Product Data Sheet S Series Traditional I o Deltav en 56834

Download as pdf or txt
Download as pdf or txt
You are on page 1of 35

DeltaV Distributed Control System Product Data Sheet

October 2022

DeltaV™ S-series Traditional I/O


„ Modular and flexible construction

„ Reduced installation time and expense

„ Easy online expansion

„ Field-mounted capable hardware

„ 1:1 Redundancy for traditional I/O

„ Plug-and-Play I/O

The DeltaV ™ I/O interfaces are easy to install and maintain.

Introduction This modular design enables you to purchase the exact


amount of I/O cards, eight-wide carriers, power/controllers,
S-series traditional I/O interfaces provide improved ease and two-wide carriers you need and add more DeltaV I/O
of installation with the same proven features of M-series as your system grows.
I/O interfaces. This modular I/O subsystem offers flexibility
Reduced installation time and expense: The DeltaV system’s
during installation and is designed for extreme environmental
S-series I/O interfaces are designed for quick assembly and
conditions of field installations. S-series traditional I/O is
error proof maintenance. All carriers snap onto T-DIN rails and
equipped with a snap-in retention system for quick installation.
interfaces snap into the I/O slots without the use of any tools.
The I/O interfaces can be installed in any of the possible
64 slots. Each I/O interface has a separate wiring terminal block,
which connects field wiring to the interface. The I/O card
All wiring is through the carriers and terminal blocks so
can easily be removed without touching the I/O wiring on the
that modules can easily be removed without disconnecting
terminal block. Some I/O cards can also use the fused terminal
any wires. Modularity, fast installation, online expansion,
block, which is equipped with in-line fuses that can be pulled
and environmentally robust hardware make DeltaV™ S-series
to isolate power to the field circuit.
traditional I/O a smart choice for your process control system.
Traditional I/O interfaces have I/O function keys that allow
the terminal block to be set to receive a specific I/O card.
Benefits
These keys ensure that the correct I/O card is always plugged
Modular and flexible construction: The S-series traditional into the corresponding terminal block. The keys provide
I/O subsystem is designed with your investment in mind. a safety measure by preventing the wrong I/O card being
Each controller supports up to eight I/O carriers that form a installed. It’s incredibly easy to use and gives you time to
robust, passive bus for up to 64 I/O interfaces. Each interface do more.
has a matching I/O terminal block and can be installed in any
I/O slot on the bus. Carriers and interfaces can be added online,
without interruption to the existing I/O communication.
DeltaV S-series Traditional I/O October 2022

Plug-and-play I/O: All S-series traditional I/O components


plug into the I/O interface carrier and are auto sensed by
the controller. There are no addressing switches or jumpers.
Cards can be installed in any order simplifying the I/O
subsystem design. New I/O interfaces are detected by the
system and added to the engineering database automatically.
Additional features can be enabled as needed and downloaded
without disruption to existing I/O communication,
allowing you to install the I/O you need today with the
ability to expand tomorrow.

Product Description

S-series terminal blocks.


The S-series traditional I/O subsystem includes:
„ I/O interface carrier (DIN-rail surface mounted) on
The I/O carriers provide integrated bussed field power which all I/O related components are installed.
distribution to the I/O interfaces. The integrated bus is divided
„ Bulk AC to 24V DC power supply for field devices.
into primary and secondary power for odd- and even-numbered
slots. Each slot is individually fused to protect power to other „ A variety of analog and discrete I/O interfaces,
cards. This significantly reduces the external power distribution consisting each of an I/O card enclosed in a common
circuits while still providing each card with fused 24V DC bussed form factor and an associated I/O terminal block,
field power. which easily plug into the I/O interface carrier.
Easy online expansion: The S-series I/O carriers and interfaces „ Cable extenders that provide flexibility in carrier mounting.
can easily be added online, without disruption of existing
I/O communication. I/O carriers can be extended online,
either by directly connecting them to the right side of the
existing carrier, or using extender cables to mount the new
carrier on a different DIN rail. The controller automatically
detects new carriers and interfaces and allows these to be
auto-sensed into the configuration database.

Field-mounted capable hardware: All S-series traditional I/O


interfaces are rated for extreme operating temperature ranges
of -40 to 70°C (-40 to 158°F). The interfaces can be installed
in field mounted enclosures so you significantly reduce the
footprint of your equipment and increase valuable control room
space for other uses. This also allows you to save on wiring
expenses by eliminating the need for long runs of multi-cores.
The integrated design of the I/O subsystem can eliminate the
need for marshaling panels. This saves you even more in your
total capital costs.

1:1 Redundancy for traditional I/O cards: Increased S-series traditional I/O Interface.
system availability is easy with S-series traditional I/O cards.
Four traditional I/O card types are available with redundant The I/O cards are connected to the field with a terminal block,
terminal blocks for critical field circuits. Simply install a pair which allows removal of I/O cards without disconnecting any
of cards on the prescribed redundant terminal block and the field wiring.
DeltaV Distributed Control System (DCS) will automatically
recognize them as a redundant pair. There is no configuration
other than to autosense the redundant pair.

www.emerson.com/deltav 2
DeltaV S-series Traditional I/O October 2022

I/O Cards All cards meet ISA G3 corrosion specifications by the careful
selection of superior electronic components and the use of
A variety of analog and discrete I/O interfaces are available to conformal coating.
meet your specific requirements. The following cards support
Pulse Counters are available on most DI cards. The supported
simplex or redundant installation:
maximum frequency varies from 0.1 Hz on AC signals to 75 or
„ AI 4-20 mA HART, eight channels 120 Hz on 24V DC inputs, and up to 50 KHz on the High-speed
Pulse input card.
„ AO 4-20 mA HART, eight channels
DeltaV DCS provides control module level time stamping for log
„ DI Dry Contact, eight channels
events and alarms. For greater event resolution the 16-channel
„ DO 24V DC High Side, 8channels Sequence of Event DI card can provide signal driven events to a
resolution of +/- 0.25 ms per card, or within 1 ms per controller.
„ AI (Plus) 4-20 mA HART, 16channels
Please refer to the Sequence of Events PDS for more information
„ AO (Plus) 4-20 mA HART, 16channels on Sequence-of-event data collection and system options for
„ DI (Plus) 24V DC, Dry Contact, 32channels this feature.

„ DO (Plus) 24V DC, High-Side, 32channels


I/O Card Redundancy
The following I/O cards are supported in simplex format to
meet your field wiring needs. Redundant I/O cards are available for critical applications.
The same card can be used in simplex or redundant
„ AI Isolated, four channels applications. When installed on a two-wide redundant terminal
„ RTD, eight channels block, the cards are recognized as a redundant pair by the
controller. The controller scans each card and determines which
„ Thermocouple, eight channels
card is acting as the active interface. When a fault is detected,
„ Millivolt, eight channels the system automatically switches to the standby I/O card.

„ DI 24V DC Isolated, eight channels DeltaV control modules reference simplex and redundant
I/O channels identically and there is no special configuration
„ Pulse Count Input, four channels (Isolated DI)
required to take advantage of redundancy.
„ Sequence of Event, 16 channels (DI 24V DC)
Switchover of a redundant I/O card is completed within
„ DI 120V AC Low Side Detection, eight channels two scans of the I/O bus. Make-before-break contacts ensure
digital field instruments remain powered and the process
„ DI 120V AC Isolated, eight channels
is undisturbed. Analog output signals are briefly driven by
„ DO 24V DC Isolated, eight channels both cards for <5 ms during switchover of the card.
„ DO 120/230V AC High Side, eight channels Hardware alerts automatically report hardware integrity errors
for both the primary and secondary cards. Any event that
„ DO 120/230 Isolated, eight channels
causes a switchover is also reported automatically through the
All I/O cards are enclosed in a common form factor that system hardware alerts and is logged in the Event Chronicle.
plugs into the I/O interface carrier. The housing is clearly
Events that can cause a switchover include:
labeled with the enclosed I/O card type. All cards have power
and internal error indicators. Eight-channel cards have clearly „ Hardware failure within the active card.
visible channel status LEDs.
„ Communications failure between the active card
and the controller.

„ Detection of a fault in the field wiring.

www.emerson.com/deltav 3
DeltaV S-series Traditional I/O October 2022

A switchover may also be initiated from the diagnostics explorer, and the health and status of both cards and their channels are
available in the diagnostics explorer.

The system automatically commissions a new standby card. In safe areas, failed cards can be replaced under power.

In hazardous areas, appropriate installation procedures must be followed.

Hardware Specifications
Common Environmental Specifications for all I/O Interfaces

Operating Temperature* -40 to 70°C (-40 to 158°F)

Storage Temperature -40 to 85°C (-40 to 185°F)

Relative Humidity 5 to 95%, non-condensing

Protection Rating IP 20
Airborne Contaminants ISA-S71.04-1985 Airborne Contaminants Class
G3 Conformal coating
Shock 10 g ½-sine wave for 11 ms
Vibration 1 mm peak-to-peak from 5 to 13.2 Hz;
0.7 g from 13.2 to 150 Hz

*Operating any electronics at the higher end of its temperature range for long periods of time will shorten its expected lifetime,
see Effects of Heat and Airflow Inside an Enclosure White Paper for more information.

S-series traditional I/O interface enclosure.

www.emerson.com/deltav 4
DeltaV S-series Traditional I/O October 2022

Analog Input signals


Specifications for AI Card, 8-channel, 4 to 20 mA, HART

Number of Channels Eight

Input Sensor Types 4 to 20 mA (span), 2-wire and 4-wire

Full Signal Range 1 to 22.5 mA, with over range checking

Transmitter Power (2-wire) 13.5V minimum at 20 mA (current limited at 29 mA max)

Accuracy Over Temperature Range 0.1% of span

Repeatability 0.05% of span

Resolution 16 bit A/D converter

Roll-off Frequency (Anti-aliasing) -3 dB at 2.7 Hz, -20.5 dB at ½ the sampling frequency

Calibration None required


Local Bus Current per Card Simplex: 120 mA typical, 150 mA maximum
(12V DC nominal) Redundant:175 mA typical, 250 mA maximum (per card)
Field Circuit Power per Card 300 mA maximum @ 24V DC (+/-10%)
Isolation Each channel is optically isolated from the system
and factory tested to 1500V DC.
Optional Fuse 2.0 A (Terminal block option)
HART Communications Support HART pass-through for AMS Device Manager.
HART variable and status reporting for control functions.
Hart Scan Time 600 – 800 ms (typical) per enabled channel

Simplified circuit and connection diagram for AI card, 8-channel, 4 to 20 mA, HART.

www.emerson.com/deltav 5
DeltaV S-series Traditional I/O October 2022

Specifications for AI and AI Plus Card, 16-channel, 4 to 20 mA, HART

Number of Channels 16

Input Sensor Types 4 to 20 mA (span), 2-wire

Full Signal Range 2 to 22 mA, with over range checking

Transmitter Power 13.5 V minimum at 20 mA (max current limited at 29 mA)

Accuracy Over Temperature Range 0.2% of span

Repeatability 0.05% of span

Resolution 16 bit A/D converter

Roll-off Frequency (Anti-aliasing) -3 dB at 2.7 Hz; -20.5 dB at 20 Hz

Calibration None required


Local Bus Current per Card Simplex: 85 mA typical, 150 mA maximum
(12V DC nominal) Redundant: 110 mA typical, 200 mA maximum
Field Circuit Power per Card 500 mA maximum @ 24V DC (+/-10%)
Isolation Each channel is optically isolated from the system
and factory tested to 1000V DC.
HART Communications Support HART pass-through for AMS Device Manager.
HART variable and status reporting for control functions.
Hart Scan Time 600 – 800 ms (typical) per enabled channel

Simplified circuit and connection diagram for simplex AI card, Simplified circuit and connection diagram for redundant AI Plus
16-channel, 4 to 20 mA, HART. card, 16-channel, 4 to 20 mA, HART.

www.emerson.com/deltav 6
DeltaV S-series Traditional I/O October 2022

Specifications for RTD Input Card, 8-channel

RTD Channels per Card Eight

Sensor Types Resistance, Pt100, Pt200, Pt500, Ni120, Cu10, User Defined.

Sensor Configuration 2-wire, 3-wire, or 4-wire

Full Scale Signal Range See Table next page

Accuracy See Table next page

Repeatability 0.05% of span

Resolution 16-bit A/D converter

Calibration None required

Units Degrees C, Degrees F

Sensor Excitation Current 100 µA

Common Mode Rejection 120 dB at 50/60 Hz

Local Bus Current (12V DC nominal) 160 mA

Open Sensor Detection Yes

RTD, ohms Sensor Type Specifications

Sensor Type Full Scale Operating Range 25° Reference Accuracy Temperature Drift Resolution

Resistance 0 to 2,000 Ω 0 to 2,000 Ω ± 06.2 Ω ± 0.112 Ω/°C ~0.02 Ω


Pt100 -200 to 850°C -200 to 850°C ± 0.5°C ± 0.018°C/°C ~0.05°C
Pt200 -200 to 850°C -200 to 850°C ± 0.5°C ± 0.012°C/°C ~0.05°C
Pt500 -200 to 850°C -200 to 850°C ± 3.5°C ± 0.063°C/°C ~0.18°C
Ni120 -70 to 300°C 70 to 300°C ± 0.2°C ± 0.006°C/°C ~0.02°C
Cu10 -30 to 140°C -30 to 140°C ± 2.0°C ± 0.157°C/°C ~0.23°C
User Defined* 0 to 1000 Ω 0 to 1000 Ω ± 0.4 Ω ± 0.009 Ω/°C ~0.05 Ω
* The Callendar-Van Dusen linearization equation can be used with user defined Pt RTDs. Refer to Recommended I/O Practices in DeltaV Books online for usage information.

Simplified circuit diagram for RTD Input card, 8 channels.

www.emerson.com/deltav 7
DeltaV S-series Traditional I/O October 2022

Specifications for Thermocouple/mV Input Card, 8-channel

Channels per Card Eight


Sensor Types B, E, J, K, N, R, S, T, uncharacterized low-level voltage source
„ Thermocouple
„ mV
Sensor Ranges See table next page

Repeatability 0.05% of span

Resolution 16-bit A/D converter

Calibration None required


Units Degrees C, Degrees F

Cold Junction Compensation (Not Available on mV Channels) ±1°C


Isolation Each channel is optically isolated from the system and factory
tested to 1500V DC.
„ Channels 1, 2, 3, and 4 are isolated from
channels 5, 6,7, and 8 (verified by 1500V DC factory test).
„ Thermocouples attached to channels 1, 2, 3, and 4
are not electrically isolated and should be within
+ 0.7V DC of each other.
„ Thermocouples attached to channels 5, 6, 7, and 8
are not electrically isolated and should be within
+ 0.7V DC of each other.
Common Mode Rejection 120 dB at DC/50/60 Hz

Local Bus Current (12V DC Nominal) 210 mA

Open Sensor Detection Yes

www.emerson.com/deltav 8
DeltaV S-series Traditional I/O October 2022

Sensor Type Specifications

Sensor Type Full Scale Operating Range 25° Reference Accuracy Temperature Drift Resolution

B 250 to 1810°C 500 to 1810°C ± 2.4°C ± 0.056°C/°C ~0.18°C


E -200 to 1000°C -200 to 1000°C ± 0.6°C ± 0.008°C/°C ~0.07°C
J -210 to 1200°C -190 to 1200°C ± 0.8°C ± 0.011°C/°C ~0.05°C
K -270 to 1372°C -200 to 1372°C ± 0.5°C ± 0.016°C/°C ~0.18°C
N -270 to 1300°C -190 to 1300°C ± 1.0°C ± 0.007°C/°C ~0.10°C
R -50 to 1768°C -50 to 1768°C ± 2.1°C ± 0.013°C/°C ~0.14°C
S -50 to 1768°C -40 to 1768°C ± 2.2°C ± 0.067°C/°C ~0.24°C
T -270 to 400°C -200 to 400°C ± 0.7°C ± 0.001°C/°C ~0.04°C
mV Source/ -100 to 100 mV -100 to 100 mV 0.1 mV ± 0.002 mV/°C ~0.003mV
Uncharacterized
(no linearization
or cold junction
compensation.)

Simplified circuit diagram of Thermocouple/mV card, 8 channels.

www.emerson.com/deltav 9
DeltaV S-series Traditional I/O October 2022

Specifications for Isolated Input Card,4 channel

Number of Channels Four


Sensor Types B, E, J, K, N, R, S, T, Uncharacterized
„ Thermocouple PT100, PT200, Ni120, Cu10, Resistance, User Defined Refer to
„ RTD Sensor Types following tables.

„ mV and V Ranges
Input Type Mix Independently configurable

Resolution 16-bit A/D converter

Calibration None required


Isolation Channel-to-system - 600V AC double insulation.
Each channel is optically isolated from the system
and factory tested to 5000V DC.
Channel-to-channel - 600V basic insulation.
Each channel is optically isolated from each
other and factory tested to 3100V DC.
CAN/CSA-C22.2 No.1010.1-92
Common Mode Rejection 120 dB at DC/50/60 Hz

Input Impedance 10 MΩ

Roll-off Frequency (Anti-aliasing) -3dB at 2.7 Hz

Local Bus Current (12V DC nominal) 350 mA

Isolated Input Card, Thermocouple and mV Input Specifications

Linearization Error +/- 0.003% full scale

Cold Junction Comp. Accuracy +/- 1.0°C


Cold Junction Compensation Local: Integrally mounted in terminal block.
(Not Available on mV Channels) External: Specified channel.
Cold Junction Compensation Range -40 to 85°C

Open Circuit Detection (Thermocouple Only) Yes

Open Sensor Detection Time 1 second

www.emerson.com/deltav 10
DeltaV S-series Traditional I/O October 2022

Isolated Input Thermocouple/mV/V Sensor Type Specifications


25°C Reference Nominal
Sensor Types Full Scale Operating Range Temperature Drift
Accuracy Resolution
B 250 to 1810°C 500 to 1810°C ±1.2°C ±0.116°C/°C 0.09°C

E -200 to 1000°C -200 to 1000°C ±0.5°C ±0.004°C/°C 0.05°C

J -210 to 1200°C -190 to 1200°C ±0.6°C ±0.005°C/°C 0.06°C

K -270 to 1372°C -140 to 1372°C ±0.5°C ±.013°C/°C 0.05°C

N -270 to 1300°C -190 to 1300°C ±1.0°C ±.015°C/°C 0.05°C

R -50 to 1768°C 0 to 1768°C ±1.7°C ±.083°C/°C 0.06°C

S -50 to 1768°C 0 to 1768°C ±1.8°C ±.095°C/°C 0.08°C

T -270 to 400°C -200 to 400°C ±0.7°C ±.025°C/°C 0.04°C


Uncharacterized
(No Linearization -100 to 100 mV -100 to 100 mV ±0.05 mV ±0.0003 mV/°C 0.0031 mV
or CJC)
20 mV Source -20 to 20 mV -20 to 20 mV ±0.02 mV ±0.001 mV/°C 0.0008 mV

50 mV Source -50 to 50 mV -50 to 50 mV ±0.03 mV ±0.0005 mV/°C 0.0017 mV

100 mV Source -100 to 100 mV -100 to 100 mV ±0.05 mV ±0.0003 mV/°C 0.0031 mV

0 - 5V 0 to 5V 0 to 5V ±0.005V ±0.0002V/°C 0.00009V

0 - 10V 0 to 10V 0 to 10V ±0.010V ±0.0004V/°C 0.00016V

1 - 5V 1 to 5V 1 to 5V ±0.0005V ±0.0002V/°C 0.00009V

1V +/- 1V +/- 1V ±0.0025V ±0.0002V/°C 0.00015V

5V +/- 5V +/- 5V ±0.005V ±0.0002V/°C 0.00017V

10V +/- 10V +/- 10V ±0.010V ±0.0004V/°C 0.0003V

Simplified circuit diagram of Isolated Input card, Thermocouple, mV, V, 4 channels.

www.emerson.com/deltav 11
DeltaV S-series Traditional I/O October 2022

Isolated Input Cards, RTD, ohms Input Specifications

Sensor Configurations 2-, 3-, and 4-wire

Excitation Current 100 µA DC

Open Sensor Detection Time 1 second

Shorted Sensor Detection Time 1 second

Pt 100 and Pt 200 alpha 0.00385

Isolated Input Card, RTD, ohms Sensor Type Specifications


25°C Reference Temperature
Sensor Type Sensor Input Range Resolution
Accuracy Drift
Pt100 -200 to 850°C ± 0.5°C ± 0.018°C 0.05°C
Pt200 -200 to 850°C ± 0.5°C ± 0.012°C 0.05°C

Ni120 -70 to 300°C ± 0.2°C ± 0.006°C 0.02°C

Cu10 -30 to 140°C ± 2.0°C ± 0.076°C 0.23°C

Resistance 1 to 1000 ohm ± 0.5 ohms ± 0.018 ohms/°C 0.02 ohms

User Defined* 0 to 1000 ohms ±0.4 ohms ±0.009 ohms/°C ~0.05 ohms
* The Callendar-Van Dusen linearization equation can be used with user defined Pt RTDs. Refer to Recommended I/O Practices in DeltaV Books online for usage information.

Simplified circuit diagram of Isolated Input card, RTD, 4 channels.

www.emerson.com/deltav 12
DeltaV S-series Traditional I/O October 2022

Analog Output Signals


Specifications for AO Card, 8-channel, 4 to 20 mA, HART

Number of Channels Eight

Device Types 4 to 20 mA

Full Signal Range 1 to 23 mA


Accuracy Over Temperature Range 0.25% of span (-40 to 60°C)
0.4% of span (60 to 70°C)
Resolution 14-bit D/A converter

Calibration None Required


Local Bus Current per Card Simplex: 120 mA typical, 150 mA maximum.
(12V DC Nominal) Redundant: 175 mA typical, 250 mA maximum.
Field Circuit Power per Card 300 mA maximum @ 24V DC (+/-10%)
Isolation Each channel is optically isolated from the system
and factory tested to 1500V DC.
Output Compliance Voltage 20 mA at 21.6V DC supply into 700 Ω load

Open-Loop Detection <0.70 mA

Optional Fuse 2.0 A (Terminal block option)


HART Communications Support HART pass-through for AMS Device Manager.
HART variable and status reporting for control functions.
Hart Scan Time 600 – 800 ms (typical) per enabled channel

Simplified circuit and connection diagram for simplex AO card, 8-channel, 4 to 20 mA, HART.

www.emerson.com/deltav 13
DeltaV S-series Traditional I/O October 2022

Specifications for AO (Plus) Card, 16-Channel, 4 to 20 mA, HART

Number of Channels 16

Device Types 4 to 20 mA

Full Signal Range 1 to 23 mA

Accuracy Over Temperature Range 0.25% of span

Resolution 14-bit A/D converter

Calibration None required


Local Bus Current per Card Simplex: 85 mA typical, 150 mA maximum.
(12V DC nominal) Redundant: 110 mA typical, 260 mA maximum.
Field Circuit Power per Card 400 mA maximum @ 24V DC (+/-10%)
Isolation Each channel is optically isolated from the system
and factory tested to 1000V DC.
HART Communications Support HART pass-through for AMS Device Manager.
HART variable and status reporting for control functions.
Hart Scan Time 600 – 800 ms (typical) per enabled channel

Simplified circuit and connection diagram for simplex AO (Plus) card, 16-channel, 4 to 20 mA, HART.

www.emerson.com/deltav 14
DeltaV S-series Traditional I/O October 2022

DC Voltage Discrete Input Cards


Specifications for DI Card, 8-channel, 24V DC, Dry Contact

Number of Channels Eight

Input Compatibility Dry contact ( known to operate with many NAMUR sensors)

Detection Level for On >2.2 mA

Detection Level for Off <1 mA

Input Impedance 5 KΩ (approximate)

Wetting Voltage 15 Volts


Fault Detection Capable Field resistor pack
(known to operate with many NAMUR sensors)
Configurable Channel Types: Input
„ Discrete Input Dry contact or discrete state sensor changing <2 Hz.
„ Pulse Count Pulse train <75 Hz

Local Bus Current Simplex: 75 mA typical, 100 mA maximum


(12V DC nominal) Redundant: 90 mA typical, 150 mA maximum
Field Circuit Power per Card 100 mA at 24V DC (±10%)
Isolation Each channel is optically isolated from the system
and factory tested to 1500V DC.
Optional Fuse 2.0 A (Terminal block option)

Simplified circuit and connection diagram for DI card, 8-channel, 24V DC, Dry Contact.

www.emerson.com/deltav 15
DeltaV S-series Traditional I/O October 2022

Specifications for DI Card, 8-channel, 24V DC, Isolated

Number of Channels Eight

Detection Level for On >10V DC

Detection Level for Off <5V DC

Input Impedance 5K Ω (approximately)

Wetting Current 6 mA at 24V DC


Configurable Channel Types: Input signal profile
„ Discrete Input Dry contact or discrete state sensor changing <2 Hz.
„ Pulse Count Pulse train <120 Hz

Local Bus Current (1V DC nominal) 75 mA typical, 100 mA maximum

Field Circuit Power per Card None


Isolation Each channel is optically isolated from the system
and from each other and factory tested to 1500V DC.
Optional Fuse 2.0 A

Simplified circuit and connection diagram for DI card, 8-channel, 24V DC, Isolated.

www.emerson.com/deltav 16
DeltaV S-series Traditional I/O October 2022

Specifications for DI (Plus) Card, 32-channel, 24V DC, Dry Contact

Number of Channels 32

Detection Level for On >2 mA

Detection Level for Off <0.25 mA


Termination Fault Detection Only available on Plus Cards when used with the S-series Mass
(A Mass Terminal Block Feature Only) Connection Solutions or P+F HiD or HiC barriers and boards.
Input Impedance 5K ohm (approximate)

Wetting Voltage 24V DC

Local Bus Current (12V DC Nominal) 50 mA typical, 75 mA maximum

Field Circuit Power per Card 150 mA maximum @ 24V DC (+20%/-15%)


Isolation Each channel is optically isolated from the system
and factory tested to 1500V DC.

Simplified circuit and connection diagram for DI Card, 32-channel,


24V DC, Dry contact.

Simplified circuit and connection diagram for simplex DI Plus Card,


32-channel, 24V DC, Dry contact.

www.emerson.com/deltav 17
DeltaV S-series Traditional I/O October 2022

Specifications for PCI Card, 4-channel, 24V DC, Dry Contact

Number of Channels Four

Detection Level for On (Min.) >4.8V DC (>5 mA)

Detection Level for Off (Max.) <1.0V DC (<1 mA)

Input Impedance 25 mA at 24V DC (960 Ohms)

Input Accuracy 0.1% reading (over 10 Hz to 50 kHz)1

Resolution +/- 1 pulse

Minimum Pulse Width 10 µS

Pulse Count Register 32-bit unsigned integer


Input Frequency Sine wave 10 Hz to 50kHz.
Square wave 0.1 Hz to 50 kHz.
Maximum Input Voltage 26.4V DC

Wetting Voltage 24V DC

Local Bus Current (12V DC nominal) 150 mA maximum


Isolation Each channel is optically isolated from the system at
and from other channels at 1500V DC.
1
Filtering may be required to meet the accuracy specification for a pulse input channel.

Simplified circuit and connection diagram for PCI card, 4 channel, 24V DC, Isolated.

www.emerson.com/deltav 18
DeltaV S-series Traditional I/O October 2022

Specifications for SOE Card, 16-channel, 24V DC, Dry Contact

Number of Channels 16

Detection Level for On >2 mA

Detection Level for Off <0.25 mA

Input Impedance 5K ohm (approximate)

Wetting Voltage 24V DC

Channel Scan Rate 0.25 msec for all 16 channels.


Time Stamp Accuracy 0.25 msec from same card.
(For SOE Enabled Channels Only) 1 msec from same controller.
Local Bus Current (12V DC Nominal) 75 mA typical, 100 mA maximum.

Field Circuit Power per Card 75 mA at 24V DC


Isolation Each channel is optically isolated from the system
and factory tested to 1500V DC.

Simplified circuit and connection diagram for SOE card, 16-channel, 24V DC, Dry contact.

www.emerson.com/deltav 19
DeltaV S-series Traditional I/O October 2022

DC Voltage Discrete Output Cards


Specifications for DO Card, 8-channel, 24V DC, High Side

Number of Channels Eight

Output Range 24V DC +/- 10%


Output Rating 1.0 A maximum continuous per channel;
3.0 A maximum per I/O Interface.
(Inrush 4.0A for <100mSec, 6.0A for <20 mSec)
Off-State Leakage 1.2 mA maximum
Configurable Channel Types: Output signal profile.
„ Discrete Output Output stays in last state submitted by the control logic.
„ Momentary Output Output remains active for a pre-configured time period.
„ Continuous Pulse Output Output is active as a percentage of a pre-configured
base time period (100 ms to 100 s). Resolution = 5 ms.
Local Bus Current (12V DC Nominal) 75 mA typical, 100 mA maximum
Field Circuit Power per Card 3.0 A at 24 V DC per I/O Interface
(internal 10-Amp fast acting non-ressettable fuse).
Isolation Each channel is optically isolated from the system
and factory tested to 1500V DC.
Optional Fuse 2.0 A

Simplified circuit and connection diagram for DO card, 8-channel, 24V DC, High Side.

www.emerson.com/deltav 20
DeltaV S-series Traditional I/O October 2022

Specifications for DO Card, 8-channel, 24V DC, Isolated

Number of Channels Eight

Output Range 2V DC to 60V DC

Output Rating 1.0 A (inrush 4.0 A for <100 ms; 6A for <20 ms)

Off State Leakage 1.2 mA maximum


Configurable Channel Types: Output signal profile.
„ Discrete Output Output stays in last state submitted by the control logic.
„ Momentary Output Output remains active for a pre-configured time period.
„ Continuous Pulse Output Output is active as a percentage of a pre-configured
base time period (100 ms to 100 s). Resolution = 5 ms.
Local Bus Current (12V DC Nominal) 100 mA typical, 150 mA maximum

Field Circuit Power per Card None


Isolation Each channel is optically isolated from the system
and from each other and factory tested to 1500V DC.

Simplified circuit and connection diagram for DO card, 8-channel, 24V DC, Isolated.

www.emerson.com/deltav 21
DeltaV S-series Traditional I/O October 2022

Specifications for DO (plus) Card, 32-channel, 24V DC, High-Side

Number of Channels 32

Output Rating 100 mA per channel

Output Range 24V DC ±10%

Off-State Leakage 0.1 mA maximum


Termination Fault Detection Only available on Plus Cards when used with the S-series Mass
(A Mass Terminal Block Feature Only) Connection Solutions or P+F HiD or HiC barriers and boards.
Local Bus Current (12V DC Nominal) 100 mA typical, 150 mA maximum.

Field Circuit Power per Card 3.2 A @ 24V DC (+20%/-15%)


Isolation Each channel is optically isolated from the system
and factory tested to 1500V DC.

Simplified circuit and connection diagram for simplex DO (Plus) Card, 32-channel, 24V DC,
High- Side.

www.emerson.com/deltav 22
DeltaV S-series Traditional I/O October 2022

AC Voltage Discrete Input Cards


Specifications for DI Card, 8-channel, 120V AC, Dry Contact

Number of Channels Eight

Detection Level for On >1.4 mA

Detection Level for Off <0.56 mA

Wetting Current 2 mA at 120V AC

Output Impedance 60 KΩ (approximately)

Local Bus Current (12V DC Nominal) 75 mA typical, 100 mA maximum

Field Circuit Power per Card 15 mA at 120V AC

Isolation Each channel is optically isolated from the system at 250V AC.

Optional Fuse 2.0 A

Simplified circuit and connection diagram for DI card, 8-channel, 120V AC, Dry Contact.

www.emerson.com/deltav 23
DeltaV S-series Traditional I/O October 2022

Specifications for DI Card, 8-channel, 120V AC, Isolated

Number of Channels Eight

Detection Level for On 84 to 130V AC

Detection Level for Off 0 to 34V AC

Wetting Current 2 mA at 120V AC

Input Impedance 60 KΩ (approximately)

Local Bus Current (12V DC Nominal) 75 mA typical, 100 mA maximum.

Field Circuit Power per Card None


Isolation Each channel is optically isolated from the system
at 250V AC and from other channels at 250V AC.
Optional Fuse 2.0 A (Terminal block option)

Simplified circuit and connection diagram for DI card, 8-channel, 120V AC, Isolated.

www.emerson.com/deltav 24
DeltaV S-series Traditional I/O October 2022

AC Voltage Discrete Output Cards


Specifications for DO Card, 8-channel, 120/230V AC, High Side

Number of Channels Eight

Output Range 20 to 250V AC


Output Rating 375mA average per channel.
1.0 A maximum continuous per channel
(inrush 5 A for <100 ms; 20 A for <20 ms)
3.0 A maximum per card.
Off-State Leakage 2 mA maximum at 120V AC.
4 mA maximum at 230V AC.
Configurable Channel Types: Output signal profile.
„ Discrete Output Output stays in last state submitted by the control logic.
„ Momentary Output Output remains active for a pre-configured time period.
„ Continuous Pulse Output Output is active as a percentage of a pre-configured
base time period (100 ms to 100 s). Resolution = 5 ms.
Local Bus Current (12V DC Nominal) 100 mA typical, 150 mA maximum.

Field Circuit Power per Card 3.0 A at 120V AC or 230V AC.

Isolation Each channel is optically isolated from the system at 250V AC.

Optional Fuse 2.0 A (inrush 5A for <10 ms at 0.1% duty cycle).

Simplified circuit and connection diagram for DO card, 8-channel, 120/230V AC, High Side.

www.emerson.com/deltav 25
DeltaV S-series Traditional I/O October 2022

Specifications for DO Card, 8-channel, 120/230V AC, Isolated

Number of Channels Eight


Off-State Leakage 2 mA maximum at 120V AC.
4 mA maximum at 230V AC.
Output Range 20 to 250V AC.
Output Rating 375mA average per channel.
1.0A maximum continuous per channel;
(inrush 5A for <100 ms: 20A for <20 ms).
3.0A maximum per card.
Configurable Channel Types: Output signal profile.
„ Discrete Output Output stays in last state submitted by the control logic.
„ Momentary Output Output remains active for a pre-configured time period.
„ Continuous Pulse Output Output is active as a percentage of a pre-configured
base time period (100 ms to 100 s). Resolution = 5 ms.
Local Bus Current (12V DC Nominal) 100 mA typical, 150 mA maximum.

Field Circuit Power per Card None


Isolation Each channel is optically isolated from system
at 250V AC and from other channels at 250V AC.
Optional Fuse 2.0 A (inrush 5A for <10 ms at 0.1% duty cycle).

Simplified circuit and connection diagram for DO card, 8-channel, 120/230V AC, Isolated.

www.emerson.com/deltav 26
DeltaV S-series Traditional I/O October 2022

I/O Terminal Blocks There are nine different simplex I/O terminal blocks available
to meet the wiring needs of field signals.
A variety of I/O terminal blocks is available to meet specific
„ 8-channel terminal block
functionality and environmental requirements of the
installation. The I/O interface is a combination of the I/O card „ Fused 8-channel terminal block
and the I/O terminal block. Each I/O interface is uniquely keyed
„ AI 8-channel terminal block
so that once installed in a carrier slot with a terminal block,
that terminal block will only accept like replacement card. „ AI 16-channel terminal block

„ AO 16-channel terminal block

„ Discrete 32-channel terminal block

„ Isolated Input terminal block

„ RTD/Resistance terminal block

„ Thermocouple terminal block

The following redundant I/O terminal blocks are available


on some I/O interfaces, allowing a pair of cards to be installed
as a redundant pair.

„ Redundant AI 8-Channel terminal block

„ Redundant AI Plus 16-Channel terminal block


8-channel standard terminal block. „ Redundant AO 8-Channel terminal block

The keying mechanism consists of two keying posts that „ Redundant AO Plus 16-Channel terminal block
rotate and lock into the terminal block base. Each post has „ Redundant Discrete 8-Channel terminal block
six positions: A-F and 1-6. Each card is assigned a unique key
„ Redundant DI Plus 32-Channel terminal block
which is marked on the side of the I/O card:
„ Redundant DO Plus 32-Channel terminal block

The table on the following page lists the compatible terminal


blocks for each card, along with the cards unique key positions.
The first terminal block listed is the recommended
terminal block.

In addition to standard signal wiring, some cards may also be


ordered with Mass Terminal blocks that allow these cards to be
connected to the S-series Mass Connection Solutions or third
party wiring solutions from Phoenix or if IS Barriers are required
from Pepperl and Fuchs, mounted in an adjacent cabinet to
meet special signal conditioning or for optimizing field wiring
solutions. Please refer to the Alliance Program website for
details on approved third party products.
Keying position for HART AI, 4-20 mA, 8-channel.
„ 16-pin Mass Terminal Block (simplex only)
The keys prevent installation of an incorrect card, and the „ 24-pin Mass Terminal Block (simplex only)
graphical information on the card makes it easy to determine
„ 40-pin Mass Terminal Block (simplex and redundant)
if a keyed slot will accept a particular card.
„ 48-pin Mass Terminal Block (simplex and redundant)

www.emerson.com/deltav 27
DeltaV S-series Traditional I/O October 2022

Low Voltage Traditional I/O and terminal block compatibility


I/O
I/O Card Card Traditional I/O Terminal Blocks Mass Terminal Blocks
Keying
AI, 8-channel, A1 AI 8-Channel Terminal Block 16-pin Mass Terminal Block
4–20 mA, HART (Supports 2 and 4 wire devices). (Supports 2-wire Devices).
Redundant AI 8-channel Terminal Block. 24-pin Mass Terminal Block
Fused 8-Channel Terminal Block. (Supports 4-wire Devices).
8-Channel Terminal Block.
AI, 16-channel, A2 AI 16-Channel Terminal Block. NA
4-20 mA HART
AI Plus, 16-channel, A6 NA 48-pin AI Mass Terminal Block.
4-20 mA HART Redundant 48-pin Mass AI Term.
Block (Supports 2 and 4-wire Devices).
AO, 8-channel, A4 8-Channel Terminal Block. 16-pin Mass Terminal Block.
4–20 mA, HART Redundant AO 8-Channel Terminal Block.
Fused 8-Channel Terminal Block.
AO Plus, 16-channel, A5 AO 16-Channel Terminal Block. 48-pin AO Mass Terminal Block.
4-20 mA HART Redundant 48-pin.
Mass AO Term. Block.
Thermocouple, mV C1 Thermocouple Terminal Block. NA
8-Channel Terminal Block.
RTD, 8-channel C3 RTD/Resistance Terminal Block. NA

Isolated Input Card C2 Isolated Input Terminal Block. NA


DI, 8-channel, B1 8-Channel Terminal Block. 16-pin Mass Terminal Block.
24V DC, Dry Contact Redundant Discrete.
8-Channel Terminal Block.
Fused 8-Channel Terminal Block.
DI, 8-channel, B2 8-Channel Terminal Block. 16-pin Mass Terminal Block.
24V DC, Isolated Fused 8-Channel Terminal Block.
DI, 32-channel, B3 Discrete 32-Channel Terminal Block. 40-pin Mass Terminal Block.
24V DC Dry contact
DI Plus, 32-channel, E3 NA Redundant 40-pin Mass DI Term. Block
24V DC Dry contact (Supports Termination Fault Detection).
PCI, 4-channel C6 Discrete 32-Channel Terminal Block. NA
SOE, 16-channel, 24V DC C5 Discrete 32-Channel Terminal Block. 40-pin Mass Terminal Block.
DO, 8-channel, B6 8-Channel Terminal Block. 16-pin Mass Terminal Block.
24V DC, High-Side Redundant Discrete 8-Ch.
Terminal Block.
Fused 8-Channel Terminal Block.
DO, 8-channel, B5 8-Channel Terminal Block. 16-pin Mass Terminal Block.
24V DC, isolated Fused 8-Channel Terminal Block.
DO, 32-channel, B4 Discrete 32-Channel Terminal Block. 40-pin Mass Terminal Block.
24V DC High-Side
DO Plus, 32-channel, B4 NA Redundant 40-pin Mass DO Term. Block
24V DC High-Side (Supports Termination Fault Detection).

www.emerson.com/deltav 28
DeltaV S-series Traditional I/O October 2022

High Voltage Traditional I/O and terminal block compatibility


I/O Card Traditional I/O Mass Terminal
I/O Card
Keying Terminal Blocks Blocks
DI, 8-channel, 120V AC, Dry contact E1 8-Channel Terminal Block NA
Fused 8-Channel Terminal Block
DI, 8-channel, 120V AC, isolated E4 8-Channel Terminal Block NA
Fused 8-Channel Terminal Block
DO, 8-channel, 120V/ 230V AC, high side F1 8-Channel Terminal Block NA
Fused 8-Channel Terminal Block
DO, 8-channel, 120V/ 230V AC, isolated F4 8-Channel Terminal Block NA
Fused 8-Channel Terminal Block

System Compatibility
Termination Fault Detection is a feature that only works within
S-series traditional I/O hardware requires:
the following cards:
„ SQ or SX controllers.
„ DI Plus, 32-channel, 24V DC Dry contact.
„ S-series horizontal carriers.
„ DO Plus, 32-channel, 24V DC High-Side.
S-series and M-series controllers can be installed on the
when used with the redundant 40-pin Mass DI or DO Terminal
same DeltaV Area Control Network in v11.3.1 and beyond.
Block combined with the S-series Mass Connection Solutions
Control modules can be assigned to any controller and
or P+F HiD or HiC IS barriers and termination boards for
inter-controller references are fully supported.
DeltaV DCS.
DeltaV SIS Safety Logic Solvers can be installed under an
All other approved third party mass termination products may
S-series controller using SIS horizontal and verticalplus
be used with both non Plus S-series and M-series I/O interfaces.
carriers. Refer to PDS_SLS_1508_LogicSolver and
PDS_S-series_Horizontal_ Carriers and as well to the S-series traditional I/O does not install on vertical carriers.
PDS_S-series_VerticalPlus Carriers product data sheets For vertical I/O applications, use Electronic Marshalling
for more information. with CHARMS I/O.

The following traditional I/O Plus cards require v13.3 S-series traditional I/O horizontal carriers are not physically
or higher Software: compatible with M-series horizontal controller carriers.
Install S-series I/O interfaces with S-series controllers and
„ AI Plus, 4-20 mA HART, 16 channels.
M-series I/O interfaces with M-series controllers.
„ AO Plus, 4-20 mA HART, 16 channels.

„ DI Plus, 32-channel, 24V DC Dry contact.

„ DO Plus, 32-channel, 24V DC High-Side.

www.emerson.com/deltav 29
DeltaV S-series Traditional I/O October 2022

Certifications Hazardous Area/Location


The following certifications are available for S-series S-series traditional I/O Cards can be installed and used based
traditional I/O (see actual certificates for exact certifications on the following standards (see actual certificates for exact
for each product): product markings for each product):

„ CE: „ FM (USA):

EMC-EN 61326-1 Class I, Division 2, Groups A, B, C, D, T4

„ FM: „ cFM (Canada):

FM 3600 Class I, Division 2, Groups A, B, C, D, T4

FM 3611 „ ATEX:

„ CSA: Installation and Field Circuits:

CSA C22.2 No. 213 II 3G Ex ec IIC T4 Gc

CSA C22.2 No. 1010-1 II 3G Ex ec [ic] IIC T4 Gc

„ ATEX: II 3G Ex nA nC IIC T4 Gc

EN60079-0 „ IEC-Ex:

EN60079-7 Installation and Field Circuits:

„ IEC-Ex: II 3G Ex ec IIC T4 Gc

IEC60079-0 II 3G Ex ec ic IIC T4 Gc

EN60079-7 II 3G Ex nA nC IIC T4 Gc
Regarding the Installation instructions please refer to the following Documents:
IEC60079-15
Class 1 Division 2 Installation Instructions DeltaV S-series 12P5402
„ Marine Certifications: IACS E10: Zone 2 Installation Instructions DeltaV S-series 12P5404

ABS Certificate of Design Assessment.


DNV Marine Certificate.

www.emerson.com/deltav 30
DeltaV S-series Traditional I/O October 2022

Ordering Information
Analog Input Cards and Terminal Blocks

Description Model Number

Analog Input, 8 channels 4-20 mA, HART

AI Card: 8 channels 4-20 mA, HART, AI 8-Channel Terminal Block. SE4003S2B1**

AI Card: 8 channels 4-20 mA, HART, Fused 8-channel Terminal Block. SE4003S2B2**

AI Card: 8 channels 4-20 mA, HART, 16-Pin Mass I/O Terminal Block. SE4003S2B4**

AI Card: 8 channels 4-20 mA, HART, 24-Pin Mass I/O Terminal Block. SE4003S2B5**

Redundant Analog Input, 8 channels 4-20 mA, HART

2 x AI Card, 8 Ch, 4-20 mA, HART, AI 8-channel redundant Terminal Block. SE4033S2B1

Analog Input 16 channels 4-20 mA, HART

Analog Input Card: 16 channels 4-20 mA, HART, AI 16-Channel Terminal Block. SE4003S2B6
Analog Input Plus Card: 16 channels 4-20 mA, HART, 48 Pin AI Mass Terminal Block SE4003S2B11
(to be used with P+F HiD or HiC IS barriers and termination boards for DeltaV DCS).
Analog Input Plus Card: 16 channels 4-20 mA, HART, 48 Pin AI Mass Terminal Block SE4053S2B11
including 16-channel AI Mass Connection Board* supporting 2-& 4-wire Devices.
Redundant Analog Input 16 channels 4-20 mA, HART
2 x AI Plus Card: 16 channels 4-20 mA, HART, Red. 48 Pin AI Mass Terminal Block SE4033S2B11
(to be used with P+F HiD or HiC IS barriers and termination boards for DeltaV DCS).
2 x AI Plus Card: 16 channels 4-20 mA, HART, Red. 48 Pin AI Mass Terminal Block SE4083S2B11
including 16-channel AI Mass Connection Board* supporting 2-& 4-wire Devices.
RTD/Resistance, 8 channels

RTD Card: 8 channels, RTD/ Resistance Terminal Block. SE4003S6B1

Thermocouple/mV, 8 channels

mV Card: 8 channels; 8-ChanneL Terminal Block. SE4003S4B1

Thermocouple Card: 8 channels; Thermocouple Terminal Block. SE4003S5B1

Isolated Input, 4 Channels (Thermocouple/mV/V, RTD)

Isolated Input Card, 4 Channels; Isolated Input terminal Block. SE4003S7B1

*For more details on the Mass Connection Boards and connection cables, please refer to the S-series Mass Connection Solutions PDS.
** DNV Marine Certification pending. If DNV certification is required, please request KJ3222X1-BK1.

www.emerson.com/deltav 31
DeltaV S-series Traditional I/O October 2022

Analog Output Cards and Terminal Blocks

Description Model Number

Analog Output, 8 channels 4-20 mA, HART

AO Card: 8 channels 4-20 mA, HART, 8-Channel Terminal Block. SE4005S2B1

AO Card: 8 channels 4-20 mA, HART, Fused 8-Channel Terminal Block. SE4005S2B2

AO Card: 8 channels 4-20 mA, HART, 16-Pin Mass Terminal Block. SE4005S2B3

Redundant Analog Output, 8 channels 4-20 mA, HART

2 x AO Card, 8 Ch, 4-20 mA, HART, Redundant AO 8-Channel Terminal Block. SE4035S2B1

Analog Output 16 channels 4-20 mA, HART

Analog Output Plus Card: 16 channels 4-20 mA, HART, AO 16-ChannelTerminal Block. SE4005S2B4
Analog Output Plus Card: 16 channels 4-20 mA, HART, 48 Pin AO Mass Terminal Block SE4005S2B5
(to be used with P+F HiD or HiC IS barriers and termination boards for DeltaV DCS).
Analog Output Plus Card: 16 channels 4-20 mA, HART, 48 Pin AO Mass Terminal Block SE4055S2B5
including 16-channel AO Mass Connection Board*.
Redundant Analog Output 16 channels 4-20 mA, HART
2 x AO Plus Card: 16 channels 4-20 mA, HART, Red. 48 Pin AO Mass Terminal Block SE4035S2B5
(to be used with P+F HiD or HiC IS barriers and termination boards for DeltaV DCS).
2 x AO Plus Card: 16 channels 4-20 mA, HART, Red. 48 Pin AO Mass Terminal Block SE4085S2B5
including 16-channel AO Mass Connection Board*.

*For more details on the Mass Connection Boards and connection cables, please refer to the S-series Mass Connection Solutions PDS.

V DC Discrete Input Cards and Terminal Blocks

Description Model Number

Discrete Input Card: 8 channels, 24V DC, Dry Contact

DI Card: 8 channels, 24V DC, Dry Contact, 8-Channel Terminal Block. SE4001S2T2B1

DI Card: 8 channels, 24V DC, Dry Contact, Fused 8-Channel Terminal Block. SE4001S2T2B2

DI Card: 8 channels, 24V DC, Dry Contact, 16-Pin Mass Terminal Block. SE4001S2T2B3

Redundant Discrete Input, 8 channels, 24V DC, Dry Contact


2 x DI Card, 8 Ch, Redundant Discrete 8-Channel Terminal Block. SE4031S2T2B1

Discrete Input Card: 8 channels, 24V DC, Isolated

DI Card: 8 channels, 24V DC, Isolated, 8-Channel Terminal Block. SE4001S2T1B1

DI Card: 8 channels, 24V DC, Isolated, Fused 8-Channel Terminal Block. SE4001S2T1B2

DI Card: 8 channels, 24V DC, Isolated, 16-Pin Mass Terminal Block. SE4001S2T1B3

Discrete Input Card: 32 channels, 24 V DC, Dry Contact

DI Card: 32 channels, 24V DC, Dry Contact, Discrete 32-Channel Terminal Block. SE4001S2T2B4
DI Card: 32 channels, 24V DC, Dry Contact, 40-pin Mass Terminal Block SE4001S2T2B5
(to be used with P+F HiD or HiC IS barriers and termination boards for DeltaV DCS).
DI Card: 32 channels, 24V DC, Dry Contact, 40-pin Mass Terminal Block SE4051S2T2B5
including 2 x 16-channel DI Mass Connection Boards*.

www.emerson.com/deltav 32
DeltaV S-series Traditional I/O October 2022

V DC Discrete Input Cards and Terminal Blocks

Description Model Number

Redundant Discrete Input Card: 32 channels, 24V DC, Dry Contact


2 x DI Plus Card: 32 channels, 24V DC, Dry Contact, Red. 40-pin DI Mass Terminal Block SE4031S2T2B7
(to be used with P+F HiD or HiC IS barriers and termination boards for DeltaV DCS).
2 x DI Plus Card: 32 channels, 24V DC, Dry Contact, Red. 40-pin DI Mass Terminal Block SE4081S2T2B7
including 2 x 16-channel DI Mass Connection Boards*.
Pulse Count Input Card: 4 channels, 24V DC, Dry Contact

PCI Card: 4 Channels, 24V DC Dry Contact; Discrete 32-channel Terminal Block. SE4015

Sequence of Event Input Card: 16 channels, 24V DC Dry Contact

SOE Card: 16 channels, 24V DC, Dry Contact; Discrete 32-Channel Terminal Block. SE4001S5T2B4

SOE Card: 16 channels, 24V DC, Dry Contact; 40-pin Mass Terminal Block. SE4001S5T2B5

V DC Discrete Output Cards and Terminal Blocks

Description Model Number

Discrete Output Card: 8 channels 24V DC, High Side

DO Card: 8 channels 24V DC, High Side, 8-Channel Terminal Block. SE4002S1T2B1

DO Card: 8 channels 24V DC, High Side, Fused 8-Channel Terminal Block. SE4002S1T2B2

DO Card: 8 channels 24V DC, High Side, 16-Pin Mass Terminal Block. SE4002S1T2B3

Redundant Discrete Output, 8 channels, 24V DC, High Side

2 x DO Card, 8 Ch, High Side, Redundant Discrete 8-Channel Terminal Block. SE4032S1T2B1

Discrete Output Card: 8 channels 24V DC, Isolated

DO Card: 8 channels 24V DC, Isolated, 8-Channel Terminal Block. SE4002S1T1B1

DO Card: 8 channels 24V DC, Isolated, Fused 8-Channel Terminal Block. SE4002S1T1B2

DO Card: 8 channels 24V DC, Isolated, 16-Pin Mass Terminal Block. SE4002S1T1B3

Discrete Output Card, 32 channels, 24V DC, High Side

DO Card, 32 channels, 24V DC, High Side, Discrete 32-Channel Terminal Block. SE4002S1T2B5
DO Card, 32 channels, 24V DC, High Side, 40-Pin Mass I/O Terminal Block SE4002S1T2B6
(to be used with P+F HiD or HiC IS barriers and termination boards for DeltaV DCS).
DO Card: 32 channels, 24V DC, High Side, 40-Pin Mass I/O Terminal Block SE4052S1T2B6
including 4 x 8-channel DO Mass Connection Boards*.
Redundant Discrete Output Card, 32 channels, 24V DC, High Side
2 x DO Plus Card, 32 channels, 24V DC, High Side, 40-Pin DO Mass I/O Terminal Block SE4032S1T2B8
(to be used with P+F HiD or HiC IS barriers and termination boards for DeltaV DCS).
2 x DO Plus Card: 32 channels, 24V DC, High Side, 40-Pin DO Mass I/O Terminal Block SE4082S1T2B8
including 4 x 8-channel DO Mass Connection Boards*.

*For more details on the Mass Connection Boards and connection cables, please refer to the S-series Mass Connection Solutions PDS.

www.emerson.com/deltav 33
DeltaV S-series Traditional I/O October 2022

V AC Discrete Input Cards and Terminal Blocks

Description Model Number

Discrete Input Card: 8 channels, 120V AC, Isolated


DI Card: 8 channels, 120V AC, Isolated, 8-Channel Terminal Block SE4001S3T1B1
(1 Power Terminal Plug incl. for dedicated to disconnect 24V DC Power supply through
the 8-Wide I/O Carrier).
DI Card: 8 channels, 120V AC, Isolated, Fused 8-Channel Terminal Block SE4001S3T1B2
(1 Power Terminal Plug incl. to disconnect 24V DC Power supply through the 8-Wide I/O Carrier).
Discrete Input Card: 8 channels, 120V AC, Dry Contact
DI Card: 8 channels, 120V AC, Dry Contact, 8-Channel Terminal Block SE4001S3T2B1
(1 Power Terminal Plug incl. for dedicated Power supply through the 8-Wide I/O Carrier).
DI Card: 8 channels, 120V AC, Dry Contact, Fused 8-Channel Terminal Block SE4001S3T2B2
(1 Power Terminal Plug incl. for dedicated Power supply through the 8-Wide I/O Carrier).

V AC Discrete Input Cards and Terminal Blocks

Description Model Number

Discrete Output Card: 8 channels 120V/230V AC, Isolated


DO Card: 8 channels 120V/230V AC, Isolated, 8-Channel Terminal Block SE4002S2T1B1
(1 Power Terminal Plug incl. to disconnect 24V DC Power supply through the 8-Wide I/O Carrier).
DO Card: 8 channels 120V/230V AC, Isolated, Fused 8-Channel Terminal Block SE4002S2T1B2
(1 Power Terminal Plug incl. to disconnect 24V DC Power supply through the 8-Wide I/O Carrier).
Discrete Output Card: 8 channels 120V/230V AC, High Side
DO Card: 8 channels 120V/230V AC, High Side, 8-Channel Terminal Block SE4002S2T2B1
(1 Power Terminal Plug incl. for dedicated Power supply through the 8-Wide I/O Carrier).
DO Card: 8 channels 120V/230V AC, High Side, Fused 8-Channel Terminal Block SE4002S2T2B2
(1 Power Terminal Plug incl. for dedicated Power supply through the 8-Wide I/O Carrier).

www.emerson.com/deltav 34
DeltaV S-series Traditional I/O October 2022

Spare Part Ordering Information


Description Model Number

250V 2A Fuse for Fused Terminal Block; Box of 20 KJ4010X1-BC1

©2022, Emerson. All rights reserved.


The Emerson logo is a trademark and service mark of Emerson Electric Co. The DeltaV logo is
a mark of one of the Emerson family of companies. All other marks are the property of their
respective owners.
The contents of this publication are presented for informational purposes only, and while
diligent efforts were made to ensure their accuracy, they are not to be construed as warranties
or guarantees, express or implied, regarding the products or services described herein or their
use or applicability. All sales are governed by our terms and conditions, which are available on
Contact Us request. We reserve the right to modify or improve the designs or specifications of our products
www.emerson.com/contactus at any time without notice.

You might also like