SITUATION
The customer’s chemical plant has an Ultrafiltration Reverse Osmosis-
based water treatment facility in which incoming river water is treated for
demineralized water generation and subsequent usage in boilers and process
applications. While the incoming water quality (Total Dissolved Solid of 200
– 250 ppm and Total Suspended Solid of ~ 10 ppm during most parts of the
year with ~ 50% variation during monsoon) is well within acceptable limits,
the Reverse Osmosis system was struggling with severe performance-related
concerns for the last several months and system throughput was reduced
to almost 50% of design. In addition, due to prolonged operation with high
feed pressure and differential pressure, almost 30% of the membrane had
premature failure (within 9 – 12 months of installation).
SOLUTION
The Nalco Water team conducted a detailed survey of the pre-treatment
and the Ultrafiltration Reverse Osmosis plant; it was evident the system was
struggling with severe bio-fouling issues based on the available data trends.
While the microbial load in the incoming water was quite high, standard
bio-management best practices were also not in place. Limitations with the
cleaning pump existed as well (it was undersized to ensure sufficient scouring
velocity during cleaning).
e ROI
SM
eROI is our exponential value: the combined outcomes of improved performance, operational efficiency and sustainable impact
delivered through our services and programs.
The Nalco Water team proposed a two-step solution to the
customer:
ENVIRONMENTAL/ECONOMIC RESULTS
With this significant reduction in feed pressure, energy
consumption declined from 21.8 kWh to 16.5 kWh, which in
full scale operation is equivalent to 14 MWh of power.