The document provides design details for a concrete column including input data, analysis, and checks of flexural and axial capacity according to ACI 318-19. It includes the concrete strength, rebar properties, loads, column dimensions, reinforcement details, moment-axial interaction diagram analysis, and checks for flexure, axial capacity, shear capacity, and reinforcement spacing.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
23 views3 pages

Concrete Column

The document provides design details for a concrete column including input data, analysis, and checks of flexural and axial capacity according to ACI 318-19. It includes the concrete strength, rebar properties, loads, column dimensions, reinforcement details, moment-axial interaction diagram analysis, and checks for flexure, axial capacity, shear capacity, and reinforcement spacing.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

PROJECT : PAGE :

CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Concrete Column Design Based on ACI 318-19

INPUT DATA & DESIGN SUMMARY


CONCRETE STRENGTH fc' = 4 ksi, (28 MPa)
REBAR YIELD STRESS fy = 60 ksi, (414 MPa)
SECTION SIZE Cx = 25 in, (635 mm)
Cy = 20 in, (508 mm)

FACTORED AXIAL LOAD Pu = 600 kip, (2669 kN), (272.16 Tn)


FACTORED MAGNIFIED MOMENT Mu,x = 150 ft-kips, (203 kN-m)
Mu,y = 120 ft-kips, (163 kN-m)
FACTORED SHEAR LOAD Vu,x = 40 kip, (178 kN), (18.14 Tn) THE COLUMN DESIGN IS ADEQUATE.
Vu,y = 30 kip, (133 kN), (13.61 Tn)
COLUMN VERT. REINFORCEMENT 5 # 6 at x dir.
(Total12 # 6)
3 # 6 at y dir.
LATERAL REINF. OPTION (0=Spirals, 1=Ties) 1 Ties
LATERAL REINFORCEMENT 4 legs,# 4 @ 12 in. (305 mm), o.c., at x dir.
3 legs,# 4 @ 12 in. (305 mm), o.c., at y dir.

ANALYSIS

6000

5000

4000 
3000
f Pn (k)
2000

1000 
0
0 500 1000 1500 2000 2500 3000
-1000

-2000

f Mn (ft-k) Solid Black Line - Tension Controlled


Solid Red Line - Transition
Dash Line - Compression Controlled
       2
Note:  c  c  , for 0 
 s E s , for  s   ty
'
 e f C 2     c o
1. Between compression & tension controlled is fC    o    o   , fS 
Transition, which the f should be by linear  '
 f y , for  s   ty
interpolation. (ACI 318-19 Tab. 21.2.2 & Fig. R10.4.2.1)   e f C , for  c   o

2. ACI 318-19 changed f (Fig.R21.2.2b) and keeps

2  e f C'  fy  ty , for compression controlled

be (22.2.2.4.1) and ecu (Fig. R21.2.2a) the same. o  ,  ty  , t  
 0.003 , for tension controlled
But AISC 360/341-16 has different f (0.9 only) and Ec Es  ty

'
be (1.0 or 0.7). E c  57 f C , E s  29000ksi ,  e  0.85 ,  cu  0.003

CHECK FLEXURAL & AXIAL CAPACITY


f Pmax =F f [ 0.85 fc' (Ag - Ast) + fy Ast] = 4315 kips., (at max axial load, ACI 318-19 22.4)
where f = 0.65 , (ACI 318-19 Fig. R21.2.2b) > Pu [Satisfactory]
F = 0.8 , (ACI 318-19 Tab. 22.4.2.1) Ag = 500 in 2
Ast = 5.28 in2
f Mn = 2812 ft-kips @ Pu = 1440 kips > Mu = 2550 ft-kips [Satisfactory]
rmax = 0.06 (ACI 318-19 18.7.4.1) rprovd = 0.012
rmin = 0.01 (ACI 318-19 18.7.4.1& 10.6.1.1) [Satisfactory]

CHECK SHEAR CAPACITY (ACI 318-19 10 & 22.5)

V u, x V u, x
  1.19 < 1.5 (ACI 318-19 22.5.1.11) [Satisfactory]
V n, x V n, x

f Vn = f (Vs + Vc) (ACI 318-19 22.5)

where f = 0.75 (ACI 318-19 21.2) fy = 60 ksi


d A0 Av Vc = 2 (fc')0.5A0 Vs = MIN (d fy Av / s , 4Vc) f Vn
x 37.5 1240 0.80 192.1 150.0 257
y 33.5 1240 0.60 192.1 100.5 219

smax = 16 (ACI 318-19 25.7) sprovd = 12 in


smin = 1 [Satisfactory]
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Magnified Moment Calculation for Concrete Column Based on ACI 318-19

INPUT DATA & DESIGN SUMMARY


EFFECTIVE LENGTH FACTOR k = 1.6 , (ACI 6.2.5)
COLUMN UNSUPPORTED LENGTH Lu = 12 ft, (3.66 m)
LARGER FACTORED MOMENT M2 = 200 ft-k
SMALLER FACTORED END MOMENT M1 = 100 ft-k, (positive if single curvature.)
CONCRETE STRENGTH fc' = 4 ksi
COLUMN DIMENSIONS h = 20 in
b = 20 in
FACTORED AXIAL LOAD Pu = 400 k
SUMMATION FOR ALL VERTICAL LOADS IN THE STORY S Pu = 1200 k
SUMMATION FOR ALL CRITICAL LOADS IN THE STORY S Pc = 13600 k, (ACI 6.6.4)

THE MAGNIFIED MOMENT: Mu = 236.7 ft-k , Sway

ANALYSIS
MAGNIFIED MOMENT - NONSWAY
r = 0.3 h = 6.0 in, ACI 6.2.5.1
k Lu / r = 38.4 > 34 - 12(M1 / M2) = 28 < = = Slenderness effect must be considered. (ACI 6.2.5)
Ec = 57000 (fc')0.5 = 3605.0 ksi, ACI 19.2.2
Ig = b h3 / 12 = 13333 in4

0.4 E c I g 0.4 E c I g
EI    0.25 E c I g  1.2E+07 k-in2 , ACI 6.6.4.4.4
1  d 1  0.6

 2EI 
Pc  2234.18 k-in2 , ACI 6.6.4.4.4
 k Lu 
2

M2,min = MAX[ M2 , Pu (0.6+0.03 h) ] = 220 ft-k, ACI 6.6.4


Cm = MAX[ 0.6 + 0.4 (M1 / M2, min) , 0.4 ] = 0.8 , ACI 6.6.4.5

 
 
 Cm 
  MAX , 1.0 1.05 , ACI 6.6.4.5.2
 1  Pu 
 0.75P c 
 

Mu, ns = d M2, min = 210.2 ft-k, ACI 6.6.4.5.1 > 1.05 M2 = 210.0 ft-k [Unsatisfactory] ,(ACI 6.6.4.3)
The column is sway. See calculation as follows.

MAGNIFIED MOMENT - SWAY


k Lu / r = 38.4 > 22 < = = Slenderness effect must be considered. ACI 6.2.5)

   
   
1
 s  MIN  MAX  , 1.0  , 2.5  1.13 , ACI 6.6.4
   Pu  
  1  0.75 P  
  c  

Ag = b h = 400 in2
Lu / r = 24.00 < 35 / [Pu / (fc' Ag)]0.5 = 70.00 [Satisfactory]
M2s = M2 = 200.0 ft-k, as given
M2ns = 5% M2s = 10.0 ft-k, assumed conservatively
Mu, s = M2ns + ds M2s = 236.7 ft-k, ACI 6.6.4.6

Note: For column subject to bending about both principal axis, the moment about each axis shall be magnified separately based
on the conditions corresponding to that axis.
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Rectangular Concrete Column Design

INPUT DATA
f 'c = 4 ksi
fy = 60 ksi
x = 48 in
y = 32 in
Bar Size ==> # 11
No. of Asx = 8 8 # 11
No. of Asy = 9 9 # 11
Total Bars ==> # 30 # 11
r = 3.0%
Pu = 1700 k
Mux = 2900 ft-k ex = 0.7 in
Muy = 1200 ft-k ey = 1.7 in

CHECK COLUMN CAPACITY BY THE BRESLER METHOD


1
P u   0.80  0.70  P o Pn  1 1 1 M nx  M ny  1.0
  M nox M noy
P ox P oy Po
1700.0 < 4407.9 ok 2428.6 < 2953.0 ok 1.270 > 1.0 NG

ANALYSIS
x DIRECTION y DIRECTION
u = 0.003 d = 45.295 in 29.295 in
d' = 2.705 in 2.705 in
As = 12.48 in2 14.04 in2
 = 0.70 b = 32 in 48 in

Mn = 4142.9 ft-k 1714.3 ft-k


1
= 0.85 Mno = 5237.1 ft-k 3581.1 ft-k
Po = 3626.1 k 5265.9 k

MOMENT STRENGTH (Pn=0)

 As f y  A's u E s   3.4 f b A  E d
2
'
A s f y  As  u E s 
' ' '
1 c s u s
c 
'
1.7  1 f b 4.100781 in 3.701729 in
c

'  c d'
f s  E s u   29612.16 psi 23425.65 psi
 c 

  1c 
'
M n  0.85 f c  1cb  d   As' f 's d  d '   4034.011 ft-k 3052.887 ft-k
 2 

AXIAL LOAD STRENGTH (Mn=0)

'
P o  0.85 f c( A g  A st )  A st f y  7871.28 k = 7871.28 k

BALANCED CONDITION

 u E s  1d
ab  
 uEs  f y 22.78616 in 14.73718 in

'  d '   u E s  f y 
f sb   u E s 1     60000 psi 60000 psi
 d   u E s 
' '
P b  0.85 f cb a b  As f sb  A s f y 
'
2479.134 k 2405.108 k

'  h ab  ' h ' h  5262.137 ft-k 3596.574 ft-k


M b  0.85 f cb a b     A s f sb   d   A s f y   d  
'

2 2  2  2 