I-9303 Addressable Dual I O Module Issue5.06

The I-9303 Addressable Dual I/O Module has the following features: 1. It provides two pairs of input and output signals that can be set to normally open or normally closed modes. 2. It occupies two consecutive addresses and can be programmed through a fire alarm control panel. 3. It monitors the power supply and has a plug-in structure.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
221 views2 pages

I-9303 Addressable Dual I O Module Issue5.06

The I-9303 Addressable Dual I/O Module has the following features: 1. It provides two pairs of input and output signals that can be set to normally open or normally closed modes. 2. It occupies two consecutive addresses and can be programmed through a fire alarm control panel. 3. It monitors the power supply and has a plug-in structure.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

I-9303

Addressable Dual I/O Module

Features
 Providing two pairs of input signals, working mode can be
set normally open and normally closed through a
programmer. Input signals are separated from the loop.
 Providing two pairs of output contact signals, it can carry
out voltage output through external circuit.
 Occupying two consecutive addresses. They can be
modified through a programmer or fire alarm control
panel (FACP).
 Monitoring power supply. If the cable conduit is inside the wall, the base is installed
 Plug-in structure. onto the Back Box (Fig. 2). If the conduit is on the surface of
the wall, B-9310 Back Box is available (Fig. 3).
Description B-9310
Back Box
With a microprocessor, I-9303 Addressable Dual I/O Module Conduit Back Box Conduit
Module Module
can communicate with FACP, monitor power supply, judge
the logic state of input signal, control output and state
indicators.
The module occupies two addresses, and each address can
independently receive start command from FACP, close the
relative relay and light the indicator. Each address
corresponds to one input. After receiving feedback r signal
from a device, the module transmits feedback signal to FACP
in the way of corresponding address. It can be used as two Fig. 2 Fig. 3
single input/output modules.
Application
Connection and Cabling
I-9303 Addressable Dual I/O Module is designed for
Fig. 1 shows terminals of the module.
controlling double input/output devices, and for receiving
65mm feedback signals of associated device action. For example, it
can control fire door, pump, and smoke exhauster fan. When
used to control the position of fire door, it can both control it
Mounting Mounting
V+ G COM1 NO1 NC1 COM2 NO2 NC2 from open to middle position and from middle to close and
Hole Hole
identify which position it is.
Mounting
8 7 2 1 The module can be programmed in field and working mode
Direction
9 10 15 16
can be set by a programmer. Refer to P-9910B Hand Held
Programmer Installation and Operation Manual for specific
D1 D2 G I1 I2 Z1 Z2 operations. Factory default working mode is both channels
normally open (4). The parameters can be set in field as
follows.
Fig. 1 Parameter Input Mode
Channel 1 auto feedback
Z1, Z2: Loop connection, non-polarized. 1
Channel 2 normally open
D1, D2: 24VDC power line, non-polarized.
Channel 1 normally open
I1 (I2), G: Volt-free input terminal of Channel I and Channel 2
Channel 2 auto feedback
II.
V+, G: 24VDC output terminals 3 Both channels auto feedback
NC1 (NC2), COM1 (COM2), NO1(NO2): Normally open Both channels normally open
4
output terminals of Channel I and Channel II. (factory setting)
Recommended Cabling Channel 1 normally closed
5
1.5mm2 or above fire cable for Z1, Z2 and 24VDC; 1.0mm2 or Channel 2 normally open
above fire cable for others, subject to local codes. Channel 1 normally open
6
Channel 2 normally closed
Installation 7 Both channels normally closed
The module is simply plugged onto the base after Channel 1 auto feedback
8
corresponding terminals are connected. Channel 2 normally closed
Note the upward arrow for mounting direction (Fig. 1). Channel 1 normally closed
9
Channel 2 auto feedback

30303406 Issue 5.06


 The module should connect with C-9302A when Specification
controlling 220VAC devices, as shown in Fig. 4.
Operating Voltage Loop: 24V(16V~28V)
 The module connects with fire door control box, as shown Power:24VDC(20VDC~28VDC)
in Fig. 5. Standby Current Loop ≤1mA; Power ≤6mA
+24V
Action Current Loop ≤4mA; Power ≤45mA
G Output Capacity Output contact capacity is
Z1 24VDC/5A
Z2 Voltage output capacity is
24VDC/1A
D1 D2 Z1 Z2 Output Control Dry contact output.
I-9303 Mode
I1 I2 G NO1 COM1 V+ G COM2 NO2 Programming Electronically addressed, the
Method module occupies two addresses.
The second address is
IN1 IN2 GND C1 C2 automatically increased 1 to the
first set within 1~241.
C-9302A
Indicators Red (flashes in polling, steadily
illuminates in action, quiet when
24V is fault)
A B C D E N Ingress Protection IP30
Rating
Fig. 4
Operating -10℃~+50℃
+24V Temperature
G Relative Humidity ≤95%, non condensing
Z1 Material and ABS, white (RAL 9016)
Z2
Color of the
Enclosure
Dimension 120mm×80mm×43mm
D1 D2 Z1 Z2
(L×W×H) (with base)
I-9303 Weight About 205g (with base)
I1 I2 G NO1 COM1 V+ G COM2 NO2
Accessories and Tools
Model Name Remark
P-9910B Hand Held Order separately
Public
Close
Middle

Smoke

Heat
Action Input

Action Input
Ground

Programmer
B-9310 Back Box Order separately
Fire Door Control Box
Limited Warranty
Fig. 5
GST warrants that the product will be free of charge for
Note: repairing or replacing from defects in design, materials and
Do not connect the module’s contact directly to AC workmanship during the warranty period. This warranty shall
control loop so that strong AC interference signal can be not apply to any product that is found to have been improperly
prevented from damaging to the module or controlled installed or used in any way not in accordance with the
devices. instructions supplied with the product. Anybody, including the
agents, distributors or employees, is not in the position to
The module is not to be used for gas extinguishing
amend the contents of this warranty. Please contact your
equipment. local distributor for products not covered by this warranty.

This Data Sheet is subject to change without notice. Please contact GST for more information or questions.

Gulf Security Technology Co., Ltd.


No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004
Tel: +86 (0) 335 8502434 Fax: +86 (0) 335 8502532
[email protected] www.gst.com.cn

30303406 Issue 5.06