REVISION SHEET
Table of Contents
1. GENERAL..................................................................................................................................10
OIL GAS REFINERY PLANT
2 MATERIALS..............................................................................................................................11
3.1 General................................................................................................................................12
5.5.1 Support.........................................................................................................................34
5.6.1 Kz ..............................................................................................................................36
5.6.2 Lz.................................................................................................................................37
1. GENERAL
1.1 Project Information
The purpose of this calculation note is to check the adequacy of Steel Pipe Rack
structure to sustain the loads that may occur during the construction & operation..
Definition of the checking procedure given hereafter includes the assumptions, the
method of analysis and the data to be used.
(1) Language
English shall be used.
(2) Units
SI unit shall be used. Nominal pipe size may be in inches.
2 MATERIALS
3.1 General
The following loads and forces shall be considered in structural and foundation design of
shelter:
p ip e p ip e + o il p ip e + w a te r
kN kN kN
Ele v + 9.00 D (in c h )
P1 10 3.60 5.20 6.10
P2 10 3.60 5.20 6.10
P3 14 4.70 5.50 6.70
P4 16 7.60 8.90 10.30
Ele v + 7.00
P5 16 8.20 10.80 11.70
P6 12 4.20 6.60 7.40
P7 12 4.20 6.60 7.40
P8 10 3.60 5.20 6.10
P9 16 5.40 11.00 14.50
P10 16 5.40 11.00 14.50
Wind Load calculation refers to SNI-1727-2013, Velocity Pressure above grade is shown in
below :
qz = 0.613 x Kz x Kzt x Kd x V2
Where :
qz = Velocity pressure evaluated at height z above ground
Kz = Velocity pressure exposure coefficient
Kzt = Topographic factor = 1
Kd = Wind directional factor (Table 6-4) = 0.7
V = Basic Wind Speed = 144km/hr (40 m/sec)
I = Importance factor = 1 (Category II)
Design wind pressure for main wind force resisting system of buildings shall be determined by
the following equation :
p = qz x G x Cp
Where :
p = Wind Pressure (N/m2)
G = Gust effect factor = 0.85
Cf = Pressure coefficient (Table 6-21 ASCE 7-05, force coefficient Cf for other structure category)
WF flange side , Flat : 1.0
WF web side : 1.8
Pipe (Round) : 0.7
3.1.8.4 Fa & Fv
OIL GAS REFINERY PLANT
For strength design foundations, the following load combinations shall be used.
NO LOADING NAME
1 SEISMIC STRUCTURE X-DIR (+SX)
2 SEISMIC STRUCTURE X-DIR (-SX)
3 SEISMIC STRUCTURE Z-DIR (+SZ)
4 SEISMIC STRUCTURE Z-DIR (-SZ)
5 DEAD LOAD (DL)
6 LIVE LOAD (LL)
7 PIPE EMPTY (PE)
8 PIPE OPERATING (PO)
9 PIPE TEST (PT)
10 EQUIPMENT EMPTY (EE)
11 EQUIPMENT OPERATING (EO)
12 EQUIPMENT TEST (ET)
13 FRICTION (TF)
14 ANCHOR (A)
15 WIND +X (+WX)
16 WIND -X (-WX)
17 WIND +Z (+WZ)
18 WIND -Z (-WZ)
OIL GAS REFINERY PLANT
Load Combination for design and details of steel structures shall be in accordance
with AISC WSD & ASCE 7-16 as follows
D+L
101 DL + PO + MO+ F+A + LL
D + 0.6W
201 DL + PO + MO+ F+A + 0.6 Wx
202 DL + PO + MO+ F+A - 0.6 Wx
201 DL + PO + MO+ F+A + 0.6 Wz
201 DL + PO + MO+ F+A - 0.6 Wz
D + 0.75(0.6W) + 0.75 L
301 DL + PO + MO+ F+A + 0.45 Wx + 0.75 LL
302 DL + PO + MO+ F+A - 0.45 Wx + 0.75 LL
303 DL + PO + MO+ F+A + 0.45 Wz + 0.75 LL
304 DL + PO + MO+ F+A - 0.45 Wz + 0.75 LL
0.6 D + 0.6W
401 0.6(DL + PO + MO+ F+ A) + 0.6 Wx
402 0.6(DL + PO + MO+ F+ A) - 0.6 Wx
403 0.6(DL + PO + MO+ F+ A) + 0.6 Wz
404 0.6(DL + PO + MO+ F+ A) - 0.6 Wz
D + 0.7 Ev + 0.7 Eh
501 1.094(DL + PO + MO+ F+A) + 0.7 Sx + 0.21 Sz
502 1.094(DL + PO + MO+ F+A) + 0.7 Sx - 0.21 Sz
503 1.094(DL + PO + MO+ F+A) - 0.7 Sx + 0.21 Sz
504 1.094(DL + PO + MO+ F+A) - 0.7 Sx - 0.21 Sz
505 1.094(DL + PO + MO+ F+A) + 0.7 Sz + 0.21 Sx
506 1.094(DL + PO + MO+ F+A) + 0.7 Sz - 0.21 Sx
507 1.094(DL + PO + MO+ F+A) - 0.7 Sz + 0.21 Sx
508 1.094(DL + PO + MO+ F+A) - 0.7 Sz - 0.21 Sx
The design and details of steel structures shall be in accordance with the AISC “Manual of
Steel Construction ASD, Thirteenth Edition”,
High Strength bolted connection shall be designed as bearing-type connections, with threads
included. The allowable loads shall be based on all bolts having threads in the shear plane.
Allowable vertical displacement shall not exceed L/240 (L = beam or girder support length).
4.4.2 Horizontal Drift
Allowable horizontal displacement shall not exceed H/100 (H = the height of structure).
Isometric View
OIL GAS REFINERY PLANT
Side View
Front View
OIL GAS REFINERY PLANT
Member Occupation
Properties Material
Group
C1 Column H200X200x5x8 steel
OIL GAS REFINERY PLANT
Member Occupation
Properties Material
Group
T1 Transversal Beam Elev +7.00 WF150X75 steel
T2 Transversal Beam Elev +9.00 WF200X100 steel
T3 Diaphragm Beam Elev +7.00 & +9.00 WF200X100 steel
L1 Longitudinal Beam Elev +7.00 & +9.00 WF200X100 steel
L2 Diaphragm Beam Elev +7.00 & +9.00 WF150X75 steel
L3 Longitudinal Beam Elev +7.00 WF200X100 steel
VB Bracing Vertical Double L80x80 steel
HB Horizontal Bracing Double L80x80 steel
5.5.1 Support
5.6.1 Kz
Kz = 0.5
OIL GAS REFINERY PLANT
Kz = 2.8
Kz = 1.8
5.6.2 Lz
OIL GAS REFINERY PLANT
5.7.8 Friction
OIL GAS REFINERY PLANT
Seismic Definition
OIL GAS REFINERY PLANT
Refer to picture maximum horizontal displacement occurred at the top of column (node 4)
which is 17 mm less than 9000/100 = 90 mm) thus the horizontal displacement is sufficient.
Displacement Allowable
Node L/C REMARKS
mm Deflection mm
18 503 140 90 NOT OK