TW-DT 400 Dynair Data Sheet
TW-DT 400 Dynair Data Sheet
TW-DT 400 Dynair Data Sheet
C
Company: - PO Box 9014, Al Ghail Industrial Park
Contact: - Ras Al Khaimah, UAE
Project: St Paul hospital Tel. +971 7 2589000
Reference: - Fax. +971 7 2589001
Psta (Pa)
Static Pressure 450 Pa
300
Total Pressure 503 Pa
Velocity Pressure 53 Pa
200
Outlet Velocity 9.34 m/s
Fan Class 1 10
Safety Factor 10 % 2
60
Minimum Speed 350 rpm 40
Maximum Speed 1400 rpm 20
Motor selection 0
0 5000 10000 15000 20000 25000
Electrical Supply 415/3/50 Q - Volume Flow (m³/h)
Motor Rating 3 kW
Drive Information
Fan Pulley / Bush / Shaft 112 mm / 1610 / 30 mm
ERP Information
ERP Compliance Exempt
Type
Regulation -
Category of measure -
Selected Accessories
1 x Auto Changeover Panel
Key W H L w1 h1 w2 h2
Value [mm] 2100 1000 1270 1700 600 1000 600
Psta (Pa)
Static Pressure 380 Pa
300
Total Pressure 432 Pa
Velocity Pressure 52 Pa
200
Outlet Velocity 9.21 m/s
40
Minimum Speed 500 rpm
Maximum Speed 1300 rpm 20
Motor selection 0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
Electrical Supply 415/3/50 Q - Volume Flow (m³/h)
Motor Rating 1.1 kW
Drive Information
Fan Pulley / Bush / Shaft 80 mm / 1210 / 25 mm
ERP Information
ERP Compliance Exempt
Type
Regulation -
Category of measure -
Selected Accessories
1 x Auto Changeover Panel
Key W w1 L H w2 h1 h2
Value [mm] 1200 1000 900 650 500 400 400
Motor selection
Electrical Supply 240/1/50
Enclosure/Class IP20 / F
Poles number 4
ERP Information
0
ERP Compliance Exempt
0 1000 2000 3000 4000 5000
Type Q - Volume Flow (m³/h)
Regulation -
Certifications
Maico Gulf LLC certifies that the DYNAIR model BOX-D are licensed to bear
the AMCA Seal. The ratings shown are based on tests and procedures
performed in accordance with AMCA Publication 211 and AMCA Publication
311 and comply with the requirements of the AMCA Certified Ratings
Program. Performance certified is for installation type D – Ducted inlet,
Ducted outlet. Performance ratings do not include the effects of
appurtenances (accessories). Speed (RPM) shown is normal. Performance is
based on actual speed of test.