Packaged A/C Units ESP Calculation
Packaged A/C Units ESP Calculation
Packaged A/C Units ESP Calculation
Calculated pressure drop for Return Air Duct = (a+b ) + 10 % safety factor = 0.219 in wg ..........(A)
Calculated pressure drop for Supply Air Duct = (a1+b1) + 10 % safety factor = 0.367 in w.g ..........(B) ESP
Design 0.7
Summary SELECTED : 0.7 in w.g
PU-01(PNGC-130C2) ESP = A+B = 0.586 in w.g Calculated 0.586
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
INPUTS OUTPUTS
www.dasco.com.kw
SIZE NECK PATTERN CFM 390 469 625 781 938 1095 1250 SIZE
AREA S.NC 19 22 28 33 37 44 49
SCFM 98 98 117 117 156 156 195 195 234 234 273 273 312 312
DD-64S
15 THROW 14 -18 16 - 19 18 - 22 19 - 24 20 - 27 21- 28 22 -29 15
SCFM 146 98 176 117 234 156 293 195 352 234 411 273 469 312
DD-63S
X X
SCFM - 195 - 235 - 313 - 391 - 469 - 548 - 625
DD-62S
15 THROW 19 - 24 20 - 27 22 - 29 22 - 31 23 - 33 24 - 35 26 - 39 15
SCFM - 390 - 469 - 625 - 781 - 938 - 1095 - 1250
DD-61S
THROW 22-31 23-33 26-39 27-42 29-46 30-48 32-51
SIZE NECK PATTERN CFM 562 675 900 1125 1350 1575 1800 SIZE
AREA S.NC <18 24 30 35 40 45 51
SCFM 141 141 168 168 225 225 281 281 337 337 394 394 450 450
DD-64S
18 THROW 17 - 22 20 - 23 22 - 27 23 - 29 25 - 31 26 - 32 28 - 33 18
SCFM 211 141 253 168 338 225 422 281 506 337 591 394 675 450
DD-63S
X X
SCFM - 281 - 338 - 450 - 563 -675 - 788 -900
DD-62S
18 THROW 23-29 25-31 28-33 28-34 30-36 31-38 32-40 18
SCFM - 562 - 675 - 900 - 1125 - 1350 - 1575 - 1800
DD-61S
THROW 28-34 30-36 32-40 33-43 35-47 36-50 38-54
SIZE NECK PATTERN CFM 765 919 1225 1530 1838 2144 2450 SIZE
AREA S.NC 22 25 30 36 42 48 54
SCFM 191 191 230 230 306 306 383 383 460 460 536 536 613 613
DD-64S
21 THROW 20 - 26 23 - 27 26 - 32 28 - 34 29 - 37 31 - 38 33 - 40 21
SCFM 287 191 345 230 459 306 574 383 690 460 804 536 919 613
DD-63S
X X
SCFM - 383 - 460 - 613 - 675 - 919 - 1072 - 1225
DD-62S
21 THROW 28-34 29-37 33-40 34-42 36-45 36-46 38-48 21
SCFM - 765 - 919 - 1225 - 1530 - 1838 - 2144 - 2450
DD-61S
THROW 34 - 42 36 - 45 38 - 48 39 - 50 41 - 53 42 - 55 44 - 58
Note
SIZE : Is the nominal neck size in inches. P(s) : Supply pressure drop in inches W.G.
NICK AREA : Is in square feet. SCFM : Side CFM.
PATTERN : Is flow pattern as detailed previously. THROW : IN feet corresponding to 100 & 50
FPM terminal velocity.
SNC : Room NC for supply based on 8 db
room effect.
11
Performance Data