The document provides installation instructions for a 3-LCD Main LCD Display Module. It describes connecting the display module to a 3-CPUx module by inserting mounting brackets, plugging the 3-CPUx module into the rail, sliding the display module onto the brackets, and connecting the ribbon and ground cables. Specifications for the display module like voltage, current draw, dimensions and compatible CPU models are also listed.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
151 views2 pages

3-LCD Installation

The document provides installation instructions for a 3-LCD Main LCD Display Module. It describes connecting the display module to a 3-CPUx module by inserting mounting brackets, plugging the 3-CPUx module into the rail, sliding the display module onto the brackets, and connecting the ribbon and ground cables. Specifications for the display module like voltage, current draw, dimensions and compatible CPU models are also listed.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

3-LCD Main LCD Display Module

Installation Sheet
Description To install the 3-LCD module:

The 3-LCD Main LCD Display Module provides the controls 1. Insert the display mounting brackets into the 3-CPUx
and indicators that make up the system user interface. See module. See Figure 2.
Figure 1. 2. Plug the 3-CPUx module into the rail, and then push the
plungers to lock the module into place. See Figure 3.
Figure 1: 3-LCD Main LCD Display Module
3. Position the 3-LCD module in its fully open position, align
the hinge pins with the hinges on the left display mounting
brackets on the 3-CPUx, and then gently slide the 3-LCD
into the brackets.
4. Connect the ribbon cable on the 3-LCD module to J1 on
the 3-CPUx module. See Figure 4.
5. Connect the ground cable on the 3-LCD module to the
two-pin header on the 3-CPUx module. The two-pin
header is located just above the Network B terminals
on TB2.
6. Verify the 3-LCD module can open and shut without
interference.

Figure 2: Display mounting bracket installation

(1) System status indicators (4) Event message controls


(2) Common controls (5) Keypad
(3) Display

At least one LCD display module is required to provide a point


of control for an entire network. Additional LCD display
modules can be installed to provide multiple points of control at
other locations throughout the protected premises.
The 3-LCD module mounts on a 3-CPUx module or on a
3-ANNCPUx module and occupies two LRM spaces on the
panel’s operator layer.

Installation
The instructions below are for new installations on a 3-CPUx (1) Top
module. Instructions for installing a 3-LCD module on a (2) Bottom
3-ANNCPUx module are similar.
If you are replacing an existing 3-LCD module (one with slide
locks), you must remove the display mounting brackets and the
rail fasteners on the 3-CPUx module or on the 3-ANNCPUx
module before proceeding.

© 2013 UTC Fire & Security Americas Corporation, Inc. 1/2 P/N 3100586-EN • REV 05 • ISS 18APR13
Figure 3: Mounting diagram Specifications
Voltage 24 VDC
Current See Table 1
Rail requirements Two slots on the operator layer
LCD display 64 × 128 pixels, backlit liquid crystal
Indicators Power: Green LED
Test: Yellow LED
CPU Failure: Yellow LED
Ground Fault: Yellow LED
Disable: Yellow LED
Reset: Yellow LED, integrated with Reset
switch
Alarm Silence: Yellow LED, integrated with
Alarm Silence switch
Panel Silence: Yellow LED, integrated with
Panel Silence switch
Drill: Yellow LED, integrated with Drill
(1) 3-CHAS7 (3) Primary power supply
switch
(2) Primary power supply monitor card
Alarm: Red LED
(4) 3-CPUx
Supervisory: Yellow LED
Trouble: Yellow LED
Monitor: Yellow LED
Figure 4: 3-LCD cable connections
Operator controls Reset switch
Alarm Silence switch
Panel Silence switch
Drill switch
Alarm queue switch
Supervisory queue switch
Trouble queue switch
Monitor queue switch
Message scroll switches
Ten-digit keypad with Enter and Delete
keys
Details switch
Command Menus switch
Compatible CPU models See Table 2
Operating environment
Temperature 32 to 120°F (0 to 49°C)
Relative humidity 0 to 93% noncondensing

Table 1: Current requirements


Connected to Standby current Alarm current
(1) Ribbon cable 3-CPU, 3-CPU1, 59 mA 59 mA
(2) Ground cable 3-ANNCPU1
3-CPU3, 3-ANNCPU3 43 mA 43 mA

Table 2: Compatible CPU models


Model Permitted in Permitted in
UL 864 8th edition UL 864 9th edition
3-CPU, 3-CPU1, Yes No
3-ANNCPU1
3-CPU3, 3-ANNCPU3 Yes Yes

Contact information
For contact information, see www.edwardsutcfs.com.