PC Inspection & Test Record

PC-JX-XX Actuated HVAC Damper


Tag No :
Description :

Subsystem : -
System : -

Drawing Ref 1 / Rev:

Drawing Ref 2 / Rev:

P&ID No: Loop Drawing No: Loop No.


Layout Drawing No: Location:
Associated Tags:

Item Description OK N/A PL Comments


1 PREPARATORY CHECKS
1.01 All temporary transit brackets, bearings, etc. removed and correct components
reinstalled.
1.02 Check lubrication of all spindles, shafts and connections.
1.03 Check that the adjustment is correctly set for the actuating rods and associated
mechanism.
1.04 Set fire dampers to the open position and check condition of fusible link.
1.05 For fire dampers, with damper fully closed, confirm no visible gaps around
blades.
2 FUNCTIONAL CHECKS
2.01 Check that the blades closes completely at the "OFF" position when operated by
hand.
2.02 Check that throttle plate perforations are completely clear of debris.
2.03 Verify the damper position transmitter & limit switch indicate correctly at the panel
/ operator station (fireman’s panel).
2.04 Set balancing dampers to the open position.
2.05 Check local "open / close" indication is correct.
2.06 Check that the blades move freely and easily.
2.07 Check operation of the dampers using pneumatic / electrical supply.
2.08 Check and record time taken for damper to close after initialization.
2.09 Confirm dampers Reset action back to normal operating position is correct.
2.10 Confirm frangible closing device.
2.11 Local external indication operates and is clearly visible.
2.12 Close damper 4 times consecutively with fan running and confirm 100% success.
2.13 Confirm correct coincident operation of grouped dampers.
2.14 Confirm removal of control access covers is unrestricted.
2.15 Confirm damper resets to normal operating mode after test.
3 FUNCTIONAL TEST

3.01 Line Cleaning (e.g. Air Instrument blowing)


3.02 Local reset
3.03 Remote Command: Solenoid Valve 1 energized
3.04 Remote Command: Solenoid Valve 2 energized
3.05 Local indication of the damper position
3.06 Open limit switch
3.07 Close limit switch
3.08 Positioner transmitter on control line
3.09 Local closing command
3.10 Local opening command

13
PC Inspection & Test Record
PC-JX-XX Actuated HVAC Damper
Tag No :
Description :

Subsystem : -
System : -

Drawing Ref 1 / Rev:

Drawing Ref 2 / Rev:

3.11 Open time sec Restriction adjusted


3.12 Closing time sec Restriction adjusted
3.13 Interlock function
3.14 Fail safe position on loss of electrical signal O = Open / C = Close
3.15 Fail safe position on loss of air pressure / power fluid O = Open / C = Close
3.16 Timer checking Value
3.17 Number of operations on accumulator

3.18 ESD signal and solenoid valve test facility


3.19 Discrepancy Alarm indication on ICSS
3.20 Solenoid Valve override indication on ICSS

3.21 Partial Stroke Checking

4 After Loop Checks


4.01 Ensure all covers are replaced and all bolts tight.
4.02 Ensure any As-Built drawing are submitted with the ITR.

23
PC Inspection & Test Record
PC-JX-XX Actuated HVAC Damper
Tag No :
Description :

Subsystem : -
System : -

Drawing Ref 1 / Rev:

Drawing Ref 2 / Rev:

Note: This form might be amended as per the project ICSS standard if necessary

Note: Tick all check item under OK - Satisfactory; N/A - Not Applicable; Punch items(s) are to be PL
Owner Charterer
Data Input
Checked By Accepted By Checked By Accepted By Witnessed By

Company / Dept : Operation CCMS Coord./


Representative Operator
Name:

Signature:

Date: