Guidelines On Interface Design of EI Installation - December 2022
Guidelines On Interface Design of EI Installation - December 2022
Guidelines on
Interface Design of
Electronic Interlocking Installation
CAMTECH/S&T/2022-23/ID-EI/ 1.0
December 2022
End Users : Signal Engineers of Indian Railways
Indian Railways
Centre for Advanced Maintenance Technology Maharajpur,
Gwalior (M P) 474005
i
ii
Guidelines on
Interface Design of
Electronic Interlocking Installation
CAMTECH/S&T/2022-23/ID-EI/ 1.0
December 2022
End Users : Signal Engineers of Indian Railways
Foreword
The relay based Signal Interlocking installations use Electro-magnetic relays which
require complex wiring, interconnections, hundreds of sheets of wiring diagrams
and occupy a large space for installation. These systems pose some drawbacks due
to the tremendous growth in freight and passenger traffic in Indian Railways, such
as long duration traffic blocks during commissioning and alterations for yard
remodeling works. To overcome the limitations of relay based interlocking
systems, microprocessor based Electronic Interlocking (EI) systems have been
introduced. They are more reliable, with less number of relays, less power
consumption and ease of installation and maintenance. Although the interlocking
functions are catered through application logic (software), some relays and external
equipments are still required to be interfaced with EI system. The Interface Design
is a very important stage which involves interfacing of various signalling functions
and associated equipments with the EI system for their proper functioning.
CAMTECH has prepared this handbook which explains the concept of Interface
Design of Electronic Interlocking and provides information on preparation and
documentation for the same during pre-commissioning stage.
I hope that this handbook will be useful for Signal Engineers of Indian Railways
concerned with EI installation to get familiar with the basic concepts of Interface
Design and help them in implementing the same in their respective installations. I
wish them all the success.
Preface
In Indian Railways, Electronic Interlocking (EI) installations are progressively
being commissioned replacing the existing relay based Signal Interlocking
installations. Unlike PI/RRI the interlocking among various signalling gears like
signals, points, track circuits etc. is achieved through software. However some
relays and other equipments are still required for interfacing with the EI for
detection and control of various field functions. During the planning stage of EI
installation, assessment of Input & Output bits, number of Relays, Relay Racks and
Cable Termination (CT) Racks, Number of Sub Racks/ Housings, System
Configuration and Communication arrangement, Interconnection of various racks
and interlocking equipment etc. has to be done.
This handbook covers basic concepts of Interface Design, procedure for
preparation of bit chart, assessment of relays, relay racks, subracks/housings for
Electronic Interlocking installation and their documentation with reference to
already commissioned stations.
We are sincerely thankful to S&T Directorate RDSO, IRISET Secunderabad, M/s
Siemens Rail Automation Pvt. Ltd., Bangalore and M/s TVM Signalling &
Transportation Systems Pvt. Ltd. (KYOSAN), Bangalore, who have provided
valuable inputs for preparing this handbook. Since technological upgradation and
learning is a continuous process, you may feel the need for some
addition/modification in this handbook. If so, please give your comments on email
address [email protected] or write to us at Indian Railways Centre for
Advanced Maintenance Technology, In front of Adityaz Hotel, Airport Road, Near
DD Nagar, Maharajpur, Gwalior (M.P.) 474005.
CAMTECH Gwalior Avadhesh Kumar Yadav
Director (S&T)
vii
viii
Table of Contents
Section I 1
Electronic Interlocking Interface Design 1
1.1 Introduction 1
1.2 Some important terms related to Interface Design 3
1.3 Objective of Interface design 8
1.4 Inputs required for preparation of Interface Design 9
1.5 Stages involved in interface design 10
1.6 Input & Output modules of different make EIs 11
1.7 Inputs/Output bits & Relays for various outdoor signalling gears 18
1.8 RDSO Report on Standardization of Typical Circuits for EI 20
1.9 Interface Design Documentation 21
Section II 27
Interface Design for 27
Siemens WESTRACE VLM6 EI 27
2.1 Introduction 27
2.2 Details of Signalling assets 27
2.3 Assessment of Vital Input /Output bits & Relays 29
2.4 Assessment of Non-Vital Input/Output bits 32
2.5 Calculation of Vital Input & Output Modules 35
2.6 Assessment of Housings for accommodation of Vital Input & Output Modules 35
2.7 Preparation of Bit Chart 36
2.8 Calculation of Non-Vital Input & Output Modules 39
2.9 Calculation of Relay Racks 41
Section III 43
Interface Design for 43
Siemens WESTRACE Mark II EI 43
3.1 Introduction 43
3.2 Details of Signalling Assets 43
ix
Where “XX” is the serial number of the concerned amendment/revision (starting from 01
onwards).
Disclaimer
It is clarified that the information given in this handbook does not
supersede any existing provisions laid down in the Signal Engineering
Manual, Railway Board and RDSO publications. This document is not
statuary and instructions given are for the purpose of guidance only.
If at any point contradiction is observed, then Signal Engineering
Manual, Telecom Engineering Manual, Railway Board/RDSO
guidelines may be referred or prevalent Zonal Railways instructions
may be followed.
Our Objective
To upgrade Maintenance Technologies and Methodologies and
achieve improvement in Productivity and Performance of all Railway
assets and manpower which inter-alia would cover Reliability,
Availability and Utilisation.
If you have any suggestion & any specific comments, please write to us:
Contact person : Director (Signal & Telecommunication)
Postal Address : Centre for Advanced Maintenance Technology, Opposite
Hotel Adityaz, Near DD Nagar, Maharajpur, Gwalior
(M.P.) Pin Code – 474 005
CAMTECH Publications
CAMTECH is continuing its efforts in the documentation and up-gradation of information on
maintenance practices of Signalling & Telecom assets. Over the years a large number of
publications on Signalling & Telecom subjects have been prepared in the form of handbooks,
pocket books, pamphlets and video films. These publications have been uploaded on the internet
as well as railnet. For viewing/downloading these publications
On Internet:
Visit www.indianrailways.gov.in
Go to About Indian Railways → Railway Board Directorates →Efficiency &
Research→CAMTECH, Gwalior → Other Important links → Publications for download →S&T
Engineering (Yearwise/ Subjectwise).
On Railnet:
Visit Railway Board website at 10.1.2.21
Go to Railway Board Directorates → →Efficiency & Research→CAMTECH, Gwalior → Other
Important links → Publications for download →S&T Engineering (Yearwise/ Subjectwise).
https://indianrailways.gov.in/railwayboard/view_section.jsp?lang=0&id=0,1,304,366,538,2713,2
718,2722,2731
A limited number of publications in hard copy are also available in CAMTECH library which
can be got issued by deputing staff with official letter from controllong officer. The letter should
be addressed to Director (S&T), CAMTECH, Gwalior.
For any further information regarding publications please contact:
List of Figures
Figure 1 : Block Diagram of Electronic Interlocking - Centralized Architecture ........................................ 2
Figure 2 : Block Diagram of Electronic Interlocking - Distributed Architecture ........................................ 3
Figure 3 : Block diagram of Input & Output Interface of EI ........................................................................ 5
Figure 4 : Parallel Input Module (PIM50) Input Circuit ........................................................................... 12
Figure 5 : Relay Output Module (ROM) Output Circuit ............................................................................ 12
Figure 6 : A typical Input Board Circuit of Kyosan K5BMC EI ................................................................ 13
Figure 7 : A typical Output Board Circuit of Kyosan K5BMC EI .............................................................. 14
Figure 8 : Typical System Configuration of an EI Installation .................................................................. 24
Figure 9: Signalling Plan of SINGRA Station (North East Frontier Railway) ........................................... 28
Figure 10 : Indications of Point 111/112 on CCIP..................................................................................... 34
Figure 11 : Indications of Point 101/102 on CCIP..................................................................................... 34
Figure 12 : Arrangement of Modules in SNGA WESTRACE VLM6 Housings .......................................... 36
Figure 13 : Front Panel Indications of DIP/DOP Card ............................................................................. 39
Figure 14 : Front view of WESTRONICS S2 Panel Processor .................................................................. 39
Figure 15 : Signalling Plan of HAYAGHAT Station (East Central Railway) ............................................. 44
Figure 16 : Arrangement of Modules in HYT WESTRACE Mark II Housings ........................................... 49
xiv
List of Tables
Table 1 : Comparative of Executive & Application Software ...................................................................... 8
Table 2 : Comparative of different make EIs .............................................................................................. 17
Table 3 : I/O Bits & Relays for Signalling Gears ....................................................................................... 18
Table 4 : Vital Input/Output bits & Relays of SNGA station with WESTRACE VLM6 EI ...................... 29
Table 5 : Additional Relays required for SNGA station ............................................................................. 32
Table 6 : Non-Vital Input/Output bits for SNGA station with WESTRACE VLM6 EI............................. 32
Table 7 : Summary of Input/Output bits & Relays (SNGA) ....................................................................... 34
Table 8 : Bit Chart for SNGA WESTRACE VLM6 Housing 1 ................................................................. 37
Table 9 : Bit Chart for SNGA WESTRACE VLM6 Housing 2 ................................................................. 37
Table 10 : Bit Chart for SNGA WESTRACE VLM6 Housing 3 ............................................................... 38
Table 11: Vital Input/Output bits & Relays of HYT station with WESTRACE Mark II EI ...................... 45
Table 12 : Additional Relays required for HYT station .............................................................................. 47
Table 13 : Summary of Input/Output bits & Relays ................................................................................... 48
Table 14 : Bit Chart for HYT WESTRACE Mark II Housing 1................................................................. 50
Table 15 : Bit Chart for HYT WESTRACE Mark II Housing 2................................................................. 50
xv
Abbreviations
ABS Automatic Block Signalling
BPAC Block Proving by Axle Counter
CCIP Control Cum Indication Panel
CD Compact Disc
CHLR Crank Handle Lock Relay
CHPR Crank Handle Proving Relay
CIU Central Interlocking Unit
CPU Central Processing Unit
CT Cable Termination
DC Direct Current
DIP Digital Input
DOP Digital Output
ECR Lamp Proving Relay
EI Electronic Interlocking
EKT Electric Key Transmitter
EPROM Erasable Programmable Read Only Memory
FCOR False Feed Cut Off Relay
FTB Fiber termination Box
IB Intermediate Block
I/O Input/Output
IPS Integrated Power Supply
LED Light Emitting Diode
LX Level Crossing
LXPR Interlocked Level Crossing Gate Proving Relay
MT Maintainer‟s Terminal
NCDM Network Communication & Diagnostic Module
OC Object Controller
OCM Object Controller Module
OEM Original Equipment Manufacturer
OFC Optical Fiber Communication
OPC Output Power Control
PCB Printed Circuit Board
PI Panel Interlocking
PIM Parallel Input Module
PM Processor Module
PP Panel Processor
PSU Power Supply Unit
RAM Random Access Memory
RI Relay Input
RO Relay Output
ROM Read Only memory/ Relay Output Module
RRI Route Relay Interlocking
SIP Signal Interlocking Plan
xvi
SM Station Manager
SYSON System On
TPR Track Proving Relay
VDU Visual Display Unit
VLC Vital Interlocking Card
VLM Vital Logic Module
VPIM (i) Vital Parallel Input Module
VR Vital Relay
VROM Vital Relay Output Module
WNCDM WESTRACE Network Communication & Diagnostic Module
WFM Wayside Function Module
Note: Relay nomenclatures have not been covered in the above list.
xvii
CAMTECH/S&T/2022-23/ID-EI/1.0 1
Section I
Electronic Interlocking Interface Design
1.1 Introduction
Electronic Interlocking (EI) system is a microprocessor based interlocking equipment to read the
inputs from the signalling gears in the yard and process commands from the operational console
in a fail-safe manner as per selection table and generate required output for controlling field
gears. This system is the alternative to the conventional Relay Interlocking system (PI & RRI).
Unlike PI/RRI the interlocking among various signalling gears like signals, points, track circuits
etc. is achieved through application software. Hence significant numbers of relays are reduced
and the human interference with interlocking functions is avoided. However in the Indian
Railways, relays are continued to be used with associated field equipment for interfacing the
feedback (through input) and control (through output) of various field functions with the EI as
given below.
The contacts of following relays are taken as inputs from field:
Track Proving Relays (TPRs),
Signal Lamp Proving Relays (ECRs),
Point position proving Relays (NWKR/RWKR) etc.
The following relays are picked up through the output voltage given by EI which in turn drive
the field gears through their contacts:
Signal Control Relays (HRs, DRs, HHRs)
Point Control Relays (WNR, WRR)
Crank Handle Relay (CHLR) etc.
The EI system also requires button inputs from the operator‟s panel. It also gives output voltage
for indications on CCIP.
The software associated with EI system are of two types (i) Executive Software or System
Software governing system working & (ii) Application Software designed and loaded as per the
signal interlocking requirements. The Executive software pertains to „Principles of Interlocking‟
and is universal for all stations. The application software pertains to „Table of Control‟ of yard
and it is station specific.
In other words, Interface design consists of organizing EI Hardware, allocation of field Inputs &
Outputs, floor plan to accommodate other peripherals like Relay Rack, Datalogger equipment
and cable termination rack etc. and associated physical wiring. Interface design also consists of
communication network design with associated configuration to connect peripherals like
Maintenance/Diagnostic Terminal , VDU and other Processor and Object Controller if any
Block line clear position are considered as Vital input functions. Panel button/ knob/ key
controls or VDU commands are considered as Non-vital input functions.
(ii) Output Functions
Signal controls (HRs, DRs, UHR/UGR), Point controls (WNRs/ WRRs), Slot controls (YRs/
CHYRs/LXYRs/KLYRs) are considered as Vital output functions. All panel/ VDU indications,
alarms, counters are considered as Non-vital output functions.
and EPROM – Erasable Programmable read only Memory. There will be separate EPROM for
Application software and Executive software. The CPU receives commands from Panel /VDU
and processes them as per the Application data stored in the EPROMs. It drives output field
functions if the interlocking conditions are satisfied. It also drives requisite indications on the
panel/ VDU.
I. VDU
VDU, Visual Display Unit is used as operator console to digitally communicate between
operator and EI hardware. VDU consists of a monitor, standard PC, network switches for
connectivity. In general VDU is arranged with a dual redundancy so as either one of the VDU
will be able to communicate to EI hardware. The operational commands (inputs), the
indications (outputs) on the VDU are mapped and configured as I/O in the network session
defined in the application software. These I/Os doesn‟t require any physical wiring or
connectivity. In the Interface design VDU connectivity in general is shown in the schematic
architectural diagram.
Note: A control terminal with VDU in lieu of or in addition to conventional CCIP is provided as
per requirement.
(x) RAM
Random Access Memory (Used for vital data processing and event/error logs).
(xi) EPROM
Erasable Programmable Read Only Memory (Used for storing Executive and Application
software).
(xii) Software
The software of the system has two layers:
Executive Software or System Software
Application Software
Application Software
The application software is programmed in Data EPROMs. It contains the logic that defines how
the inputs and outputs for a particular station are related. It pertains to „Table of Control‟ of yard.
This shall be station specific.
The Executive Software and Application Software are programmed into Read Only Memories
(ROMs) by the manufacturer. Both the ROMs shall be separated and isolated from each other. A
comparative study is shown in the following table:
At the time of yard alteration work, Data EPROMs are to be replaced with new Data EPROMs
programmed with software pertaining to revised table of control as per altered yard data.
Compiler software is used for yard alteration.
Why required?
The significance of the items listed above is given below:
Communication arrangements
This helps in preparation of System Configuration of EI. The system configuration is designed
specific to the station depending upon the requirements.
and input/output with various apparatus, etc.). In addition, it also processes interlocking
connections by reading station-based data and driver data for inputs and outputs of each card
from IC cards. The Interlocking Logic Module of K5BMC EI uses two identical interlocking
logic modules (LK7-C) for redundancy.
1.7 Inputs/Output bits & Relays for various outdoor signalling gears
Inputs/output bits & relays for various outdoor signalling gears are tabulated as below:
Note:
In addition to above, some other relays are also required for additional interlocking
equipments (if provided) to be interfaced with EI. For example, relays associated with Block
instrument, BPAC, Timer, SM‟s Key, Crank Handle, EKT, Point operation, IPS Health
Monitoring, Relay Room Door Lock, Repeater relays (for point, signal, track circuit), System
related Input & Output etc.
The quantity of various relays is calculated as above.
Number of relay racks required is calculated as below:
Total no. of Relay Racks = (Total no. of Relays + 15% Spare) divided by (Capacity of
Standard relay Rack)
After finding out final quantity of Vital and Non-vital I/O bits, quantity of various
Input/Output modules is derived as given below:
(i) Total No. of Vital Output Modules = (Total no. of Vital Outputs + 15% spare) divided
by (Capacity of Vital Output Module)
(ii) Total No. of Vital Input Modules = (Total no. of Vital Inputs + 15% spare) divided by
(Capacity of Vital Input Module)
(iii) Total No. of Non-Vital Output Modules = (Total no. of Non-Vital Outputs + 15%
spare) divided by (Capacity of Non-Vital Output Module)
(iv) Total No. of Non-Vital Input Modules = (Total no. of Non-Vital Inputs + 15% spare)
divided by (Capacity of Non-Vital Input Module)
The requirement of Vital & Non-Vital Input/Output Modules will depend upon the make of EI.
In case of VDU, Non-Vital Inputs & Outputs cards are not required as requirements of
indications and controls of VDU are catered internally through direct communication with EI
system. The digital signals between VDU and EI system are configured to the processor module
through network sessions or network modules (like NCDM in WESTRACE VLM6). VDU or
Operator PC can communicate directly with EI System but for communication between CCIP
and EI System an interface with separate set of cards or hardware called Panel Processor is
required. In case of CCIP, the communication between EI system and CCIP is in the form of
analog signals. Hence for converting these signals into digital signals, a Panel Processor is
required. When CCIP is not used, there is no need to calculate Non-Vital Inputs & Outputs.
As per RDSO Report on Standardization of Typical Circuits for EI Ver.2.0 dated 29.03.2022, in
all future installations, EI shall be provided with Dual VDU and therefore no provision in
standardized logic has been kept for CCIP working.
The typical EI circuits under this report are available at the following link:
http://10.100.2.19/signal/policy/uniform_circuit_diagram.htm
(A hyperlink is also provided in Annexure I)
The salient feature of this report are given below which may be useful in the Interface design of
all future EI installations.
(i) All EI shall be provided with Dual VDU and therefore no provision in standardized logic
has been kept for CCIP working.
(ii) All EI shall be having route setting feature, but point chain group feature is not considered
essential as maximum of 2 to 3 points may be required to be operated at any time.
(iii) Currently recommended standardized logics are proposed to be used for way side station
with maximum of 100 routes. This will cover more than 95% of stations on Indian
railways.
(iv) These stations of less than 100 routes shall not be having Sectional route release feature.
(v) All operation through VDU shall be by drop down menu.
(vi) A drop down menu can generate multiple command bits which is equivalent to press of
multiple buttons simultaneously.
(vii) For emergency operations, it is recommended that an additional physical key shall be
provided which shall be configured as redundant Vital input to Electronic Interlocking like
vital field inputs.
(viii) For each independent route with each independent overlap, there shall be one controlling
relay (LR). Thus LR shall be equal to number of routes in Route control table. This will
not require provision of swinging locking/conditional locking. Direct locking of all
conflicting movement shall be provided in LR circuit.
(ix) Logic for FCOR relay/bit is not prepared as there are no such directives in codes and
manuals and there are differences of opinion regarding its requirement among the OEM.
Hence FCOR logic is not recommended here.
(x) Circuits for automatic signalling, IB signalling, operation of Interlock LC gates, axle
counter resetting are not included as they are external to EI. These shall be catered in next
Phase.
(xi) Siding control through Ground frame are also excluded as now most of them are
converted to motor operation.
(xii) The recommended circuits are valid only for EI installation with Metal to Carbon interface
relays. However, in case of Proved type Signalling relays (Metal to Metal), the
requirement of circuit design is different where opening of front contact of relay is proved
by closing of back contact. Hence, the present recommended circuits shall not be used for
EI installation with Metal to Metal interface relays.
details, Fuse details, Relay Contact Analysis etc. Generally following details are covered in
Interface Design documentation:
(a) Index
The index contains list of all the drawings with description, drawing number and sheet number
on which it is available.
(b) Symbols
The various symbols used in the interface design along with description are listed under this
head.
(c) Material Reference List
This list contains details of material (like EI modules, Racks & Fittings, Computer accessories,
Connectors & Accessories etc.) used in the installation including description, material part
number or type, manufacturer and quantity.
(d) Approved Floor Plan
This contains the details of various rooms such as EI Room, SM Room Axle Counter Room, IPS
Room as applicable. All the details like spacing between various racks/equipments and spacing
from the wall, location of windows and doors, location of building with respect to track etc. are
marked in the floor plan.
The VDU is kept in SM Room as an operator console. In Relay Room the EI hardware is
installed along with other equipments such as Diagnostic module (Maintainer Terminal) and
Data logger. In the EI system shown above there are two processor modules in hot standby
mode. The Processor communicates with the diagnostic module, data logger and VDU through
manageable Ethernet switch connections. Relay Room to SM Room communication is done
through Optic Fibre Communucation cable which is connected through Fibre Termination Box
(FTB).
In the following sections assessment of Vital and Non-Vital Inputs /Outputs, Relays, Relay
Racks and Module requirements of already commissioned stations with EI are explained along
with hyperlink to detailed Interface circuits of concerned vendor.
Section II
Interface Design for
Siemens WESTRACE VLM6 EI
2.1 Introduction
In this section the assessment of Vital & Non-Vital Input/Output bits, Relays, Relay Racks, Vital
Input/Output modules and housings for SINGRA station of North East Frontier Railway
commissioned with Siemens WESTRACE VLM6 EI is explained. In this station both VDU and
CCIP are provided for operation. The mini Signalling plan layout given in Fig. is for the purpose
of understanding which is based on approved SIP.
A. Signals
UD UP Distant
S2 DN Advance Starter -2 Aspect
S3 UP Home -3 Aspect with Route Indicator
C3 UP Calling On
SH7 UP Shunt (to L1 & L2)
S35 UP Line 2 Starter – 2 Aspect
SH35 UP Line 2 Shunt (to S47)
S37 UP Line 1 Starter – 2Aspect
SH37 UP Line 1 Shunt (to S47)
S12 DN Line 2 Starter -2 Aspect
SH12 DN Shunt (to S2)
S14 DN Line 1 Starter – 2 Aspect
SH14 DN Line 1 Shunt (to S2)
S47 UP Advance Starter – 2 Aspect
S46 DN Home – 3 Aspect with Route Indicator
C46 DN Calling On
SH44 DN Shunt (to L1 & L2)
DD DN Distant
B
C 111T
C3T 3T 101T 0A1T 0A2T 47AT 46T C46T
2AT
101 111
B
A
S2 SH44 C DD
S12 SH12 SH37 S37 S46 C46
102
0C1T 0C2T 112
102T
112T
S14 SH14
Note: Block Proving by Axle Counter (BPAC) in SNGA –DPRA and SNGA-BOKO sections with Single Line tokenless Block
instruments
B. Points
C. Track Circuits
C3T, 3T, 2AT, 101T, 0A1T, 0A2T, 111T, 47AT, 46T, C46T, 102T, 0C1T, 0C2T, 112T
* As per latest RDSO Report on Standardization Typical Circuits for EI Ver.2.0 dated
29.03.2022:
In case of Independent Shunt Signal, a common GECR is to be picked up means that Pilot Lamp
along with „OFF‟ or „ON‟ is litting at site. However two Inputs ( ‘ON’ ECR & ‘OFF’ ECR) are
to be considered for Interface.
For Dependent Shunt Signal, only one Input (‘OFF’ ECR) is to be considered.
Table 6 : Non-Vital Input/Output bits for SNGA station with WESTRACE VLM6 EI
Capacity of Vital Input Module (VPIM) in WESTRACE VLM6 – 12 Vital Inputs per module
No. of VROMs required = (Total no. of Vital Output bits + 15% spare bits) divided by (capacity
of one VROM)
= (38+8) /8
= 46/8
= 5.75
~ 6
No. of VPIMs required = (Total no. of Vital Input bits + 15% spare bits) divided by (capacity of
one VPIM)
= 75 /12
= 6.25
~ 7
2.6 Assessment of Housings for accommodation of Vital Input & Output Modules
Various modules are installed in one or more WESTRACE housings as per the following
guidelines:
(1) There are four housings in a WESTRACE rack.
(2) Each housing has 16 slots.
(3) Numbering of slots is from Right to Left.
(4) Numbering of housings is from Top to Bottom.
(5) First slot in first housing should be blank. A Blanker card is provided for continuity.
(6) There will be Output Power Control (OPC) card in second slot, Vital Logic Module
(VLM) in third slot and Network Communication & Diagnostic Module (NCDM) in
fourth slot. VLM and OPC together form VLM6.
(7) Slot 5 to 15 in the first housing can be Vital Parallel Input Module (VPIM) or Vital Relay
Output Module (VROM).
(8) Each VPIM and VROM occupies two slots.
(9) There will be no NCDM, VLM or OPC in second, third and fourth housings.
(10) Each housing has a slot reserved for PSU card.
(11) Normally one PSU card caters power supply requirements for two housings. However for
better system availability, one PSU card per housing is desirable.
Based on the above guidelines the arrangement of various modules in WESTRACE VLM6
housing can be as given below:
Slot 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
number
Blanker Card
Blanker Card
NCDM Card
Housing 1
VLM6 Card
OPC Card
PSU Card
Blanker Card
Blanker Card
Blanker Card
Housing 2
Blanker Card
Blanker Card
Blanker Card
Blanker Card
Blanker Card
Blanker Card
Blanker Card
Blanker Card
Blanker Card
Blanker Card
Housing 3
PSU Card
VPIM VROM
7 6
Blanker Card
NCDM Card
VLM6 Card
Bit 3 SH37_HR DD_HHR DNSAR SH12_HR UD_HHR
OPC Card
PSU Card
Blanker Card
Blanker Card
WESTRACE HOUSING 3
VPIM 7 VROM 6
Slot No. 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Bit 1 SNGA_BOKO_VPR UPTAR
Bit 2 SNGA_BOKO_PPR UPASR_TPR
Blanker Card
Blanker Card
Blanker Card
Blanker Card
Blanker Card
Blanker Card
Blanker Card
Blanker Card
Blanker Card
Blanker Card
PSU Card
For details please refer SINGRA WESTRACE Interface Circuits through Annexure I.
DIP Card
DIP stands for Digital Input Card. Each DIP card caters for 32 inputs and numbers of cards are
provided depending upon the requirement. A DIP Card takes input from panel and connects to
the scanner which in turn sends it to WESTRACE. Thus the output bit of any button pressed on
the operating panel will go through DIP Card. Two indicators ACK A and ACK B are provided
on the front plate. Flashing Red shows healthy communication with the scanner. 32 LEDs (Red)
are provided on the DIP card in which each LED when lit indicates receiving bit from the panel.
DOP Card
DOP stands for Digital Output Card. Each DOP card caters for 32 outputs and numbers of cards
are provided depending upon the requirement. Indication received from WESTRACE in the
scanner is given to DOP card which in turn delivers the 24 V DC output to the LEDs in the
panel. ACK A and ACK B LED indications flashing indicate healthy communication with the
scanners. 32 LEDs (Red) are also provided in which each LED when lit indicates received bits
from WESTRACE.
Capacity of Digital Input (DIP) Card in WESTRACE VLM6 – 32 Non-Vital Inputs per card
Capacity of Digital Output (DOP) Card in WESTRACE VLM6 – 32 Non-Vital Outputs per card
No. of DIP Cards required = (Total no. of Non-Vital Input bits + 15% spare bits) divided by
(capacity of one DIP Card)
= (40+6) /32
= 46/32
= 1.43
~ 2
No. of DOP Cards required = (Total no. of Non-Vital Output bits + 15% spare bits) divided by
(capacity of one DOP Card)
= (117+18) /32
= 46/32
= 4.21
~ 5
Bit chart for Non-Vital Inputs & Outputs can be prepared similar to given in para 2.7.
No. of Relay racks required = (Total no. of Relays + 15% spare) divided by (Capacity of one
Relay Rack)
= (101+16)/90
= 117/90
= 1.3
~ 2
The detailed Interface Circuits (as built) may be seen through the link provided in Annexure I.
Section III
Interface Design for
Siemens WESTRACE Mark II EI
3.1 Introduction
In this section the assessment of Vital Input/Output bits, Relays, Relay Racks, Vital Input/Output
modules and housings for HAYAGHAT station of East Central Railway commissioned with
Siemens WESTRACE Mark II EI are explained. Non-Vital Inputs/Outputs are not considered as
only VDU is used as control panel (no CCIP is used) for which the bits are catered internally in
Mark II system. The mini Signalling plan layout is given for the purpose of understanding which
is based on approved SIP.
E. Signals
DD DN Distant
S1 DN Home -3 Aspect
S2 UP Advance Starter -2 Aspect
C3 DN Calling On
S4 UP Line 1 Starter -2 Aspect
S5 DN Line 1 Starter – 2 Aspect
S6 UP Line 2 Starter – 2 Aspect
S7 DN Line 2 Starter – 2Aspect
C10 UP Calling On
S11 DN Advance Starter – 2 Aspect
S12 UP Home – 3 Aspect
UD UP Distant
F. Points
B
B A1T A2T
A10T 12T 22T AT 1T A3T
A11T
22a 21a
B
A
S11 S5 B DD
S6 S1 C3
22b
B1T BT 21b
21bT
22bT
S7
L-Xing No.
11 B
NOTE
Proving of clearance of berthing portion of Line no. 2 through HASSDAC in addition to
berthing track circuit no. B1T & BT.
UFSBI Block Panel with HASSDAC single line type working between HYT-RBZ stations.
Single line block working with Diado type tokenless Block instrument between HYT-
TLWA stations.
Sliding boom barrier provided in addition to existing Lifting Barrier at LC Gate No. 11B.
Interface Design of Electronic Interlocking Installation December 2022
CAMTECH/S&T/2022-23/ID-EI/1.0 45
G. Track Circuits
A10T, 12T, A11T, 22T, A1T, AT, 21T, A2T, 1T, A3T, 22bT, B1T, BT, 21bT
Capacity of Vital Input Module (PIM) in WESTRACE Mark II – 12 Vital Inputs per module
No. of ROMs required = (Total no. of Vital Output bits + 15% spare bits) divided by (capacity of
one ROM)
= (31+5) /8
= 36/8
= 4.5
~ 5
No. of PIMs required = (Total no. of Vital Input bits + 15% spare bits) divided by (capacity of
one PIM)
= 76 /12
= 6.34
~ 7
3.5 Assessment of Housings for accommodation of Vital Input & Output Modules
WESTRACE Mark II housings are available in following configurations:
5-slot (a half 19" width) housing that holds 5 modules maximum - Processor Module, I/O
Modules & Hot standby Modules (if provided)
10-slot (a full 19" width) housing that holds 10 modules maximum - Processor Module (PM),
I/O Modules & Hot standby Modules (if provided)
A PM is normally placed in slot 1 of housing 1.
Hot-standby PMs are normally placed in slots 1 and 2 of housing 1 or slot 1 in each of two co-
located housings.
The other modules are Parallel Input Module (PIM) and Relay Output Module (ROM). Both
PIM and ROM can be duplicated for Hot Standby operation.
The arrangement of various modules in a 10 slot housing based on the assessment of Vital Input
and Output modules is given below:
Slot
10 9 8 7 6 5 4 3 2 1
No.
Housing 1
SPARE
SPARE
ROM ROM ROM ROM ROM ROM PM PM
7 6 5 4 2 1 2 1
Housing 2
SPARE
SPARE
SPARE
Thus 2 PMs in Hot Standby mode, 5 ROMs and 7 PIMs are accommodated in 2 Nos. 10 slot
housings.
No. of Relay racks required = (Total no. of Relays + 15% spare) divided by (Capacity of one
Relay Rack)
= (146+22)/90
= 168/90
= 1.87
~ 2
The detailed Interface Circuits (as built) may be seen through the link provided in Annexure I.
ANNEXURE I
Interface Circuits documentation of stations
commissioned with Electronic Interlocking