Crossbonding Joint S1953-4 MPFP1.145-32
Crossbonding Joint S1953-4 MPFP1.145-32
Crossbonding Joint S1953-4 MPFP1.145-32
145-32
Cross-bonding joint MPFP 1.145-32
The copyright of his document is reserved. It is forbidden to reproduce it, either communicated or made accessible to third persons without written authorisation of our company. All information is subject to change without notice.
Koaxialkabel
Coaxial-cable Leiterverbinder
Conductor connector
Schutzmuffe
Protection box Füllmasse
Filling compound
max. A
ca. B B mm 477
C mm 275
Min. / Max. Durchmesser über Aderisolierung geschält / Min. / Max. Diameter over prepared insulation 78-115 mm
Max. Kabeldurchmesser / Max. cable diameter 140 mm
Typprüfung nach IEC 60840 / Type Test Data according to IEC 60840
Teilentladungsprüfung / Partial discharge test <5pC (1.5 U0) 114 kV
Lastwechselspannung / Heating cycle voltage test 152 kV
Blitzstossspannungsprüfung / Lightning impulse voltage test (BIL) 650 kV
Produktion Stückprüfung am Muffenkörper ASMK / Factory Routine Test on insulating body ASMK
Wechselspannungsprüfung 30 min. / Power frequency voltage test 30 min. (2.5 U0) 190 kV
Teilentladungsprüfung bei Umgebungstemperatur / Partial discharge test at ambient temperature( <5pC) (1.5 U0) 114 kV
Verbinder / Connector
Typ / Type Gepresst oder geschraubt / Compression or bolted
Querschnitt / Cross section
max. Querschnitt Verbinder Typ Kabel Isolationsdicke min.
max. Cross section Connector Type Insulation Thickness min.
2
1600mm Compression 10.5 mm
2
1000 mm bolted 1 pc. 10.5 mm
2
2500 mm bolted 2 pc. 18 mm
Lieferdaten / Delivery Data
Lieferumfang / Scope of delivery Material für 3 Muffen / Material for 3 joints
Materialdisposition / Material disposition Export Holzkisten / Export wooden boxes
Gesamtvolumen / Total Volume 2.5 m³
Gesamtgewicht / Total Weight 450 kg