3-LCD Installation
3-LCD Installation
Installation Sheet
Description To install the 3-LCD module:
The 3-LCD Main LCD Display Module provides the controls 1. Insert the display mounting brackets into the 3-CPUx
and indicators that make up the system user interface. See module. See Figure 2.
Figure 1. 2. Plug the 3-CPUx module into the rail, and then push the
plungers to lock the module into place. See Figure 3.
Figure 1: 3-LCD Main LCD Display Module
3. Position the 3-LCD module in its fully open position, align
the hinge pins with the hinges on the left display mounting
brackets on the 3-CPUx, and then gently slide the 3-LCD
into the brackets.
4. Connect the ribbon cable on the 3-LCD module to J1 on
the 3-CPUx module. See Figure 4.
5. Connect the ground cable on the 3-LCD module to the
two-pin header on the 3-CPUx module. The two-pin
header is located just above the Network B terminals
on TB2.
6. Verify the 3-LCD module can open and shut without
interference.
Installation
The instructions below are for new installations on a 3-CPUx (1) Top
module. Instructions for installing a 3-LCD module on a (2) Bottom
3-ANNCPUx module are similar.
If you are replacing an existing 3-LCD module (one with slide
locks), you must remove the display mounting brackets and the
rail fasteners on the 3-CPUx module or on the 3-ANNCPUx
module before proceeding.
© 2013 UTC Fire & Security Americas Corporation, Inc. 1/2 P/N 3100586-EN • REV 05 • ISS 18APR13
Figure 3: Mounting diagram Specifications
Voltage 24 VDC
Current See Table 1
Rail requirements Two slots on the operator layer
LCD display 64 × 128 pixels, backlit liquid crystal
Indicators Power: Green LED
Test: Yellow LED
CPU Failure: Yellow LED
Ground Fault: Yellow LED
Disable: Yellow LED
Reset: Yellow LED, integrated with Reset
switch
Alarm Silence: Yellow LED, integrated with
Alarm Silence switch
Panel Silence: Yellow LED, integrated with
Panel Silence switch
Drill: Yellow LED, integrated with Drill
(1) 3-CHAS7 (3) Primary power supply
switch
(2) Primary power supply monitor card
Alarm: Red LED
(4) 3-CPUx
Supervisory: Yellow LED
Trouble: Yellow LED
Monitor: Yellow LED
Figure 4: 3-LCD cable connections
Operator controls Reset switch
Alarm Silence switch
Panel Silence switch
Drill switch
Alarm queue switch
Supervisory queue switch
Trouble queue switch
Monitor queue switch
Message scroll switches
Ten-digit keypad with Enter and Delete
keys
Details switch
Command Menus switch
Compatible CPU models See Table 2
Operating environment
Temperature 32 to 120°F (0 to 49°C)
Relative humidity 0 to 93% noncondensing
Contact information
For contact information, see www.edwardsutcfs.com.