Unit 4 (4.3) Differential Protection
Unit 4 (4.3) Differential Protection
Roshan Chhetri
CST
1
⚫ Merz price differential protection is nothing
but a percentage differential protection which
works under the principle of circulating
current scheme
⚫ used to protect the generators and
transformer from internal short circuit,
Internal ground faults and inter turn shorts.
2
3
Protection of generators
4
1. Stator Protection
– Percentage differential protection
– Protection against stator inter-turn faults
– Stator-overheating protection
2. Rotor protection
– Field ground-fault protection
– Loss of excitation protection
– Protection against rotor overheating because of
unbalance three-phase stator current
5
3. Miscellaneous
– Over voltage protection
– Over speed protection
– Protection against motoring
– Protection against vibration
– Bearing-over heating protection
– Protection against auxiliary failure
– Protection against voltage regulator failure
6
Stator Protection
7
Percentage differential protection
8
Percentage differential protection
9
10
11
Protection against stator inter-turn
faults
12
⚫ Longitudinal percentage differential protection does not detect
intertern faults.
⚫ It is employed for the protection of the generator against stator
interturn faults.
⚫ Is used for generators having parallel windings separately
brought to the terminals.
⚫ Hydro generators having parallel winding in each phase
employs such protection and detects inter turn faults. This
scheme is also known as split-phase protection.
⚫ In this scheme, a single C.T. having double primary is used. No
bias is necessary because a common C.T. is employed so that
errors due to C.T differences do not occur.
13
Interturn protection based on zero-
sequence component
14
⚫ If generator does not have access to parallel winding, a method
based on zero-sequence voltage measurement can be
employed for the protection against stator interturn faults. This
scheme is also applicable to single winding generators having
multi-turn per phase slot to protect against interturn faults.
⚫ The zero-sequence voltage does not exist during normal
condition. If one or more turn of phase is short-circuited, the
generated emf contains zero-sequence component. The
secondary winding of the voltage transformer is in open-delta
connection to provide the zero sequence component of the
voltage to protective relay. A filter is provided to extract a third
harmonic component from the V.T. out put and apply it as relay
bias.
15
⚫ The zero-sequence voltage is also produce in case of external
earth faults. But most of this faults across the earth resistor. A
very small amount, 1 or 2% , appears across the generator.
Therefore, zero-sequence voltage is measured across the
generator winding at the line terminal rather than the zero-
sequence voltage to the earths shown in the figure to activate
the relay on occurrence of internal faults.
16
stator-overheating protection
17
⚫ Over current relays can not detect the winding temperature
because electrical protection can not detect the failure of the
cooling system
⚫ Over heating of the stator may be caused by the failure of the
cooling systems, overloading or core faults like short circuited
by laminations and failure of core bolt insulation.
⚫ Modern generators employ two methods to detects overheating
both being used in large generators (above 2MW).
⚫ In one method, the inlet and outlet temperature of the cooling
medium which may be hydrogen/water are compared for over
heating.
⚫ In other method, temperature sensing element are embedded
18 in the stator slot to sense the temperature.
⚫ When the temperature exceed a certain pre-set maximum
temperature limits, the relay sounds an alarm.
⚫ This scheme employs a temperature detector unit, relay and
the Wheatstone-bridge for the purpose.
⚫ The sensing elements may be thermistors, thermocouples or
resistance temperature indicators.
19
Rotor protection
– Field ground-fault protection
– Loss of excitation protection
– Protection against rotor overheating because of
unbalance three-phase stator current
20
Field ground-fault protection
21
⚫ This also causes vibrations.
⚫ Even though the second ground faults may not bypass enough
portion of the field winding to cause magnetic unbalance, the
arcing at the fault causes local heating.
⚫ A dc voltage is impressed between the field circuit and earth
through a polarised moving iron relay.
⚫ It is not necessary to trip the machine when a single field earth
faults occurs.
⚫ Usually an alarm is sounded. Then immediate steps are taken
to transfer the load from the faulty generator and to shut it down
as quickly as possible to avoid further problems.
22
23
Loss of excitation protection
24
⚫ A large machine may upset the system stability because it
draws reactive power from the system when it run as an
induction generator whereas it supplies reactive power when it
runs as a generator.
⚫ Field failure may be caused by the failure of excitation or mal-
operation of a faulty field breaker.
⚫ A protective scheme employing offset mho or directional
impedance relay are recommended for large modern
generators.
25
26
Protection against rotor overheating because of
unbalance three-phase stator current
27
28
Miscellaneous
29
Over voltage protection:
30
Over speed protection
31
Protection against motoring
32
Protection against vibration and
distortion of rotor
33
Bearing overheating protection
34
Protection against auxiliary failure
37
Protection of Transformer
⚫ The protective scheme depends upon the size of
transformer.
⚫ The rating of transformer used in transmission and
distribution system range from a few kVA to several
hundreds MVA.
⚫ For small transformer, simple protective device like
switches is used.
Types of faults encountered in transformers
1. External faults (or through faults)
2. Internal faults
38
External faults
40
2. Incipient faults
– Initially, such faults are minor nature but slowly might
develop into major faults.
– Such faults are not detectable at the winding terminals by
unbalances in voltage or current and hence, the protective
devices meant to operate under short circuit conditions are
not capable of detecting this type of faults.
– Such fault includes poor electrical connections, core faults,
failure of the coolant, regulator faults and bad load sharing
between transformers.
41
Percentage Differential Protection
42
43
⚫ The condition are made in such a way that under normal
condition or in case of operating coil of external faults the
current flowing in the coil of the relay due to C.T.s of primary
side is opposition to the current flowing due to the C.T.s of the
secondary side. Consequently the relay does not operate under
such condition.
⚫ If the faults occurs on the winding, the polarity of the induce
voltage of the C.T. of the secondary side is reversed. Now the
current in the operating coil from C.T.s of both primary and
secondary sides are in the same direction and cause the
operation of relay.
⚫ To supply, matching the C.T.s which are on the star side of the
transformer are connected in delta and vice versa.
44
Over heating protection
45
Protecting against magnetising
inrush current
47
⚫ The tuned circuit Xc and XL allows only current of
fundamental frequency to flow through the operating
coil.
⚫ The dc and harmonic, mostly second harmonics in
case of magnetic inrush current, are diverted into the
restraining coil.
⚫ The relay is adjusted so as not to operate when the
second harmonic exceeds 15% of the fundamental
current.
⚫ The minimum operating time is about 2 cycles.
48
49
⚫ If the harmonic restrain relay fails to operate
during internal faults. To over come this
difficulty, an instantaneous relay is also
incorporated.
⚫ It will operate on heavy internal faults in less
than one cycle.
50
Buchholz Relay
51
52
53
⚫ Buchholz relay is a type of oil and gas actuated protection relay
universally used on all oil immersed transformers having rating
more than 500 kVA
⚫ Buchholz relay is used for the protection of transformers from
the faults occurring inside the transformer.
⚫ Short circuit faults such as inter turn faults, incipient winding
faults, and core faults may occur due to the impulse breakdown
of the insulating oil or simply the transformer oil.
⚫ Buchholz relay will sense such faults and closes the alarm
circuit
54
⚫ Buchholz relay operates during three
conditions:
– Whenever gas bubbles are formed inside the
transformer due to severe fault.
– Whenever the level of transformer oil falls.
– Whenever transformer oil flows rapidly from the
conservation tank to the main or from the main
tank to the conservation tank.
55
Oil Pressure Relief Devices
56
Rate of Rise of Pressure Relay
57
58
Overcurrent Relay
59
Earth Fault Relay
66
⚫ The operating principle is based on Kirchhoff’s Law. The
average sum of all current entering and leaving the bus bar
zone must be zero, unless there is fault therein.
⚫ The relay connected will trip all the circuit breakers.
⚫ The main drawback of differential scheme is that there may be
a false operation in case of external faults.
⚫ This is due to the saturation of one of the C.T. of the faulted
feeder, which reduce the output.
67
Frame Leakage Protection
68
⚫ Thanks
69