The document discusses process control using PID controllers. PID controllers attempt to correct the error between a measured process variable and desired setpoint by calculating the difference and adjusting the process accordingly. They do this through three parameters: Proportional (P), Integral (I), and Derivative (D). While on/off controllers are simpler, PID controllers allow for better fine-tuning adjustments and control of industrial processes. The document then discusses the specifics of P, I, and D control parameters and their effects on process control.

Uploaded by

cyprian obota
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
66 views28 pages

Pid Eeee

The document discusses process control using PID controllers. PID controllers attempt to correct the error between a measured process variable and desired setpoint by calculating the difference and adjusting the process accordingly. They do this through three parameters: Proportional (P), Integral (I), and Derivative (D). While on/off controllers are simpler, PID controllers allow for better fine-tuning adjustments and control of industrial processes. The document then discusses the specifics of P, I, and D control parameters and their effects on process control.

Uploaded by

cyprian obota
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 28

Introduction

Process controls are necessary for designing safe and productive plants. A variety of
process controls are used to manipulate processes, however the most simple and often
most effective is the PID controller. The controller attempts to correct the error
between a measured process variable and desired setpoint by calculating the difference
and then performing a corrective action to adjust the process accordingly. A PID
controller controls a process through three parameters: Proportional (P), Integral (I),
and Derivative (D). These parameters can be weighted, or tuned, to adjust their effect
on the process.

Much more practical than the typical on/off controller, PID controllers allow for much
better adjustments to be made in the system. While this is true, there are some
advantages to using an on/off controller including that they are (1) relatively simple to
design and execute and (2) binary sensors and actuators (such as an on/off controller)
are generally more reliable and less expensive.

Although there are some advantages, there are large disadvantages to using an on/off
controller scheme. They are (1) inefficient (using this control is like driving with full gas
and full breaks), (2) can generate noise when seeking stability (can dramatically
overshoot or undershoot a set-point), and (3) physically wearing on valves and switches
(continuously turning valves/switches fully on and fully off causes them to become worn
out much quicker).

To allow for much better control and fine-tuning adjustments, most industrial processes
use a PID controller scheme. This section will provide a brief introduction on PID
controllers as well as methods to model a controlled system in Excel.

The Process Gain (K) is the ratio of change of the output variable (responding


variable) to the change of the input variable (forcing function). It specifically defines the
sensitivity of the output variable to a given change in the input variable.

Gain can only be described as a steady state parameter and give no knowledge about
the dynamics of the process and is independent of the design and operating variables.
A gain has three components that include the sign, the value, the units. The sign
indicates how the output responds to the process input. A positive sign shows that the
output variable increases with an increase in the input variable and a negative sign
shows that the output variable decreases with an increase in the input variable. The
units depend on the process considered that depend on the variables mentioned.
For example, the pressure was increased from 21 psi to 29 psi. This change increased
the valve position from 30% vp to 22% vp.

Dead Time (t0) is the between the change in an input variable and when the
output variable begins. Dead time is important because it effects the
controllability of the control system. A change in set point is not immediate
because of this parameter. Dead time must be considered in tuning and
modeling processes.

Types of Control
Process controls are instruments used to control a parameter, such as temperature,
level, and pressure. PID controllers are a type of continuous controller because they
continually adjust the output vs. an on/off controller, when looking at feed forward or
feed backward conditions. An example of a temperature controller is shown in
Figure 9.2.1

As shown in Figure 1, the temperature controller controls the temperature of a


fluid within a CSTR (Continuous Stirred Tank Reactor). A temperature sensor first
measures the temperature of the fluid. This measurement produces a
measurement signal. The measurement signal is then compared to the set point,
or desired temperature setting, of the controller. The difference between the
measured signal and set point is the error. Based on this error, the controller
sends an actuating signal to the heating coil, which adjusts the temperature
accordingly. This type of process control is known as error-based control because
the actuating signal is determined from the error between the actual and desired
setting. The different types of error-based controls vary in the mathematical way
they translate the error into an actuating signal, the most common of which are
the PID controllers. Additionally, it is critical to understand feed-forward and
feed-back control before exploring P, I, and D controls. Feed Forward Control
Feedback Control

I, D, PI, PD, PID Control


As previously mentioned, controllers vary in the way they correlate the controller input
(error) to the controller output (actuating signal). The most commonly used controllers
are the proportional-integral-derivative (PID) controllers. PID controllers relate
the error to the actuating signal either in a proportional (P), integral (I), or derivative
(D) manner. PID controllers can also relate the error to the actuating signal using a
combination of these controls.

Proportional (P) Control

One type of action used in PID controllers is the proportional control. Proportional control is a
form of feedback control. It is the simplest form of continuous control that can be used in a
closed-looped system. P-only control minimizes the fluctuation in the process variable, but it
does not always bring the system to the desired set point. It provides a faster response than
most other controllers, initially allowing the P-only controller to respond a few seconds faster.
However, as the system becomes more complex (i.e. more complex algorithm) the response
time difference could accumulate, allowing the P-controller to possibly respond even a few
minutes faster. Although the P-only controller does offer the advantage of faster response time,
it produces deviation from the set point. This deviation is known as the offset, and it is usually
not desired in a process. The existence of an offset implies that the system could not be
maintained at the desired set point at steady state. It is analogous to the systematic error in a
calibration curve, where there is always a set, constant error that prevents the line from
crossing the origin. The offset can be minimized by combining P-only control with another form
of control, such as I- or D- control. It is important to note, however, that it is impossible to
completely eliminate the offset, which is implicitly included within each equation.

P-control linearly correlates the controller output (actuating signal) to the error
(diference between measured signal and set point). This P-control behavior is
mathematically illustrated in Equation 9.2.19.2.1 (Scrcek, et. al).
In this equation, the bias and controller gain are constants specific to each controller.
The bias is simply the controller output when the error is zero. The controller gain is the
change in the output of the controller per change in the input to the controller. In PID
controllers, where signals are usually electronically transmitted, controller gain relates
the change in output voltage to the change in input voltage. These voltage changes are
then directly related to the property being changed (i.e. temperature, pressure, level,
etc.). Therefore, the gain ultimately relates the change in the input and output
properties. If the output changes more than the input, Kc will be greater than 1. If the
change in the input is greater than the change in the output, Kc will be less than 1.
Ideally, if Kc is equal to infinity, the error can be reduced to zero. However, this
infinitesimal nature of Kc increases the instability of the loop because zero error would
imply that the the measured signal is exactly equal to the set point. As mentioned in
lecture, exact equality is never achieved in control logic; instead, in control logic, error
is allowed to vary within a certain range. Therefore, there are limits to the size of Kc,
and these limits are defined by the system. Graphical representations of the effects of
these variables on the system is shown in PID Tuning via Classical Methods.

As can be seen from the above equation, P-only control provides a linear relationship
between the error of a system and the controller output of the system. This type of
control provides a response, based on the signal that adjusts the system so that any
oscillations are removed, and the system returns to steady-state. The inputs to the
controller are the set point, the signal, and the bias. The controller calculates the
difference between the set point and the signal, which is the error, and sends this value
to an algorithm. Combined with the bias, this algorithm determines the action that the
controller should take. A graphical representation of the P-controller output for a step
increase in input at time t0 is shown below in Figure 2. This graph is exactly similar to
the step input graph itself.
To illustrate this linear P-control relationship, consider the P-only control that controls the level
of a fluid in a tank. Initially, the flow into the tank is equal to the flow out of the tank. However,
if the flow out of the tank decreases, the level in the tank will increase because more fluid is
entering than is leaving. The P-only control system will adjust the flow out of the tank so that it
is again equal to the flow into the tank, and the level will once again be constant. However, this
level is no longer equal to the initial level in the tank. The system is at steady-state, but there is
a difference between the initial set point and the current position in the tank. This difference is
the P-control offset.

Integral (I) Control

Another type of action used in PID controllers is the integral control. Integral control is a second
form of feedback control. It is often used because it is able to remove any deviations that may
exist. Thus, the system returns to both steady state and its original setting. A negative error will
cause the signal to the system to decrease, while a positive error will cause the signal to
increase. However, I-only controllers are much slower in their response time than P-only
controllers because they are dependent on more parameters. If it is essential to have no offset
in the system, then an I-only controller should be used, but it will require a slower response
time. This slower response time can be reduced by combining I-only control with another form,
such as P or PD control. I-only controls are often used when measured variables need to remain
within a very narrow range and require fine-tuning control. I controls affect the system by
responding to accumulated past error. The philosophy behind the integral control is that
deviations will be affected in proportion to the cumulative sum of their magnitude. The key
advantage of adding a I-control to your controller is that it will eliminate the offset. The
disadvantages are that it can destabilize the controller, and there is an integrator windup, which
increases the time it takes for the controller to make changes.

I-control correlates the controller output to the integral of the error. The integral of the error is
taken with respect to time. It is the total error associated over a specified amount of time. This
I-control behavior is mathematically illustrated in Equation 9.2.2 (Scrcek, et. al).
In Equation 9.2.29.2.2, the integral time is the amount of time that it takes for the
controller to change its output by a value equal to the error. The controller output
before integration is equal to either the initial output at time t=0, or the controller
output at the time one step before the measurement. Graphical representations of the
effects of these variables on the system is shown in PID Tuning via Classical Methods.

The rate of change in controller output for I-only control is determined by a number of
parameters. While the P-only controller was determined by e, the rate of change for I-
only depends on both e and Ti. Because of the inverse relationship between c(t) and Ti,
this decreases the rate of change for an I-only controller.

The I-only controller operates in essentially the same way as a P-only controller. The
inputs are again the set point, the signal, and the bias. Once again, the error is
calculated, and this value is sent to the algorithm. However, instead of just using a
linear relationship to calculate the response, the algorithm now uses an integral to
determine the response that should be taken. Once the integral is evaluated, the
response is sent and the system adjusts accordingly. Because of the dependence on Ti,
it takes longer for the algorithm to determine the proper response. A graphical
representation of the I-controller output for a step increase in input at time t0 is shown
below in Figure 3. As expected, this graph represents the area under the step input
graph.
Derivative (D) Control

Another type of action used in PID controllers is the derivative control. Unlike P-only
and I-only controls, D-control is a form of feed forward control. D-control anticipates
the process conditions by analyzing the change in error. It functions to minimize the
change of error, thus keeping the system at a consistent setting. The primary benefit of
D controllers is to resist change in the system, the most important of these being
oscillations. The control output is calculated based on the rate of change of the error
with time. The larger the rate of the change in error, the more pronounced the
controller response will be.

Unlike proportional and integral controllers, derivative controllers do not guide the
system to a steady state. Because of this property, D controllers must be coupled with
P, I or PI controllers to properly control the system.

D-control correlates the controller output to the derivative of the error. The derivative
of the error is taken with respect to time. It is the change in error associated with
change in time. This D-control behavior is mathematically illustrated in
Equation 9.2.3(Scrcek, et. al).

Graphical representations of the effects of these variables on the system is shown in


PID Tuning via Classical Methods.

Mathematically, derivative control is the opposite of integral control. Although I-only


controls exist, D-only controls do not exist. D-controls measure only the change in
error. D-controls do not know where the setpoint is, so it is usually used in conjunction
with another method of control, such as P-only or a PI combination control. D-control is
usually used for processes with rapidly changing process outputs. However, like the I-
control, the D control is mathematically more complex than the P-control. Since it will
take a computer algorithm longer to calculate a derivative or an integral than to simply
linearly relate the input and output variables, adding a D-control slows down the
controller’s response time. A graphical representation of the D-controller output for a
step increase in input at time t0 is shown below in Figure 4. As expected, this graph
represents the derivative of the step input graph.

Controller Effects on a System


The following images are intended to give a visual representation of how P, I, and D
controllers will affect a system.

Description

Figure 5. Stable data sample.


Continue reading to see the results of combining controllers.

Proportional-Integral (PI) Control

One combination is the PI-control, which lacks the D-control of the PID system. PI control is a
form of feedback control. It provides a faster response time than I-only control due to the
addition of the proportional action. PI control stops the system from fluctuating, and it is also
able to return the system to its set point. Although the response time for PI-control is faster
than I-only control, it is still up to 50% slower than P-only control. Therefore, in order to
increase response time, PI control is often combined with D-only control.

PI-control correlates the controller output to the error and the integral of the error. This PI-
control behavior is mathematically illustrated in Equation 9.2.4 (Scrcek, et. al).

In this equation, the integral time is the time required for the I-only portion of the
controller to match the control provided by the P-only part of the controller.

The equation indicates that the PI-controller operates like a simplified PID-controller
with a zero derivative term. Alternatively, the PI-controller can also be seen as a
combination of the P-only and I-only control equations. The bias term in the P-only
control is equal to the integral action of the I-only control. The P-only control is only in
action when the system is not at the set point. When the system is at the set point, the
error is equal to zero, and the first term drops out of the equation. The system is then
being controlled only by the I-only portion of the controller. Should the system deviate
from the set point again, P-only control will be enacted. A graphical representation of
the PI-controller output for a step increase in input at time t0 is shown below in Figure
5. As expected, this graph resembles the qualitative combination of the P-only and I-
only graphs.
Effects of Kc and Ti

With a PI control system, controller activity (aggressiveness) increases


as Kc and Ti decreases, however they can act individually on the aggressiveness of a
controller’s response. Consider Figure 11 below with the center graph being a linear
second order system base case.
The plot depicts how Ti and Kc both affect the performance of a system, whether they
are both affecting it or each one is independently doing so. Regardless of integral time,
increasing controller gain (moving form bottom to top on the plot) will increase
controller activity. Similarly, decreasing integral time (moving right to left on the plot)
will increase controller activity independent of controller gain. As expected,
increasing Kc and decreasing Ti would compound sensitivity and create the most
aggressive controller scenario.

With only two interacting parameters in PI control systems, similar performance plots
can still cause confusion. For example, plots A and B from the figure both look very
similar despite different parameters being affected in each of them. This could cause
further problems and create a wildly aggressive system if the wrong parameter is being
corrected. While trial and error may be feasible for a PI system, it becomes
cumbersome in PID where a third parameter is introduced and plots become
increasingly similar.

Another noteworthy observation is the plot with a normal Kc and double Ti. The plot
depicts how the proportional term is practical but the integral is not receiving enough
weight initially, causing the slight oscillation before the integral term can finally catch up
and help the system towards the set point.
Proportional-Derivative (PD) Control

Another combination of controls is the PD-control, which lacks the I-control of the PID
system. PD-control is combination of feedforward and feedback control, because it
operates on both the current process conditions and predicted process conditions. In
PD-control, the control output is a linear combination of the error signal and its
derivative. PD-control contains the proportional control’s damping of the fluctuation and
the derivative control’s prediction of process error.

As mentioned, PD-control correlates the controller output to the error and the derivative
of the error. This PD-control behavior is mathematically illustrated in Equation 5
(Scrcek, et. al).

The equation indicates that the PD-controller operates like a simplified PID-controller
with a zero integral term. Alternatively, the PD-controller can also be seen as a
combination of the P-only and D-only control equations. In this control, the purpose of
the D-only control is to predict the error in order to increase stability of the closed loop
system. P-D control is not commonly used because of the lack of the integral term.
Without the integral term, the error in steady state operation is not minimized. P-D
control is usually used in batch pH control loops, where error in steady state operation
does not need to be minimized. In this application, the error is related to the actuating
signal both through the proportional and derivative term. A graphical representation of
the PD-controller output for a step increase in input at time t0 is shown below in Figure
6. Again, this graph is a combination of the P-only and D-only graphs, as expected.
Proportional-Integral-Derivative (PID) Control

Proportional-integral-derivative control is a combination of all three types of control


methods. PID-control is most commonly used because it combines the advantages of
each type of control. This includes a quicker response time because of the P-only
control, along with the decreased/zero offset from the combined derivative and integral
controllers. This offset was removed by additionally using the I-control. The addition of
D-control greatly increases the controller's response when used in combination because
it predicts disturbances to the system by measuring the change in error. On the
contrary, as mentioned previously, when used individually, it has a slower response
time compared to the quicker P-only control. However, although the PID controller
seems to be the most adequate controller, it is also the most expensive controller.
Therefore, it is not used unless the process requires the accuracy and stability provided
by the PID controller.

PID-control correlates the controller output to the error, integral of the error, and
derivative of the error. This PID-control behavior is mathematically illustrated in
Equation 6 (Scrcek, et. al).
As shown in the above equation, PID control is the combination of all three types
of control. In this equation, the gain is multiplied with the integral and derivative
terms, along with the proportional term, because in PID combination control, the
gain affects the I and D actions as well. Because of the use of derivative control,
PID control cannot be used in processes where there is a lot of noise, since the
noise would interfere with the predictive, feedforward aspect. However, PID
control is used when the process requires no offset and a fast response time. A
graphical representation of the PID-controller output for a step increase in input
at time t0 is shown below in Figure 7. This graph resembles the qualitative
combination of the P-only, I-only, and D-only graphs.

In addition to PID-control, the P-, I-, and D- controls can be combined in other
ways. These alternative combinations are simplifications of the PID-control.
Note: Order of e(t)
The order of the elements in the e(t) can vary depending on the situation. It could be
the fixed element minus the varying element or the other way around. To better
illustrate the concept let's go to an example. Let's say you are creating a PID control to
control the fluid level in a tank by manipulating the outlet valve. When the fluid level in
the tank exceeds your set value, you will want the valve to open up more to allow more
flow out of the tank. You are looking for a positive response. Therefore your e(t) should
give a positive value when the fluid level is higher than the set. In this case your e(t)
will be (V-Vset). The same logic can be used for other systems to determine what the
e(t) should be in the PID controls.

Modeling PID Controllers With Euler in Excel


As with many engineering systems, PID controllers can be modeled in Excel via
numerical methods such as Euler's Method. First begin with the initial value for a given
parameter. Determine the change in that parameter at a certain time-step by summing
the three controllers P, I, and D at that step, which are found using the equations listed
in the P, I, D, PI, PD, PID Control section above. Take this change, multiply it by the
chosen time-step and add that to the previous value of the parameter of interest. For
more detailed information see Numerical ODE Solving in Excel. An example of a
chemical engineering problem that uses this method can be seen in Example 4 below.

Troubleshooting PID Modeling in Excel


When setting up an Excel spreadsheet to model a PID controller, you may receive an error
message saying that you have created a circular reference. Say you are controlling the flow rate
of one reactant (B) to a reactor which is dependent upon the concentration of another reactant
(A) already inside the reactor. Your PID equations look as follows:

And
After you have set up your columns for A−Aset, d(A−Aset)/dt)/, xi, and the cells for
your parameters like Kc, τi and τd, you will need to set up your PID column with your
PID equation in it. After entering your equation into the first cell of the PID column, you
may receive the Circular Reference error message when trying to drag the equation
down to the other cells in your column.

There are two things you can do:

1. It is likely that you need to start your PID equation in the second or third cell of
your PID column. Enter reasonable values into the first couple of cells before you
start the PID equation, and you will find that these values shouldn’t affect the
end result of your controller.
2. You can also try decreasing the step size (Δt).

Summary Tables

A summary of the advantages and disadvantages of the three controls is shown below
is shown in Table 1.

Table 1. Advantages and disadvantages of controls


A guide for the typical uses of the various controllers is shown below in Table 2.

Table 2. Typical uses of P, I, D, PI, and PID controllers

A summary of definitions of the terms and symbols are shown below in Table 3.

Table 3. Definitions of terms and symbols.


Example 9.2.19.2.1
Hypothetical Industries has just put you in charge of one of their batch reactors. Your
task is to figure out a way to maintain a setpoint level inside of the reactor. Your boss
wants to use some type regulator controller, but he is not quite sure which to use. Help
your boss find the right type of controller. It is extremely important that the level inside
the reactor is at the setpoint. Large fluctuation and error cannot be tolerated.

Solution

You would want to use a PID controller. Because of the action of P control, the system will
respond to a change very quickly. Due to the action of I control, the system is able to be
returned to the setpoint value. Finally, because it is so critical for the system to remain at a
constant setpoint, D control will measure the change in the error, and help to adjust the system
accordingly.
Example 9.2.29.2.2
You go back to your high school and you notice an oven in your old chemistry class. The oven is
used to remove water from solutions. Using your knowledge from ChE 466, you begin to wonder
what type of controller the oven uses to maintain its set temperature. You notice some high
school students eager to learn, and you decide to share your knowledge with them in hopes of
inspiring them to become Chemical Engineers. Explain to them the type of controller that is most
likely located within the oven, and how that controller works.

Solution

Since the oven is only used to remove water from a solution, fluctuation, error, and lag between
the set point and the actual temperature are all acceptable. Therefore, the easiest and simplest
controller to use would be the On-Off controller. The On-Off controller turns on the heating
mechanism when the temperature in the oven is below the setpoint temperature. If the
temperature of the oven increases above the set temperature, the controller will turn the heating
mechanism off.

Example 9.2.39.2.3
Having taken your advice, your boss at Hypothetical Industries decides to install a PID
controller to control the level in the batch reactor. When you first start up the reactor,
the controller initially received a step input. As the reactor achieves steady state, the
level in the reactor tends to fluctuate, sending pulse inputs into the controller. For a
pulse input, provide a grahical representation of the PID controller output.

Solution

The PID-controller output will be a combination of the P-only, I-only and D-only
controller outputs. Analogous to the P-controller output for the step input, the P-
controller output for the pulse input will exactly resemble the input.
Figure 9. P-controller output for pulse input.

The I-controller output represents the area under the input graph. Unlike the step
input, the area under the pulse input graph dropped back down to zero once the pulse
has passed. Therefore, rather than continually increase, the I-controller output graph
will level off in the end.

Figure 10. I-controller output for pulse input.

The D-controller output represents the derivative of the input graph. The derivative at
the first discontinuity of the graph would be positive infinity. The derivative of the
second downward discontinuity is negative infinity.

Figure 11. D-controller output for pulse input.

Combining the qualitative characteristics of all three graphs we can determine the PID-
controller output for a pulse input.
Figure 12. PID-controller output for pulse input.
Example 9.2.39.2.3
Different kinds of disturbances are possible when determining the PID controller robustness.
These different disturbances are used to simulate changes that might occur within your system.
For a CSTR reactor, you decide to heat up your system to account for the cold outside weather.
The disturbance in the input temperature is a ramp disturbance, as shown in figure #. If the
controller responds to the input temperature, what will be the PID controller output?

Figure 13. Ramp input.

Solution

Using a controller with a p-only controller only, we will see a proportional change in the
controller output corresponding to the input variable change. See figure 14 below

Figure 14. P-controller output for ramp input.


Using an I-only controller, we will see the controller corresponding to the area under the graph,
which in this case, seem to increase exponentially with the ramp geometry.

Figure 15. I-controller output for ramp input.

Using a D-only controller, we will see a step response to the ramp disturbance. This is because
the D-component corresponds to the derivative, and a ramp input shows a constant slope
(positive in this case) which is different than the starting condition slope (zero usually). See
figure 16.

Figure 16. D-controller output for ramp input.

Using a PID controller, the three components all come to play in the controller output. As we
would expect, the result will be just a simple addition of the three separate component graphs.

Figure 17. D-controller output for ramp input.


Example 9.2.69.2.6
Following is a P&ID of the process A+B-->C.

Figure
18. P&ID for a reaction process.

What is the PID controller expression on V3 controlling the volume in TK001 to a setpoint of 50
liters? Note: The PID controller uses LC1 to measure the volume.

Solution

The general equation for a PID controller is:


In this problem, the differential equations describing a particular first-order system with a PID
controller will be determined. This is designed to show how well-defined systems can be
modeled or explained mathematically. As a supplement to this problem, visit Constructing Block
Diagrams. Note that this is an example of solution using integro-differential operators rather than
Laplace transforms. Here we have set Kp=1.

Consider a general first-order process:

Where Y(t) is the output of the system and X(t) is the input. Add a PID controller
to the system and solve for a single, simple differential equation. The operator or
equation for a PID controller is below. Assume there is no dead time in the
measurement.

Solution: Use Constructing Block Diagrams as a reference when solving this


problem.
Equations defining system,

When these equations are combined into one equation, the following equation
results. This is achieved by adding the measurement to the comparator to the
controller to the process equation.
A microbiology laboratory discovered a deadly new strain of bacteria, named P.
Woolfi, in the city's water supply. In order to sterilize the water, the bacteria has
to be heat killed at a temperature of 105 degrees Celsius. However, this is above
the boiling point of water at 1 atm and the bacteria is only susceptible to heat
when in liquid due to spore formation when in gas or vapor. To accomplish this
sterilization it was suggested that an auto-clave be used to keep the water in the
liquid state by keeping it at a pressure of 5 atm while heated for 30 seconds. The
auto-clave can only handle up to 7 atm of pressure before exploding, so to
ensure that the process is running at the desired specifications, a PID Controller
Model must be created in Excel. See figure 18 for a visual of the system.

Figure 18.Auto-clave with PID Controls for Temperature and Pressure

lick on this link for the worked out Excel Solution

Explanation:

To simulate the real situation of pressure varying in the system, column B calls an
equation to generate a random fluctuation in pressure. Pset is simply the desired
specification. Error is the difference between the set pressure and measured signal.
du/dt is the sum of the P, I, and D terms. The equations used to calculate each of these
can be found in the article, these take into account the error associated with each time-
step. dU/dt is the parameter that is varied in order to correct for the difference between
the measured pressure and desired pressure.