AxiomV Hardware Manual
AxiomV Hardware Manual
HARDWARE MANUAL
new generation
building security
Copyright Notice
Copyright© 1995-2013 by RBH Access Technologies Inc.
All rights reserved Worldwide. Printed in Canada. This publication has been provided
pursuant to an agreement containing restrictions on its use. No part of this book may be
copied or distributed, transmitted, stored in a retrieval system, or translated into any
human or computer language, in any form or by any means, electronic, mechanical,
magnetic, manual, or otherwise, or disclosed to third parties without the express written
consent of RBH Access Technologies Inc., Brampton, Ontario, Canada.
Trademark
AxiomV™ is the trademark of RBH Access Technologies Inc. Windows is a trademark
of Microsoft Corporation. All other product names mentioned herein are the property of
their respective owners. Use of a term in this book should not be regarded as affecting
the validity of any trademark or service mark.
Disclaimer
This book is provided as is, without warranty of any kind, either express or implied,
including but not limited to performance, merchantability, or fitness for any particular
purpose. Neither RBH Access Technologies Inc. nor its dealers or distributors shall be
liable to any person or entity with respect to any liability, loss, nor damage, caused, or
alleged to have been caused directly or indirectly by this information. Further RBH
Access Technologies Inc. reserves the right to revise this publication, and to make
changes to the content hereof from time to time, without the obligation of RBH Access
Technologies Inc. to notify any person or organization of such revision or changes.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
Contents
CHAPTER 1 INTRODUCING AXIOMV™ .................................................................. 1
CHAPTER 2 NETWORK CONTROLLER (NC-100) ................................................ 4
CONNECTION DETAILS ................................................................................................................................ 5
Power...................................................................................................................................................... 5
Host Interface ......................................................................................................................................... 5
C-NET CH1 and CH2 ............................................................................................................................. 6
D-NET CH1 and CH2 ............................................................................................................................ 6
Auxiliary Output ..................................................................................................................................... 6
Earth ....................................................................................................................................................... 6
DIP SWITCH SETTINGS ................................................................................................................................ 6
Controller Addressing ............................................................................................................................ 7
Master Controller ................................................................................................................................... 7
Slave Controller...................................................................................................................................... 7
Direct Connect........................................................................................................................................ 7
Computer Port Baud Rate Selection (Master Only) ............................................................................... 8
RS485 4 Wire Interface Selection (Master Only) ................................................................................... 8
PANEL RESET .............................................................................................................................................. 8
PC CONNECTION ......................................................................................................................................... 8
RS232 CONNECTION ................................................................................................................................... 9
Cable Specification ................................................................................................................................. 9
Maximum Cable Length ......................................................................................................................... 9
RS485 CONNECTION ................................................................................................................................. 10
Cable Specification ............................................................................................................................... 10
Maximum Cable Length ....................................................................................................................... 10
NC-100 NETWORKS .................................................................................................................................. 11
C-NET (CONTROLLER NETWORK) ............................................................................................................ 11
C-NET Cable ........................................................................................................................................ 13
C-NET Maximum Cable Length ........................................................................................................... 13
STATUS LED'S........................................................................................................................................... 13
Computer/ Modem Port ........................................................................................................................ 13
C-NET LEDs ......................................................................................................................................... 13
D-NET LEDs ........................................................................................................................................ 13
Run LED ............................................................................................................................................... 13
Diagnostic LEDs 1 and 2 ..................................................................................................................... 13
D-NET DEVICE NETWORK ........................................................................................................................ 14
D-NET Maximum Cable Length ........................................................................................................... 16
D-NET Cable ........................................................................................................................................ 16
D-NET Termination .............................................................................................................................. 16
CLEARING NC-100 MEMORY .................................................................................................................... 17
CHAPTER 3 READER CONTROLLER (RC-2) ....................................................... 18
CONNECTION DETAILS .............................................................................................................................. 20
Output 1 A/B (Terminals 1, 2, 3) .......................................................................................................... 20
Output 2 A/B (Terminals 4, 5, 6) .......................................................................................................... 20
Output 3 A/B (Terminal 7) .................................................................................................................... 20
Output 4 A/B (Terminal 8) .................................................................................................................... 20
Auxiliary Power Output (Terminals 9, 10) ........................................................................................... 20
Reader A/B (Terminals 11 To 20) ......................................................................................................... 20
Inputs 1, 2, 3, And 4 A/B (Terminals 21 To 26) .................................................................................... 20
Lock Power DC Output (Terminals 27, 28 Side A) .............................................................................. 20
Lock AC Power Input (Terminals 29, 30 Side A) ................................................................................. 20
Main AC Power (Terminals 27, 28 Side B) .......................................................................................... 21
Powering From DC .............................................................................................................................. 21
™
RBH Access Technologies Inc. AxiomV Hardware Guide
i
Backup Battery (Red and Black Leads) ................................................................................................ 21
Fire Release Input (Terminals 29, 30 Side B) ...................................................................................... 21
Tamper.................................................................................................................................................. 21
DIP SWITCH SETTINGS .............................................................................................................................. 22
RC-2 Addressing ................................................................................................................................... 22
STATUS LED'S........................................................................................................................................... 22
Run ....................................................................................................................................................... 22
AC High ................................................................................................................................................ 22
AC Low ................................................................................................................................................. 22
Battery Trouble ..................................................................................................................................... 22
Reader Fuse .......................................................................................................................................... 23
Auxiliary Fuse ...................................................................................................................................... 23
Lock Fuse ............................................................................................................................................. 23
D-NET LED's........................................................................................................................................ 23
BATTERY TEST .......................................................................................................................................... 23
BATTERY PROTECTION .............................................................................................................................. 23
INPUTS ...................................................................................................................................................... 24
RTE Request to Exit (Input 1A, 1B) ...................................................................................................... 24
Door Contact (Input 2A, 2B) ................................................................................................................ 24
INPUT CIRCUIT TYPES ............................................................................................................................... 25
OUTPUTS ................................................................................................................................................... 28
Switching Inductive Devices (Locks, Bells) .......................................................................................... 28
DEFAULT OUTPUT OPERATION .................................................................................................................. 29
Lock Output (Relay Outputs 1A, 1B) .................................................................................................... 29
Forced / Tamper (Relay Outputs 2A, 2B) ............................................................................................. 30
Door Held Open (Electronic Outputs 3A, 3B) ...................................................................................... 31
Alarm Shunt (Electronic Outputs 4A, 4B) ............................................................................................ 32
ACCESS POINT OPERATING MODES ........................................................................................................... 33
Two Person (Escort) ............................................................................................................................. 33
High Security ........................................................................................................................................ 33
Unlocked ............................................................................................................................................... 33
Tamper.................................................................................................................................................. 33
Lockout Alarm ...................................................................................................................................... 33
Door Held Open Warning .................................................................................................................... 33
Door Held Open Alarm ........................................................................................................................ 33
Keypad / Reader Combination ............................................................................................................. 33
Access Granted ..................................................................................................................................... 33
Access Denied ....................................................................................................................................... 33
READER CONNECTION DIAGRAMS ............................................................................................................. 34
Cable Specification ............................................................................................................................... 34
Maximum Cable Length ....................................................................................................................... 34
Cable Specification ............................................................................................................................... 35
Maximum Cable Length ....................................................................................................................... 35
Cable Specification ............................................................................................................................... 36
Maximum Cable Length ....................................................................................................................... 36
Cable Specification ............................................................................................................................... 37
Maximum Cable Length ....................................................................................................................... 37
CHAPTER 4 INPUT/OUTPUT CONTROLLER (IOC-16) ...................................... 38
CONNECTION DETAILS .............................................................................................................................. 39
Auxiliary Power Output ........................................................................................................................ 39
Backup Battery (Red and Black Lead) ................................................................................................. 39
AC Power ............................................................................................................................................. 39
Powering From DC .............................................................................................................................. 39
Fire Release Input (Terminals) ............................................................................................................. 39
Tamper.................................................................................................................................................. 39
™
AxiomV Hardware Guide RBH Access Technologies Inc.
ii
DIP SWITCH 1 SETTINGS ........................................................................................................................... 40
IOC-16 Addressing ............................................................................................................................... 40
STATUS LED'S........................................................................................................................................... 41
Run ....................................................................................................................................................... 41
AC High ................................................................................................................................................ 41
AC Low ................................................................................................................................................. 41
Battery Trouble ..................................................................................................................................... 41
Auxiliary Fuse ...................................................................................................................................... 41
Network LEDs ...................................................................................................................................... 41
BATTERY TEST .......................................................................................................................................... 41
BATTERY PROTECTION .............................................................................................................................. 41
Input / Output Selection ........................................................................................................................ 42
INPUTS ...................................................................................................................................................... 43
OUTPUTS ................................................................................................................................................... 43
Switching Inductive Devices (Locks, Bells) .......................................................................................... 44
Fail Safe Output Operation .................................................................................................................. 44
Elevator Control ................................................................................................................................... 44
INDEX.............................................................................................................................. 59
™
RBH Access Technologies Inc. AxiomV Hardware Guide
iii
Chapter 1
™
Introducing AxiomV
Chapter 1
™
Introducing AxiomV
The RBH AxiomV™ System combines access control, building management, and
security monitoring in a highly integrated and expandable package. AxiomV ™
Security Management Software runs on a standard IBM compatible PC and is
designed for use in installations ranging from simple two door systems to
complex systems covering multiple sites and containing thousands of access
points and tens of thousands of cardholders.
The system can monitor over 1,000 networked controller units (NC-100) with
each controller capable of monitoring eight card readers and 320 input/output
points. Remote site monitoring capability is 4,096 readers and 65,535
input/output points. Local site capacity exceeds 8,000 readers and 250,000
input/output points. A minimum configuration consists of a PC, a single
controller unit (NC-100) and a single reader controller (RC-2) that allows
connection of two card readers, eight inputs and eight outputs.
The PC is used for data entry, setting up the database, and monitoring activity on
the system. Once the database is downloaded to the controllers, the PC is not
required for system operation. Should the PC be powered down, the NC-100
controller will perform all access and other control functions, including logging
up to 100,000 events. When the connection is restored, the log is reported to the
PC.
All controllers in the network are connected together in a fault tolerant, high
speed Arcnet LAN. Arcnet is a highly reliable networking architecture and is
widely used in industrial control applications. This LAN module transfers data
at speeds of 156k bits/second to 2.5M bits/second and when wired in a ring is
immune to a single point of attack. The network will continue to operate
normally with a single short or a cut on any inter- controller connection.
The controllers use a powerful Motorola 32-bit micro controller and come
standard with 256k bytes of RAM. A plug in memory expansion board allows
the memory to be expanded to 16 Megabytes. All RAM is battery backed by a
™
RBH Access Technologies Inc. AxiomV Hardware Guide
1
Chapter 1
™
Introducing AxiomV
Each controller has a second local network (D-NET) for connection to card
reader controllers (RC-2) and input/output boards (IOC-16). This RS485
network operates at 38400 bits/second and is also wired in a fault tolerant ring
providing protection from a single point of failure. Devices can be placed on the
local network up to 3000 feet (1000 meters) apart and the network supports up to
twenty devices (up to four RC-2s and up to sixteen IOC-16s). The controller
polls each device on the network and processes any data reported such as access
verification requests and input status changes.
A RC-2 (Reader Controller) supports two access points. Each RC-2 can
monitor two reader or reader/keypad units; eight input points and control eight
output points. Inputs and outputs are programmable for dedicated access point
functions such as door contact, request to exit button and door lock or can be
used as general purpose I/O.
All operating information including times, facility codes, card formats and other
parameters are stored locally in non-volatile memory in the RC-2. If
communication is lost with the controller, the RC-2 can be programmed to
operate in facility code mode where access is granted upon presentation of a
valid facility code only. The system reverts to normal operation when
communication resumes with the controller.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
2
Chapter 1
™
Introducing AxiomV
™
AxiomV System Diagram
™
RBH Access Technologies Inc. AxiomV Hardware Guide
3
Chapter 2
NC-100
Chapter 2
Network Controller (NC-100)
The AxiomV™ access control system consists of one or more network controllers
(NC-100). All information required by the controller is downloaded from the
PC and stored locally in battery backed flash memory. This information includes
configuration data, cardholder records, access levels, schedules, and all other
records necessary for the operation of the system. The controller operates
independent of the PC and all decision-making is performed locally, even in the
event of total power loss.
The NC-100 contains a powerful 32-bit micro-controller and has a base RAM
configuration of 256k, expandable to 16M. Advanced features including 32-bit
processing, built in high speed LAN interface, Flash RAM, and fault tolerant
design make the NC-100 one of the most powerful and versatile controllers
currently available.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
4
Chapter 2
NC-100
Connection Details
Power
The controller does not require a built in battery-backed power supply. Rather
the NC-100 obtains its power from either the reader controller (RC-2) or the
Input/Output controller (IOC-16).
The NC-100 requires 9-14vdc and draws about 220mA in the standard 256k
RAM configuration.
Host Interface
The Host interface connects the NC-100 to a PC through either an RS232,
TCP/IP Ethernet or an RS485 (4 wire) interface.
™
RBH Access Technologies Inc. AxiomV Hardware Guide
5
Chapter 2
NC-100
Auxiliary Output
This is a dry contact relay output rated for 2A@30vdc that does not have a valid
use at this time.
Earth
The controller contains several layers of protection against induced high voltage
transients from static discharge, lightning, and power line spikes. In order for
this protection to be fully effective, a good connection to earth ground is
essential. Wire this connection to a metal cold water pipe or similar structure.
Do not connect directly to the AC earth. Use 16 AWG or heavier cable and keep
the length as short as possible (less than 50 feet [15meters]).
Although the NC-100 has three possible ground connection points, the ground
connections are normally made at the PC. This leaves the ground connections at
the C-NET and D-NET ports available for cable shield connections.
DIP Switch
DIP Switch Function
1-4 Controller Address
5 Direct Host Connection
6,7 Controller Baud Rate
8 4 Wire RS485 (Always Off)
™
AxiomV Hardware Guide RBH Access Technologies Inc.
6
Chapter 2
NC-100
Controller Addressing
Use DIP switches 1, 2, 3 and 4 to select the controller address. The address is
binary coded and the switch settings for all fifteen possible addresses are given
below.
Controller Addressing
Switch 1 Switch 2 Switch 3 Switch 4 Address
On Off Off Off 1 (Master)
Off On Off Off 2 (Slave)
On On Off Off 3 (Slave)
Off Off On Off 4 (Slave)
On Off On Off 5 (Slave)
Off On On Off 6 (Slave)
On On On Off 7 (Slave)
Off Off Off On 8 (Slave)
On Off Off On 9 (Slave)
Off On Off On 10 (Slave)
On On Off On 11 (Slave)
Off Off On On 12 (Slave)
On Off On On 13 (Slave)
Off On On On 14 (Slave)
On On On On 15 (Slave)
Master Controller
Each C-NET must have a single NC-100 designated as the master controller.
The master controller connects to the PC. Setting the DIP switch address to 1
will automatically designate a NC-100 as the master controller.
Slave Controller
NC-100 Controllers occupying addresses 2 through 15 in the C-NET are referred
to as slave controllers.
Direct Connect
Leave DIP switch 5 off, modem selection is no longer supported.
™
RBH Access Technologies Inc. AxiomV Hardware Guide
7
Chapter 2
NC-100
Panel Reset
Setting all DIP switches to the off position and powering up the NC-100 will
reset the memory completely.
PC Connection
The master controller is connected to a serial port on the PC. The PC serial port
is assigned to the C-NET under the Communication Port Setup screen in the
AxiomV™ software.
Normally the baud rate is set to 9600 for direct connection to the PC using the
standard RS232 interface. The baud rate may be lowered if the distance between
the PC and controller is greater than 150 feet (45 meters) or 38400 baud may be
used if the distance is less than 30 feet (9 meters).
To maintain speed at distances greater than 150 feet (45 meters), the RS485
interface should be used. RS485 is built into the NC-100 controller but is not
part of the standard PC. The PC must be fitted with either an RS485 serial card
or an external RS232 to RS485 serial port converter.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
8
Chapter 2
NC-100
RS232 Connection
Cable Specification
3 or 4 conductor shielded, 18 to 22 AWG
™
RBH Access Technologies Inc. AxiomV Hardware Guide
9
Chapter 2
NC-100
RS485 Connection
The NC-100 controller supports 4 wire RS485 interfaces. DIP switch 8 should
always be set to the OFF position, and will then always be ready for 4-wire
RS485 operation.
The RS485 interface allows the distance between the controller and the PC to be
extended up to 4000 feet (1200 meters) at 38.4k baud. RS485 requires two
twisted pair cables and must be terminated at both ends with a 130-ohm resistor.
This termination is already built into the NC-100. Ensure that the PC end
provides proper termination. If not provided on board, add a 130-ohm resistor
across both A/B connections at the PC end.
Cable Specification
2 twisted pair, individually shielded, 18 to 22 AWG
™
AxiomV Hardware Guide RBH Access Technologies Inc.
10
Chapter 2
NC-100
NC-100 Networks
The NC-100 controller has two separate network interfaces. The C-NET
(Controller Network) connects the master NC-100 to other slave NC-100
controllers using a secure bi-directional Arcnet LAN. The D-NET (Device
Network) connects up to four RC-2 and sixteen IOC-16 controllers to each NC-
100 in the C-NET using secure bi-directional RS485 communications. All field
devices, such as readers, locks and contacts, are in turn wired into the RC-2 and
IOC-16 device controllers.
The controllers are wired together in a high-speed fault tolerant ring network.
Fault tolerance means the system is immune to a single point of failure and will
continue to operate with a short or cut on any single cable section. The fault
condition is reported to the PC.
™
RBH Access Technologies Inc. AxiomV Hardware Guide
11
Chapter 2
NC-100
™
AxiomV Hardware Guide RBH Access Technologies Inc.
12
Chapter 2
NC-100
C-NET Cable
Use 20 to 22 AWG shielded stranded twisted pair cable for all C-NET
connections.
Status LED's
Computer/ Modem Port
The computer port has two LEDs to show the flow of data between the NC-100
controller and PC. The red RX LED flashes when the controller receives data.
The green TX LED flashes when the controller transmits data. If the controller
is connected directly to the PC, the status LED flashes continuously.
C-NET LEDs
The inter-controller network (C-NET) has two status LEDs. The red RX LED
flashes when data is received from another controller. The green TX LED
flashes when the controller transmits data. On a properly functioning system the
C-NET LEDs flash continuously and may appear to be on all the time.
D-NET LEDs
The device-controller network (D-NET) has two status LEDs. The red RX LED
flashes when data is received from a network device (RC-2, IOC-16). The green
TX LED flashes when data is transmitted by the NC-100 to any device controller
on the D-NET. On a properly functioning system the D-NET LEDs flash
continuously and may appear to be on all the time.
Run LED
The run LED flashes every half-second and indicates the system is running
normally.
™
RBH Access Technologies Inc. AxiomV Hardware Guide
13
Chapter 2
NC-100
The D-NET connects IOC-16 and RC-2 device controllers in a daisy chain
fashion to the NC-100 controller. Each NC-100 controller has two D-NET ports
designated Channel 1 and Channel 2 and the D-NET is wired in a ring by
connecting Channel 2 on the NC-100 controller to Channel 1 on the first RC-2 or
IOC-16. Connect Channel 2 on the first device controller to Channel 1 on the
next device controller and so on. Channel 2 on the last device is wired back to
Channel 1 on the NC-100 controller to complete the ring.
Device controllers do not have to be in address sequence in the ring. However,
using sequential device controller addressing is recommended as this makes your
cabling diagrams easier to follow and simplifies troubleshooting as the devices
are in the correct numerical sequence. Connect RC-2 Controllers (up to four)
first in the D-NET, followed by up to sixteen IOC-16 Controllers as per the
diagram on page 18.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
14
Chapter 2
NC-100
™
RBH Access Technologies Inc. AxiomV Hardware Guide
15
Chapter 2
NC-100
D-NET Cable
Use 20 to 22 AWG shielded twisted pair cable for all D-NET connections.
Shielded cable is recommended to minimize problems that can arise in
electrically noisy environments. In addition, shielded cable may be necessary to
prevent the network from interfering with signals on other cables in the same
trunk.
D-NET Termination
There are some controllers/devices that do not have termination built into the
unit. These devices are: UNC500, PC100, and SafeSuite. In most cases,
termination is not needed because the devices are connected to other devices on
the network that will have termination built in. Units which terminate
automatically are the NC100, RC2, and IOC16. The NRC and NURC (trimmed
down replacements for the RC-2) can be terminated using jumpers JP2, JP3, and
JP4 or JP1, JP2, and JP3 (respectfully). All three jumpers must be ON.
SafeSuite units are normally installed with Riser boards which have termination
on each leg of the 485 connections so nothing else needs to be done to terminate
these units. PC100s will normally be added to networks which have terminated
devices such as RC2s or IOC16s. If possible, always put a device that can be
terminated at the start and end of the line. For example; if you have a system
where the PC100 is mixed with NRCs or NURCs, make sure that PC100 is not
the last device. This will allow you to set the jumpers on the NRC or NURC for
termination on the first and last device. Because the UNC does not have
termination jumpers, the first device connected to the UNC500 will have
termination as will the last device on that DNET.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
16
Chapter 2
NC-100
5. Power down the controller and set the DIP switches to configure the
controller.
Clearing the RAM in this manner is only necessary in the rare occasion where
RAM is completely corrupted and the system is unable to communicate with the
PC.
™
RBH Access Technologies Inc. AxiomV Hardware Guide
17
Chapter 3
RC-2
Chapter 3
Reader Controller (RC-2)
Each RC-2 monitors two readers or reader/keypad units as well as eight inputs
and controls eight outputs. RBH recommends that RC-2‟s be used for dedicated
access point operation. However in certain instances inputs and outputs may be
individually configured for general I/O purposes.
The RC-2 has two sides, labeled A and B, and each side implements an
independent access point. Typically an access point includes a reader, door
contact, request to exit button and programmable outputs for lock, forced entry,
door held open and alarm shunt.
Each RC-2 includes two built in power supplies. The 1Amp reader power
supply provides both 5 and 12 volt DC power for reader devices. An additional
1Amp@12volts is available on the auxiliary power output to power other devices
such as motion detectors and warning devices. The system requires a 40 or 80
VA transformer and a rechargeable backup battery.
The RC-2 performs extensive system status monitoring and provides a high
degree of local feedback on system status for the technician. AC power, battery
voltage, reader, and auxiliary fuses are all monitored. Status LEDs indicate the
status of all inputs and outputs, AC fault, low voltage, fuse blown,
communication activity, and run information.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
18
Chapter 3
RC-2
™
RBH Access Technologies Inc. AxiomV Hardware Guide
19
Chapter 3
RC-2
Connection Details
The RC-2 has two sides labeled A and B. References to A and B below refer to
side A and B of the RC-2.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
20
Chapter 3
RC-2
Powering From DC
To power the RC-2 from an external DC supply, connect a 12 to 14volt external
supply to the AC inputs. Do not connect to the battery input as the battery input
is disconnected until power, which normally comes from the AC, is applied to
the controller. The system will report an AC low condition if the input voltage
drops below 14volts.
Tamper
Connect the tamper leads to a normally closed cabinet tamper switch. If a
cabinet tamper switch is not used, the tamper leads should be shorted.
™
RBH Access Technologies Inc. AxiomV Hardware Guide
21
Chapter 3
RC-2
DIP Switch
DIP Switch Function
1-5 RC-2 Address
6, 7, 8 Not used (Always set to OFF)
RC-2 Addressing
Up to four RC-2 devices can be attached to a controller allowing a total of eight
readers to be connected. The four RC-2s must be assigned addresses in the
range 1 to 4. Addresses must be unique and the network will not operate
properly if duplicate addresses are programmed.
RC-2 Addressing
Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 Address
On Off Off Off Off 1
Off On Off Off Off 2
On On Off Off Off 3
Off Off On Off Off 4
Status LED's
Run
The run LED indicates that the RC-2 is operating. Normally the LED flashes
once every second. Very rapid flashing indicates the RC-2 is not communicating
with the controller.
AC High
The AC high LED comes on when the AC voltage is above 20volts RMS.
AC Low
The AC low LED comes on when the AC voltage drops below 14volts RMS.
Battery Trouble
The battery trouble LED indicates that the battery voltage is below 11volts.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
22
Chapter 3
RC-2
Reader Fuse
The reader fuse LED indicates the 1Amp reader fuse is blown. This fuse is
blown if the reader 5 or 12volt output is overloaded.
Auxiliary Fuse
The auxiliary fuse LED indicates the 1Amp auxiliary fuse is blown.
Lock Fuse
LED on indicates the lock fuse is blown.
D-NET LED's
The local-controller network has two status LEDs. The red RX LED flashes
when data is received from the controller. The green TX LED flashes when data
is transmitted by the RC-2. Normally the status LEDs flash continuously.
Battery Test
A dynamic battery test is performed under scheduled control. During the test a
1Amp load is switched across the battery and the voltage is monitored. At the
end of the test a pass or fail message is reported to the PC. The frequency and
duration of the test are programmable from the AxiomV™ software. Typically
the battery is tested once every day and the test duration is thirty seconds.
Battery Protection
The backup battery is protected from deep discharge and possible irreversible
damage during a prolonged ac power failure. The battery voltage is continuously
monitored and will disconnect if the voltage drops below 10 volts.
™
RBH Access Technologies Inc. AxiomV Hardware Guide
23
Chapter 3
RC-2
Inputs
The RC-2 has eight fully supervised inputs, four on side A and four on side B.
Each input is individually programmable from the PC. The RC-2 employs
digital filtering to eliminate the effect of interference on the input loops and
verifies all loop changes before reporting to the controller. Loop resistance is
continuously monitored using a built in eight bit analog to digital converter and
can be viewed from the PC, providing the service technician with a valuable
diagnostic tool and allowing marginal circuit loops to be detected and repaired
before a full blown fault develops.
Each input has four states: Restore, Alarm, Trouble, and Illegal. Trouble is
reported if a short or break is detected on a supervised circuit and illegal is
reported if the measured loop resistance lies between valid states. For example,
if the circuit type is programmed as „2 resistor normally closed‟, 1k represents a
restored state and 2k represents an alarm state. If the loop resistance changes by
more than 15% but not enough to enter the next state, an illegal state is reported.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
24
Chapter 3
RC-2
™
RBH Access Technologies Inc. AxiomV Hardware Guide
25
Chapter 3
RC-2
This circuit provides a high degree of supervision and detects both short and
open circuit fault conditions. Use this circuit in high security applications.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
26
Chapter 3
RC-2
This circuit type is used where normally open and normally closed contacts are
used in the same loop.
™
RBH Access Technologies Inc. AxiomV Hardware Guide
27
Chapter 3
RC-2
Outputs
The RC-2 has eight outputs, four on side A and four on side B. Outputs 1A/B
and 2A/B are dry contact relays capable of switching 2Amps@30vdc. Outputs
3A/B and 4A/B use electronic drivers and can switch 100ma. Outputs are
programmable from the PC as normally energized or normally de-energized.
Normally energized outputs are used for fail-safe operation where it is essential
that the output return to a safe state when the system fails due to power loss,
communications failure, or fire.
Electronic outputs are „switched negative‟ which means that they switch the
power negative to the terminal. When the output is off, the output terminal is
electronically disconnected. Outputs can be programmed to operate in a default
mode described below or they can be used as general-purpose outputs. However,
the output definition in the AxiomV™ configuration software should never be
left blank. If the output is unused, use the default output definitions provided in
the AxiomV™ configuration software.
For magnetic locks, the relay should be configured from the PC as normally
energized for fail-safe operation. If power fails (AC and battery) or the fire input
is released, the power to the magnetic lock is removed and the door is opened.
™
RBH Access Technologies Inc. AxiomV Hardware Guide
29
Chapter 3
RC-2
™
AxiomV Hardware Guide RBH Access Technologies Inc.
30
Chapter 3
RC-2
Output 3 turns on if the door is held open longer than the PC programmed limit.
This output remains on until the door closes. During the warning period, this
output will pulse every second.
™
RBH Access Technologies Inc. AxiomV Hardware Guide
31
Chapter 3
RC-2
The alarm shunt output turns on when the door is unlocked. This output turns
off when the door is re-locked if the door is closed at that time; otherwise the
output turns off when the door closes. Normally the shunt output is used to
shunt the door contact if a secondary alarm panel monitors the contact.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
32
Chapter 3
RC-2
High Security
The Red LED flashes quickly.
In high security mode, only cardholders with high security clearance are allowed
access.
Unlocked
The green LED turns on to indicate the door is unlocked.
Tamper
The Buzzer sounds continuously.
Lockout Alarm
The Buzzer beeps rapidly.
A lockout alarm occurs when a user-defined number of „Access Denied‟
messages occur. These messages can include „Invalid Card Number‟, „No
Access at this Time‟, „No Access at this Reader‟, or „Invalid PIN Code‟.
Access Granted
The Buzzer emits one long beep and the green LED turns on for the duration of
the unlock time.
Access Denied
The Buzzer emits two short beeps and the red LED flashes twice.
™
RBH Access Technologies Inc. AxiomV Hardware Guide
33
Chapter 3
RC-2
The RC-2 supports any reader device using the Wiegand format.
Cable Specification
5-conductor, stranded, shielded cable (not twisted), 20 to 22 AWG
1
Reader wire colours may vary for different reader manufactures. Please verify your wiring.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
34
Chapter 3
RC-2
Cable Specification
7-conductor, stranded, shielded cable (not twisted), 20 to 22 AWG
2
Reader wire colours may vary for different reader manufactures. Please verify your wiring.
™
RBH Access Technologies Inc. AxiomV Hardware Guide
35
Chapter 3
RC-2
Cable Specification
6-conductor, stranded, shielded cable (not twisted), 20 to 22 AWG
3
Reader wire colours may vary for different reader manufactures. Please verify your wiring.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
36
Chapter 3
RC-2
Cable Specification
7-conductor, stranded, shielded cable (not twisted), 20 to 22 AWG
4
Keypad wire colours may vary for different keypad manufactures. Please verify your wiring.
™
RBH Access Technologies Inc. AxiomV Hardware Guide
37
Chapter 4
IOC-16
Chapter 4
Input/Output Controller (IOC-16)
The I/O Module (IOC-16) has sixteen I/O ports, each of which is configurable as
a zone input or a relay output. A single LED indicates the status of each I/O
point. If the I/O point is configured as an input, the LED is off if the input is
restored and on otherwise. If the I/O point is configured as and output, the LED
is off if the output is de-energized and on if the output is energized.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
38
Chapter 4
IOC-16
Connection Details
Auxiliary Power Output
This fused output provides 12v@1A to power external devices.
AC Power
The IOC-16 is powered from a 16.5vac 40VA transformer. The IOC-16 draws
about 0.5Amps when all 16 relays are energized. An additional on board power
supply provides 1Amp at 13.8volts and can be used to power external devices or
the NC-100 controller. An external 12volt rechargeable battery provides backup
power.
Powering From DC
To power the IOC-16 from an external DC supply, connect a 12 to 14volt
external supply to the AC inputs. Do not connect to the battery input as the
battery input is disconnected until power, which normally comes from the AC, is
applied to the controller.
If fire signal monitoring is not required, this input must be connected to the IOC-
16 auxiliary power output.
********************************************************************************
Tamper
Connect the tamper leads to a normally closed cabinet tamper switch. If a
cabinet tamper switch is not used, the tamper leads should be shorted.
™
RBH Access Technologies Inc. AxiomV Hardware Guide
39
Chapter 4
IOC-16
DIP Switch
DIP Switch Function
1-5 IOC-16 Address
6,7 Not used (Always OFF)
8 Output Fail Safe Operation (ON)
IOC-16 Addressing
IOC-16 Addressing
Switch 1 Switch 2 Switch 3 Switch 4 Switch 5 Address
On Off On Off Off 5
Off On On Off Off 6
On On On Off Off 7
Off Off Off On Off 8
On Off Off On Off 9
Off On Off On Off 10
On On Off On Off 11
Off Off On On Off 12
On Off On On Off 13
Off On On On Off 14
On On On On Off 15
Off Off Off Off On 16
On Off Off Off On 17
Off On Off Off On 18
On On Off Off On 19
Off Off On Off On 20
™
AxiomV Hardware Guide RBH Access Technologies Inc.
40
Chapter 4
IOC-16
Status LED's
Run
The run LED indicates that the IOC-16 is operating. Normally the LED flashes
once every second. Very rapid flashing indicates the IOC-16 is not
communicating with the NC-100 controller.
AC High
The AC high LED comes on when the AC voltage is above 20volts RMS.
AC Low
The AC low LED comes on when the AC voltage drops below 14volts RMS.
Battery Trouble
The battery trouble LED indicates that the battery voltage is below 11volts.
Auxiliary Fuse
The auxiliary fuse LED indicates the 1Amp auxiliary fuse is blown.
Network LEDs
The local-controller network has two status LEDs. The red RX LED flashes
when data is received from the controller. The green TX LED flashes when data
is transmitted by the IOC-16. Normally the status LEDs flash continuously.
Battery Test
A dynamic battery test is performed under scheduled control. During the test a
1Amp load is switched across the battery and the voltage is monitored. At the
end of the test a pass or fail message is reported to the PC. The frequency and
duration of the test are programmable from the PC. Typically the battery is
tested once every day and the test duration is thirty seconds.
Battery Protection
The backup battery is protected from deep discharge and possible irreversible
damage during a prolonged ac power failure. The battery voltage is continuously
monitored and disconnected if the voltage drops below 10volts.
™
RBH Access Technologies Inc. AxiomV Hardware Guide
41
Chapter 4
IOC-16
™
AxiomV Hardware Guide RBH Access Technologies Inc.
42
Chapter 4
IOC-16
Inputs
The IOC-16 has sixteen fully supervised inputs. Each input is individually
configurable from the PC for various circuit types.
For full details of circuit types, refer to Input Circuit Types on page 25.
IOC-16 Input Connection Diagram
Outputs
The IOC-16 has sixteen dry contact relays capable of switching 2Amps@30vdc.
Outputs are programmable from the PC as normally energized or normally de-
energized. Normally energized outputs are used for fail-safe operation where it
is essential that the output return to a safe state when the system fails due to
power loss, communications failure, or fire.
IOC-16 Output Connection Diagram
™
RBH Access Technologies Inc. AxiomV Hardware Guide
43
Chapter 4
IOC-16
Elevator Control
AxiomV™ provides extensive elevator access control capability. A standard
reader or keypad is mounted in the elevator cabin(s). Upon presentation of a
valid code by a user, the system enables all floors that the user is authorized to
access. The user access level determines the floors and time periods during
which access is allowed. Turning on a relay output on the IOC-16 controller
enables floor access. The relay outputs are wired to the elevator control
interface board provided by the Elevator Company. A single IOC-16 controls up
to sixteen floors and up to sixteen IOC-16s can be connected to a single NC-100
controller.
A single input on the RC-2 can be configured as a floor reset input for each
elevator cabin. This input is connected to an output from the elevator that trips
when a floor is selected. All floors currently enabled will be disabled when this
input trips. This feature increases the security of the elevator control, as the
possibility of a second unauthorized person pressing a button from the previous
person‟s selection is eliminated. As soon as the first person selects a floor, all
other floors selections are canceled.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
44
Chapter 4
IOC-16
™
RBH Access Technologies Inc. AxiomV Hardware Guide
45
Chapter 4
IOC-16
™
AxiomV Hardware Guide RBH Access Technologies Inc.
46
Chapter 4
IOC-16
Chapter 5
NRC2000 & NURC2000
™
RBH Access Technologies Inc. AxiomV Hardware Guide
47
Chapter 5
NRC-NURC
Wiring
To connect NRC2000s and NURC2000s to an NC100 simply connect them all in parallel (on the
RS485 connection connect all A‟s together & all B‟s together) and jumper channel 1 & channel 2
together on the NC100 (A to A, & B to B).
It is not recommended to mix RC2s and IOC16s with NRC2000s and NURC2000s because of the
loop wiring of the RC2s and IOC16s.
The NRC2000 uses an IRC2000 board to provide most of the functionality of the RC2 board to
the Axiom system. The NRC2000 firmware version 3 is based on RC firmware version 34, and
includes all updates and bug fixes associated with that version.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
48
Chapter 4
IOC-16
Modification
Due to the lack of internal power supply and fewer I/O lines the NRC2000 does not provide the
following functionality:
1) Reader Tamper – the reader tamper inputs can be used to monitor AC failure and low
battery. Reader “A” tamper is used for AC voltage detection and should be shorted to
ground to avoid “AC FAIL” message, if the power supply modifications are not done.
Reader “B” tamper is used for battery voltage detection and should be left open to avoid
the “BATTERY FAIL” message, if the power supply modifications are not done.
2) Cabinet Tamper – always reports normal.
3) Fuse monitoring – due to lack of power supply – always normal
4) Dual RS485 redundant communications – has only a single channel so must be wired
differently!
Technical bulletin TB53 will show how to modify the IRC2000 board and how to
connect to the power supply to monitor for ‘Battery Low’ and ‘AC Failure’.
™
RBH Access Technologies Inc. AxiomV Hardware Guide
49
Chapter 5
NRC-NURC
Chapter 6
PC-100
The PC-100 connects to the NC-100 through the DNet, as does all devices. Into channel 1 and out
from channel 2.
Power:
9-14vdc @ 150ma
LEDs
DIAG1 – Interface status
DIAG2 – Axiom status:
Communication Channel LEDs – Each communication channel has a green transmit LED and a red
receive LED.
Normally flashing at a rate of once a second, DIAG2 will flash twice as fast if the unit is offline
with the Axiom Device network.
™
AxiomV Hardware Guide RBH Access Technologies Inc.
50
Specifications
™
RBH Access Technologies Inc. AxiomV Hardware Guide
51
Appendix 1
Specification Sheets
NC-100 Specification
D-NET (NC-100 to RC-2 and IOC-16): Network Type RS485 High Speed Network
Ports Two fully supervised RS485 ports
Communications speed 38400 bits/second
Circuit Type Ring (short or open circuit protection)
Local PC & Remote Communications: Type RS232, TCP/IP Ethernet, RS485 4 wire
Serial Port Speed Programmable, 1200 to 38,400 baud
™
AxiomV Hardware Guide RBH Access Technologies Inc.
52
RC-2 Specification
Controller Power Requirements: One 16.5vac 40VA transformer Controller & Auxiliary
One 12/18vac 80VA transformer Door Lock Power
D-NET (NC-100 to RC-2 and IOC-16): Ports Two fully supervised RS485 ports
Communications speed 38400 bits/second
Circuit Type Ring (short or open circuit protection)
™
RBH Access Technologies Inc. AxiomV Hardware Guide
53
Appendix 1
Specification Sheets
IOC-16 Specification
Controller Power Requirements: One 16.5vac 40VA transformer
Current Consumption: 500ma max per controller (with all relays energized)
™
AxiomV Hardware Guide RBH Access Technologies Inc.
54
NRC-2000 Specification
™
RBH Access Technologies Inc. AxiomV Hardware Guide
55
Appendix 1
Specification Sheets
NURC-2000 Specification
™
AxiomV Hardware Guide RBH Access Technologies Inc.
56
PC-100 Specification
™
RBH Access Technologies Inc. AxiomV Hardware Guide
57
Appendix 1
Specification Sheets
Cable Specification
PC To Controller
RS232: 3 or 4 conductor shielded, 18 to 22 AWG
Maximum Cable Length
9600 baud 150 feet (45 meters)
38400 baud 30 feet (9 meters)
RC-2 to Reader:
20 to 22 AWG, 6 or 8-conductor, stranded, shielded (not twisted)
Maximum Cable Length
22 AWG Cable 250 feet (75 meters)
20 AWG Cable 500 feet (150 meters)
™
AxiomV Hardware Guide RBH Access Technologies Inc.
58
Index
Index
IOC16 ---------------------------------------------- 40
A NC100 ----------------------------------------------- 6
Access Denied --------------------------------------- 33 RC2 ------------------------------------------------- 22
Access Granted -------------------------------------- 33 D-Net-------------------------------------------------- 14
Access Point Operating Modes ------------------ 33 Connection Diagram ---------------------------- 15
Alarm Shunt------------------------------------------ 32 Maximum Cable Length ----------------------- 16
Alarm Shunt Output - Connection Diagram --- 32 Termination --------------------------------------- 16
Auxiliary Output --------------------------------------6 Door Contact ---------------------------------------- 24
Connection Diagram ---------------------------- 24
B Door Held Open ------------------------------------ 31
Backup Battery Door Held Open Alarm --------------------------- 33
IOC16 ---------------------------------------------- 39 Connection Diagram ---------------------------- 31
RC2 ------------------------------------------------- 21 Door Held Open Warning ------------------------ 33
Battery Test Door Strike - Connection Diagram ------------- 30
IOC16 ---------------------------------------------- 41
RC2 ------------------------------------------------- 23
E
Electronic Output - Connection Diagram------ 28
C Elevator Control ------------------------------------ 44
Clearing NC-100 Memory ------------------------ 17 Connection Diagram ---------------------------- 46
C-Net -------------------------------------------------- 11 Elevator Control Overview ----------------------- 45
Connection Diagram ---------------------------- 13
Maximum Cable Length ------------------------ 13
F
Connection Details Fire Release Input
IOC16 ---------------------------------------------- 39 IOC16 ---------------------------------------------- 39
NC100 ------------------------------------------------5 RC2 ------------------------------------------------- 21
RC2 ------------------------------------------------- 20 Forced / Tamper ------------------------------------ 30
Connection Diagram
C-Net ----------------------------------------------- 13 H
D-Net ----------------------------------------------- 15 High Security Mode-------------------------------- 33
Door Contact -------------------------------------- 24
Door Held Open ---------------------------------- 31 I
Door Strike ---------------------------------------- 30 Input / Output Selection --------------------------- 42
Electronic Output -------------------------------- 28 Input Circuit Types--------------------------------- 25
Elevator Control ---------------------------------- 46 Input/Output Controller --------------------------- 38
Magnetic Lock ------------------------------------ 29 Inputs
RC2 to 12 volt Keypad-------------------------- 37 IOC16 ---------------------------------------------- 43
RC2 to 12 volt Reader -------------------------- 35 RC2 ------------------------------------------------- 24
RC2 to 24 volt Reader -------------------------- 36 Interface Wiring
RC2 to 5 volt Reader ---------------------------- 34 RS232 ------------------------------------------------ 9
Controller Network --------------------------------- 11 RS485 ---------------------------------------------- 10
Introducing AxiomV --------------------------------- 1
D IOC16 ------------------------------------------------- 38
Default Output Operation ------------------------- 29 Backup Battery ----------------------------------- 39
Device Network ------------------------------------- 14 Battery Test --------------------------------------- 41
Diagnostic LEDs ------------------------------------ 13 Connection Details ------------------------------ 39
DIP Switch Settings DIP Switch Settings ----------------------------- 40
™
RBH Access Technologies Inc. AxiomV Hardware Guide
59
Appendix 1
Specification Sheets
RC2 ------------------------------------------------- 28 U
System Diagram ---------------------------------------3
Unlocked Mode ------------------------------------- 33
T W
Tamper ------------------------------------------------ 33
Wiring
IOC16 ---------------------------------------------- 39
NRC2000/ NURC2000 ------------------------- 48
RC2 ------------------------------------------------- 21
Termination ------------------------------------------ 16
Two Person Mode ---------------------------------- 33
™
RBH Access Technologies Inc. AxiomV Hardware Guide
61