KY8T1P6B

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 6

DEV REF.

MATERIAL NAME MAKE/BRAND DESCRIPTION

195 MVAXM31B1CH1005A GE/ALSTOM TRIP COIL SUPERVISION RELAY - TC-1


2M 2B SR : FLAG-REV : 220/250 V DC WD: 01MVAXM31 004
295 MVAXM31B1CH1005A GE/ALSTOM TRIP COIL SUPERVISION RELAY - TC-2
2M 2B SR : FLAG-REV : 220/250 V DC WD: 01MVAXM31 004
30AB MVAAM23D1BA2541A GE/ALSTOM AUXILIARY RELAY - BUCHOLZ/OTI TRIP
VX1 = 110-125V DC : VX2 = 220-250V DC : 2M 2 C/0 : 2M 2 C/O : HR  WD:F1MVAAM23001
30CD MVAAM23D1BA2541A GE/ALSTOM AUXILIARY RELAY - TRIP FROM DRIVE/SPARE
VX1 = 110-125V DC : VX2 = 220-250V DC : 2M 2 C/0 : 2M 2 C/O : HR  WD:F1MVAAM23001
30EF MVAAM23D1BA2541A GE/ALSTOM AUXILIARY RELAY - WTI/PRV TRIP
VX1 = 110-125V DC : VX2 = 220-250V DC : 2M 2 C/0 : 2M 2 C/O : HR  WD:F1MVAAM23001
30GH MVAAM23D1BA2541A GE/ALSTOM AUXILIARY RELAY - EMERGENCY TRIP FROM DRIVE/TRIP FROM PLC
VX1 = 110-125V DC : VX2 = 220-250V DC : 2M 2 C/0 : 2M 2 C/O : HR  WD:F1MVAAM23001
30JK MVAAM23D1BA2541A GE/ALSTOM AUXILIARY RELAY - CB CLOSE FROM PLC/CB CLOSE PERMISSIVE FROM PLC
VX1 = 110-125V DC : VX2 = 220-250V DC : 2M 2 C/0 : 2M 2 C/O : HR  WD:F1MVAAM23001
50ZX MVAJM15JA1002A GE/ALSTOM HIGH SPEED TRIPPING RELAY - LBB OPTD
220-250V DC: ELECTRICAL/HAND RESET: 8M + 2B CONTACT CONFIG: CASE SIZE:2
67/67N P14391RA6M0520J GE/ALSTOM NUMERICAL FEEDER MANAGEMENT RELAY
16I/P & 14O/P; AUX: 110-250 V DC / 100-240V AC, CT SEC: 1/5A, VN=100-120V AC;REDUNDANT ETHERNET
PRP/HSR/RSTP/HOT STANDBY, 2 MULTI-MODE FIBRE PORTS +MODULATED/UN-MODULATED IRIG-B
;IEC 61850 OVER ETHERNET AND COURIER VIA REAR K-BUS/RS485;
75A MVAJM14JB1000A1 GE/ALSTOM CONTROL RELAY E / R LOW BURDEN - BUS VT SELECTION
10 NO-ER : FOLLOW ON FLAG 220 TO 250 V DC WD:01 MVAJM14 011
75B MVAJM14JB1000A1 GE/ALSTOM CONTROL RELAY E / R LOW BURDEN - BUS VT SELECTION
10 NO-ER : FOLLOW ON FLAG 220 TO 250 V DC WD:01 MVAJM14 011
80A MVAAM11B1CJ5515A GE/ALSTOM AC SUPPLY SUPERVISION RELAY - AC SOURCE-1
4B SR : FLAG-REV : 240V 50HZ : 80-120 mS TDDO WD:Z1MVAAM11010SHT1
80B MVAAM11B1CJ5515A GE/ALSTOM AC SUPPLY SUPERVISION RELAY - AC SOURCE-2
4B SR : FLAG-REV : 240V 50HZ : 80-120 mS TDDO WD:Z1MVAAM11010SHT1
80C MVAAM11B1CJ5515A GE/ALSTOM AC SUPPLY SUPERVISION RELAY - AC CHANGEOVER
4B SR : FLAG-REV : 240V 50HZ : 80-120 mS TDDO WD:Z1MVAAM11010SHT1
80D MVAAM11B1CJ5516A GE/ALSTOM AC SUPPLY SUPERVISION RELAY - DC FAIL ACCEPT
2M 2C/O SR : FLAG-REV : VX1:110-125VAC/DC , VX2:220-250VAC/DC: 100+-20 MS WD:01 MVAAM11 014

SCHEME REF: ENGG.REF.NO: KY8T CUSTOMER: TATA STEEL - KPO LEGEND TO GA DRAWING PREPARED BY: KB REVISION: B

NETWORK NO.: . PROJECT: 132kV MSDS BH GE T&D India Ltd. PANEL TYPE: 1P6B FILE: KY8T1P6B CHECKED BY: JKK DATE: 24.08.2022

FINISHED GOOD: . P.O.NO.: 2300051008/118 Grid Automation-Pallavaram India TITLE: 132kV BF BLOWER-5 APPROVED BY: SSS SCALE: NIL
Dated 13.03.2019
SALES ORDER-ITEM: - DRG. NO.: CPG KY8T 1P6B (L) SHT 1 OF 6
DEV REF. MATERIAL NAME MAKE/BRAND DESCRIPTION

80E MVAAM11B1CJ1012A GE/ALSTOM DC SUPPLY SUPERVISION RELAY - DC SOURCE-1


1M 3B SR : FLAG-REV : 220-250V DC : 80-120 MS TDDO WD: 01MVAAM11021
80F MVAAM11B1CJ1012A GE/ALSTOM DC SUPPLY SUPERVISION RELAY - DC SOURCE-2
1M 3B SR : FLAG-REV : 220-250V DC : 80-120 MS TDDO WD: 01MVAAM11021
80G MVAAM11B1CJ1012A GE/ALSTOM DC SUPPLY SUPERVISION RELAY - DC SOURCE-1
1M 3B SR : FLAG-REV : 220-250V DC : 80-120 MS TDDO WD: 01MVAAM11021
80H MVAAM11B1CJ1012A GE/ALSTOM DC SUPPLY SUPERVISION RELAY - DC SOURCE-2
1M 3B SR : FLAG-REV : 220-250V DC : 80-120 MS TDDO WD: 01MVAAM11021
85 MVAJM15JA1002A GE/ALSTOM HIGH SPEED TRIPPING RELAY - INTERTRIP
220-250V DC: ELECTRICAL/HAND RESET: 8M + 2B CONTACT CONFIG: CASE SIZE:2
86A MVAJM15JA1002A GE/ALSTOM HIGH SPEED TRIPPING RELAY - GROUP-A
220-250V DC: ELECTRICAL/HAND RESET: 8M + 2B CONTACT CONFIG: CASE SIZE:2
86B MVAJM15JA1002A GE/ALSTOM HIGH SPEED TRIPPING RELAY - GROUP-B
220-250V DC: ELECTRICAL/HAND RESET: 8M + 2B CONTACT CONFIG: CASE SIZE:2
87T1 P64392RA6M0070M GE/ALSTOM NUMERICAL TRANSFORMER DIFF. PROTECTION RELAY - MAIN-1
16I/P & 16 O/P;60TE CASE; AUX: 110-250V DC(110-240V AC); IN:1/5A, VN:100-120V;REDUNDANT ETHERNET
PRP/HSR/RSTP/HOT STANDBY, 2 MULTIMODE FIBRE PORTS + MODULATED/UNMODULATED IRIG-B ;
IEC 61850 OVER ETHERNET AND COURIER VIA REAR K-BUS/RS485
87T2 P64392RA6M0070M GE/ALSTOM NUMERICAL TRANSFORMER DIFF. PROTECTION RELAY - MAIN-2
16I/P & 16 O/P;60TE CASE; AUX: 110-250V DC(110-240V AC); IN:1/5A, VN:100-120V;REDUNDANT ETHERNET
PRP/HSR/RSTP/HOT STANDBY, 2 MULTIMODE FIBRE PORTS + MODULATED/UNMODULATED IRIG-B ;
IEC 61850 OVER ETHERNET AND COURIER VIA REAR K-BUS/RS485
96 MVAJM15JA1002A GE/ALSTOM HIGH SPEED TRIPPING RELAY - BB OPTD
220-250V DC: ELECTRICAL/HAND RESET: 8M + 2B CONTACT CONFIG: CASE SIZE:2
BCU EC264-G8840 ALSTOM BAY CONTROL UNIT
6 DI, 3 DO , AUX DC:220V
BPTSS S24N90SPPM102 GE/ALSTOM SELECTOR SWITCH - BUS/LINE PT SELECTION
SELECTOR SWITCH 24 WAY NON-LOCK STAYPUT
DCSS GBSS-KAY-RP21012 KAYCEE DC.S/SW 4 POSITION SOURCE-1- INDEPENDENT-SOURCE-2
DSQ0 GBMK131122060 MULTIMODE DISCREPANCY CONTROL SWITCH WITH INBUILT LED LAMP AND FLASHER RELAY; MODEL NO : MK1311, AUX VOLTAGE
: 220 V DC, PLATE SIZE : 75X75MM, KNOB SIZE: 60MM DIA

SCHEME REF: ENGG.REF.NO: KY8T CUSTOMER: TATA STEEL - KPO LEGEND TO GA DRAWING PREPARED BY: KB REVISION: B

NETWORK NO.: . PROJECT: 132kV MSDS BH GE T&D India Ltd. PANEL TYPE: 1P6B FILE: KY8T1P6B CHECKED BY: JKK DATE: 24.08.2022

FINISHED GOOD: . P.O.NO.: 2300051008/118 Grid Automation-Pallavaram India TITLE: 132kV BF BLOWER-5 APPROVED BY: SSS SCALE: NIL
Dated 13.03.2019
SALES ORDER-ITEM: - DRG. NO.: CPG KY8T 1P6B (L) SHT 2 OF 6
DEV REF. MATERIAL NAME MAKE/BRAND DESCRIPTION

DSQ1 GBMK131122060 MULTIMODE DISCREPANCY CONTROL SWITCH WITH INBUILT LED LAMP AND FLASHER RELAY; MODEL NO : MK1311, AUX VOLTAGE
: 220 V DC, PLATE SIZE : 75X75MM, KNOB SIZE: 60MM DIA
DSQ2 GBMK131122060 MULTIMODE DISCREPANCY CONTROL SWITCH WITH INBUILT LED LAMP AND FLASHER RELAY; MODEL NO : MK1311, AUX VOLTAGE
: 220 V DC, PLATE SIZE : 75X75MM, KNOB SIZE: 60MM DIA
DSQ51 GBMK131122060 MULTIMODE DISCREPANCY CONTROL SWITCH WITH INBUILT LED LAMP AND FLASHER RELAY; MODEL NO : MK1311, AUX VOLTAGE
: 220 V DC, PLATE SIZE : 75X75MM, KNOB SIZE: 60MM DIA
DSQ53 GBMK131122060 MULTIMODE DISCREPANCY CONTROL SWITCH WITH INBUILT LED LAMP AND FLASHER RELAY; MODEL NO : MK1311, AUX VOLTAGE
: 220 V DC, PLATE SIZE : 75X75MM, KNOB SIZE: 60MM DIA
DSQ8 GBMK131122060 MULTIMODE DISCREPANCY CONTROL SWITCH WITH INBUILT LED LAMP AND FLASHER RELAY; MODEL NO : MK1311, AUX VOLTAGE
: 220 V DC, PLATE SIZE : 75X75MM, KNOB SIZE: 60MM DIA
DSQ9 GBMK131122060 MULTIMODE DISCREPANCY CONTROL SWITCH WITH INBUILT LED LAMP AND FLASHER RELAY; MODEL NO : MK1311, AUX VOLTAGE
: 220 V DC, PLATE SIZE : 75X75MM, KNOB SIZE: 60MM DIA
FC GBANNUN312B0-001 MINILEC MICROPROCESSOR BASED FACIA ANNUNCIATOR 3C*4R MANUAL RESET AUX
SUP:90-270 V AC / DC
K39 MVAAM11B1BA8254A ALSTOM AUXILIARY RELAY - LMS TRIP
4M 4B S/R; FLAG-YES : VX1 24-30 V DC; VX2 48-54 V DC ; WD:01MVAAM11027
LRS S16N90SPPM101 GE/ALSTOM SELECTOR SWITCH - CRP/SAS SELECTION
SELECTOR SWITCH 16 WAY NON-LOCK STAYPUT
MFM GBED5914000010274C SATEC MULTIFUNCTION METER PM130EH+; 3PH 4 WIRE 3 ELE; CL0.2S; CT /PT SEC: 1A/110V AC; AUX 110-240VAC/DC
; PT PRI: 33KV CT PRI: USER PROGRAMMABLE; RS485, MODBUS;
PB01 GBCPB1363104 SIEMENS PUSH BUTTON, BLACK,1N0+1NC - ANNUN ACCEPT
PB02 GBCPB1363104 SIEMENS PUSH BUTTON, BLACK,1N0+1NC - ANNUN RESET
PB03 GBCPB1363104 SIEMENS PUSH BUTTON, BLACK,1N0+1NC - ANNUN TEST
PB04 GBCPB1363104 SIEMENS PUSH BUTTON, BLACK,1N0+1NC - ANNUN MUTE
PB05 GBCPB1363104 SIEMENS PUSH BUTTON, BLACK,1N0+1NC - DC FAIL ACCEPT
PB06 GBCPB1363104 SIEMENS PUSH BUTTON, BLACK,1N0+1NC - DC-1 FAIL TEST
PB07 GBCPB1363104 SIEMENS PUSH BUTTON, BLACK,1N0+1NC - DC-2 FAIL TEST
PB08 GBCPB1363104 SIEMENS PUSH BUTTON, BLACK,1N0+1NC - 85 RESET
PB09 GBCPB1363104 SIEMENS PUSH BUTTON, BLACK,4N0 - DISC SW LAMP TEST
PS GBCPE0000346 ANCHOR/OSWAL 15/5A SOCKET 3 PIN 240V AC
SL01 GBCIL3315100 TEKNIC UNIVERSAL LED,24-240V AC/DC,WHITE - PANEL DC-1 HEALTHY
SL02 GBCIL3315100 TEKNIC UNIVERSAL LED,24-240V AC/DC,WHITE - PANEL DC-2 HEALTHY

SCHEME REF: ENGG.REF.NO: KY8T CUSTOMER: TATA STEEL - KPO LEGEND TO GA DRAWING PREPARED BY: KB REVISION: B

NETWORK NO.: . PROJECT: 132kV MSDS BH GE T&D India Ltd. PANEL TYPE: 1P6B FILE: KY8T1P6B CHECKED BY: JKK DATE: 24.08.2022

FINISHED GOOD: . P.O.NO.: 2300051008/118 Grid Automation-Pallavaram India TITLE: 132kV BF BLOWER-5 APPROVED BY: SSS SCALE: NIL
Dated 13.03.2019
SALES ORDER-ITEM: - DRG. NO.: CPG KY8T 1P6B (L) SHT 3 OF 6
DEV REF. MATERIAL NAME MAKE/BRAND DESCRIPTION

SL03 GBCIL3315100 TEKNIC UNIVERSAL LED,24-240V AC/DC,WHITE - TC-1/2 FAULTY


SL04 GBCIL3313100 TEKNIC UNIVERSAL LED,24-240V AC/DC,GREEN - Q69 ISO OPEN
SL05 GBCIL3312100 TEKNIC UNIVERSAL LED,24-240V AC/DC,RED - Q69 ISO CLOSE
SS S16LT90SPPM107 GE/ALSTOM SELECTOR SWITCH - SYNCH ON/OFF
SELECTOR SWITCH 16 WAY LOCKABLE STAYPUT
TTB GBCTB4000010 DAV TEST TERMINAL BLOCK 3PH,4WIRE, TYPE SSBL - MFM

INTERNALLY MOUNTED EQUIPMENTS

80AC1 GB3TF34000AUP041 SIEMENS SIEMENS CONTACTOR-240V AC- 4NO+1NC-FOR AC CHANGE OVER CIRCUIT
80AC2 GB3TF34000AUP041 SIEMENS SIEMENS CONTACTOR-240V AC- 4NO+1NC-FOR AC CHANGE OVER CIRCUIT
80DCO1 GB3TC44170AM442 SIEMENS SIEMENS CONTACTOR-220V DC- 4NO+2NC-FOR DC CHANGE OVER CIRCUIT
80DCO2 GB3TC44170AM442 SIEMENS SIEMENS CONTACTOR-220V DC- 4NO+2NC-FOR DC CHANGE OVER CIRCUIT
CIL GBCPE0000600F PHILIPS 2 FEET LED LAMP - 12W WITH DOOR SWITCH
CILS GBCPF0500901 SWITRON HEATER SWITCH CUBICLE ILLUMINATION LAMP SWITCH
D1 GBDIODE51HM60 RUTTONSHA FORWARD DIODE 50A,PIV-600V ,MILTARY GRADE 51HM60
D2 GBDIODE51HM60 RUTTONSHA FORWARD DIODE 50A,PIV-600V ,MILTARY GRADE 51HM60
D3 GBDIODE51HM60 RUTTONSHA FORWARD DIODE 50A,PIV-600V ,MILTARY GRADE 51HM60
D4 GBDIODE51HM60 RUTTONSHA FORWARD DIODE 50A,PIV-600V ,MILTARY GRADE 51HM60
D10 GBDIN4007 REPUTED DIODE IN4007 ; DC BLOCKING VOLTAGE - 1000V ; AVERAGE RECTIFIED OUTPUT CURRENT - 1A
D11 GBDIN4007 REPUTED DIODE IN4007 ; DC BLOCKING VOLTAGE - 1000V ; AVERAGE RECTIFIED OUTPUT CURRENT - 1A
D12 GBDIN4007 REPUTED DIODE IN4007 ; DC BLOCKING VOLTAGE - 1000V ; AVERAGE RECTIFIED OUTPUT CURRENT - 1A
D13 GBDIN4007 REPUTED DIODE IN4007 ; DC BLOCKING VOLTAGE - 1000V ; AVERAGE RECTIFIED OUTPUT CURRENT - 1A
D14 GBDIN4007 REPUTED DIODE IN4007 ; DC BLOCKING VOLTAGE - 1000V ; AVERAGE RECTIFIED OUTPUT CURRENT - 1A
D15 GBDIN4007 REPUTED DIODE IN4007 ; DC BLOCKING VOLTAGE - 1000V ; AVERAGE RECTIFIED OUTPUT CURRENT - 1A
D16 GBDIN4007 REPUTED DIODE IN4007 ; DC BLOCKING VOLTAGE - 1000V ; AVERAGE RECTIFIED OUTPUT CURRENT - 1A
D17 GBDIN4007 REPUTED DIODE IN4007 ; DC BLOCKING VOLTAGE - 1000V ; AVERAGE RECTIFIED OUTPUT CURRENT - 1A
D18 GBDIN4007 REPUTED DIODE IN4007 ; DC BLOCKING VOLTAGE - 1000V ; AVERAGE RECTIFIED OUTPUT CURRENT - 1A
D5 GBDIN4007 REPUTED DIODE IN4007 ; DC BLOCKING VOLTAGE - 1000V ; AVERAGE RECTIFIED OUTPUT CURRENT - 1A
D6 GBDIN4007 REPUTED DIODE IN4007 ; DC BLOCKING VOLTAGE - 1000V ; AVERAGE RECTIFIED OUTPUT CURRENT - 1A
D7 GBDIN4007 REPUTED DIODE IN4007 ; DC BLOCKING VOLTAGE - 1000V ; AVERAGE RECTIFIED OUTPUT CURRENT - 1A
D8 GBDIN4007 REPUTED DIODE IN4007 ; DC BLOCKING VOLTAGE - 1000V ; AVERAGE RECTIFIED OUTPUT CURRENT - 1A
D9 GBDIN4007 REPUTED DIODE IN4007 ; DC BLOCKING VOLTAGE - 1000V ; AVERAGE RECTIFIED OUTPUT CURRENT - 1A

SCHEME REF: ENGG.REF.NO: KY8T CUSTOMER: TATA STEEL - KPO LEGEND TO GA DRAWING PREPARED BY: KB REVISION: B

NETWORK NO.: . PROJECT: 132kV MSDS BH GE T&D India Ltd. PANEL TYPE: 1P6B FILE: KY8T1P6B CHECKED BY: JKK DATE: 24.08.2022

FINISHED GOOD: . P.O.NO.: 2300051008/118 Grid Automation-Pallavaram India TITLE: 132kV BF BLOWER-5 APPROVED BY: SSS SCALE: NIL
Dated 13.03.2019
SALES ORDER-ITEM: - DRG. NO.: CPG KY8T 1P6B (L) SHT 4 OF 6
DEV REF. MATERIAL NAME MAKE/BRAND DESCRIPTION

EBZ GBCBH1000000 BHARANI MULTITONE BUZZER 40-300VDC/240VAC - FOR ANNUNCIATION


HS GBCPF0500901 SWITRON HEATER SWITCH
HT GBCPA0178101SURYA SURYA 230V,60 WATTS HEATER
K1A GBDRM570220LTC WEIDMULLER PLUG IN MINIATURE RELAY WITH LED ,TEST LEVER; MODEL DRM570220LT; 4 C/O; AUX: 220V DC;
MCB1 GBCMB7245100A LEGRAND/ABB MCB DOUBLE POLE 110/240V AC 32A WITH 1C/O CONTACT
MCB11 GBCMB7213100A LEGRAND/ABB MCB DOUBLE POLE 110/250V DC 6A WITH 1C/O CONTACT
MCB12 GBCMB7212100A LEGRAND/ABB MCB DOUBLE POLE 110/250V DC 4A WITH 1C/O CONTACT
MCB13 GBCMB7213100A LEGRAND/ABB MCB DOUBLE POLE 110/250V DC 6A WITH 1C/O CONTACT
MCB14 GBCMB7212100A LEGRAND/ABB MCB DOUBLE POLE 110/250V DC 4A WITH 1C/O CONTACT
MCB15 GBCMB7215100A LEGRAND/ABB MCB DOUBLE POLE 110/250V DC 16A WITH 1C/O CONTACT
MCB17 GBCMB7215100A LEGRAND/ABB MCB DOUBLE POLE 110/250V DC 16A WITH 1C/O CONTACT
MCB2 GBCMB7245100A LEGRAND/ABB MCB DOUBLE POLE 110/240V AC 32A WITH 1C/O CONTACT
MCB21 GBCMB7213100A LEGRAND/ABB MCB DOUBLE POLE 110/250V DC 6A WITH 1C/O CONTACT
MCB22 GBCMB7213100A LEGRAND/ABB MCB DOUBLE POLE 110/250V DC 6A WITH 1C/O CONTACT
MCB23 GBCMB7212100A LEGRAND/ABB MCB DOUBLE POLE 110/250V DC 4A WITH 1C/O CONTACT
MCB24 GBCMB7215100A LEGRAND/ABB MCB DOUBLE POLE 110/250V DC 16A WITH 1C/O CONTACT
MCB26 GBCMB7214100A LEGRAND/ABB MCB DOUBLE POLE 110/250V DC 10A WITH 1C/O CONTACT
MCB27 GBCMB7213100A LEGRAND/ABB MCB DOUBLE POLE 110/250V DC 6A WITH 1C/O CONTACT
MCB3 GBCMB7224100A LEGRAND/ABB MCB DOUBLE POLE 110/240V AC 10A WITH 1C/O CONTACT
MCB4 GBCMB7223100A LEGRAND/ABB MCB DOUBLE POLE 110/240V AC 6A WITH 1C/O CONTACT
MCB41 GBCMB7257100A LEGRAND/ABB MCB TRIPLE POLE+ NEUTRAL 110/240V AC 2A WITH 1C/O CONTACT
MCB42 GBCMB7257100A LEGRAND/ABB MCB TRIPLE POLE+ NEUTRAL 110/240V AC 2A WITH 1C/O CONTACT
MCB43 GBCMB7221100A LEGRAND/ABB MCB DOUBLE POLE 110/240V AC 2A WITH 1C/O CONTACT
MCB44 GBCMB7221100A LEGRAND/ABB MCB DOUBLE POLE 110/240V AC 2A WITH 1C/O CONTACT
MCB45 GBCMB7257100A LEGRAND/ABB MCB TRIPLE POLE+ NEUTRAL 110/240V AC 2A WITH 1C/O CONTACT
MCB5 GBCMB7255100A LEGRAND/ABB MCB DOUBLE POLE 110/250V DC 32A WITH 1C/O CONTACT
MCB51 GBCMB7257100 LEGRAND/ABB MCB TRIPLE POLE+ NEUTRAL 110/240V AC 2A
MCB52 GBCMB7257100 LEGRAND/ABB MCB TRIPLE POLE+ NEUTRAL 110/240V AC 2A
MCB53 GBCMB7257100 LEGRAND/ABB MCB TRIPLE POLE+ NEUTRAL 110/240V AC 2A
MCB54 GBCMB7257100 LEGRAND/ABB MCB TRIPLE POLE+ NEUTRAL 110/240V AC 2A
MCB55 GBCMB7257100 LEGRAND/ABB MCB TRIPLE POLE+ NEUTRAL 110/240V AC 2A
MCB56 GBCMB7257100 LEGRAND/ABB MCB TRIPLE POLE+ NEUTRAL 110/240V AC 2A

SCHEME REF: ENGG.REF.NO: KY8T CUSTOMER: TATA STEEL - KPO LEGEND TO GA DRAWING PREPARED BY: KB REVISION: B

NETWORK NO.: . PROJECT: 132kV MSDS BH GE T&D India Ltd. PANEL TYPE: 1P6B FILE: KY8T1P6B CHECKED BY: JKK DATE: 24.08.2022

FINISHED GOOD: . P.O.NO.: 2300051008/118 Grid Automation-Pallavaram India TITLE: 132kV BF BLOWER-5 APPROVED BY: SSS SCALE: NIL
Dated 13.03.2019
SALES ORDER-ITEM: - DRG. NO.: CPG KY8T 1P6B (L) SHT 5 OF 6
DEV REF. MATERIAL NAME MAKE/BRAND DESCRIPTION

MCB6 GBCMB7255100A LEGRAND/ABB MCB DOUBLE POLE 110/250V DC 32A WITH 1C/O CONTACT
MCB91 GBCMB7225100A LEGRAND/ABB MCB DOUBLE POLE 110/240V AC 16A WITH 1C/O CONTACT
R50ZX MZB9015006 RESISTOR 3.3K
R85 MZB9015006 RESISTOR 3.3K
R86A MZB9015006 RESISTOR 3.3K
R86B MZB9015006 RESISTOR 3.3K
R96 MZB9015006 RESISTOR 3.3K
TH GBCPE0000612 APT THERMOSTAT

SCHEME REF: ENGG.REF.NO: KY8T CUSTOMER: TATA STEEL - KPO LEGEND TO GA DRAWING PREPARED BY: KB REVISION: B

NETWORK NO.: . PROJECT: 132kV MSDS BH GE T&D India Ltd. PANEL TYPE: 1P6B FILE: KY8T1P6B CHECKED BY: JKK DATE: 24.08.2022

FINISHED GOOD: . P.O.NO.: 2300051008/118 Grid Automation-Pallavaram India TITLE: 132kV BF BLOWER-5 APPROVED BY: SSS SCALE: NIL
Dated 13.03.2019
SALES ORDER-ITEM: - DRG. NO.: CPG KY8T 1P6B (L) SHT 6 OF 6