SAMPLE PROBLEMS IN TRANSMISSION LINES diameter is 1.2 cm.
Find the charging current per
phase. 1. In a three-phase transmission line the three 10. A 13.2 KV, 3-mile transmission line is composed conductors are placed at the corners of a triangle of 336, 400 cmil, 26/7 (Linnet) ACSR has GMR of sides 1.5 m, 3 m and 2.6 m respectively. If the of 0.0244 ft and a resistance of 0.306 ohm per diameter of each conductor is 1.4 cm and the mile. The conductors are spaced horizontally 3 ft conductors are transposed, calculate the apart. What is the series impedance? inductance per phase per km of the line. 11. A 115 kV three-phase transposed transmission 2. A single-circuit three-phase transposed line is composed of 2-ACSR 336, 400 cmil, 30/7 transmission line is composed of four ACSR, Oriole conductor per phase with horizontal 1,272,00-cmil conductor per phase with configuration: D12 = 7 ft, D23 =7 ft, D13 =14 horizontal configuration of 14 m between ft. The line spacing is measured from the center centers of the bundle. The bundle spacing is 45 of the bundled conductors. The distance cm. The diameter of each conductor in the between the conductors of the bundle is 6 bundle is 3.574 cm and GMR of 1.419 cm. inches. The conductors have a diameter of 0.741 Determine the inductance per phase per km of inch and a GMR of 0.02255 ft. Find the the line. capacitance per phase for 20 km of the line in 3. Determine the capacitance of an 80 km long 3- microfarads. phase, 50 Hz overhead transmission line 12. A 200 km line has a resistance of the line per consisting of 3 conductors, each of 1.8 cm in phase per km is 0.08 Ω, a susceptance per phase diameter and spaced 2.4 m at the corners of an per km = 6 x 10-6 mho and a reactance per equilateral triangle. phase per km is 0.8 Ω. Using nominal T method, 4. The conductors of a 3-phase, 3-wire system are determine constant B in the line. transposed and are arranged in a horizontal 13. A three-phase transmission line is 300 mi long configuration with D12 = D23 = 1.8 m; D31 = and serves a load of 400 MVA, with 0.8 lagging 2D12. If the diameter of each conductor is 2.2 power factor at 345 KV. The ABCD constants of cm, solve for the inductance of the line per phase the line are: A = D = 0.818 cis 1.3˚; B = 172.2 per km. cis 84.2˚; C = 0.001933 cis 90.4˚. Find the 5. A three-phase line is designed with equilateral receiving end line to neutral voltage at no-load. spacing of 16 ft. It is decided to build the line 14. The ABCD constants of a three-phase with horizontal spacing (D13 = 2D12 = 2D23). transmission line are: A = D = 0.936 + j0.016 B The conductors are transposed. What should be = 33.5 + j138 C = (-5.18 + j914) x 10^(-6) The the spacing between adjacent conductors in load at the receiving end is 50 MW at 220 KV order to obtain the same inductance as in the with a pf of 0.9 lagging. Find the voltage original design? regulation of the line. Assume that the 6. Calculate the loop inductance per km of a single- magnitude of the sending end voltage remains phase overhead line consisting two conductors the same. each 1 cm in diameter and 1.2 m apart. 15. A three-phase short transmission line has a per 7. A three-phase 60 Hz transmission line has its phase impedance of 0.3 + j0 4 Ω The receiving conductors arranged in a triangular formation so that two of the distances between conductors end voltage is 6 351 volts per phase and the are 25 ft and the third distance is 42 ft. The voltage regulations is not exceed 5 percent. Calculate the total line loss when it is supplying conductors are ACSR Osprey (GMR = 0.0284 ft). maximum power. Determine the inductive reactance per phase per mile. 16. A 10-km long, single-phase short transmission 8. A three-phase, 60 Hz transmission line has its line has0 5 < 60 Ω/km impedance. The line conductors arranged in a triangular formation so supplies a 316.8 kW load at 0.8 power factor that two of the distances between conductors lagging. What is the voltage regulation if the are 25 ft and the third is 42 ft. The conductors receiving and voltage is 3.3 kV? are ACSR Osprey having a diameter of 0.879 inch. Determine the capacitive reactance to neutral in ohm-miles. 9. A three-phase 132 KV, 100 km, 50 Hz single circuit line has a horizontal spacing with 3.5 m between adjacent conductors. The conductor