I-9303 Addressable Dual I O Module Issue5.06
I-9303 Addressable Dual I O Module Issue5.06
Features
Providing two pairs of input signals, working mode can be
set normally open and normally closed through a
programmer. Input signals are separated from the loop.
Providing two pairs of output contact signals, it can carry
out voltage output through external circuit.
Occupying two consecutive addresses. They can be
modified through a programmer or fire alarm control
panel (FACP).
Monitoring power supply. If the cable conduit is inside the wall, the base is installed
Plug-in structure. onto the Back Box (Fig. 2). If the conduit is on the surface of
the wall, B-9310 Back Box is available (Fig. 3).
Description B-9310
Back Box
With a microprocessor, I-9303 Addressable Dual I/O Module Conduit Back Box Conduit
Module Module
can communicate with FACP, monitor power supply, judge
the logic state of input signal, control output and state
indicators.
The module occupies two addresses, and each address can
independently receive start command from FACP, close the
relative relay and light the indicator. Each address
corresponds to one input. After receiving feedback r signal
from a device, the module transmits feedback signal to FACP
in the way of corresponding address. It can be used as two Fig. 2 Fig. 3
single input/output modules.
Application
Connection and Cabling
I-9303 Addressable Dual I/O Module is designed for
Fig. 1 shows terminals of the module.
controlling double input/output devices, and for receiving
65mm feedback signals of associated device action. For example, it
can control fire door, pump, and smoke exhauster fan. When
used to control the position of fire door, it can both control it
Mounting Mounting
V+ G COM1 NO1 NC1 COM2 NO2 NC2 from open to middle position and from middle to close and
Hole Hole
identify which position it is.
Mounting
8 7 2 1 The module can be programmed in field and working mode
Direction
9 10 15 16
can be set by a programmer. Refer to P-9910B Hand Held
Programmer Installation and Operation Manual for specific
D1 D2 G I1 I2 Z1 Z2 operations. Factory default working mode is both channels
normally open (4). The parameters can be set in field as
follows.
Fig. 1 Parameter Input Mode
Channel 1 auto feedback
Z1, Z2: Loop connection, non-polarized. 1
Channel 2 normally open
D1, D2: 24VDC power line, non-polarized.
Channel 1 normally open
I1 (I2), G: Volt-free input terminal of Channel I and Channel 2
Channel 2 auto feedback
II.
V+, G: 24VDC output terminals 3 Both channels auto feedback
NC1 (NC2), COM1 (COM2), NO1(NO2): Normally open Both channels normally open
4
output terminals of Channel I and Channel II. (factory setting)
Recommended Cabling Channel 1 normally closed
5
1.5mm2 or above fire cable for Z1, Z2 and 24VDC; 1.0mm2 or Channel 2 normally open
above fire cable for others, subject to local codes. Channel 1 normally open
6
Channel 2 normally closed
Installation 7 Both channels normally closed
The module is simply plugged onto the base after Channel 1 auto feedback
8
corresponding terminals are connected. Channel 2 normally closed
Note the upward arrow for mounting direction (Fig. 1). Channel 1 normally closed
9
Channel 2 auto feedback
Smoke
Heat
Action Input
Action Input
Ground
Programmer
B-9310 Back Box Order separately
Fire Door Control Box
Limited Warranty
Fig. 5
GST warrants that the product will be free of charge for
Note: repairing or replacing from defects in design, materials and
Do not connect the module’s contact directly to AC workmanship during the warranty period. This warranty shall
control loop so that strong AC interference signal can be not apply to any product that is found to have been improperly
prevented from damaging to the module or controlled installed or used in any way not in accordance with the
devices. instructions supplied with the product. Anybody, including the
agents, distributors or employees, is not in the position to
The module is not to be used for gas extinguishing
amend the contents of this warranty. Please contact your
equipment. local distributor for products not covered by this warranty.
This Data Sheet is subject to change without notice. Please contact GST for more information or questions.