Motor Operator
Motor Operator
Wiring Connections
Standard Connection
The Circuit breaker can be operated remotely or manually.
** Both AL and FAL Auxiliaries uses the same circuit diagram. AL=FAL
Manual Operation
1. Insert the manual handle into the slot of Motor
Operator surface and rotate it clockwise.
2. It must be rotated just 180° clockwise for safe
operation of micro switch in the motor operator.
3. Return the manual handle after the manual
operation
4. Turn the slide switch back to the position of
AUTO.
Automatic operation
1. Set the slide switch to AUTO, then internal
power is closed automatically.
2. Operating frequency should be less than these
below regulated values. TD160N/H/L,
TS250N/H/L:180 operations per hour
3. Use the ON/OFF switch in the range of
regulated values.
4. It may interfere near communication
equipment’s because of internal switching
power supply. It is recommended that a noise
filter be installed to power supply.
5. Please do not input ON/OFF signals at the
same time during the automatic operation.
6. If the circuit breaker has a UVT attached inside,
charge the UVT on the rated voltage before
performing the MOTOR OPERATOR.