Datasheet PLC ABB Analog Input Module AI523
Datasheet PLC ABB Analog Input Module AI523
DATA SHEET
AI523
Analog Input Module
1 Ordering data
Part no. Description Product life cycle phase *)
1SAP 250 300 R0001 AI523, analog input module, 16 AI, Active
U/I/Pt100, 12 bits + sign, 2-wires
1SAP 450 300 R0001 AI523-XC, analog input module, 16 AI, Active
U/I/Pt100, 12 bits + sign, 2-wires,
XC version
*) Modules in lifecycle Classic are available from stock but not recommended for
planning and commissioning of new installations.
2 Dimensions
1 Din rail 15 mm
2 Din rail 7.5 mm
3 Technical data
The system data of AC500 and S500 are applicable to the standard version Ä Chapter 4 “System
data AC500” on page 5.
The system data of AC500-XC are applicable to the XC version Ä Chapter 5 “System data AC500-
XC” on page 10.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter Value
Process voltage
Connections Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V
(UP) as well as 1.9, 2.9, 3.9 and 4.9 for 0
V (ZP)
Rated value 24 V DC
Max. ripple 5%
Parameter Value
Protection against reversed voltage Yes
Rated protection fuse on UP 10 A fast
Galvanic isolation Yes, per module
Current consumption
From 24 V DC power supply at the terminals Ca. 2 mA
UP/L+ and ZP/M of the CPU/communication
interface module
From UP at normal operation / with outputs 0.15 A + output loads
Inrush current from UP (at power up) 0.050 A2s
Max. length of analog cables, conductor cross section > 100 m
0.14 mm2
Weight 300 g
Mounting position Horizontal or vertical with derating
(output load reduced to 50 % at 40 °C
per group)
Cooling The natural convection cooling must not
be hindered by cable ducts or other parts
in the control cabinet.
NOTICE!
All I/O channels (digital and analog) are protected against reverse polarity, reverse
supply, short circuit and temporary overvoltage up to 30 V DC.
Parameter Value
Resolution Range 0 V ... 10 V: 12 bits
Range -10 V ... +10 V: 12 bits + sign
Range 0 mA ... 20 mA: 12 bits
Range 4 mA ... 20 mA: 12 bits
Conversion error of the analog values caused Typ. ±0.5 % of full scale
by non-linearity, adjustment error at factory and
resolution within the normal range at 25 °C
Max. ±1 % of full scale (all ranges)
at 0 °C ... 60 °C or EMC disturbance
Relationship between input signal and hex code
Unused voltage inputs Are configured as "unused"
Unused current inputs Have a low resistance, can be left open-circuited
Overvoltage protection Yes
NOTICE!
Risk of damaging the PLC due to improper voltage levels!
– Never exceed the maximum tolerance values for process and supply voltages.
– Never fall below the minimum tolerance values for process and supply voltages.
Observe the system data Ä Chapter 4 “System data AC500” on page 5 and the
technical data of the module used.
NOTICE!
Improper voltage level or frequency range which cause damage of AC inputs:
– AC voltage above 264 V
– Frenquency below 47 Hz or above 62.4 Hz
NOTICE!
Improper connection leads cause overtemperature on terminals.
PLC modules may be destroyed by using wrong cable type, wire size and cable
temperature classification.
Parameter Value
Temperature
Operating 0 °C ... +60 °C: Horizontal mounting of modules.
0 °C ... +40 °C: Vertical mounting of modules.
Output load reduced to 50 % per group.
Storage -40 °C ... +70 °C
Transport -40 °C ... +70 °C
Humidity Max. 95 %, without condensation
Air pressure
Operating > 800 hPa / < 2000 m
Storage > 660 hPa / < 3500 m
Parameter Value
24 V circuits (supply, 24 V 350 V AC 2 s
inputs/outputs, analog inputs/
outputs), if they are galvanically
isolated against other circuitry
COM interfaces, galvanically 350 V AC 2 s
isolated
Not applicable Not applicable
Ethernet 350 V AC 2 s
According to
IEC 61010-2-201 The content of the following table is only valid for PM56xx and TB56xx.
Safety Extra Low Voltage (SELV) and Protective Extra Low Voltage (PELV)
To ensure electrical safety of AC500/AC500-eCo extra low voltage circuits, 24 V DC
supply, communication interfaces, I/O circuits, and all connected devices must be
powered from sources meeting requirements of SELV, PELV, class 2, limited voltage
or limited power according to applicable standards.
WARNING!
Improper installation can lead to death by touching hazardous voltages!
To avoid personal injury, safe separation, double or reinforced insulation and separa-
tion of the primary and secondary circuit must be observed and implemented during
installation.
– Only use power converters for safety extra-low voltages (SELV) with safe galvanic
separation of the primary and secondary circuit.
– Safe separation means that the primary circuit of mains transformers must be
separated from the secondary circuit by double or reinforced insulation. The pro-
tective extra-low voltage (PELV) offers protection against electric shock.
Table 4: Immunity against electrostatic discharge (ESD), according to IEC 61000-4-2, zone B, crite-
rion B
Parameter Value
Electrostatic voltage in case of air discharge 8 kV
Electrostatic voltage in case of contact discharge 4 kV, in a closed control cabinet 6 kV 1)
ESD with communication connectors In order to prevent operating malfunctions, it is
recommended, that the operating personnel dis-
charge themselves prior to touching communica-
tion connectors or perform other suitable meas-
ures to reduce effects of electrostatic discharges.
ESD with connectors of terminal bases The connectors between the terminal bases and
processor modules or communication modules
must not be touched during operation. The same
is valid for the I/O bus with all modules involved.
1) High requirement for shipping classes are achieved with additional specific measures (see specific
documentation).
Table 5: Immunity against the influence of radiated (CW radiated), according to IEC 61000-4-3, zone
B, criterion A
Parameter Value
Test field strength 10 V/m
Table 6: Immunity against fast transient interference voltages (burst), according to IEC 61000-4-4,
zone B, criterion B
Parameter Value
Power supply (DC) 2 kV
Power supply (AC) 2 kV
Digital inputs/outputs (24 V DC) 1 kV
Digital inputs/outputs (120 V AC ... 240 V AC) 2 kV
Parameter Value
Analog inputs/outputs 1 kV
CS31 bus 1 kV
Serial RS-485 interfaces (COM) 1 kV
Serial RS-232 interfaces (COM) 1 kV
Ethernet 1 kV
I/O supply (DC-out) 1 kV
Table 7: Immunity against the influence of line-conducted interferences (CW conducted), according to
IEC 61000-4-6, zone B, criterion A
Parameter Value
Test voltage 3V zone B, 10 V is also met.
High energy surges According to IEC 61000-4-5, zone B, criterion B
Power supply (DC) 1 kV CM / 0.5 kV DM ²)
DC I/O supply 0.5 kV CM / 0.5 kV DM ²)
Communication Lines, shielded 1 kV CM ²)
AC I/O unshielded 3) 2 kV CM / 1 kV DM ²)
I/O analog, I/O DC unshielded 3) 1 kV CM / 0.5 kV DM ²)
Radiation (radio disturbance) According to IEC 55011, group 1, class A
NOTICE!
Risk of damaging the PLC due to improper voltage levels!
– Never exceed the maximum tolerance values for process and supply voltages.
– Never fall below the minimum tolerance values for process and supply voltages.
NOTICE!
For the supply of the modules, power supply units according to PELV or SELV specifi-
cations must be used.
NOTICE!
Improper voltage level or frequency range which cause damage of AC inputs:
– AC voltage above 264 V
– Frenquency below 47 Hz or above 62.4 Hz
NOTICE!
Improper connection leads cause overtemperature on terminals.
PLC modules may be destroyed by using wrong cable type, wire size and cable
temperature classification.
The creepage distances and clearances meet the requirements of the overvoltage
category II, pollution degree 2.
Parameter Value
Temperature
Operating -40 °C ... +70 °C
-40 °C ... -30 °C: Proper start-up of system; tech-
nical data not guaranteed
-40 °C ... 0 °C: Due to the LCD technology, the
display might respond very slowly.
-40 °C ... +40 °C: Vertical mounting of modules
possible, output load limited to 50 % per group
+60 °C ... +70 °C with the following deratings:
● System is limited to max. 2 communication
modules per terminal base
● Digital inputs: maximum number of simultane-
ously switched on input channels limited to
75 % per group (e.g. 8 channels => 6 chan-
nels)
● Digital outputs: output current maximum
value (all channels together) limited to 75 %
per group (e.g. 8 A => 6 A)
● Analog outputs only if configured as
voltage output: maximum total output cur-
rent per group is limited to 75 %
(e.g. 40 mA => 30 mA)
● Analog outputs only if configured as current
output: maximum number of simultaneously
used output channels limited to 75 % per
group (e.g. 4 channels => 3 channels)
Storage / Transport -40 °C ... +85 °C
Humidity Operating / Storage: 100 % r. H. with condensa-
tion
Air pressure Operating:
-1000 m .... 4000 m (1080 hPa ... 620 hPa)
> 2000 m (< 795 hPa):
● max. operating temperature must be reduced
by 10 K (e.g. 70 °C ... 60°C)
● I/O module relay contacts must be operated
with 24 V nominal only
Parameter Value
Immunity to corrosive gases Operating: Yes, according to:
ISA S71.04.1985 Harsh group A, G3/GX
IEC 60721-3-3 3C2 / 3C3
Immunity to salt mist Operating: Yes, horizontal mounting only,
according to IEC 60068-2-52 severity level: 1
NOTICE!
Risk of corrosion!
Unused connectors and slots may corrode if XC devices are used in salt-mist environ-
ments.
Protect unused connectors and slots with TA535 protective caps for XC devices.
NOTICE!
Risk of malfunctions!
Unused slots for communication modules are not protected against accidental phys-
ical contact.
– Unused slots for communication modules must be covered with dummy communi-
cation modules to achieve IP20 rating.
– I/O bus connectors must not be touched during operation.
Parameter Value
Vibration resistance IEC 61131-2 / IEC 60068-26: 5 Hz ... 500 Hz, 2 g (with memory
card inserted)
IEC 60068-2-64: 5 Hz ... 500 Hz, 4 g rms
Shock resistance IEC 60068-2-27: all 3 axes 15 g, 11 ms, half-sinusoidal
— —
ABB AG © Copyright 2017-2023 ABB.
Eppelheimer Str. 82 We reserve all rights in this document and in the information contained
69123 Heidelberg, Germany therein. Reproduction, use or disclosure to third parties without express
Telephone: +49 (0)6221 701 1444 authority is strictly forbidden.
E-mail: [email protected]
new.abb.com/plc
new.abb.com/plc/automationbuilder
new.abb.com/contact-centers