UF Ultrafiltration Manual 45 D00874 en
UF Ultrafiltration Manual 45 D00874 en
UF Ultrafiltration Manual 45 D00874 en
Ultrafiltration Technical
Manual
Version 1
May 2022
NOTICE: The information provided in this literature is given in good faith for informational purposes only. DuPont assumes no obligation or liability
for the information presented herein. NO WARRANTIES ARE GIVEN; ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE ARE EXPRESSLY EXCLUDED.
Table of contents
1 INTRODUCTION TO ULTRAFILTRATION 6
1.1 Introduction 6
1.2 Ultrafiltration Applications 7
1.3 Ultrafiltration Advantages 7
1.4 Ultrafiltration Operating Modes 8
1.4.1 Dead-End Mode 8
1.4.2 Cross-Flow and Bleed Mode 8
1.5 Ultrafiltration Module and System Configuration 9
1.6 Ultrafiltration Membrane Features 10
1.6.1 Materials 10
1.6.2 Flow Pattern 10
1.7 Ultrafiltration Filtrate Quality 11
2 WATER CHEMISTRY AND PRETREATMENT 12
2.1 Water chemistry 12
2.2 ULTRAFILTRATION PRETREATMENT 14
3 DuPont ULTRAFILTRATION MODULES DESCRIPTION 17
3.1 DuPont Ultrafiltration Module Features 17
3.2 DuPont Ultrafiltration Certifications 18
3.3 DuPont Ultrafiltration Product Code 18
3.4 DuPont Ultrafiltration Product Portfolio 20
3.4.1 DuPont UF 26/28 Series Modules 22
3.4.2 IntegraFlux™ Series Modules 23
3.4.3 IntegraPac™ Ultrafiltration Modules 24
3.4.4 IntegraPac™ Ultrafiltration Skids 26
3.4.5 IntegraFlux™ UXA-2680XP Modules: 30
3.5 DuPont Ultrafiltration Product Selection Guidelines 32
3.6 DuPont Ultrafiltration Modules Installation 32
4 DuPont ULTRAFILTRATION SYSTEM DESIGN 39
4.1 Introduction 39
4.2 System design software 39
5 DuPont ULTRAFILTRATION PROCESS DESCRIPTION 40
5.1 Filtration 41
5.2 Air Scour 42
5.3 Gravity Drain 43
5.4 Backwash Top 44
5.5 Backwash Bottom 45
5.6 Forward Flush 46
6 DuPont ULTRAFILTRATION CLEANING 47
6.1 Membrane Fouling 47
6.2 Chemically Enhanced Backwash (CEB) 48
6.3 Cleaning In Place (CIP) 49
6.3.1 Introduction 49
6.3.2 Safety Precautions 49
6.3.3 CIP Requirements 50
6.3.4 CIP Equipment 51
6.3.5 CIP Procedure 53
6.3.6 CIP Tips 55
6.3.7 CIP Chemicals 55
6.4 Alternative Cleaning Protocols 56
6.4.1 Mini-CIP 56
6.4.2 Elimination of Backwash 57
6.4.3 Backwash with RO Brine 57
7 HANDLING AND STORAGE PROCEDURES FOR DuPont ULTRAFILTRATION MODULES 58
7.1 General 58
7.2 Factory Storage & Shipping of DuPont Ultrafiltration Modules 58
7.3 Storage of New DuPont Ultrafiltration Modules 59
7.4 Short-Term Shutdown & Storage of Used DuPont Ultrafiltration Modules 60
1.1 Introduction
A separation spectrum diagram is shown on Figure 1. It depicts the most common technologies applied for the removal
of diverse contaminants or substances present in a feed stream of water supplies. While Electrodeionization (EDI), Ion
Exchange (IER), Reverse Osmosis (RO) and Nanofiltration (NF) target the removal of solutes from the feed stream,
Ultrafiltration (UF), Fine Particle Filtration (FPF) and Microfiltration (MF) separate fine particles, suspended solids,
colloidal matter, microorganisms (e.g., cryptosporidium or giardia cysts) and low molecular weight species.
UF is a pressure-driven process that achieves separation through sieving (i.e., size exclusion) depending on its pore size
and molecular weight cut-off (MWCO) expressed in kilodaltons (kDa). The pore size is the nominal diameter of the
micropores in the membrane expressed in microns (µm). The MWCO is the molecular mass or weight of a solute that is
rejected greater than 90 percent. UF membranes can be as fine as 3 kDa or as coarse as 150 kDa. Typically, coarse UF
membranes in the range of 80 – 150 kDa (equivalent to a pore size of 0.02 – 0.03 µm) are used in water treatment
applications as they have a good balance between rejection and permeability. This pore size can provide a barrier to
viruses often found in water sources.
The main applications for UF in the water and wastewater field are seawater RO pretreatment, seawater NF
pretreatment (e.g., water injection in the Oil & Gas field), groundwater or surface water treatment (e.g., to produce
drinking water, as a stand-alone technology), water treatment for industrial use and wastewater treatment (either
municipal or industrial, e.g., for reuse).
1. Ability to cope with difficult and variable waters: Ultrafiltration membranes are a physical barrier against most
particles, suspended matter, colloids, bacteria and even viruses, that can produce an excellent water quality
independently of variations in the influent water quality.
2. Improved and more consistent product quality: Due to their fine pores, ultrafiltration membranes can provide
a very high quality filtrate, with typical ultrafiltrate turbidity less than 0.1 NTU (independent of the raw water
turbidity), SDI less than 3%/min and 6-log or more removal of pathogens such as Cryptosporidium-i1- and -i-
Giardia cysts.
3. Smaller plant footprint and less weight: UF pretreatment systems require a smaller footprint (up to 50%
lower) and weight than media filtration systems. This can lead to a reduced cost of land acquisition, building
design, and transport.
4. Module and skid Integrity Testing can be done easily on line to detect potential leakages without significant
plant downtime.
5. Membrane modules can be individually isolated for repair, maintenance or replacement without
compromising the plant output.
6. Ease of design and operation: Despite requiring more focus on sustained permeability and productivity,
ultrafiltration systems offer much more stable water quality than a multimedia filtration system, without the
need to monitor filter ripening time or breakthrough, or the need of ensuring appropriate layering of
multimedia after backwash. Therefore process design is less complicated and control is more automated than
with conventional pretreatment.
7. Lower environmental impact: Conventional systems typically require chemical pretreatment such as
coagulation and pH adjustment for the removal of silt and fine particles, but UF can remove these
contaminants just by size exclusion due to the small size of the membrane pores. This can lead to lower
chemical consumption and lesser environmental concerns for wastewater disposal.
8. Lower RO stage cost: The potential for lower downstream cost, based on improved and more consistent water
quality facilitated by the UF system, is a key aspect. UF as pretreatment also allows higher design flux in the
RO stage, as well as lower requirements for membrane cleaning and ultimately lower replacement rates, by
facilitating a RO feed water with lower fouling tendency. In addition, cartridge filters use can be significantly
reduced or eliminated (especially when there is no break tank in between UF and RO).
In the Dead-End operation mode (also known as “Deposition Mode”), all the feed volume entering the UF elements
passes through the membrane (there is no reject stream) and is collected on the filtrate side, so there is 100% recovery
of the water. The contaminants that are not small enough to pass through the membrane are either trapped on the
membrane surface or stuck inside the pore channels, leading to an increase in the TMP and a decline of permeability. At
some point the system is taken off-line and the membranes are cleaned hydraulic or chemically.
These operating modes are used on high fouling waters to avoid excessive build-up of contaminants on the membrane
surface. The shear force generated on the membrane surface by the tangential flow (parallel to the membrane) reduces
the fouling rate as it continuously removes the contaminants away from the module.
In the Concentrate Recirculation mode (or Cross-Flow), the concentrate flow exceeds the filtrate flow passing through
the membrane (typically in a ratio of 5:1 or higher). The concentrate stream is then typically recycled back to the feed
tank or to the recirculation pump suction side (see Figure 3). This allows increasing the flow velocity through the feed
channels and therefore achieving a shear force effect.
In the Bleed Operation (see Figure 4), half way between Dead-End and Cross-Flow mode, most of the feed water will
pass through the membrane while the rest will get out of the UF element directly through the concentrate side
(typically 5 – 15% of the feed flow). This concentrate stream will carry part of the contaminants out of the elements and
is normally sent to drain. This operating mode is typically achieved by just partially opening the concentrate valve of the
UF skid during the filtration cycle, and can be a good alternative to dead-end operation to better control the fouling rate
during episodes of worsened feed water quality.
Depending on the type of driving filtration force, the UF modules can be categorized as pressurized or vacuum driven.
In the pressurized form, the membranes are placed inside pressure vessels (with vertical or horizontal orientation), and
the UF modules are grouped in parallel to form skids, racks, or trains. Typical operating pressure of pressurized UF
systems is up to 2.5 barg (35 psi). The vertical orientation allows easier drain, the use of air as an aid to increase cleaning
efficiency and the elimination of extra vessels or housings.
1.6.1 Materials
The most common materials for UF membranes for water treatment applications are organic polymers, such as
Polyvinylidene Difluoride (PVDF), Polysulfone (PS), Polyethersulfone (PES), Polypropylene (PP) or Cellulose Acetate (CA).
PVDF and PES are the most common product in the market.
The polymer desired properties are good permeability, hydrophilicity (easier to wet and more resistant to adsorptive
fouling), narrow pore size distribution, good tolerance to pH, temperature and chemicals, robustness (strength and
elongation), and long life.
PVDF is a very flexible and robust material (i.e., good strength and elongation), with excellent break resistance and
superior tolerance to chlorine (significantly higher than other materials such as PS/PES or PP), which is a key advantage
in water treatment applications.
In a hollow fiber the flow pattern can be from “inside to outside” or from “outside to inside” and is manufacturer
specific. When operated in an inside-out mode, the feed water enters the fiber lumen and passes through the fiber wall
to produce filtrate in the outer side. When operated in the outside-in mode, on the contrary, the feed water enters the
module, passes through the fibers from the outer wall and the filtrate is collected in the inside lumen.
In Outside-In configuration there is no risk of fiber plugging, so the UF modules can cope better with challenging feed
water conditions and are more suitable for treatment of higher fouling waters. In addition, it allows the use of air for
fouling control and needs lower volume for backwash compared to Inside-Out fibers. Typically a flexible and robust
material such as PVDF is used in Outside-In hollow fibers.
However, dissolved substances are not removed by UF membranes at a high extent (removal of e.g., Dissolved Organic
Carbon is typically < 15%). Removing these substances by UF requires them to be transformed first into particulate form,
e.g., through oxidation, pre-coagulation or adsorption.
Removal of metals such as Iron (Fe) and Manganese (Mn) is dependent on the oxidation state of these species. UF can
remove Fe and Mn if they are in precipitate form (not in dissolved form). Fe and Mn can be oxidized upstream of the UF
with aeration (more effective for Fe) or chemical oxidizing agents such as chlorine, permanganate, ozone or chlorine
dioxide. Higher pH favors precipitation.
In order to have a comprehensive understanding of the feed water quality and its fouling potential, there are a few key
parameters that need to be monitored during operation. This section will introduce these parameters, which are
summarized in Table 1 together with their recommended monitoring frequency.
Turbidity: Sediments, clay, silt, small particles, solids etc. cause a liquid to appear turbid, “hazy”. These particles can, host
or shield microorganisms like bacteria and viruses. Turbidity is measured by the intensity of light that passes through
the water sample, and expressed in NTU (Nephelometric Turbidity Units). DuPont's ultrafiltration modules provide
consistent product water with turbidity values < 0.1 NTU.
TSS (Total Suspended Solids): It is the measure of the total weight of solids contained in a water sample, and is
expressed in mg/L. This parameter is more accurate than turbidity (i.e., turbidity usually does not detect very fine
particles).
SDI (Silt Density Index): Is a Fouling Index. This parameter provides an indication of the particulate fouling potential of
the water (see Figure 6). It is based on the measurement of the time it takes to collect 500 mL of water sample through
a paper filter of 0.45 µm at the start of the test (ti) and after the water has flowed through the filter at 2.1 bar (tf) for 15
minutes (T). SDI number is calculated by Equation 1:
Eq. 1
DOC (Dissolved Organic Carbon): Fraction of TOC which is dissolved (filtered through 0.45 µm). Generally TOC and
DOC are the same value, except in wastewaters and some surface waters.
COD (Chemical Oxygen Demand): It is a measure of the amount of compounds in a sample which have been oxidized
by a strong oxidizing agent. Although inorganic substances such as Fe may also be subject to oxidation, for most natural
and industrial waters, the matter to be oxidized is organic in nature.
UV254 Absorbance: It is an indirect measurement of NOM, based on the fact that most organics compounds can absorb
UV light. Expressed in cm-1. Surrogate of TOC. Above 0.5 cm-1 indicates biofouling is likely.
SUVA (Specific UV Absorbance): Ratio between UV254 and DOC (if > 4, mostly humic matter; if < 2, indication of algae
bloom).
O&G (Oil & Grease, Hydrocarbons): Even in very small quantities i.e., < 0.05 mg/L, it can cause accelerated fouling in
membranes.
Iron and Manganese: If they are in oxidized form, behave as particles and can be rejected by membrane systems, but
will cause fouling. Iron (Fe) can be naturally occurring (e.g., well waters), coming from corrosion of upstream piping
and/or equipment, or residuals from pre-coagulation processes.
Calcium and Magnesium: Hardness in water is due primarily to Ca and Mg ions. Based on hardness, the water can be
classified as Soft (up to 60 mg/L as CaCO3), Hard (up to 180 mg/L as CaCO3) and Very Hard (> 180 mg/L as CaCO3).
Hardness has no harmful effects on health, but leads to formation of scaling deposits in pipes, equipment or
membranes.
Conductivity: The electrical conductivity of water is linearly related to the total dissolved solids (TDS). It is the ability of
the water to conduct an electrical current. Expressed in µS/cm.
pH: Is a numeric scale used to express the acidity or alkalinity of the water. Solutions with a pH less than 7 are acidic and
solutions with a pH greater than 7 are basic. Pure water has a pH of 7 and is neutral. In water, high pH causes a bitter
taste, water pipes and equipment become encrusted with deposits. Low-pH water will corrode or dissolve metals and
other substances.
Silica: Can be Reactive Silica (Soluble) or Un-Reactive Silica (Colloidal). Colloidal form can cause fouling in membrane
systems.
DuPont Ultrafiltration Modules designs are based on qualified feed water conditions as shown in Table 2. The UF
modules can tolerate period excursions in feed water quality as shown as the maximum recommended. If the feed
water quality is outside of the design basis range shown below, a pilot study should be operated to confirm
performance or pretreatment must be considered. If the system is designed and installed to the qualified conditions
below but the feed water quality is not maintained DuPont Water Solutions should be consulted.
Notes:
[1] Note: Maximum values recommended refer to continuous operation, consult your local representative for values beyond those shown.
Otherwise, very little pretreatment is required if microorganisms and particles are the target contaminants. Prefilters
(100 – 300 µm) need to be installed upstream the UF process to protect the UF system from large particles, sand, etc.
See Table 3 for strainer selection guidelines. A variety of technologies can be used such as self-cleaning screens and
bag, cartridge, or disc filters.
Notes:
[1] Recommended for initial specification, and to be reviewed against site-specific raw water quality and project drivers.
[2] Strainer size of 100 µm or lower is recommended to control the growth of barnacles and mussel larvae inside the UF system pipes, as well as to prevent sand particles to reach
the UF membranes.
Depending on the type of water or range of feed water parameters other pretreatment technologies such as
coagulation/flocculation, clarification/sedimentation, flotation or granular media filtration may also be recommended.
Coagulation/Flocculation: Chemical and Physical process to form particle aggregates (flocs) from silt, clay, colloids,
suspended material, microorganisms, NOM (by adsorption in the flocs) for removal in subsequent steps such as
clarification, flotation or granular media filtration. In coagulation, chemicals such as alum or ferric salts are added to the
water to reduce repulsion forces between particles (“destabilization”). This enables particles to become attached to each
other. It is achieved by rapid mixing (“flash mixing”) in order to disperse the coagulant quickly in the water. In contrast,
flocculation consists in a low-intensity mixing to increase the rate of agglomeration. Chemicals might be used to assist,
such as cationic, anionic or non-ionic polymers.
l High-Rate Sedimentation (Lamella Settlers): It uses inclined plates for more efficient removal of solids (by
providing a larger settling area), typically at 60° and 5 cm separation. It allows higher loading rates; reduced
footprint (65 – 80% compared to conventional clarifiers). Appropriate when inlet turbidity > 50 NTU.
l Microsand Ballasted Clarification: Small sand grains are added in the flocculation basin to act as nucleus for
floc formation. Increased settling velocity. Reduced time and footprint requirements.
l Dissolved Air Flotation (DAF): Solids removal occurs at the surface of the clarifier, through flotation, rather
than at the floor (i.e., clarified water is removed from bottom, instead of from top). Smaller footprint than
conventional settlers. DAF is ideal for removal of light particles with slow settling time (e.g., coagulated NOM),
algae or Oil & Grease, when turbidity < 50 NTU. Micro air bubbles (∼50 µm) adhere or push-up the flocs at the
DAF inlet and force them to float. It includes Coagulation + Flocculation chambers. It can achieve clarified water
< 0.5 NTU.
Granular Media filtration: It is the oldest (4000 BC) and most commonly used pretreatment process. The water flows
through one or more layers of porous granular medium (e.g., sand, pumice, anthracite) to remove suspended solids.
Typically it removes 90 – 99% of the solids. There are different types of granular media filtration:
l Single-Medium: Typically sand or anthracite, only if feed turbidity is < 2 NTU, TSS < 3 mg/L.
l Multimedia: Pumice or Anthracite over Sand. It is the most common.
l Two-Stage (for > 20 NTU and TOC > 6 mg/L): Typically 1st stage is coarse single or dual filter (60 – 80%
removal) and 2nd stage is polishing dual-media filter which removes 99% remaining fine solids. TOC removal is
low, typically 20 – 30% or even up to 50% if a carbon layer is installed at the top. It can achieve outlet turbidity <
0.1 NTU.
l Gravity Filters: Need only 2 – 3 meters (6.5 – 9.8 ft) head, housed in open tanks.
l Pressurized Filters: need higher pressure; enclosed in steel vessels.
l Slow Sand Filters: Gravity. Typically < 0.5 m/h (gpm/ft2) loading rate. Best for feeds < 5 – 10 NTU and TOC < 3
mg/L. They can achieve filtrate turbidity < 1 NTU.
l Rapid Sand Filters: they can be gravity or pressurized. Up to 12 m/h (gpm/ft2). Usually require pre-coagulation.
They can achieve filtrate turbidity < 1 NTU.
l High-Rate Filters: Pressurized filters. Up to 30 m/h (gpm/ft2). They can achieve filtrate turbidity < 0.5 NTU with
coagulant aid.
l 0.03 µm nominal pore diameter for removal of bacteria, viruses, and particulates including colloids.
l PVDF fibers free of macro voids for high mechanical strength with excellent chemical resistance offering long
membrane life and reliable operation.
l Hydrophilic PVDF fibers for easy cleaning and wettability that help maintain long term performance.
l Outside-In flow configuration for high tolerance to feed solids and the use of air scour cleaning.
l U-PVC housings eliminate the need for pressure vessels and are resistant to UV light.
l In addition, the XP fiber products provide up to 35% higher permeability than previous generation modules
improving operating efficiencies and productivity.
The outside-in flow configuration allows the use of highly effective air scour cleaning which enhances particle removal
and improves recovery. A dead-end flow format achieves higher recovery and energy savings. The module housing
design eliminates the need for separate pressure vessels while the vertical orientation allows gravity draining and
facilitates the removal of air from cleaning and integrity testing processes.
The hollow fiber membranes are 1.3 mm outside diameter and 0.7 mm inside diameter and are made from PVDF
polymer. The fibers are strong because of a combination of the PVDF polymer, dense substructure and selective active
layer formed on the feed side of the fiber. The PVDF membranes offer high chemical resistance, coping with NaOCl
concentrations up to 2000 mg/L, and are tolerant to temperatures of 40°C. The hydrophilicity of the PVDF fibers is
increased by using a proprietary treatment during manufacturing.
The 0.03 μm nominal pore size combines high filtration performance and high flux. The smaller pore size provides
stabile long term filtration performance compared to microfiltration membranes.
Notes:
[1] Refer to NSF listings webpage for certifications.
The DuPont Ultrafiltration Modules should be rinsed prior to startup to remove preservative fluid shipped in the
modules. Flushing should be performed until no foam is observed in the wash water. Depending on the treatment
application, additional rinsing or disposal of the filtrate may be required.
NSF / ANSI Standard 61 certified modules require the following conditioning rinse prior to producing potable water:
1. Rinse the modules at a feed rate of 40 LMH minimum for a period of 4 hours.
2. Achieve a minimum total rinse volume of 160 LMH·hours using the feed water available.
3. The concentrate bleed rate should be set from between 0 – 20% with the balance being filtrate.
4. During the rinse cycle, perform standard cleaning protocols as per DuPont's recommendations which are
specifically designed to consider the feed water quality available.
5. The filtrate should be sent to the appropriate disposal system based on the regulations that apply to the
location where the conditioning rinse is carried out and not used as potable water.
6. Local regulations may require additional conditioning of the system prior to producing potable water.
l IntegraPac™ Module:
l IntegraPac™ Skid:
The 2660 module is an excellent choice for systems capacities of 50 m3/hr (220 gpm) or less. This 1.5 m (60 inch) length
module offers higher efficiencies over a wider range of feed water conditions compared to longer length modules. The
15 cm (6 inch) diameter module allows a more compact design for space constrained installations.
The 2860, which is shorter in length, is recommended for smaller systems and where building height is a concern. The
2880 has higher membrane area for the same footprint offering a more economical design.
There are four connections in each module. Feed flow enters and is distributed into the modules through the side feed
port located at the side bottom of each module. The air inlet is located at the bottom of the module and is used for air
scouring and integrity testing. The concentrate (discharge of waste flows from the outside of the fiber) is the top central
port and the filtrate (inside of fiber) is located at the side top port of the module.
Table 5 shows dimensions, connections and specifications for the DuPont Ultrafiltration SFP/D and SFP/D XP modules
family, as depicted in Figure 11 and Figure 12. Note that manufacturing and thermal expansion tolerances and the
thickness of the base clip are not included in the dimensions below. Refer to the installation drawings for this
information.
IntegraFlux™ Ultrafiltration Modules with XP fiber are made from high permeability, high mechanical strength, hollow
fiber PVDF membranes. The modules provide excellent performance, industry leading membrane area with low energy
and chemical consumption. IntegraFlux™ modules have up to 35% higher permeability than previous generation
modules, helping to improve operating efficiencies and productivity.
These modules are an excellent choice for systems with capacities greater than 50 m3/hr (220 gpm). The shorter SFP-
2860XP or SFD-2860XP modules are well suited for installations with limited height. Larger and longer, 20 cm (8 inch)
diameter and 2 m (80 inch) in length, the SFP-2880XP or SFD-2880XP modules offer a high effective membrane area
combined with high permeability that provides the most economical and efficient membrane system design.
There are four connections in each module. Feed flow enters and is distributed into the modules through the side feed
port located at the side bottom of each module. The air inlet is located at the bottom of the module and is used for air
scouring and integrity testing. The concentrate (discharge of waste flows from the outside of the fiber) is the top central
port and the filtrate (inside of fiber) is located at the side top port of the module.
Table 5 shows dimensions, connections and specifications for the DuPont Ultrafiltration SFP/D and SFP/D XP modules
family, as depicted in Figure 11 and Figure 12. Note that manufacturing and thermal expansion tolerances and the
thickness of the base clip are not included in the dimensions below. Refer to the installation drawings for this
information.
Innovative end-cap design helps direct coupling of IntegraPac™ modules reducing the need for piping and manifolds.
These modules are an ideal choice for systems requiring a small footprint. The IP-77 and IPD-77 modules offer a high
effective membrane area, which contributes to a more economical membrane system design. The IP-51 and IPD-51
modules are shorter in height and are suitable for applications where there is a head space constraint. The IP-77XP
module offers a high effective membrane area combined with high permeability fibers that offer an economical and
efficient membrane system design. The IP-51XP module is shorter in height and is suitable for applications where height
is a constraint while maximizing productivity and efficiency with high permeability fibers.
The IntegraPac™ module is shown in Figure 13. There are six connections on each module. Feed flow enters and is
distributed into the modules through the side feed ports located on the bottom end cap. Feed flow enters the module
on the outside of the fiber. The air connection is located on the side of the bottom end cap and is used for air scouring
and integrity testing. The concentrate (discharge of waste flows from the outside of fiber) and filtrate port (inside of
fiber) are located on the top cap.
Included with the module are the couplers, air fitting, and transparent filtrate elbow.
Figure 14. IntegraPac™ IP/D-51, IP/D-51XP, IP/D-77, and IP/D-77XP Module Reference Drawing
for Dimensions
The IntegraPac™ skid with IP/D-51(XP) or IP/D-77(XP) modules is a pre-engineered, standardized skid design consisting
of IntegraPac™ Ultrafiltration Modules, auxiliary parts and piping. It is designed to significantly streamline design,
assembly and installation, making possible lower skid costs, reduced engineering design costs, easy assembly, smaller
footprint and shortened delivery schedule. Features include:
l Direct coupling of modules eliminate ancillary piping, help saving costs and reducing footprint.
l Modular and scalable for design across a wide range of flowrates.
l Materials of construction selected for corrosion resistance and chemical compatibility.
l Shipped unassembled to lower transportation cost and help prevent damage in transit.
l Standardized and pre-fabricated components eliminate measuring, cutting, gluing and welding.
l Easily accessible for physical inspection or replacement at end of life.
l Operator-friendly transparent filtrate elbow designed and located for easy visual integrity inspection.
l High pressure rating to enable direct feed to reverse osmosis feed pumps.
Table 7 shows skid details for the IntegraPac™ IP/D-51, IntegraPac™ IP/D-77 and IntegraPac™ IP/D-51XP, IntegraPac™
IP/D-77XP skids, as depicted in Figure 15 and Figure 16.
The IntegraFlux™ UXA-2680XP UF module, featuring enhanced XP fibers, provides an ideal drop-in replacement for 50
m2 active area modules, having 10% more membrane area compared to 50 m2 active area modules, reducing plant
footprint and producing more water per module with no need of hardware or process changes. Additionally,
IntegraFlux™ UXA-2680XP ultrafiltration membrane with 0.03 µm nominal pore diameter provides a higher removal
efficiency of bacteria, viruses, and particulates as compared to a microfiltration membrane.
The IntegraFlux™ UXA-2680XP UF module bottom feed port and top filtrate port are both DN50 (2”) connections, while
the top side concentrate port is DN40 (1 ½”). Air and water both enter at the bottom of the module.
Table 8 shows dimensions, connections and specifications for the IntegraFlux™ UXA-2680XP modules, and Figure 17
depicts detailed drawings of the modules and the three different available versions for the End-Caps.
Figure 21. Installation Drawing for IntegraPac™ IP/D-51, IP/D-51XP, IP/D-77 and IP/D-77XP
Modules
4.1 Introduction
The Ultrafiltration system design software is a powerful tool that allows to size new systems or evaluate the
performance of existing ones. In order to design a new Ultrafiltration system it is important to understand the main
inputs needed to get an accurate and optimized design. These inputs include information about the feed water source
(e.g., municipal, seawater, wastewater, well water or surface water), quality (refer to Section 2.1 of this document),
temperature range and required feed flow or net plant output. On the other hand, the final application of the project is
of interest, as in the case of drinking water applications, specific DuPont Ultrafiltration Modules must be used (refer to
Section 3.3. of this document).
For a given feed water type and quality, the appropriate design guidelines must be applied. These design guidelines
have been created based on extensive experiences and references in similar waters. The design guidelines include
suitable operating flux, duration of the filtration cycles or frequency of the chemical cleanings. Further information on
Ultrafiltration system operation can be found in Sections 5 and 6 of this document.
Once all this information is introduced in the system design software, it will populate a detailed Ultrafiltration System
Design report, which includes a general process flow diagram, module selection, sizing and quantity of trains, sizing of
water and chemical tanks, process parameters and sequence tables, as well as estimations for chemical and energy
consumption, among others.
The WAVE technology uses a powerful hydraulic modeling calculation engine which improves the accuracy of the
model. WAVE capabilities help engineers and original equipment manufacturers (OEM) configure water treatment
components better and faster through integrating all DWS technologies into one tool - allowing for easier iterations as
the design process proceeds. The WAVE tool also offers accurate water quality predictions for multiple components
simultaneously – reducing calculation errors and data re-entry from one calculation tool to another.
At initial plant start-up the modules must be flushed in order to remove any residual storage chemicals or air trapped
during the module installation. This flush occurs on the outside of the fibers, i.e., no filtrate is produced. Once the initial
flush is done, the plant can begin producing filtrate. When starting the initial filtration cycle the flow should be slowly
increased before being put into operation at the design conditions.
At initial plant start-up the modules must be flushed in order to remove any residual storage chemicals or air trapped
during the module installation. This flush occurs on the outside of the fibers, i.e., no filtrate is produced. Once the initial
flush is done, the plant can begin producing filtrate. When starting the initial filtration cycle the flow should be slowly
increased before being put into operation at the design conditions.
l Inadequate pretreatment
l Overdosing of upstream process coagulants
l Improper materials selection (pumps, piping, etc.)
l Failure of chemical dosing systems
l Inadequate backwash and unsuitable shutdown
l Improper operational control
l Slow build-up of precipitates over extended periods
l Change in feed water composition
l Biological contamination of the feed or filtrate water
l Oil & inorganic contamination of the feed water
From the point of view of the fouling mechanism, there are basically three categories for fouling, being cake formation,
pore adsorption and pore blocking.
Cake Formation normally occurs when the contaminants are too large to enter the membrane pores, so they deposit on
the membrane surface and create an additional resistance to the passage of water, resulting in a TMP increase.
Pore Adsorption typically happens when the contaminants are smaller than the membrane pore size, so they deposit on
the internal walls of the pores, hence reducing the diameter of the pores and therefore providing also an additional
resistance to the flow.
Finally, Pore Blocking takes place when the contaminants are of similar size to the membranes pores, so that blocking
occurs and therefore the number of actual pores is reduced, providing also an additional resistance to the flow.
According to the nature of the contaminants, the fouling can also be categorized as follows:
Particulate: This type of fouling is caused by organic and inorganic particles, suspended solids, colloids and turbidity
present in the feed, which are not in dissolved form, and typically larger than the pore size. This can be reduced by
operations upstream the UF system such us coagulation, sedimentation, clarification or media filtration. The common
cleaning method for this type of fouling is air scour and backwash.
Biological fouling: This is caused by the attachment and growth of microorganisms on the membranes, which can also
lead to the formation of a viscous biofilm. This can be reduced by using in-line chemical feed of chlorine or biocide or
by elimination of nutrients by using adsorption (e.g., powdered or granular activated carbon, PAC or GAC), or
coagulation upstream the UF system. The common cleaning method for removal of biological fouling is cleaning with
oxidizers or biocides (e.g., Cl2, H2O2, SBS). Note PAC is available in different grades and can damage the membranes. If
using PAC consult with DuPont TS&D.
Organic fouling: This is the one of the major causes of fouling in the UF processes and is caused by organics adsorbing
on the membrane (silt, organic acids, humic substances), as the majority of these substances are too small to be retained
by the membrane and hence go through. This can be reduced by using PAC, GAC, or coagulation upstream the UF
system. The common cleaning method for removal of organic fouling is cleaning regimes with alkali at pH 12 (e.g.,
NaOH).
The CEB process is typically programmed to occur automatically at a preset frequency but this can be field adjusted
after gaining site specific operating experience. Alternatively it can be initiated based on a TMP set point. The CEB is
performed using UF filtrate.
The CEB is performed following the same steps of a normal backwash sequence except a soak step is added after the
addition of the chemicals, for 5 – 20 minutes, to allow time for the chemicals to react with contaminants that have
attached to the membrane surface or penetrated the fiber wall. It is recommended however to invert the order of the
backwash steps, i.e., backwash bottom first and then backwash top as the second step, to make sure that the system
remains filled with the chemical solution during the soaking time. Intermittent air scour (e.g., 5 – 10 seconds every 5
minutes) can be applied as well during the soak step to increase effectiveness.
After the soak a routine backwash including air scour, gravity drain, top and bottom backwash, and forward flush is
performed to remove any remaining particulates and purge residual chemicals. After a CEB and at the start of the
operating step, the initial filtrate produced might need to be sent to waste to remove residual chemicals. This step is
dependent on the system piping and valve design and the downstream requirements for the filtrate. In addition, the
CEB can be performed at reduced flux than that used for standard backwash (e.g., 80 LMH).
6.3.1 Introduction
The fouling of membrane surfaces results in the gradual performance decline of the UF System in terms of high
operating transmembrane pressure , lower sustainable filtrate flow or flux, and/or high chemical and power
consumption.
Clean-in-Place (CIP) may be accomplished effectively due to the excellent physical properties and chemical tolerances
of the DuPont Ultrafiltration Hydrophilic-Polyvinyldifluoride (H-PVDF) membrane material and module components,
which are compatible and resistant to elevated levels of pH, chlorine oxidants, and temperature. Concentration,
cleaning time, temperature, intermittent air scour, and hydraulic conditions during the cleaning process are important
considerations which will affect cleaning efficiency.
UF system performance should be monitored on a regular and frequent basis. If cleaning is delayed too long, fouling
may become irreversible and result in potential physical damage to the UF module or appurtenance equipment. The
DuPont Ultrafiltration Normalization Tool may be used to analyze UF system performance on a normalized basis, to
remove or minimize the effects of temperature, pressure, and flow so that the user may differentiate between normal
phenomena and real performance upsets due to fouling. The DuPont Ultrafiltration Normalization Tool is available
from your local DWS Technical Service.
CIP is most effective if it is tailored to remove the specific fouling problem. Sometimes a wrong choice of cleaning
chemicals can make a situation worse. Therefore, the type of foulants on the UF membrane surface should be
understood prior to the CIP, so that the most effective CIP cleaning solution and sequence may be used for the
procedure. There are different ways to accomplish this:
l When using any chemicals indicated here or in subsequent sections, follow accepted safety practices. Consult
the chemical manufacturer for detailed information about safety, handling and disposal.
l When preparing cleaning solutions, ensure that all chemicals are dissolved and well mixed before circulating
the solutions through the modules.
l During pumping and recirculation of cleaning solutions, observe maximum temperature and pH limits. Please
refer to Table 11 below.
During regular operation, the surface of the fibers of the UF modules may become fouled by particles, biological matter,
colloidal particles and/or insoluble organic constituents. Deposits build up on the fiber surfaces during operation, until
they result in an increase of TMP to levels or a decrease of normalized filtrate flow that cannot be recovered on
sustainable basis by regular backwash and CEBs.
DuPont Ultrafiltration Modules should be cleaned to restore membrane permeability, when one or more of the below
parameters are encountered during regular operation, after a CEB event. Permeability is the flux, per unit of
transmembrane driving force, and is expressed as LMH/bar or gfd/psi.
If delayed too long, the membrane fouling may become irreversible, where cleaning may not restore membrane
permeability. Heavily fouled membranes are more challenging to clean as it becomes more difficult for the cleaning
chemical to penetrate the membrane surface, and flushing the foulants out of the membranes. Furthermore, the time
between cleanings may become more frequent as the membranes which are not completely cleaned foul or scale more
rapidly.
The equipment for CIP is shown in the CIP system flow diagram below (Figure 31). The materials of construction for
selected equipment and ancillaries of the CIP system should be compatible with the pH, chemical types and
concentrations, and temperature of the CIP solutions.
A general rule of thumb used in sizing of the CIP Tank is to use the approximate volume of all of the UF
modules, and add the hold-up volume in the feed and return lines, within the boundaries of the UF system
to be cleaned in one CIP event plus enough volume to maintain a Net Positive Suction Head (NPSH) for the
CIP pump.
For example, to clean a DuPont Ultrafiltration system containing ten (10) nos. of DuPont Ultrafiltration SFD /
SFP-2880 modules, to be cleaned in one CIP event, the following calculations may be considered:
a. Volume in UF Modules
Vmodule = 39 L (10.3 gal) / module
b. Volume in Pipes
(assume 10 m (32.8 ft) length of DN50 PN10 (2-in. SCH 80) UPVC pipe)
2. The CIP Pump should be sized for the flows and pressures given in Table 12, making allowances for pressure
loss in the piping and across the CIP cartridge filter.
3. Appropriate valves, flow meters and pressure gauges should be installed to adequately control the flow.
Service lines may be either hard-piped or use flexible hoses. In either case, the flow velocity should be
maintained at 3 m/s (10 ft/s) or less.
4. Ensure that the CIP concentrate and filtrate return lines are submerged in the CIP Tank to minimize foaming.
The cleaning duration for each CIP solution is expected to require about 6 hours, depending on target recycle and soak
durations, and actual time required to prepare chemicals and equipment. The permeability of the UF membranes to be
cleaned should be measured with online instrumentation for before and after the CIP with each type of solution, to
allow for baseline and assessment of chemical cleaning efficiency and indication of the type of fouling. Permeability
(LMH/bar, or gfd/psi) may be measured on normalized terms using the DuPont Ultrafiltration Normalization Tool, or on
approximate basis using field measured values of flow and pressure at the feed and filtrate.
Table 13 provides a general valve sequence table for the steps of the CIP procedure. A description of each step of the
CIP procedure follows in this section.
Notes:
X – Valve Closed, or Equipment Off
O – Valve Open, or Equipment On
1
Valve positions and equipment status are dependent on the previous step in the sequence. For example, during Regular Backwash, Pre-CIP (Step 3) the CIP Pump is not required to
be On in the stand-alone step, however the CIP Pump continues to be On to allow for mixing of cleaning solution (Step 2) which occurs in-parallel.
2
Valve sequence will differ if low-flow recirculation is practiced during extended soak duration. Refer to Section 6.3.6, CIP Tips.
3
If intermittent air scour is practiced during Soak step, the Forward Flush Valve should be opened to allow venting of air introduced into UF modules. Elevation of system piping
will help prevent drain out of CIP solution during this process.
2. Make up cleaning solution. Preheat cleaning solution to desired temperature, and meanwhile, open the CIP
recycle valve to mix the solution with pump and/or agitator. For seawater applications, RO permeate is
preferred for the UF CIP make-up solution; however, potable water or UF filtrate may be used if there is no
alternative water source. Always add the chemical to the CIP make up water to avoid exothermic reactions.
3. Regular backwash, pre-CIP. Conduct a regular backwash of the UF skid to remove loose contaminants prior
to the CIP.
4. Remove from Service. Remove the UF skid to be cleaned from service by normal shutdown procedures.
Ensure manual and actuated valves are in correct position prior to the CIP.
6. Low-flow pumping. After the UF skid is drained of residual water, activate the CIP pump. Pump mixed, pre-
heated cleaning solution through the feed side of the UF modules (i.e., filtrate valve closed) at conditions of
low flowrate (about half of that shown in Table 12) and low pressure to displace remaining standing water and
solids in the UF modules and rack.
7. Recycle. Recycle the cleaning solution at the flowrates shown in Table 12. CIP solution continues to be
introduced into the UF modules from the feed side. Continue to recycle and allow the temperature to
stabilize. Measure the pH of the solution and adjust the pH, if needed – e.g., if pH falls or increases by greater
than 1 pH unit from target level. If NaOCl is included in the CIP solution, the recycled solution may also be
measured for free chlorine using a portable colorimeter, where NaOCl chemical is replenished if the
measured chlorine falls below 75% of target concentration. The recycle step typically lasts 1 hour, depending
on extent of fouling. Initially, recycle only through the feed side of the module (i.e., filtrate valve closed) so
that the solids accumulated on the membrane surface are flushed out of the system and not pushed back
again into the membrane; after 15 – 20 minutes open as well the filtrate valve (while the concentrate/reject
valve remains partially open) so that the chemical solution also flows through the fiber and filtrate piping back
to the CIP tank (target 10 – 20% filtrate and 80 – 90% concentrate returns).
8. Soak. Deactivate the CIP Pump and CIP Tank Heater. Close the CIP inlet, outlet and return valves, and allow
the modules to soak. The soak step is typically 2 hours, depending on extent of fouling; sometimes, an
overnight soak of 10 – 15 hours is effective for recovery of severe fouling. To maintain a high temperature and
to improve cleaning efficiency during an extended soak period, use a slow recirculation rate (about 10% of
that shown in Table 11). We recommend intermittent air scour for a few seconds, every 30 minutes of the soak
period, to agitate fibers for enhanced cleaning benefits; if intermittent air scour is practiced during soak step,
the Forward Flush Valve should be opened to allow venting of air introduced into UF modules.
9. Final Recycle. Recycle the cleaning solution at the flowrates shown in Table 11. CIP solution is again
introduced into the UF modules from the feed side. The final recycle step typically lasts 20 – 30 minutes
duration.
10. Flush out. After the final recycle period, drain the modules and drain the CIP Tank. Fill the tank with RO
permeate (preferred, for seawater applications), potable water, or UF filtrate to prepare for the Flush out step.
RO permeate is preferred for seawater applications, to prevent reaction of impurities in the flush-out water
with the remaining cleaning solution. Perform the Flush out of the CIP tank and piping by repeat of Low-flow
pumping (Step 6), and Recycle (Step 7) for a period of 10 minutes. A plan for discharge of the chemical wastes
in accordance to local regulations should be developed prior to performing the CIP.
11. Regular backwash, post-CIP. Conduct a regular backwash of the UF skid to prepare the system for return to
service.
1. The fouling of membrane modules typically consists of a combination of fouling mechanisms, e.g., a mixture
of organic fouling, colloidal fouling and biofouling, which often requires a two-step cleaning program: alkaline
cleaning followed by acid cleaning. We recommend alkaline cleaning as the first cleaning step. Acid cleaning
should only be applied as the first cleaning step if it is known that only calcium carbonate or iron hydroxide is
present on the membrane surface. Acid cleaners typically react with silica, organics (e.g., humic acids), and
biofilm present on the membrane surface, which may cause further decline of membrane performance if
being introduced first.
2. Always measure the pH during cleaning. If the pH increases more than 1 pH units during acid cleaning, more
acid needs to be added. If the pH decreases more than 1 pH units during alkaline cleaning, more caustic needs
to be added.
3. Inspect the appearance of the spent CIP solution at various points during the recycle and soak steps. The
visual appearance sometimes provides indication of the type of fouling, especially in the case of inorganic
metals.
4. Long soak times. It is possible for the chemical cleaning solution to be fully saturated, which allows the
foulants to precipitate back onto the fiber surface. In addition, the temperature will drop during this period;
therefore the soaking becomes less effective. It is recommended to circulate the solution regularly in order to
maintain the temperature (temperature should not drop more than 5°C/41°F) and add chemicals if the pH
needs to be adjusted.
5. Fresh cleaning solution needs to be prepared when the cleaning solution becomes turbid and/or discolored.
The cleaning is repeated with a fresh cleaning solution.
6. Intermittent air scour immediately before the CIP (prior to Step 5, Drain out water in UF skid), during, and just
at the end of the soaking step (Step 8, Soak), can benefit the cleaning effectiveness in more challenging cases.
It might occur that due to the aeration and depending on the system piping layout, some of the chemical
solution volume is lost through the module top port; in this case the system must be refilled again with
chemical solution using the CIP pump.
7. Thermal Shock should be considered in cold water environments, to prevent damage to UF modules and
piping systems in cases where high-temperature CIP solution is introduced into low-temperature system (e.g.,
Step 6, Low-flow Pumping), or low-temperature flush water is introduced into a warm or heated system (e.g.,
Step 10, Flush Out). In this case it is recommended to recirculate the solution while it is being heated-up up for
a gradual temperature increase. Similarly, at the end of the cleaning, it is recommended to let the system cool
down before flushing it out (Step 10 of previous section) with cold water.
8. Use the least harsh cleaning solution possible, including cleaning parameters of pH, temperature, and solution
strength.
Table 14 lists general cleaning chemicals that are effective to recover membrane permeability in most situations.
Generic acid cleaners and alkaline cleaners are standard, widely available cleaning chemicals. Acid cleaners are used to
remove inorganic precipitates (e.g., including iron), while alkaline cleaners are used to remove organic fouling (e.g.,
biological matter). Specialty cleaning chemicals may be used in cases of severe fouling, or unique cleaning
requirements. For seawater applications, RO permeate is preferred for the UF CIP make-up solution; in cases when RO
permeate is not available, please discuss project-specific conditions of water quality with DWS Technical Service to
evaluate if potable water or UF filtrate may be used as an alternative water source. Depending on the make-up solution
water source, the feed water may be highly buffered (i.e, high alkalinity), where additional acid or base chemical may
need to be added to reach the target pH level – which is pH 2 for acid cleans, and pH 12 for alkaline cleans. Also, a
softener can be used on the CIP make up water system to remove hardness.
6.4.1 Mini-CIP
This approach consists of substituting the standard approach based on regular Chemically Enhanced Backwash (CEB) by
Cleanings in Place (CIP) of short duration, and is applicable to all water types. For this purpose, the existing auxiliary
system used for the standard CIP is employed to perform more frequent but shorter chemical cleanings, called mini-CIP,
so there is no need of additional installation or hardware. However, due to the relatively high frequency of mini-CIP (i.e.
typically from 1 to 3 times per week), it is recommended to automate the process in order to reduce labor.
The total duration of the mini-CIP is typically 30 minutes and includes a regular Backwash pre-cleaning, a heated
chemical solution recirculation step with a soaking period in between (with intermittent Air Scour), and a final Backwash
post-cleaning. Note that the mini-CIP substitutes the CEB, not the standard intensive CIP program which still might be
needed regularly.
l Increased UF system recovery and availability (as the frequency of mini-CIP and water consumption is typically
lower than CEB).
l Lower UF system footprint and system complexity, by reducing the hardware associated to the CEB systems.
l Higher cleaning efficiency, due to the use of recirculation, temperature aid, higher flexibility to use special
chemicals and the possibility to use low TDS water (e.g. RO permeate) as solvent.
l Reduced chemical consumption and waste, due to the operation in a closed loop as opposed to CEB’s flush-
through mode.
l Lower risk of RO membrane oxidation in integrated systems due to the lower system exposure to chlorine as
compared to more frequent on-line CEB’s.
Depending on the feed water source and quality it might be possible as well to remove the backwash step from the UF
operation (and therefore all the equipment associated to it) and rely on regular Air Scour and Forward Flush as the only
hydraulic methods to help removing membrane fouling. However, regular chemical cleanings must be still applied.
Please contact DuPont for further details.
In integrated systems where UF is used as pretreatment of RO, it might be possible to backwash the UF system with RO
brine, instead of the standard approach using ultrafiltrate water, with no detrimental impact on the UF system
performance or membrane integrity. This is only feasible for specific water sources and under certain conditions, and
simply refers to backwash and not to chemical cleanings. Please contact DuPont for further details.
Some of the benefits of using RO brine for UF backwash as opposed to ultrafiltrate water are:
DuPont Water Solutions (DWS) recommends that the procedures for DuPont Ultrafiltration long-term shutdown &
storage, in particular, be closely coordinated with local DWS technical service to facilitate a positive experience, and to
train facility operations & engineering staff.
7.1 General
DuPont Ultrafiltration Modules should be handled in such a way to help control the spread of and reduce bio-growth
during long-term storage, shipping or system shutdowns. DWS recommends that the modules be shipped and stored in
their original factory packaging, and loaded into the system skids just prior to start-up. There are cases when the
customer may prefer to install the modules onto the skids with significant time before start-up and commissioning;
storage guidelines for these cases are also addressed in this chapter. If the module is exposed to air for an extended
period of time, the membrane may become dry and at risk to irreversible damage; therefore, it is important to keep the
membrane wetted.
Preservative solution is automatically delivered into the module housings prior to sealing of the module’s feed and
outlet ports by blinds at the grooved couplings and plug at the threaded air connection. The approximate volume of
standard storage solution used at shipping for each module is 2 L (0.5 gal) for SFD / SFP-2660; 4 L (1 gal) for SFD / SFP-
2860(XP), IP / IPD-51(XP) and UXA-2680XP; and 6 L (1.6 gal) for SFD / SFP-2880(XP) and IP / IPD-77(XP). If glycerin is
added for freeze protection the holdup module volume will be used. After adding preservative and sealing the
openings, the modules are wrapped in plastic bags prior to boxing for dust protection. Precise solution volume and
good sealing of the couplings help ensure a stable preservative environment during transportation and storage of new
modules.
The wrapped modules are stored in cardboard boxes, with one module per box. A small box containing installation parts
is inserted into each cardboard box shipped. Saddle-shaped cushion inserts are located at both ends and along the
module to support and protect the modules from damage during shipping and handling. The modules are stored in the
horizontal position, with the sealed port connections facing upwards. Labels to identify the port locations and position
the boxes are provided on the exterior of the packaging to allow proper storage. To prevent collapse of the boxed
modules, stacking is limited to four layers for all SFD / SFP, IntegraPac™, IntegraFlux™ and IntegraFlux™ UXA products.
Depending on the total number of modules and required shipping method, the boxed modules are either palleted or
crated for transportation.
Mechanical damage to module housing, membrane, and connections may result if the module, boxed module, pallet, or
crate is dropped, and otherwise miss-handled. The modules should be handled with care, with particular attention
during transportation.
These guidelines should be followed for storage of new DuPont Ultrafiltration Modules:
l Keep modules in original factory packaging. There are cases when the customer may prefer to load the modules
onto the skids with prior to start-up & commissioning; guidelines for storage of modules installed on-skid are
provided in the Sections 7.4 and 7.5, Short-Term and Long-Term Shutdown & Storage of Used DuPont
Ultrafiltration Modules.
l To minimize the potential for leakage of preservative, modules should be stored in horizontal position, with the
sealed port connections facing upwards. Labels of the port locations are provided on the exterior of the box to
facilitate storage. If leakage is observed, please refer to guidelines for replenishment of storage solution
provided in the Sections 7.4 and 7.5, Short-Term and Long-Term Shutdown & Storage of Used DuPont
Ultrafiltration Modules.
l To prevent collapse of the boxed modules, limit vertical stacking to four layers for all SFD/SFP, IntegraPac™,
IntegraFlux™ and IntegraFlux™ UXA modules.
l Store inside a cool and dry building or warehouse, away from sources of heat, ignition, and direct sunlight. An
ambient temperature of 20°C (68°F) to 35°C (95°F) is recommended for ideal storage conditions.
l Temperature limits for modules during shipping and storage is 1°C (33.8°F) to 40°C (104°F). Modules must be
protected from freezing or excessive heat during shipping and storage. Avoid abrupt variations in temperature;
equalization should be allowed to occur at a maximum temperature differential of ± 1°C (1.8°F) per minute. If
freezing conditions are anticipated during the customer’s shipping and storage of modules, please notify
DW&PS at the time of order placement. Glycerin may be added to the storage solution by DW&PS at the factory
prior to shipping to allow for shipment and storage at freezing conditions.
l Sealed modules may be stored up to 18 months from date of manufacture, at the recommended storage
conditions in the original packaging, without additional measures required for storage. If storage exceeds 18
months from date of manufacture, guidelines for confirmation and replenishment of storage are provided in
Section 7.5, Long-Term Shutdown & Storage of Used DuPont Ultrafiltration Modules.
Note that the quantities of storage solution required for on-skid storage is greater than for off-skid storage to allow for
complete wetting of fibers; off-skid storage allows for horizontal storage which decreases the amount of required
solution.
If the modules are expected to be exposed to freezing conditions, glycerin should be added to the storage solution for
either short- or long-term shutdown & storage conditions. Refer to Section 7.6, Freeze-Protection of Used DuPont
Ultrafiltration Modules.
For cases of short-term shutdown & storage, where the modules will be stored off-skid, and the modules will be placed
in service within the next 4 days, SMBS storage solution is not required. Clean water alone is sufficient to keep the fibers
in wetted condition to avoid dehydration. Clean water sources may be from potable water or RO permeate. The
approximate volume of water required for each module is 2 L (0.5 gal) for SFD / SFP-2660; 4 L (1 gal) for DuPont SFD /
SFP-2860(XP), IP / IPD-51(XP) and IntegraFlux™ UXA-2680XP and 6 L (1.6 gal) for SFD / SFP-2880(XP) and IP / IPD-77(XP).
If the modules have been in-service, a normal system chemical enhanced backwash (CEB) of alkaline, followed by acid,
should be conducted before removal of the modules for short-term shutdown & storage. If CEB facilities are not
available, then a normal backwash consisting of water and air scour steps should be conducted prior to removal of
modules off the skid.
Once the modules are removed water may be fed into the module through the feed port by gravity or low-rate
pumping. The module should be kept in horizontal position at time of fill, with the far side filtrate and concentrate ports
sealed by blind disc at the grooved couplings. Once the water is added into the module, all service port connections
should be sealed tightly using the original blind discs and plugs to retain the solution inside the module. If these parts
have not been retained an isolation package can be ordered from the DuPont Ultrafiltration Module Spare Parts List. To
minimize the potential for leakage of preservative, modules should be stored in the horizontal position, with the sealed
port connections facing upwards. Modules may be kept in the original cardboard boxes. Labels of the port locations are
provided on the exterior of the box to facilitate storage.
For cases of short-term shutdown & storage, where the modules will be stored on the skid, and the modules will be
placed in service within the next 4 days, clean water alone is sufficient to keep the fibers in wetted condition to avoid
dehydration. As for off-rack storage, clean water sources from potable water or RO permeate should be used. The
approximate volume of water required for each module is 16 L (4 gal) for SFD/SFP-2660; 23 L (6 gal) for IntegraFlux™
UXA-2680XP; 35 L (9 gal) for SFD/SFP-2860(XP); 39 L (10 gal) for SFD/SFP-2880(XP); 49 L (13 gal) for IP/IPD-51(XP) and
53 L (14 gal) for IP/IPD-77(XP). These quantities of water allow for near to complete fill of the module with water.
If the modules have been in-service, a normal system CEB of alkaline, followed by acid, should be conducted on the
modules before short-term shutdown & storage. If CEB facilities are not available, then a normal backwash consisting of
water and air scour steps should be initiated prior to short-term shutdown & storage.
DWS recommends that the UF CIP system be used for delivery of the water into the modules from the feed side. Refer
to section 6.2.5 in this document for general procedure.
Note that the quantities of storage solution required for on-skid storage is greater than for off-skid storage to allow for
complete wetting of fibers; off-skid storage allows for horizontal storage which decreases the amount of required
solution.
Re-preserved elements should be visually inspected for biological growth every three months. If the storage solution is
not clear, the module should be re-preserved and re-packed as described above. Contact of the SMBS solution with air /
oxygen will oxidize bisulfite to sulfuric acid. Therefore, the pH of the solution should be spot checked on random
modules every 3 months. Re-storage is required when the measured pH is 3 or lower. For medium to large orders, to
avoid inspection of every module, a representative sampling of the total number of modules (e.g. 5%) may be inspected
for visual appearance and pH.
If the modules are expected to be exposed to freezing conditions, glycerin should be added to the storage solution for
either short- or long-term shutdown & storage conditions. Refer to Section 7.6, Freeze-Protection of Used DuPont
Ultrafiltration Modules.
For cases of long-term shutdown & storage, where the modules will be stored off-skid, and the modules will remain
out-of-service for more than 4 days, a storage solution containing pH buffered 1 wt% food-grade SMBS is required to
effectively minimize biological growth in the modules during the storage period.
If the modules have been in-service, a normal system CEB and CIP should be conducted on the modules before removal
of the modules for long-term shutdown & storage. Refer to Section 6.2.5 in this document for CIP Procedure. If CEB
and/or CIP facilities are not available, then a normal backwash consisting of water and air scour steps should be
initiated prior to removal of modules off the skid.
The approximate volume of storage solution required for each module is 2 L (0.5 gal) for SFD / SFP-2660; 4 L (1 gal) for
SFD / SFP-2860(XP), IP / IPD-51(XP) and IntegraFlux™ UXA-2680XP; and 6 L (1.6 gal) for SFD / SFP-2880(XP) and IP / IPD-
77(XP). For every liter of solution required, 12 grams of food-grade SMBS are added for biostat, and 8 grams of sodium
hydroxide and 27 grams of citric acid for pH buffer (quantities refer to active ingredient). Scale-up the preservative
formulation to prepare the required volumes of storage solution for number and type of modules to be preserved.
The storage solution may be fed into the module through the feed port by gravity or low-rate pumping. The module
should be kept in horizontal position at time of fill, with the far side filtrate and concentrate ports sealed by blind disc at
the grooved couplings. Once the target volume of storage solution is added into the module, all service port
connections should be sealed tightly using the original blind discs and plugs to retain the solution inside the module. To
minimize the potential for leakage of preservative, modules should be stored in horizontal position, with the blanked
port connections facing upwards. Modules may be kept in the original cardboard boxes. Labels of the port locations are
provided on the exterior of the box to facilitate storage.
For cases of long-term shutdown & storage, where the modules will be stored on the skid, and the modules will remain
out-of-service for more than 4 days, a storage solution containing pH buffered 1 wt% food-grade SMBS is required to
effectively minimize biological growth in the modules during the storage period.
Similar to off-skid storage, if the modules have been in-service, a normal system CEB and CIP should be conducted
before removal of the modules for long-term shutdown & storage. If CEB and/or CIP facilities are not available, then a
normal backwash consisting of water and air scour steps should be initiated prior to removal of modules off the skid.
The approximate volume of storage solution required for each module is 16 L (4 gal) for SFD/SFP-2660; 23 L (6 gal) for
IntegraFlux™ UXA-2680XP; 35 L (9 gal) for SFD/SFP-2860(XP); 39 L (10 gal) for SFD/SFP-2880(XP); 49 L (13 gal) for
IP/IPD-51(XP); and 53 L (14 gal) for IP/IPD-77(XP). These quantities of solution allow for near to complete fill of the
module with water. For every liter of solution required, 12 grams of food-grade SMBS are added for biostat, 8 grams of
sodium hydroxide and 27 grams of citric acid for pH buffer (quantities refer to active ingredient). Scale-up as required
during the solution preparation procedure to prepare the required quantities of storage solution for number and type of
modules to be preserved.
DWS recommends that the UF CIP system be used for delivery of the storage solution into the modules from the feed
side. Refer to Section 6.2.5 in this document for CIP general procedure.
If the modules are expected to be exposed to freezing conditions, glycerin should be added to the storage solution for
either short- or long-term shutdown & storage conditions. For cases when freezing is expected and notified to DWS,
glycerin is added to the storage solution by DWS at the factory prior to shipping to allow for shipment and storage at
freezing conditions. For re-storage by customer, food-grade glycerin should be applied to the storage solution, at the
target strengths detailed in Table 15.
2. Pressurize the module with UF feedwater to a target pressure of 4.75 bar (68.9 psi). The UF feed pump should
be of adequate capacity to meet the target pressure at low flow conditions. During pressurization, slowly close
the filtrate until the target pressure is achieved. Close the feed and filtrate valves for hold at the target
pressure for 30 minutes. Take care that the filtrate port is re-opened slowly as the feed pressure is released.
Do not exceed a transmembrane pressure (TMP) (pressure drop from feed to filtrate side of the membrane) of
2.1 bar (30.5 psi). This procedure should be carried out while the modules are installed on the skid.
3. Soak modules in 1% HCl or 4% HNO3 solution for 24 hours. During fill of the module, ensure that the module is
in a vertical position to allow the escape of entrapped air.
8.1 Introduction
Proper data record keeping and plant performance normalization are indispensable for early detection of performance
issues in ultrafiltration systems. Adequate instruments and regular calibration are also critical to ensure accurate
readings and anticipate potential operating issues. This section will cover basic aspects for a proper maintenance of
ultrafiltration systems as well as some troubleshooting tips.
For a detailed Process and Instrumentation Diagram of a typical UF system using DuPont UF Modules contact DuPont.
The following list shows the minimum recommended measurements to be taken in an ultrafiltration system:
Refer to Chapter 2 for details of the recommended water quality parameters to be monitored on a regular basis during
the operation of the plant.
Examples of data logging sheets are shown in Figure 32 and Figure 33 below.
8.4.1 Introduction
The temperature of the feed water affects the permeability of a membrane filtration system. At lower temperatures
water becomes increasingly viscous (approximately 3% for every Celsius degree); therefore, lower temperatures require
increasing the transmembrane pressure (TMP) to maintain a constant flux or reduce the flux through the membrane at
constant TMP, as the resistance through the membrane increases. Consequently, this viscosity effect should be
considered in the facility design to ensure adequate production capacity in all scenarios and understand the impact to
energy consumption.
The term “Normalization” is an industry practice for correcting variations that would otherwise appear as a filtrate flux
or TMP change, and lead to misinterpretations of the membrane process performance (e.g., a decrease in membrane
permeability (i.e., flux divided by TMP) that would mistakenly be interpreted as a result of a fouling phenomenon, when
it is only due to a decrease in water temperature). The technical basis for Normalization is provided in the ASTM D5090
standard, however, membrane manufacturers modify these formulas to allow better calibration and fit to the
membrane characteristics of their product as demonstrated in fiber construction and field operating performance.
DuPont uses a viscosity-temperature correction factor based on the latest expression for the viscosity of liquid water
from the International Association for the Properties of Water and Steam (IAPWS,
www.iapws.org/relguide/LiquidWater.html).
Eq. 2
Where:
The numerator is the dynamic viscosity of water at 25°C in µPa·s, the denominator is the viscosity of water at the actual
operating temperature. This expression results in a TCF of 1 at 25°C.
Table 17 shows the different values of the TCF from 0 – 40°C (32 – 104°F) at 5°C increments, based on Equation 2 above:
(Permeability is defined as operating Flux (L/m2·h) divided by TMP (bar), with units of L/m2·h·bar, also expressed as
LMH/bar).
As an example to illustrate the importance of data Normalization, let us consider two hypothetical scenarios of UF plant
performance:
In this example it can be seen that it we look only at the actual values, in summer we seem to have a more favorable
scenario, with lower TMP (0.35 vs. 0.40) and higher membrane permeability compared to winter (185.7 vs. 162.5
LMH/bar). However, if we apply the temperature correction factors, the normalized permeability in summer is actually
lower than in winter (185.7 vs. 208.3), which might be an indication of a more fouled membrane, a fact which would
have been overlooked had we not considered temperature normalization.
Therefore, data Normalization is a very important tool to assess UF performance, as it allows studying trends of TMP
and membrane permeability without the distortion of the temperature effect, so that fouling episodes can be
anticipated and the operating parameters and cleaning activities can be adjusted accordingly.
The DuPont Ultrafiltration Normalization tool is an Excel based file that allows the plant operator to enter the operating
parameters to automatically calculate the normalized values based on the formulas described above. General plant
information are the inputs to be filled by the plant operator, which includes parameters like water temperature, UF feed
pressure, UF filtrate pressure, flows or feed water quality. The tool also has the option to simulate concentrate-bleed
operation.
The tool calculates the Temperature Correction Factor, as well as the Normalized TMP and the Normalized Permeability
as described above, and automatically populates the following graphs:
8.5.1 Introduction
DuPont UF membranes are considered to be an absolute barrier to most of suspended matter, particles and
microorganisms (such as Crypstosporidium, Giardia or even viruses), producing a very high filtrate quality (typically with
a SDI < 2.5 and Turbidity < 0.1 NTU).
However, occasionally, a seal or valve may leak or a fiber break during operation, resulting in a loss of integrity. Leaking
seals or broken fibers could allow contaminants to pass to the filtrate side and compromise its quality. This is not
generally detected by the measurement instruments located in the filtrate side, like turbidity meters, as they are not
sensitive enough to detect small leaks.
Therefore, a specific test should be employed to detect and isolate modules (or racks) containing leaks, for subsequent
repair. Direct Integrity Testing (as opposed to Indirect Integrity Testing, which are based on the monitoring of some
parameters of the filtrate water quality, such us turbidity or particle count) represent the most accurate and reliable way
of determining the integrity of a membrane filtration system and is able to detect even small breaches in the
membranes.
The Pressure Decay Test (PDT) is an example of Direct Integrity Test. In the PDT, a pressure below the bubble point is
applied to the membrane, and the subsequent loss in pressure is measured during several minutes (typically 5 – 10
minutes). An integral membrane will maintain the initial pressure or will show a very slow rate of decay (due to the
normal air diffusion through the membrane).
This is based on the Bubble Point Theory. The bubble point of a membrane is referred as the threshold air pressure
required to displace water from the membrane pores in a fully wetted membrane. Integrity breaches such as broken
fibers or defects on its surface are detected when applying pressures below the bubble point.
The general practice is to carry out the Pressure Decay Test applying a minimum pressure able to detect breaches of 3
microns or less, corresponding to the conservative size of the Cryptosporidium oocyst. The corresponding test pressure
is dependent on several factors, such as the intrinsic properties of the membrane fiber and module design, but typically
1 – 2 barg (14.5 – 30 psig) is applied.
In case of an integrity breach, a bubble formation will be observed during the PDT in the clear pipes located in the
filtrate side of each DuPont Ultrafiltration Module. It is important to note that a small passage of air is normal due to air
diffusion through the membrane. A real integrity breach would result in a significant continuous stream of bubbles,
accompanied by boiling water like noise and vibration.
If routine direct integrity testing will be performed it is recommended that the piping design include a transparent
filtrate pipe section on each module. The transparent pipe will make it easy to identify modules having integrity issues
during the direct integrity test. If large continuous bubbles combined with a failed pressure decay test occur, identify or
mark these modules. While the modules are pressurized also inspect the clamps and couplers for leaks around gaskets
and seals. A soapy water solution can be applied to detect these types of leaks.
There are two types of membrane integrity testing. In the “Indirect” integrity test methods, a filtrate water quality
parameter (e.g., turbidity or particle counts) is monitored to detect compromised membrane units. The advantage of
the indirect test methods is that the membrane unit does not need to be taken off-line, and continuous monitoring
provides real-time integrity indication. However they are not as sensitive or accurate as the “Direct” integrity test
methods. In the “Direct” integrity test methods, a physical test is applied to a membrane unit to detect leaks. Examples
of “Direct” integrity test methods are the Pressure Decay Test, the Diffusive Air Flow Test, the Water Displacement Test,
or the Seeding Test.
DuPont recommends the Pressure Decay Test in order to check the integrity of the ultrafiltration membranes, due to its
simplicity and sensitivity. The test must be done off-line to the individual UF trains. For municipal/drinking water
installations the frequency of testing is set by the local regulatory agency. Once a leak is detected, visual inspection
through a transparent pipe is used to identify the leaking module.
The integrity test will be carried out manually on-demand or automatically. Testing is performed after the membrane
rack has been cleaned. A fouled membrane could hide some membrane defects.
1. Take the UF unit, skid or module out of the filtration mode (they should be in clean condition to avoid foulants
to interfere in the results). Isolate the skid being tested from other skids in the system. Close the feed and
concentrate valves (refer to Figure 35 below). Open the filtrate valve to allow water flow through the
transparent pipe.
2. Pressurize the skid using oil free compressed air (note that a blower is not suitable for this purpose, consult
DuPont for further details) from the air inlet valve, and slowly raise the air pressure to 1.5 bar (~20 psi). Do not
exceed 2 bar (~30 psi). Note that a minimum of 1.25 bar (~18 psi) is required to detect a 3 micron resolution.
Displaced water may flow through the filtrate side for approximately two minutes.
4. Hold the pressure for 5 minutes (unless duration is specified by the local regulatory agency) to determine
whether there are leaks or broken fibers. While the pressure hold test is ongoing visually inspect the modules
for leaks. If installed, look for large continuous bubbles in the transparent filtrate pipes.
5. The integrity test is successful if the pressure drop is ≤ 0.05 bar (~0.73 psi) for the 5-minute test or the
calculated value as determined by the EPA Membrane Filtration Guidance Manual (2005) for the specific
system design.
Eq. 5
If the module exceeds the allowable pressure decay rate, the membrane might be compromised or leaking valves,
instruments, pipes, etc. may exist. Check for system leaks or repair the modules and hollow fibers following the fiber
test and repair procedure described below.
8.6.1 Introduction
If a broken fiber is detected, it can be disabled in order to avoid by-pass of feed water to the filtrate side, and hence
contamination.
8.6.2 Equipment
The following items are needed to complete the fiber repair procedure:
l DuPont UF Fiber Repair Kit, available from DuPont and which includes concentrate tube plug, glue and repair
pins).
l A clean source of water with at least UF filtrate quality.
l Oil-free compressed air (meeting ISO 8573-1, Class 1/3/1 for oil/water/particles)
l Air connection (if module repaired off skid)
l Personal protection equipment (gloves, safety glasses, etc.)
1. Drain the water from the feed side of the modules. Close the filtrate valve to avoid water draining from the filtrate
pipe. Remove the top end cap of the module (the bottom end cap is not removed).
2. Close or seal concentrate connections and feed valve. Supply air to module.
3. Provide a clean water source to wet the filtrate/permeate end of the fibers.
4. Pressurize the feed side (outside of membrane) of the wetted membrane with oil free compressed air (a blower is
not suitable for this purpose). Slowly increase the pressure to the value identified above. Air will be supplied
through the air inlet connection on the module.
10. Repeat steps 8 - 9 to make sure all broken fibers are repaired.
11. To determine whether the membrane has been properly repaired follow the pressure decay test procedure
described above.
For further information and visual demonstration, watch the DVD included in the Fiber Repair Kit, or consult the website
www.dupont.com/water/ultrafiltration.html
9.1 Terminology
Air Scour Cleaning method where air is used to shake the fibers and help to dislodge the solids from its
surface. Also known as Air Scrub.
Backwash Hydraulic cleaning method where filtrate water is pumped from the filtrate to the feed side of the
membrane in order to remove accumulated foulants. Also known as Backflush or Backpulse.
Bleed-Mode Flow pattern where most of the feed water will pass through the membrane while the rest will
Operation get out of the membrane element directly through the concentrate side (typically 5 – 15% of the
feed flow). This concentrate stream will carry part of the contaminants out of the elements and is
normally sent to waste.
BOD (Biological Similar to COD except BOD detects substances that are susceptible to biological oxidation which
Oxygen indicates biologically active organics. Therefore COD & BOD can be used to characterize the
Demand) organic load of water. Expressed as mg/L of Oxygen.
Chemically Chemical cleaning method, typically initiated automatically, where some chemicals are added
Enhanced into the Backwash stream in order to improve the effectiveness of the cleaning. Usually includes a
Backwash (CEB) soaking step.
Clean-In-Place Chemical cleaning method, typically initiated manually, where one or several chemical solutions
(CIP) are consecutively applied in the ultrafiltration trains in order to restore clean membrane
condition.
COD (Chemical It is a measure of the amount of compounds in a sample which have been oxidized by a strong
Oxygen oxidizing agent. Although inorganic substances such as Fe may also be subject to oxidation, for
Demand) most natural and industrial waters, the matter to be oxidized is organic in nature.
Conductivity The electrical conductivity of water is linearly related to the total dissolved solids (TDS). It is the
ability of the water to conduct an electrical current. Expressed in µS/cm.
Cross-Flow Flow pattern where the concentrate flow exceeds the filtrate flow passing through the membrane
Operation (typically in a ratio of 5:1 or higher). The concentrate stream is then typically recycled back to the
feed. This allows increasing the flow velocity through the feed channels and therefore achieving a
shear force effect that helps to reduce membrane fouling.
Dalton Unit of mass (Symbol: Da), typically used as unit to measure the molecular weight cut-off of the
ultrafiltration membranes.
Dead-End Flow pattern, also known as “Deposition Mode”, where all the feed volume entering the system
Operation flows through the membrane (i.e., there is no waste stream) and is collected in the filtrate side,
while the foulants build up on the membrane.
Direct Integrity Physical test applied to a membrane unit to detect integrity breaches.
Test
DOC (Dissolved Fraction of TOC which is dissolved (filtered through 0.45 µm).
Organic Matter)
Filtrate The water stream that goes through the membrane, and is free from impurities.
Flux The throughput of a membrane filtration system expressed as flow per unit of membrane area
(e.g., gallons per square foot per day (GFD) or liters per hour per square meter (LMH).
Fouling The gradual reduction in filtrate flow at constant pressure (or increase in transmembrane
pressure at constant filtrate flow) due to adsorption or deposition of contaminants within or on
the membrane.
Hollow-Fiber A configuration in which hollow-fiber membranes are bundled horizontally or vertically and
Module either encased in a pressure vessel or submerged in a tank.
Indirect Some filtrate water quality parameter is monitored to detect compromised membrane units.
Integrity Test
Integrity Breach Any leak in the membrane system that could lead to by-pass of feed to filtrate side, and hence
contamination.
Log Removal Filtration removal efficiency for a target organism, particulate, or surrogate expressed as log10
Value (LRV) [Concentrationfeed/Concentrationfiltrate].
Microfiltration A pressure-driven membrane filtration process that typically employs hollow-fiber membranes
with a pore size range of approximately 0.1 – 0.5 µm.
Module This refers to the simplest unit composed of the membranes, the vessel, the end-caps, the feed
and air inlets, the filtrate outlet and the waste outlet. Several modules form a membrane train,
rack, bank or skid.
Molecular Lowest molecular weight (expressed in Daltons) in which 90% of the solute is removed by the
Weight Cut-off membrane.
or MWCO
O&G Oil & Grease, Hydrocarbons.Even in very small quantities i.e., < 0.05 mg/L, it can cause accelerated
fouling in membranes.
pH It is a numeric scale used to express the acidity or alkalinity of the water. Solutions with a pH less
than 7 are acidic and solutions with a pH greater than 7 are basic. Pure water has a pH of 7 and is
neutral. In water, high pH causes a bitter taste, water pipes and equipment become encrusted
with deposits. Low-pH water will corrode or dissolve metals and other substances.
Permeability The capability of a membrane to allow the flow of water. It is the best indicator for membrane
performance. It is calculated as Flux divided by TMP and expressed in LMH/bar or gfd/psi, and is
typically temperature-corrected (i.e., “normalized”) to 20°C or 25°C.
Pore Size The size of the openings of a porous membrane, expressed either as nominal (average) or the
absolute (maximum), typically in terms of microns.
Recovery The ratio of feed water that is converted to filtrate. Recovery equals to filtrate flow produced by
the membrane unit divided by the feed flow and is expressed as percentage.
SDI (Silt Density Fouling Index. This parameter provides an indication of the particulate fouling potential of the
Index) water. It is based on the measurement of the time it takes to collect 500 mL of water sample
through a paper filter of 0.45 µm at the start of the test and after the water has flowed through
the filter for 15 minutes.
SUVA (Specific Ratio between UV254 and DOC (if > 4, mostly humic matter; if < 2, indication of algae bloom).
UV Absorbance)
TMP Transmembrane Pressure (bar or psi). It is the pressure difference between the feed and the
filtrate side of the UF module or skid.
TOC (Total It is the most widely used parameter to determine the organic content in water. It includes
Organic Carbon) Natural Organic Matter (NOM) and synthetic sources. It is indicative of the tendency of the water
to cause organic fouling and biofouling in membranes. It is expressed in mg/L.
TSS (Total It is the measure of the total weight of solids contained in a water sample, and is expressed in
Suspended mg/L. This parameter is more accurate than turbidity (i.e., turbidity usually does not detect very
Solids) fine particles).
Turbidity Sediments, clay, silt, small particles, solids etc. cause a liquid to appear turbid, “hazy”. These
particles can, besides, host or shield microorganisms like bacteria and viruses. Turbidity is
measured by the intensity of light that passes through the water sample, and expressed in NTU
(Nephelometric Turbidity Units). DuPont Ultrafiltration gives consistent product water with
turbidity values < 0.1 NTU.
Ultrafiltration A pressure-driven membrane filtration process that typically employs hollow-fiber membranes
with a pore size range of approximately 0.01 – 0.05 μm.
UV254 It is an indirect measurement of NOM, based on the fact that most organics compounds can
Absorbance absorb UV light. Expressed in cm-1. Surrogate of TOC.
9.2 Acronyms
ANSI American National Standards Institute
AS Air Scour
BOD Biological Oxygen Demand
BW Backwash
CDPH California Department of Public Health
CEB Chemically Enhanced Backwash
CIP Clean-In-Place
COD Chemical Oxygen Demand
DOC Dissolved Organic Carbon
DWS DuPont Water Solutions
EDI Electrodeionization
FRP Fiberglass-reinforced plastic
GAC Granular Activated Carbon
GFD U.S. gallons/ft2/day
gpm U.S. gallons/minute
IER Ion Exchange Resins
kDa Kilodalton
LMH Liter/m2·h
PP Polypropylene
PS Polysulfone
www.dupont.com/water/contact-us
All information set forth herein is for informational purposes only. This information is general information and may differ from that based on actual conditions. Customer is responsible for determining whether products and the information in
this document are appropriate for Customer's use and for ensuring that Customer's workplace and disposal practices are in compliance with applicable laws and other government enactments. The product shown in this literature may not
be available for sale and/or available in all geographies where DuPont is represented. The claims made may not have been approved for use in all countries. Please note that physical properties may vary depending on certain conditions
and while operating conditions stated in this document are intended to lengthen product lifespan and/or improve product performance, it will ultimately depend on actual circumstances and is in no event a guarantee of achieving any
specific results. DuPont assumes no obligation or liability for the information in this document. References to “DuPont” or the “Company” mean the DuPont legal entity selling the products to Customer unless otherwise expressly noted. NO
WARRANTIES ARE GIVEN; ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSLY EXCLUDED. No freedom from infringement of any patent or trademark owned by
DuPont or others is to be inferred.
© 2022 DuPont. DuPont™, the DuPont Oval Logo, and all trademarks and service marks denoted with ™, ℠ or ® are owned by affiliates of DuPont de Nemours Inc., unless otherwise noted.