (Read/Write Multiple registers).
- In the “Elements” sections, both in “Read settings” and “Write settings”, write 120.
- Click “Ok”.

This will create a transaction which both reads and writes 120 elements (240 bytes).

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Studio 5000 Implementation Example 24

9. Add another transaction:


- Name it “MyTrans2”.
- Choose Modbus function code 16 (Write Multiple Registers).
- Set the number of elements to 20.
- Click “Ok”.

This will create a transaction which writes 20 elements (40 bytes).

10. Complete the configuration:


- Create another server and name it “My_Server2”.
- Add a transaction to this server, and click “Edit”.
- Name it “MyTrans3”.
- Choose Modbus function code 23 (Read/Write Multiple registers).
- In the “Elements” section, both in “Read settings” and “Write settings”, write 120.
- Click “Ok”.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Studio 5000 Implementation Example 25

11. When configuration is complete, find “HMS-EN2MB-R Management” in the menu bar to the
left. “Click “Apply” in the Apply changes section, to download the configuration to the Linking De-
vice.

12. Close the HMS-EN2MB-R configuration pages window, to show the tag editor again.

13. The tag editor is now updated. It has automatically created named and structured tags from the
Modbus configuration made in the previous steps.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Studio 5000 Implementation Example 26

14. Close the tag editor.

15. The tags from the configuration are now imported into Studio 5000, as named and structured
Studio 5000 controller tags.

16. Download the configuration to the Studio 5000 project by right-clicking the computer icon and
then choosing “Download”.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
SD Card Functionality 27

Chapter 4

4. SD Card Functionality
Using an SD card with the HMS-EN2MB-R linking device adds the following features:
• Easy backup.
Every applied change in the configuration will automatically be saved to the linking device and
the SD card. See “Easy Backup” on page 28.
• Simple configuration copy.
Using the SD card, the configuration on one linking device can be copied to other linking devic-
es. See “Simple Configuration Copy” on page 28.
• Easy replacement.
If a linking device malfunctions during operation, a replacement device can easily be configured
by moving the SD card to the new device. See “Easy Replacement” on page 29.
A configuration on the linking device is saved automatically to the SD card in any of these two events:
• A configuration is applied in the Management section
• A configuration is restored from a backup file

Important
The SD card acts as a master in the linking device. When an device is turned on with an SD card inserted,
and that SD card contains a valid configuration file, the configuration on the SD card will always over-
write any configuration on the linking device.

4.1 General Advice and Guidelines


Turn the power off before inserting or removing an SD card from the linking device.
Do not turn the linking device off while the SD LED indicates that the SD card is being accessed. Refer
to “Status LEDs” on page 17 for more information.
The linking device will not write any data to a write-protected SD card.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
SD Card Functionality 28

4.2 Starting Up
1. Format the SD card for the FAT file system using a PC. The linking device cannot use an unfor-
matted SD card.
2. Make sure the SD card is empty and that it is not write-protected.
3. Turn the linking device off.
4. Insert the SD card into the SD card slot in the linking device.
5. Turn the linking device on.
6. Create the configuration. When finished, press the apply button in the Management section to
reboot using the new configuration. During the reboot, the latest applied configuration will au-
tomatically be copied and saved to the SD card.
7. Now, the SD card is synchronized with the linking device. Both the SD card and the linking de-
vice contain the latest applied configuration.
Every time a new configuration is applied in the Management section, it is also copied to the SD card to
ensure synchronization.

4.3 Easy Backup


Every time a configuration change is applied in the Management section using the configuration web
pages, the configuration is saved to Studio 5000 and the Logix PLC memory, as well as to the linking
device and the SD card. This is the easiest way of keeping a continuously updated configuration backup.

4.4 Simple Configuration Copy


If a configuration on one linking device needs to be copied to one or more other linking devices, it is
easily done using an SD card.
1. Turn the linking device running the desired configuration off.
2. Remove the SD card from the linking device containing the desired configuration and insert it
into another one.
Note 1: The firmware version must be the same or higher in the new linking device.
Note 2: The new linking device must support the same network type as the first linking device.
3. Turn the new linking device on. The new linking device will automatically start up using the con-
figuration found on the SD card.

Important
If the configuration was protected by authentication information, the same information will be needed
to alter the configuration in the new linking device.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
SD Card Functionality 29

4.5 Easy Replacement


If a linking device malfunctions during operation, the SD card functionality makes it easy to get the ap-
plication up and running again fast.
1. Turn the malfunctioning linking device off.
2. Replace the linking device with a new one.
Note 1: The firmware version must be the same or higher in the new linking device.
Note 2: The new linking device must support the same network type as the old linking device.
3. Remove the SD card containing the configuration file from the old linking device and insert it
into the new one.
4. Turn the new linking device on. If the SD card contains a valid configuration file, the linking de-
vice will automatically start up using the configuration found on the SD card.

Important
If the configuration was protected by authentication information, the same information will be needed
to alter the configuration in the new linking device.
Depending on the settings of the master network, the communication link between the linking device
and the master may no longer be valid. Linking Device settings that were configured from outside the
configuration web pages will need to be set again.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
SD Card Functionality 30

4.6 SD Card Synchronization Failure


In the event of applying a configuration or restoring a configuration from a backup file, the SD card
synchronization can fail. There are many possible reasons for an SD card write failure:
• The SD card is write-protected.
• The configuration file on the SD card is write-protected.
• The SD card memory is full.
• The SD card file system is corrupt.
• The SD card is damaged.
If the SD card write process fails, the reboot cycle of the linking device will halt. The GW LED will
indicate “invalid configuration” and the SD LED will indicate “failure”. See “Status LEDs” on page 17.
To eliminate the problem, follow the steps below:
1. Turn the linking device off.
2. Remove the SD card. Find the cause of the problem.
3. Insert an SD card.
Note: This SD card must not contain a configuration file. If it does, the configuration on the SD
card will overwrite the configuration on the linking device.
4. Turn the linking device on. The linking device will run the configuration that was applied or re-
stored when the SD card write process failed.
5. Apply the configuration in the Management section to save the configuration to the SD card.
6. Now, the SD card is synchronized with the linking device. Both the SD card and the linking de-
vice contain the latest applied configuration.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Modbus-TCP Functions 31

Chapter 5

5. Modbus-TCP Functions
The Modbus-TCP protocol is an implementation of the standard Modbus protocol, running on top of
TCP/IP. The same function codes and addressing model are used.
The HMS-EN2MB-R Linking Device supports a subset of the functions described in the Modbus-TCP
specification.
Modbus-TCP transactions are normally transmitted and received on TCP port no. 502. The linking de-
vice features the possibility to set TCP ports individually for each Modbus-TCP server.
For detailed information regarding the Modbus-TCP protocol, consult the Open Modbus-TCP Specifi-
cation.
The EtherNet/IP to Modbus-TCP Linking Device supports the following Modbus-TCP functions:

Modbus Function Function Code No. of Bits/Registersa Direction Associated with Buffer
Read Coils 1 1-2000 Modbus to linking Input buffer
Read Discrete Inputs 2 1-2000 device
Read Holding Registers 3 1-125
Read Input Registers 4 1-125
Write Single Coil 5 1 Linking device to Output buffer
Write Single Register 6 1 Modbus
Write Multiple Coils 15 1-1968
Write Multiple Registers 16 1-123
Read/Write Multiple Registers 23 1-125 read Bidirectional Input and output buffers
1-121 write
a. Please refer to the Modbus Application Protocol Specification V1.1B for more detailed information.

Modbus-TCP functions are used as important parts of transactions to Modbus-TCP servers. After con-
figuring a server within the Modbus-TCP network, functions can be assigned to it by clicking the ‘Add
transaction’ button in the built-in web interface.
See also...
• “Modbus Configuration Manager” on page 38
• “Modbus Servers” on page 43

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Chapter 6

6. Tag Editor
The tag editor is supported by Windows 7 and later.

6.1 Tag Editor Overview


Initially, the tag editor looks like this.
The “Config Line” text in the lower right corner tells if the PLC is online or offline. No configuration
is possible while the PLC is online.

HMS-EN2MB-R Linking Device - EtherNet/IP


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Tag Editor 33

6.1.1 Menu Choices

File

• Import
Import a configuration from the hard drive.

• Export
Export a configuration and save for future use.

• Exit

Edit

• Select All

• Deselect All

Tools

• Edit Modbus Configuration


This option will launch the Modbus configuration manager.
For more information, see the “Modbus Configuration Manager” on page 38.

• Launch IPconfig
With the IPconfig tool, it is possible to scan for devices and alter IP settings for the linking de-
vice.

• Create Mapping Report


Saves a detailed list of all tags and their mappings on the hard drive. For documentation and error
tracking.

• Factory Reset
Resets the linking device to default values.

• Reboot

• Restore Configuration
Loads the latest stored configuration from Studio 5000.

• Wink
Winking the device will make all left LEDs blink for a short while.

• Options
- Hide report on retrieve configuration from gateway.
- Group tags on PLC (by Modbus server)

Help

• About

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Tag Editor 34

6.2 Tag Editor Basics


When the Modbus configuration manager is closed after configuration, the tag editor will be filled with
resulting Studio 5000 tags.
Tags that are new or altered since last time, will be presented in magenta color.
The “Include” column makes it possible to choose which tags should be exported to the Studio 5000
environment. Only tags that are checked will be exported.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Tag Editor 35

Right-clicking on a server or a transaction in the tree structure will present the menu below.

• Select All
Checks the “Include” check box for all tags associated with that server/transaction

• Deselect All
Unchecks the “Include” check box for all tags associated with that server/transaction

• Convert Transactions to Arrays


Attempts to create the biggest possible array for every transaction in that tree branch
- Ignore Transactions With Existing Arrays
If there are already arrays in the transaction/transactions, they will not be affected.
- Override Existing Arrays
Existing arrays may be affected

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Tag Editor 36

6.2.1 Tag Arrays

Arranging tags into arrays is a good way to get a better overview of the configuration, since a big con-
figuration may result in a large number of tags.
Creating an array is easy. Writing the array size in the dimension field of the first tag of the array, will
allocate that tag and the following tags to the array. All tags except the first element of the array will then
become uneditable. Original tag names will be remembered by the tag editor.

To remove the array, just set the dimension of the first array element back to 0 (zero).
For even more overview of the configuration, there is the possibility to collapse tags. This will present
a view of the configuration where all arrays are only represented by its first element, according to the
picture below.

Check the check box “Collapse arrays” to collapse arrays. If there is a need to see all individual tags, un-
check the check box.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Tag Editor 37

6.3 Tag Rule Definitions


IMPORTANT:
The default and automatically generated tags will follow and adhere to the rules below. They are only
informative.
When adding process tags (controller tags) to the configuration the following rules must apply:
• The designated memory address of the process tag must be inside the process data area bound-
aries.
• The memory address of the process tag must be divisible by four, for data types DINT or REAL
or a tag whose dimension is above zero.
• The memory address of the process tag must be dividable by two for data type INT.
• Two process tags can not occupy the same memory address area on the EtherNet/IP side.
• Two process tags can address the same memory address on the Modbus-TCP side.
• The designated memory address of the process tag must smaller than or equal to the correspond-
ing designated memory address in the configuration.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Chapter 7

7. Modbus Configuration Manager

7.1 General Information


The EtherNet/IP to Modbus-TCP Linking Device features built-in configuration pages for easy Mod-
bus configuration. To access the configuration pages, the following system requirements need to be met:
• Javascript enabled

There are things to take into consideration when making the configuration.
• Remember to apply the configuration in order for changes to take effect. See “HMS-EN2MB-R
Management” on page 47. As soon as you have saved data to the configuration but not yet ap-
plied it, you will see the box below at the top of the web pages:

• A maximum of 64 Modbus-TCP servers can be added to the configuration.


• A maximum of 64 transactions can be set up to the servers in the configuration.
• The data limits are 4096 bytes input data and 4096 bytes output data, including optional control/
status word and live list.
• Modbus transactions are assembled in multiple Class 1 Exclusive Owner (IO) Connections, on
the EtherNet/IP side. There are a maximum of 10 available connections (with an associated in-
put and output connection parameter per each) available. Connections will be made as needed.
Transactions will be added to connections in the order they are created in the Modbus configu-
ration manager. If a transaction does not fit into the remaining parts of a connection, it will be
moved to the next connection. The bytes left in the previous connection will then be padded and
left unused. Consequently, take care when creating the Modbus transactions, to optimize the
available memory in the input and output IO areas as much as possible.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Modbus Configuration Manager 39

7.2 Overview
The Modbus configuration and status pages are divided into three sections:

1. Headline Section
Shows the HMS logo and the name of the product.

2. Navigation Section
All functionality is easily accessed from the different links. Every link and its corresponding func-
tionality will be explained later in this chapter.

3. Content Section
Clicking a link will display its contents in the content section. A short text describing the func-
tionality of the current page will be available at the top of the section.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Modbus Configuration Manager 40

7.2.1 Home

The introductory window of the configuration and status pages presents important error tracking infor-
mation, as well as general information and statistics.

Operation Mode
The table below shows the correlation between the operation modes of the Modbus-TCP network and
the EtherNet/IP network.

EtherNet/IP (Network 1)
I/O data exchanged No I/O data exchanged
Modbus-TCP Run Data is exchanged between the two net- The EtherNet/IP network exchanges no
(Network 2) works. data. Data to the Modbus-TCP network is in
clear, freeze, safe value or stop state.
Idle The Modbus-TCP network exchanges no No data is exchanged. Both networks, inde-
data. Data to the EtherNet/IP network is in pendently, are in clear, freeze, safe value or
clear or freeze state. stop state.

In case of an error on the EtherNet/IP network, the following additional statuses may appear:

EtherNet/IP (Network 1) Description


Error Class 1 connection error.
Duplicate IP address detected.
Shutdown Unexpected error (the linking device needs a restart).

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Modbus Configuration Manager 41

7.3 Configuration
Please note that changes made to the configuration will not be used by the linking device until they have
been applied and saved. See “HMS-EN2MB-R Management” on page 47.

7.3.1 Authentication

Authentication can be enabled or disabled. If enabled, it is possible to set a username and password to
protect the configuration.

When choosing a username and a password, use only the valid characters shown below.

Item Valid characters


Username A-Z, a-z, 0-9, _ (underscore). Max length: 13 characters.
Password A-Z, a-z, 0-9, _ (underscore). Max length: 12 characters.

Important Notice
Note that when restoring a configuration from Studio 5000, or when importing a configuration (using
either the tag editor or the configuration pages), authentication has to be disabled. Restore or import is
only possible when authentication is disabled.
Note also that it is very important to save the authentication information. There is no way to retrieve a
lost username or password. If the authentication information is lost, the only way to restore the linking
device is to download new firmware via the USB interface. This will erase any configuration currently
on the module.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Modbus Configuration Manager 42

7.3.2 Modbus Client

Configuration of the client side of the Modbus-TCP network. On this side, the linking device will act as
a Modbus-TCP client. To the right, in the “Actual” column, the currently used values can be seen.

Available IP Configuration Settings

Item Description
IP address If not set by DHCP (or HICP), set these values manually.
Subnet mask
Router IP address
DHCP Enabled by default. When enabled, the linking device can obtain the TCP/IP settings dynamically
from the DHCP server of the Modbus-TCP network.

Start-up Operation Mode

Value Description
Running The Modbus-TCP client starts to exchange data with the servers as soon as possible
after start-up.
Idle The Modbus-TCP client does not exchange any data with the servers and waits for
instructions via the control word.

Action in Case of Irrecoverable Error


If the linking device encounters an irrecoverable error, there are two possible options.

Value Description
Shutdown The linking device will shut down. All LEDs will display red.
Restart The linking device will restart.

When finished configuring the Modbus-TCP client, click ‘Save settings’. Note that the changes will not
take effect until they are applied in the HMS-EN2MB-R management section. See “HMS-EN2MB-R
Management” on page 47.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Modbus Configuration Manager 43

7.3.3 Modbus Servers

The configuration of the servers on the Modbus-TCP network is made here. The linking device can han-
dle up to 64 different servers, and a maximum of 64 transactions distributed among those servers. It is
possible to map up to 4096 bytes of data in either direction, including control/status word and live list.
The global configuration limits box keeps track of the number of added transactions and the current
amount of I/O mapped input and output data. It also keeps track of the total amount of data in the
configuration (both I/O mapped and not I/O mapped data).

Add Server
Click ‘Add server’ to add a server to the configuration. Click ‘Edit’ to see and edit the settings:

Available editable settings:

Setting Description
Name While not required, renaming the server makes the configuration easier to comprehend. Note that it
is only possible to use uppercase and lowercase characters, numerals and underscore (_).
Default name is ‘New_Server’, followed by an incremental suffix.
Max length: 32 characters.
Server address The IP address of the server.
Protocol TCP.
Port Default Modbus-TCP port is 502. If the server requires it, it is possible to change.
Value range: 0 - 65535.

When the server is configured, click ‘Ok’.


Note: When the server and its settings are configured, transactions must be added to the server. See
“Add Transactions” on page 44. At any time, it is possible to have only one server without specified
transactions.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Modbus Configuration Manager 44

Add Transactions
Transactions represent the data that is read from/written to the servers of the Modbus-TCP network.
The global configuration limits box keeps track of the number of added transactions, the current mini-
mum allowed scan time, and the current amount of I/O mapped data as well as total amount of data
(both I/O mapped and not I/O mapped data).

To add transactions, find the server in the server list and click ‘Transactions’. This presents a list of all
transactions configured for that server. Click ‘Add transaction’ to add a new default transaction to the
list and click ‘edit’.

See a description of the settings on the next page.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Modbus Configuration Manager 45

Available settings

Setting Description
Function code The function code defines the purpose of the transaction.
Choose from the available different Modbus functions, see “Modbus-TCP Functions” on page 31.
Data encoding Decides in what order the different bytes of the received/transmitted data shall be sent on the Mod-
bus network.
Trigger Only applicable for write transactions.
Cyclic.
On data change.
I/O mapped Decides whether to map the data to the memory that is cyclically exchanged between the Ether-
Net/IP network and the Modbus-TCP network (I/O mapped data).
Note: data that is not I/O mapped will be exchanged acyclically.
Name While not required, renaming the transaction makes the configuration easier to comprehend. On
the EtherNet/IP side, this name will also propagate to tag name, for identification purposes. Note
that it is only possible to use uppercase and lowercase characters, numerals and underscore (_).
Default name is ‘New_Trans’, followed by an incrementing suffix.
Max length: 32 characters.
Timeout (ms) The time span within which the server must return a response to the transaction.
If no response is received within the timeout period, the connection to the server will be closed.
If the connection to the server is closed, all transactions to that server will be affected.
Value range: 10 - 65535 (ms).
Scan time (ms) The scan time defines how often the transaction shall be resent, e.g. the time cycle of a repeating
transaction.
Minimum scan time (ms) is calculated by multiplying the total number of transactions by three.
The minimum scan time will increase by adding more transactions.
Value range: 10 - 10000 (ms).
Unit ID Only applicable for Modbus RTU servers. If the Modbus-TCP server work as a router to Modbus
RTU servers, it is possible to send transactions to a single Modbus RTU server using the unit ID.
Value range: 0 - 247; 255.
If not communicating with a Modbus RTU server, use the value 255 (default).
Starting register The starting Modbus server register or bit to write to/read from.
Value range: 1 - 65536.
Elements The number of elements to write/read.
Value range: See “Modbus-TCP Functions” on page 31.
When EtherNet/IP Note: Only available for I/O mapped write transactions.
(Network 1) is not Clear data to Modbus server: only zeros will be transmitted.
exchanging I/O data Freeze data to Modbus server: the data that was stored last will be repeated.
Write safe value: choose a specific value to transmit for every element (See safe element value
below).
Stop: no data will be transmitted to the Modbus server.
Data type Write/read data either as two byte integers (uint16) or four byte integers (uint32).
Registers The resulting amount of registers to write/read.
The calculation is based on the number of elements to read/write and the chosen data type.
Safe Element Value Note: Only available for write transactions.
A numeric value to send for every element if network 1 (EtherNet/IP) is not exchanging I/O data.
Startup-mode Wait for data: all data for the transaction must have been sent from the EtherNet/IP network and
received by the linking device before the transaction is carried out.
Directly: the data is sent as soon as possible after start-up.

When finished editing the transaction, click ‘Ok’. All data resulting from configured transactions will be
mapped to the internal memory of the linking device. Read transactions will be mapped to the input area,
and write transactions will be mapped to the output area. See “Mapping Overview” on page 48 for more
information.
Note: The linking device needs to be restarted before any changes will take effect. See “HMS-EN2MB-
R Management” on page 47.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Modbus Configuration Manager 46

7.3.4 EtherNet/IP (Adapter Interface)

Configuration of the EtherNet/IP adapter interface of the linking device.

What is shown is the currently stored configuration, provided that all changes are saved and applied to
the linking device.
The column ‘Actual’ presents the settings that are currently used.
It is possible to override the TCP/IP and Ethernet settings set from the network by entering new values
in the Configured column and pressing “Save settings”.
Note that no changes will take effect until the configuration has been applied. See “HMS-EN2MB-R
Management” on page 47.

Available settings for the EtherNet/IP network

Setting Description
IP address If not detected automatically, set these items manually.
Subnet mask
Gateway
DHCP If enabled, the linking device can obtain TCP/IP settings from a DHCP server.
Ethernet settings 1 Network speed and communication model.
Ethernet settings 2
Secure Host IP Configuration If enabled, the linking device can be found on the network using the IPconfig tool.
Protocol (HICP)
When Modbus-TCP (Network The “Freeze data to master” option instructs the linking device to keep sending the latest
2) error received data from the Modbus-TCP network to the EtherNet/IP scanner.
The “Clear data to master” option instructs the linking device to clear the input data area
and send only zeros to the EtherNet/IP scanner.
I/O mapped control/status word If enabled, the control/status word is mapped to the output/input area respectively. See
“I/O Mapped Data” on page 10.
I/O mapped live list If enabled, the live list is mapped to the input area. See “Live List” on page 11.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Modbus Configuration Manager 47

7.4 Tools

7.4.1 HMS-EN2MB-R Management

Apply changes
Permanently store changes made to the configuration and reboot, using the new configuration.
No changes made in the configuration will be permanently stored or used by the linking device until they
are applied by clicking ‘Apply’.
Before storing and rebooting, the linking device will validate the not yet stored configuration. If errors
are found, the linking device will produce an information message with instructions to correct the errors.
The linking device will not store an invalid configuration.

Reboot and undo changes


The linking device will be restarted. All changes made since the last configuration was loaded will be
undone.

Undo changes
Undo all changes made since the last configuration was loaded.

Factory reset
Reset the linking device to completely remove the configuration currently stored in the module.

Wink device
Clicking the “Wink device” button will start a 15 second LED sequence on LEDs 1, 5 and 6 on the link-
ing device. For identification purposes.

7.4.2 Backup and Restore

Backup the configuration that is currently used to file, or restore a previously saved configuration from
file.
It is not possible to backup or restore the configuration until all changes are either applied or undone.
See “HMS-EN2MB-R Management” on page 47.
Two things can happen when loading an old configuration:
• Configuration valid:
The linking device will reboot and automatically use the previously stored configuration.
• Configuration not valid:
The linking device will produce an error message. The chosen configuration will not be accepted
or loaded into memory.

Important Notice
Before loading a previously stored configuration, locate any authentication information associated with
it. If a valid configuration is loaded that is protected by a password, the linking device can not be recon-
figured until the correct authentication information has been provided.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Modbus Configuration Manager 48

7.4.3 Mapping Overview

This page provides a description of all data resulting from the transactions of the currently applied con-
figuration. It is divided into two parts. The first part describes the linking device interface to the Ether-
Net/IP network, and the second part all applied transactions on the Modbus-TCP network.
If needed, it is possible to print the configuration to paper. Click the printer symbol to the right on the
mapping overview page to access a printer friendly version of the mapping overview.

EtherNet/IP
The I/O mapped data will always be presented according to the following priority order:

• Input data
Data from the Modbus-TCP network to the EtherNet/IP network.
- Status word (optional)
- Live list (optional)
- Input data (bit transactions will always be mapped first)

• Output data
Data from the EtherNet/IP network to the Modbus-TCP network.
- Control word (optional)
- Output data (bit transactions will always be mapped first)

The parameter section data presents a detailed list of all data, including both the I/O mapped and the
not I/O mapped data, available acyclically from the linking device to the EtherNet/IP network. This list
also includes the transaction status and exception code lists, available for error identification.
- “Exception Code List” on page 13
- “Transaction Status List” on page 12

Modbus-TCP network
A detailed list of all Modbus servers and transactions in the configuration.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Modbus Configuration Manager 49

7.4.4 Transaction Monitor

The transaction monitor interface presents a detailed list of all transactions currently operating on the
Modbus-TCP network.

To start or stop the transaction monitor, press the desired button.


The data in the transaction monitor is automatically updated, and it is possible to choose to view the
data either in decimal or in hexadecimal values. The time that has passed since the last update is visible
at the top of the transaction list. Every post in the list contains the following transaction information:
• Server name and transaction name
• The type of Modbus function chosen for the transaction
• The size of the data read from or written to the Modbus-TCP network
• The actual data read from or written to the Modbus-TCP network
• The bit position of the transaction in the live list (also presented as byte.bit)
If there is a transaction error, an error message will appear instead of the data.
A red frame around the list indicates that the web browser has lost connection to the web server of the
linking device. If this happens, try reloading the page by clicking on “Transaction Monitor” in the menu
to the left.
Note: Viewing the transaction monitor may affect performance.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Chapter 8

8. CIP Objects

8.1 General Information


This chapter specifies the CIP-object implementation in the linking device. These objects can be ac-
cessed from the network.

Mandatory Objects:
• “Identity Object (01h)” on page 51
• “Message Router (02h)” on page 53
• “Assembly Object (04h)” on page 54
• “Connection Manager (06h)” on page 56
• “DLR Object (47h)” on page 59
• “QoS Object (48h)” on page 60
• “Port Object (F4h)” on page 63 (Optional)
• “TCP/IP Interface Object (F5h)” on page 64
• “Ethernet Link Object (F6h)” on page 67

Manufacturer Specific Objects:


• “ADI Object (A2h)” on page 61

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 51

8.2 Identity Object (01h)

Object Description

Supported Services

Class: Get_Attribute_Single
Get_Attributes_All
Instance: Get_Attribute_Single
Set_Attribute_Single
Get_Attributes_All
Reset

Class Attributes

# Name Access Type Value


1 Revision Get UINT 0001h (Object revision)

Instance #1 Attributes

# Name Access Type Value


1 Vendor ID Get UINT 005Ah (HMS Industrial Networks AB)
2 Device Type Get UINT 000Ch (Communications Adapter)
3 Product Code Get UINT 0057h (EtherNet/IP to Modbus-TCP Linking Device)
4 Revision Get Struct of: Major and minor firmware revision
{USINT, USINT}
5 Status Get WORD
6 Serial Number Get UDINT Unique serial number (assigned by HMS)
7 Product Name Get SHORT_STRING “EtherNet/IP to Modbus-TCP Linking Device” (Name of product)
11 Active language Set Struct of:
USINT
USINT
USINT
12 Supported Lan- Get Array of:
guage List Struct of:
USINT
USINT
USINT

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 52

Device Status

Bit(s) Name
0 Module Owned
1 (reserved)
2 Configureda
3 (reserved)
4... 7 Extended Device Status:
Value:Meaning:
0000b Unknown
0010b Faulted I/O Connection
0011b No I/O connection established
0100b Non-volatile configuration bad
0110b Connection in Run mode
0111b Connection in Idle mode
(other) (reserved)
8 Set for minor recoverable faults
9 Set for minor unrecoverable faults
10 Set for major recoverable faults
11 Set for major unrecoverable faults
12... 15 (reserved)
a. This bit shows if the product has other settings than “out-of-box”.

Service Details: Reset Service

There are two types of network reset requests on EtherNet/IP:

• Type 0: ‘Power Cycling Reset’


This service emulates a power cycling of the module, and corresponds to Anybus reset type 0
(Power cycling).

• Type 1: ‘Out of box reset’


This service sets a “out of box” configuration and performs a reset, and corresponds to Anybus
reset type 2 (Power cycling + factory default).

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 53

8.3 Message Router (02h)

Object Description

Supported Services

Class: -
Instance: -

Class Attributes

Instance Attributes

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 54

8.4 Assembly Object (04h)

Object Description

The Assembly object uses static assemblies and holds the Process Data sent/received by the host appli-
cation. The default assembly instance IDs used are in the vendor specific range.

Supported Services

Class: Get_Attribute_Single
Instance: Get_Attribute_Single
Set_Attribute_Single

Class Attributes

# Name Access Type Value


1 Revision Get UINT 0002h (Object revision)
2 Max Instance Get UINT (Highest instance number)

Instance C6h Attributes (Heartbeat, Input-Only)

This instance is used as heartbeat for Input-Only connections.

# Name Access Type Value


3 Data Set N/A - (The data size of this attribute is zero)

Instance C7h Attributes (Heartbeat, Listen-Only)

This instance is used as heartbeat for listen-only connections.

# Name Access Type Value


3 Data Set N/A - (The data size of this attribute is zero)

Instance 05h Attributes (Configuration Data)

Configuration Data that is sent through the ‘Forward_Open’-service will be written to this instance.

# Name Access Type Value


3 Data Get/Set N/A - (Configuration data written to the application when the forward
open command has the configuration data included)

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 55

Instance C3h Attributes (Heartbeat, Input-Only Extended)

This instance is used as heartbeat for input-only extended connections, and does not carry any attributes.
If the connection times out, the module does not switch to the Error state.

Instance C4h Attributes (Heartbeat, Listen-Only Extended)

This instance is used as heartbeat for listen-only extended connections, and does not carry any attributes.

Instance 64h Attributes (Producing Instance)

# Name Access Type Value


3 Produced Data Get Array of BYTE This data corresponds to the Write Process Data

Instance 96h Attributes (Consuming Instance)

# Name Access Type Value


3 Consumed Data Set Array of BYTE This data corresponds to the Read Process Data

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 56

8.5 Connection Manager (06h)

Object Description

Supported Services

Class: -
Instance: Forward_Open
Forward_Close

Instance Descriptions

(No supported instance attributes)

Class 1 Connection Details

General
Class 1 connections are used to transfer I/O data, and can be established to instances in the Assembly
Object. Each Class 1 connection will establish two data transports; one consuming and one producing.
The heartbeat instances can be used for connections that shall only access inputs. Class 1 connections
use UDP transport.
• Total number of supported Class 1 connections: 4
• Max input connection size: 256 bytes
• Max output connection size: 256 bytes
• Supported API: 2... 3200 ms
• T  O Connection type: Point-to-point, Multicast
• O  T Connection type: Point-to-point
• Supported trigger types: Cyclic, COS

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 57

Connection Types

• Exclusive-Owner connection
This type of connection controls the outputs of the Anybus module and does not depend on oth-
er connections.
- Max. no. of Exclusive-Owner connections: 1
- Connection point O  T: Assembly Object, instance 64h (Default)
- Connection point T  O: Assembly Object, instance 96h (Default)

• Input-Only connection
This type of connection is used to read data from the Anybus module without controlling the
outputs. It does not depend on other connections.
- Max. no. of Input-Only connections: Up to 41
- Connection point O  T: Assembly Object, instance 03h (Default)
- Connection point T  O: Assembly Object, instance 96h (Default)

Note: If an Exclusive-Owner connection has been opened towards the module and times out,
the Input-Only connection times out as well. If the Exclusive-Owner connection is properly
closed, the Input-Only connection remains unaffected.

• Input-Only Extended connection


This connections functionality is the same as the standard Input-Only connection. However
when this connection times out it does not affect the state of the application.
- Max. no. of Input-Only connections: Up to 4a
- Connection point O  T: Assembly Object, instance 05h (Default)
- Connection point T  O: Assembly Object, instance 96h (Default)

Note: If an Exclusive-Owner connection has been opened towards the module and times out,
the Input-Only connection times out as well. If the Exclusive-Owner connection is properly
closed, the Input-Only connection remains unaffected.

• Listen-Only connection
This type of connection requires another connection in order to exist. If that connection (Exclu-
sive-Owner or Input-Only) is closed, the Listen-Only connection will be closed as well.
- Max. no. of Listen-Only connections: Up to 42
- Connection point O  T: Assembly Object, instance 04h (Default)
- Connection point T  O: Assembly Object, instance 96h (Default)

• Listen-Only Extended connection


The functionality of this connection is the same as the standard Listen-Only connection. How-
ever when this connection times out it does not affect the state of the application.
- Max. no. of Listen-Only connections: Up to 4b
- Connection point O  T: Assembly Object, instance 07h (Default)
- Connection point T  O: Assembly Object, instance 96h (Default)

• Redundant-Owner connection
This connection type is not supported by the module.

1. Shared with Exclusive-Owner and Listen-Only connections


2. Shared with Exclusive-Owner and Input-Only connections

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 58

Class 3 Connection Details

• Explicit message connection


Class 3 connections are used to establish connections towards the message router. Thereafter,
the connection is used for explicit messaging. Class 3 connections use TCP transport.
- No. of simultaneous Class 3 connections: 16
- Supported API: 2 - 10000 ms
- T  O Connection type: Point-to-point
- O  T Connection type: Point-to-point
- Supported trigger type: Application

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 59

8.6 DLR Object (47h)

Object Description

Supported Services

Class: Get_Attribute_Single
Get_Attributes_All
Instance: Get_Attribute_Single
Set_Attribute_Single

Class Attributes

# Name Access Type Value


1 Revision Get UINT 0002h (Object revision)

Instance #1 Attributes

# Name Access Type Value


1 Network Topol- Get USINT Bit:Contents:
ogy 0 “Linear”
1 “Ring”
2 Network Status Get USINT Bit:Contents:
0 “Normal” (N/A)
1 “Ring Fault”
2 “Unexpected Loop Detected”
3 “Partial Network Fault”
4 “Rapid Fault/Restore Cycle”
10 Active Get Struct of: This attribute holds the IP address (IPv4) and/or the Ethernet Mac
Supervisor {UDINT, Array of address of the active ring supervisor
Address 6 USINTs}
12 Capability Flags Get DWORD 01h (Announce-based ring node)

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 60

8.7 QoS Object (48h)

Object Description

Supported Services

Class: Get_Attribute_Single
Get_Attributes_All
Instance: Get_Attribute_Single
Set_Attribute_Single

Class Attributes

# Name Access Type Value


1 Revision Get UINT 0001h (Object revision)

Instance #1 Attributes

# Name Access Type Value


1 802.1Q Tag Set USINT Enables or disables sending 802.1Q frames
Enable Bit:Contents:
0 Disabled (Default)
1 Enabled
4 DSCP Urgent Set USINT CIP transport Class 1 messages with priority Urgent
Default: 55
5 DSCP Set USINT CIP transport Class 1 messages with priority Scheduled
Scheduled Default: 47
6 DSCP High Set USINT CIP transport Class 1 messages with priority High
Default: 43
7 DSCP Low Set USINT CIP transport Class 1 messages with priority Low
Default: 31
8 DSCP Explicit Set USINT CIP UCMM and CIP Class 3
Default: 27

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 61

8.8 ADI Object (A2h)

Object Description

Supported Services

Class: Get_Attribute_Single
Instance: Get_Attribute_Single
Set_Attribute_Single

Class Attributes

# Name Access Type Value


1 Revision Get UINT Object revision (Current value = 0001h)
2 Max Instance Get UINT
3 Number of instances Get UINT

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 62

Instances Attributes

Each instance corresponds to an instance within the Application Data Object.

# Name Access Type Description


1 Name Get SHORT_STRING Parameter name (including length)
2 ABCC Data type Get USINT Data type of instance value
3 No. of elements Get USINT Number of elements of the specified data type
4 Descriptor Get USINT Bit field describing the access rights for this instance
Bit:Meaning:
0 Set = Get Access
1 Set = Set Access
5 Valuea Get/Set Determined by Instance value
6 Get attribute #2 The maximum permitted parameter value
Max valuea
7 Min valuea Get The minimum permitted parameter value
8 Default valuea Get The default parameter value

a. Converted to/from CIP standard by the module

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 63

8.9 Port Object (F4h)

Object Description

Supported Services

Class: Get_Attributes_All
Get_Attribute_Single
Instance: Get_Attributes_All
Get_Attribute_Single

Class Attributes

# Name Access Type Value


1 Revision Get UINT Object revision (Current value = 0001h)
2 Max Instance Get UINT Max. instance number
3 Number of instances Get UINT Number of ports
8 Entry Port Get UINT Returns the instance of the Port Object that describes the port
through which this request entered the device.
9 Port Instance Info Get Array of: Array of structures containing instance attributes 1 and 2 from
each instance. The array is indexed by instance number, up to
the maximum number of instances. The value at index 1 (off-
set 0) and any non-instantiated instances will be zero.
Struct of:
UINT (Type) Enumerates the type of port
UINT (Number) CIP port number associated with this port

Instance Attributes (Instance #1)

This instance reflects the properties associated with the Ethernet interface.

# Name Access Type Value


1 Port Type Get UINT 0h (default)
2 Port Number Get UINT 2h
3 Link Object Get Struct of: -
UINT 2h
Padded EPATH 20 F5 24 01h
4 Port Name Get SHORT_STRING “EtherNet/IP”
7 Node Address Get Padded EPATH -
8 Port Node Range Get Struct of: -
UINT (Min.)
UINT (Max.)

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 64

8.10 TCP/IP Interface Object (F5h)

Object Description

The object groups TCP/IP-related settings.

Supported Services

Class services: Get_Attribute_All


Get_Attribute_Single
Instance services: Get_Attribute_All
Get_Attribute_Single
Set_Attribute_Single1

Class Attributes

# Access Name Type Value Description


1 Get Revision UINT 0001h Revision 2

1. Support for this service can be disabled by implementing attribute #9 in the EtherNet/IP Host Object.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 65

Instance Attributes

# Access Name Type Value Comments


1 Get Status DWORD 0000 0001h Bit #: Meaning:
0000 0002h 0: Attribute #5 contains valid information from
0000 0010h DHCP or nonvolatile storage
1: Attribute #5 contains valid information from
hardware settings
4: Mcast pending
6: AcdStatus. Set to 1 if an address conflict is
detected. Address conflict detection is
enabled/disabled in attribute #10.
Attribute #5 contains valid information from hard-
ware settings.
Mcast pending
2 Get Configuration DWORD 0000 0016h The ‘Configuration Settable’-bit (bit 4) in this attrib-
Capability - or - ute reflects the value of instance attribute #9 in the
0000 0006h EtherNet/IP Host Object.
- or - The module is capable of resolving host names by
0000 0026h querying a DNS server
- or -
0000 0036h
3 Get/Set Configuration DWORD - Value:Meaning:
Control 0 Configuration from nonvolatile memory
2 Configuration from DHCP
4 Get Physical Link Struct of: - -
Object UINT (Path size) 0002h 2 words
Padded EPATH 20 F6 24 03h Path to Ethernet Link Object, Instance 3
5 Get/Set Interface Struct of: -
Configuration UDINT (IP) IP address
UDINT (Mask) Subnet mask
UDINT (GW) Default gateway
UDINT (DNS1) Primary DNS
UDINT (DNS2) Secondary DNS
STRING (Domain) Default domain
6 Get/Set Host Name STRING - Host name of Anybus module
8 Get/Set TTL Value USINT 1 TTL value for EtherNet/IP multicast packets
9 Get/Set Mcast Config Struct of:
Alloc Control USINT 0 Value:Meaning:
0 Use default allocation algorithm to
generate multicast addresses
1 Allocate multicast addresses according
to the values in the ‘Num Mcast’- and
‘Mcast Start Addr’-fields
(reserved) USINT 0 Set to zero. Do not change
Num Mcast UINT 1 Number of multicast addresses to allocate for Eth-
erNet/IP
Mcast Start UDINT - Starting multicast address from which to begin allo-
Addr cation
10 Set SelectAcd Bool 1 Value: Meaning:
0: Disable ACD
1: Enable ACD (default)
If ACD (address conflict detection) is
enabled, bit 6 in attribute #1 will be set if
an ACD conflict is detected. The Network
Status LED will also indicate a detected
conflict.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 66

# Access Name Type Value Comments


11 Set LastConflictDe- Struct of: ACD Diagnostic parameters related to the last con-
tected flict detected.
AcdActivity USINT - State of ACD activity when last conflict
detected
RemoteMAC ARRAY of 6 USINT - MAC address of remote node form the ARP
PDU in which a conflict was detected
ArpPdu ARRAY of 28 USINT - Copy of the raw ARP PDU in which a conflict
was detected

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 67

8.11 Ethernet Link Object (F6h)

Object Description

This object groups diagnostic information for the Ethernet interface.

Supported Services

Class services: Get_Attribute_All


Get_Attribute_Single
Instance services: Get_Attribute_All
Get_Attribute_Single
Set_Attribute_Single
Get_And_Clear

Class Attributes

# Access Name Type Value Comments


1 Get Revision UINT 3 Revision 3
2 Get Max Instance UINT 3 Instance 3 is the max instance
3 Get Number of UINT 3 3 instances
instances

Instance Attributes

# Access Name Type Value Comments


1 Get Interface Speed UDINT 10 or 100 Actual Ethernet interface speed
2 Get Interface Flags DWORD - See “Interface Flags” on page 68.
3 Get Physical Address Array of 6 USINTS (MAC ID) Physical network address
6 Get/Set Interface Control Struct:
Control Bits WORD - Interface control bits
Forced Interface UINT - Speed at which the interface shall be forced to
Speed operate. Returns ‘Object state Conflict’ if auto-
negotiation is enabled.
7 Get Interface Type USINT - See “Interface Type” on page 68
10 Get Interface Label SHORT_STRING - See “Interface Label” on page 68

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
CIP Objects 68

Interface Flags

Bit Name Description


0 Link status Indicates whether or not the Ethernet 802.3 communications interface is con-
nected to an active network.
Value:Meaning:
0 Inactive link
1 Active link
1 Half/full duplex Indicates the duplex mode currently in use.
Value:Meaning:
0 Half duplex
1 Full duplex
2 - 4 Negotiation Status Indicates the status of link autonegotiation
Value:Meaning:
0 Autonegotiation in progress.
1 Autonegotiation and speed detection failed (using default values)
2 Autonegotiation failed but detected speed (using default duplex value)
3 Successfully negotiated speed and duplex.
4 Autonegotiation not attempted. Forced speed and duplex.
5 Manual Setting requires Reset Value:Meaning:
0 Interface can activate changes to link parameters during runtime
1 Reset is required in order for changes to have effect
6 Local Hardware Fault Value:Meaning:
0 No local hardware fault detected
1 Local hardware fault detected
7-31 (reserved) (ignore)

Interface Type

Instance Value Description


1 2 Twisted-pair
2 2 Twisted-pair
3 1 Internal interface

Interface Label

Instance Value
1 Port 1
2 Port 2
3 Internal

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Technical Specification 69

Appendix A

A. Technical Specification

A.1 Protective Earth (PE) Requirements


In order to achieve proper EMC behavior, the product must be connected to protective earth (PE) via
the DIN-rail connector. If the DIN-rail cannot be used, PE must be connected to the power connector.
HMS Industrial Networks does not guarantee proper EMC behavior unless these PE requirements are
fulfilled.
Note: Make sure the DIN-rail is properly connected to PE.

A.2 Power Supply

Supply Voltage
The HMS-EN2MB-R linking device requires a regulated 24 V (20.4 V to 28.8 V) DC power source.

Power Consumption
The typical power consumption is 150 mA at 24 V.

A.3 Environmental Specification

A.3.1 Temperature

Operating
-25º to +70º Celsius

Non-operating
-40º to +85º Celsius

A.3.2 Relative Humidity

The product is designed for a relative humidity of 5% to 95% noncondensing.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Technical Specification 70

A.4 EMC (CE) Compliance


EMC compliance testing has been conducted according to the Electromagnetic Compatibility Directive
2004/108/EC. For more information please consult the EMC compliance document, see product/sup-
port pages for EtherNet/IP to Modbus-TCP Linking Device at www.anybus.com.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Copyright Notices 71

Appendix B

B. Copyright Notices
This product includes software developed by Carnegie Mellon, the Massachusetts Institute of Technology, the Uni-
versity of California, and RSA Data Security:
*****************************************************************************
Copyright 1986 by Carnegie Mellon.
*****************************************************************************
Copyright 1983,1984,1985 by the Massachusetts Institute of Technology
*****************************************************************************
Copyright (c) 1988 Stephen Deering.
Copyright (c) 1982, 1985, 1986, 1992, 1993
The Regents of the University of California. All rights reserved.
This code is derived from software contributed to Berkeley by Stephen Deering of Stanford University.
Redistribution and use in source and binary forms, with or without modification, are permitted provided that the
following conditions are met:
• Redistributions of source code must retain the above copyright notice, this list of conditions and the fol-
lowing disclaimer.
• Redistributions in binary form must reproduce the above copyright notice, this list of conditions and the
following disclaimer in the documentation and/or other materials provided with the distribution.
• Neither the name of the University nor the names of its contributors may be used to endorse or promote
products derived from this software without specific prior written permission.
THIS SOFTWARE IS PROVIDED BY THE REGENTS AND CONTRIBUTORS ``AS IS'' ANDANY EXPRESS OR
IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANT-
ABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE RE-
GENTS OR CONTRIBUTORS BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL,
EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF
SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION)
HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY,
OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS
SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.
*****************************************************************************
Copyright (C) 1990-2, RSA Data Security, Inc. All rights reserved.
License to copy and use this software is granted provided that it is identified as the "RSA Data Security, Inc. MD4
Message-Digest Algorithm" in all material mentioning or referencing this software or this function.
License is also granted to make and use derivative works provided that such works are identified as "derived from
the RSA Data Security, Inc. MD4 Message-Digest Algorithm" in all material mentioning or referencing the derived
work.
RSA Data Security, Inc. makes no representations concerning either the merchantability of this software or the
suitability of this software for any particular purpose. It is provided "as is" without express or implied warranty of
any kind.
These notices must be retained in any copies of any part of this documentation and/or software.
*****************************************************************************
Copyright (C) 1991-2, RSA Data Security, Inc. Created 1991. All rights reserved.
License to copy and use this software is granted provided that it is identified as the "RSA Data Security, Inc. MD5
Message-Digest Algorithm" in all material mentioning or referencing this software or this function.
License is also granted to make and use derivative works provided that such works are identified as "derived from
the RSA Data Security, Inc. MD5 Message-Digest Algorithm" in all material mentioning or referencing the derived
work.
RSA Data Security, Inc. makes no representations concerning either the merchantability of this software or the
suitability of this software for any particular purpose. It is provided "as is" without express or implied warranty of
any kind.
These notices must be retained in any copies of any part of this documentation and/or software.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008
Copyright Notices 72

Copyright (c) 2008-2013 Marshall A. Greenblatt. Portions Copyright (c)


2006-2009 Google Inc. All rights reserved.
Redistribution and use in source and binary forms, with or without modification, are permitted provided that the
following conditions are met:
* Redistributions of source code must retain the above copyright notice, this list of conditions and the following
disclaimer.
* Redistributions in binary form must reproduce the above copyright notice, this list of conditions and the follow-
ing disclaimer in the documentation and/or other materials provided with the distribution.
* Neither the name of Google Inc. nor the name Chromium Embedded Framework nor the names of its contrib-
utors may be used to endorse or promote products derived from this software without specific prior written permis-
sion.
THIS SOFTWARE IS PROVIDED BY THE COPYRIGHT HOLDERS AND CONTRIBUTORS "AS IS" AND ANY
EXPRESS OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT
SHALL THE COPYRIGHT OWNER OR CONTRIBUTORS BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDEN-
TAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PRO-
CUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS
INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT,
STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF
THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.

EtherNet/IP to Modbus-TCP Linking Device


Doc.Rev. 1.1 Doc.Id. SCM-1202-008

You might also like