EE4203 POWER SYSTEM 1 - Chapter 1 Basic of Power System 2023
EE4203 POWER SYSTEM 1 - Chapter 1 Basic of Power System 2023
Faculty of Engineering
CHAPTER 1
BASIC OF POWER SYSTEM
POWER SYSTEMS 1
A Simple Generator
The fundamental structure of a simple generator is shown in the diagram which consists of
lines of field produced by the main pole (N-S). The coil is rotated externally by prime mover
in the direction shown, an alternating e.m.f of one cycle is induced across the coil (terminals
1-4) when the coil completes one rotation.
Right-hand rule
POWER SYSTEMS 1
Single-phase System
In Brunei Darussalam, majority of the residential consumers employed a 3-phase
system rather than a single-phase system which is very rare.
e.m.f induced
Ê
t
0
Prime 2
mover
Eˆ
Synchronous generator In r.m.s, E 0o E 0o
2
Single-phase equivalent circuit:
IA RA jXs
100 Hz
VˆL sin t Iˆ sin t p1 t
VˆL Iˆ
cos
1500
VL I sin t sin t
ˆ ˆ 2 1000
1
Using: sin A sin B cos A B cos A B
500
2 0
Therefore:
VˆL Iˆ -500
p2 t cos 2t
2
Problems: The instantaneous power oscillates at 2f (double frequency) and this
will cause flickering in lamp, humming in fluorescent starter, vibration in motor &
transformer.
POWER SYSTEMS 1
Three-phase System
The three-phase voltage waveforms, i.e. the A phase, B phase and C phase, produce
from the synchronous generator are displaced by 120o with each other.
400
3-phase supply eA eB eC
200
0
Prime
mover -2 0 0
Synchronous generator -4 0 0
0 0 .0 1 0 .0 2 0 .0 3 0 .0 4
Armature Circuit
The armature winding of a three-phase synchronous generator can be connected in
either star (wye) or delta configuration. However, it is common to find the winding in
wye because the line-to-line voltage is higher for a given phase voltage.
Delta-connected Armature Wye-connected Armature
A A
B B
VBC VBC
C C
I L 3 I p EL E p EL 3 E p I L I p
POWER SYSTEMS 1
EAB
A’ Neutral current IN
N
ECA
EBN EBN 120
B’ o
C’
ICN IB
ECN ECN 240o IBN
Line B
Line current
IC EBC
Line C
Line current
POWER SYSTEMS 1
Three-phase voltages
400
-2 0 0
-4 0 0
0 0 .0 1 0 .0 2 0 .0 3 0 .0 4
If a conductor is not connected from the neutral point to the load, the system is called:
Phase Voltages,
From the diagram, the voltage across the
conductors w.r.t neutral is called the phase
voltage which are defined as: Wye/Star/Y-connected Generator
EAN , EBN and ECN
Line voltages,
The voltage across the line conductors is
called the line voltage which are defined as:
EAB , EBC and ECA
Where: EAB EAN EBN
EBC EBN ECN
ECA ECN EAN
Phase Currents,
By inspection from the diagram,
Line current = Phase current In general:
Phase sequence,
The phase sequence is the order in which the phasors representing the phase
voltages pass through a fixed point on the phasor diagram.
The phase sequence is,
rad/s
C ECN
Phase sequence
ZL
ECA
EAB IN
ECN N n
Vcn
EBN IBN B IB Vbn Ibn
ICN Icn
EBC IC ZL = RL+ jXL
C c
b
Assume the load is balanced, the neutral current,
IN IA IB IC 0
For a balanced 3-phase system, the circuit above can be modeled by its single-phase
equivalent circuit.
POWER SYSTEMS 1
N IN
n
POWER SYSTEMS 1
Example:
For the three-phase system of figure below. Assume the phase sequence is ABC.
(a)Construct a single-phase equivalent circuit of the three-phase system.
(b)Find the magnitude of per phase voltage at the terminal of the generator, EAN and draw its
three voltage phasors in part (b) with labelled EAN, EBN and ECN.
(c) Find the magnitude of the line voltage at the terminal of the generator, and draw the three
current phasors in (b).
(d) Find the magnitude of the per phase current, both phase and line and draw the three
current phasor on the phasor diagram.
(e) Verify that the phasor sum of the neutral current is equal to zero.
Given that,
Ep = 120 V
RL = 3
XL = 4
POWER SYSTEMS 1
Solution:
(a) Construct a single-phase equivalent circuit of the three-phase system.
A a
IAN IA
N n
(b) Find the magnitude of per phase voltage at the terminal of the generator, EAN and draw its
three voltage phasors, labelled EAN, EBN and ECN. ECN
rad/s
The magnitude of EAN = 120 V
Phase sequence
120o
CABCABCAB 120o E AN
120o 120 V
EAN 1200o V
EBN 120 120o V E BN Phasor diagram
ECN 120 120o V
POWER SYSTEMS 1
Solution:
(c) Find the magnitude of the line voltage at the terminal of the generator, and draw the three
voltage phasors extended in part (b). Phasor diagram
The magnitude of the line voltage, rad/s
E AN C
EL 3 E p E AB 207.85 V
ECN 120 V
E BN
EL 3 120 207.85 V
ECA 207.85 V
120o
120o 30o A
From the phasor diagram, the phasor E 120 V
line voltages can be obtained as, 120o AN
E BN 120 V
EAB 207.85 30o V
EBC 207.85 90o V B
E BC 207.85 V
ECA 207.85 150o V
ECN
POWER SYSTEMS 1
Solution:
(d) Find the magnitude of the per phase current, both phase and line and draw the three
current phasor on the phasor diagram. Phasor diagram
The magnitude of the phase current, rad/s
E AN
IL I p C
ECN 120 V E AB 207.85 V
Vp 120 I C 24 A E BN
IL I p 24 A
ZL 32 42
ECA 207.85 V 120o
Since the load is inductive, 30o
thereforethe current must lag the 120o A
I B 24 A E AN 120 V
voltage across the load by an 120 o
angle, ,
E BN 120 V I A 24 A
Impedance diagram,
B
ZL
XL =4 Phasor line (phase)currents, E BC 207.85 V
Solutions:
(e) Verify that the phasor sum of the neutral current is zero.
Phasor line (phase) currents, Phasor diagram
rad/s
IA 24 53.13o A E AN
C
ECN 120 V E AB 207.85 V
I C 24 A
IB 24 173.13o A E BN
ECA 207.85 V 120o
IC 24 66.87 A
o
120o
30o A
I B 24 A E AN 120 V
120o
Phasor neutral current,
E BN 120 V I A 24 A
IN IA IB IC
B
24 53.13o 24 173.13o 24 66.87o
0A E BC 207.85 V
Z Z
ZY
Balanced Load
ZY ZY Z
Z 3 ZY
Z Z ZY
Z
ZY
3
Z ZY ZY
POWER SYSTEMS 1
iA t
eAN t van t
ZL = RL+ jXL
N iN t n
eCN t ZL = RL+ jXL
vcn t
iB t vbn t
eBN t
ZL = RL+ jXL
iC t
Three-Phase Power
Instantaneous 3- voltages across the load : Instantaneous 3- currents:
van t Vˆan sin t i t Iˆ sin t
A A
Vbn
POWER SYSTEMS 1
Three-Phase Power
Instantaneous 3- voltages: Instantaneous 3- currents:
van t Vˆan sin t iA t IˆA sin t o
vbn t Vˆbn sin t 120o iB t IˆB sin t 120o
Vbn
POWER SYSTEMS 1
1
Using: sin A sin B cos A B cos A B then the average power is:
2
Vˆ Iˆ
P3 cos cos 2t cos cos 2t 240 cos cos 2t 240
2
Vˆ Iˆ Wye-connected:
cos cos cos
2 Vˆ Iˆ
Vrms I rms VL 3 V p I L I p
ˆ
3V I ˆ 2
cos 2
2
Three-phase power:
or
The total power in the circuit is the sum of each of the per-phase power
Wye-connected load
Three-phase power:
or
The total power in the circuit is the sum of the three per-phase power
Delta ()-connected load
3VL
IL
cos V p Vab Vbc Vca
3
the angle between phase voltage and phase current
3 VL IL cos
POWER SYSTEMS 1
P3 3 3 120 24 cos53.13 5184.1W
IC
120o
P3 3 I p2 RL 120o Van
53.13o
120o
IB IA
P3 3 24 3 5184 W
2
Vbn
Only active or real power dissipated in resistive part of the load
POWER SYSTEMS 1
Example:
For the three-phase system of figure below. Assume the phase sequence is ABC.
(a) Construct a single-phase equivalent circuit of the three-phase system.
(b) Determine the magnitude of the line current.
(c) Find the magnitude of line-to-neutral voltage at the terminal of the load and draw its three-
phase sequence voltages and line currents phasor diagram.
(d) Find the magnitude of the line voltage at the terminal of the load, and draw its three-phase
sequence phasor diagram.
(e) Calculate the power loss in the line. (f) Calculate the power delivered by the load.
A a
IAN 0.5 j 2
EAN
N
ECN
ZL1 ZL2
IBN
EBN B 0.5 j 2
b
ICN
ZL1 = 30+ j 60 ZL2 = 90+ j 30
C 0.5 j 2 c
POWER SYSTEMS 1
Power Triangle
ZL I2ZL SL
XL I2 I2XL QL
RL I2RL PL
PL I 2 RL QL I 2 X L SL I 2 Z L
POWER SYSTEMS 1
ZL
E VL Z L RL jX L
XL
RL
Complex power,
PL
I 2 RL j I 2 X L S L I 2 Z L Apparent power
2
Note : I I I I 2
*
POWER SYSTEMS 1
VL I
2
cos sin
2 2 SL VL I
VL I QL = VL.I.sin
QL P
tan 1
P
L PL = VL.I.cos
POWER SYSTEMS 1
E VL Z L RL jX L XL
ZL
VL I
2
cos sin
2 2
QL = VL.I.sin
SL VL I
VL I
QL
tan 1 jQ Power Triangle
P
L diagram
POWER SYSTEMS 1
In general,
Active or real power, Reactive power, Apparent power,
P V I cos Q V I sin S V I
Power factor is defined as,
True Power V I cos
P.F cos
Apparent Power V I
Load
VL E
(2) Power factor is lagging when I lags V (inductive)
VL
I
POWER SYSTEMS 1
E V P1 P2 P3 Pn
Q1 Q2 Q3 Qn
V I1 I 2 I3 I n
*
Power Triangle
V I1* V I2* V I3* V In*
S1 S2 S3 Sn ST
QT
PT jQT P1 jQ1 P2 jQ2 P3 jQ3 Pn jQn
T
P1 P2 P2 Pn j Q1 Q2 Q2 Qn
PT
where PT P1 P2 P2 Pn , QT Q1 Q2 Q2 Qn
QT PT
ST PT2 QT2 tan 1 P.F cos
P
T ST
POWER SYSTEMS 1
The total power triangle for the network can be obtained by joining the individual
power triangle from each branch, vertex to vertex.
PT jQT P1 jQ1 P2 jQ2 P3 jQ3 Assume inductive load
3
S2
P3
Q2 Q2 QT = Q 1+ Q 2 + Q3
2
P2
S1
T Q1 Q1
1
P1 P2 P3
PT = P 1 + P 2 + P3
POWER SYSTEMS 1
QT = Q1- Q2 + Q3
Q1
2 P2 Q3
S2 S3
Q1 Q2
S1 3 P3
Q2
1 T
P1 P2 P3
P T = P 1 + P 2 + P3
POWER SYSTEMS 1
S3
Effect of capacitive load of power factor
Q3
3
S2
P3
Q2 QT
2
P2
S1
T Q1
1 P1
PT
2 P2 Q3
S2 S3
Q1 Q2 QT
S1 3 P3
1 P1 T
PT
Effect of capacitive load reduces QT and T, hence increases power factor P.F
POWER SYSTEMS 1
INTRODUCTION
E VL Z L RL jX L jX c
=0 I I
VL VL I c3
L I I c2
L VL
I c1 L
IL IL
I IL Ic IL
I IL Ic
1 1 I IL Ic
1 1 VL
VL RL jX L jX c 1 1
RL jX L jX c VL
VL GL j BL Bc R jX jX
VL GL jBL jBc L L c
Example:
Three loads are connected in parallel across a 1400-V, 60-Hz single-phase supply as
shown in figure below.
Load 1: Inductive load, 125 kVA at 0.28 power factor
Load 2: Capacitive load, 10 kW and 40 kVar
Load 3: Resistive load of 15 kW
(a) Find the total kW, kVar, kVA and the supply power factor.
(b) A capacitor of negligible resistance is connected in parallel with the above loads to
improve the power factor to 0.8 lagging. Determine the kVAr rating of this
capacitor and capacitance in µF.
Load 1 Load 2 Load 3
E V C
POWER SYSTEMS 1
Solution:
Load 1: Inductive load, 125 kVA at 0.28 power factor
1 cos 1 0.28 73.74o lagging
The load complex powers are
S1 12573.74o kVA S 2 10 j 40 kVA S3 15 j 0 kVA
ST S1 S 2 S3 10053.13 kVA
S * 100 53.13o
IT T
71.43 53.13o
A
V* 14000 o
Solution:
(b) A capacitor of negligible resistance is connected in parallel with the above loads to
improve the power factor to 0.8 lagging. Determine the kVAr rating of this capacitor
and capacitance in µF.
Load 1 Load 2 Load 3
E V C
ST 100 kVA
Qc=?
Qc 80 45 35 kVar
=53.13o QT=80 kVar
V 2 14002
’ =36.87o
Xc 56
Qc 35
PT=60 kW
POWER SYSTEMS 1
Solution:
(b) A capacitor of negligible resistance is connected in parallel with the above loads to
improve the power factor to 0.8 lagging. Determine the kVAr rating of this capacitor
and capacitance in µF.
1 1
C 47.37 F
2fX c 2 60 56
V * 14000o
71.43 53.57
% reduction in current 100 25%
71.43
POWER SYSTEMS 1
Example:
For the single-phase as shown in the figure,
(a) Calculate the load impedance, the current, the voltage across the load, and the complex power i.e. the
real an the reactive power supplied to the load
(b) Calculate the capacitance required in parallel with the load to increase the power factor to unity.
(c) Calculate the current in the load, the voltage across it, and the complex power supplied to the load.
(d) Calculate the complex power in the capacitor
(e) Draw the phasor diagram.
j 10
IL
j 10
IL
E 100o kV VL Z L 64 j 48
j 10
IL Ic
9.26 103
2
2
=36.87o V
Qc=643.27 kVAr Xc c
133.29
PL=857.69 kW Qc 643.27 103
1
C
2 f X c
QL=643.27 kVAr 1
2 50 133.29
23.87 F
=0o
Qc=643.27 kVAr
PL=857.69 kW
POWER SYSTEMS 1
Nominal power of 1000 kW,
j 10 at 10 kV, and P.F=0.8 lagging
Alternatively,
IL 125 36.87o A Ic
Let us look at the effect of connecting the capacitor across the load
Before Power Factor Improvement After Power Factor Improvement
j 10 j 10 I
S
PSpice Simulation
(1) Before power factor correction
Simulation result:
(1) Current:
(2) Voltage:
10 10 3
0 o
IL 85.79 j 77.75 A = 115.78 - 42.19o A
64 j 48 j10
PSpice Simulation
(2) After power factor correction Simulation result:
(1) Current:
E 10 103 0o
IS 99.01 j9.9
ZT 100 j10
(2) Voltage
99.50 5.71 A
o
PowerWorld Simulation
(1) Before power factor correction
10 103 0o
IL 85.79 j 77.75 A = 115.78 - 42.19o A
64 j 48 j10
PowerWorld Simulation
(2) After power factor correction
E 10 103 0o
IS VL IS Z//
ZT 100 j10
99.50 5.71o 100
99.01 j9.9
9.95 5.71o kV
99.50 5.71 Ao
POWER SYSTEMS 1
Tutorial
Two Y-connected balanced loads with impedance (100 + j 40) and (30 + j 20)
are both connected to a three-phase four wire ABC system with a line-to-neutral
voltage of 120 V.
The power factor is improved by adding capacitors in parallel with the loads.
Determine the rating (in kVAr) of the capacitors needed in order to improve the
overal power factor becomes unity.