Advancements in Organic Rankine Cycle System Optimisation For Combined Heat and Power Applications Components Sizing and Thermoeconomic Considerations
Advancements in Organic Rankine Cycle System Optimisation For Combined Heat and Power Applications Components Sizing and Thermoeconomic Considerations
Advancements in Organic Rankine Cycle System Optimisation For Combined Heat and Power Applications Components Sizing and Thermoeconomic Considerations
net/publication/318420437
CITATIONS READS
8 385
2 authors:
Some of the authors of this publication are also working on these related projects:
Special Issue: Organic Rankine Cycle - 'Frontiers In Energy Research' (ISSN 2296-598X) View project
Special Issue "Power Cycles and Thermal Energy Storage for Industrial Waste Heat Recovery" View project
All content following this page was uploaded by Maria Anna Chatzopoulou on 14 July 2017.
Abstract:
There is great interest in distributed combined heat and power (CHP) generation in the built environment due to the
higher overall efficiencies attained in comparison to separate provision of these vectors. Organic Rankine cycle
(ORC) systems are capable of generating additional electricity from the thermal outputs of CHP engines, improving
the electrical conversion efficiency and power-to-heat ratio of such systems. Thermodynamic analysis and technical
feasibility are at the core of the development of these systems, while a critical factor for the wider adoption of ORC
systems concerns their economic proposition. Obtaining credible estimates of system costs requires correct sizing
of individual components. This work focuses on the thermodynamic optimisation, sizing and costing of ORC units in
CHP applications, over a range of heat-source temperatures. The working fluids examined include R245fa,
R1233zd, Pentane and Hexane, due to their good performance and favourable environmental characteristics. The
optimal cycles obtained can increase the power-to-heat ratio of the complete CHP-ORC system by up to 65%.
Alternative equipment sizing methods are then applied for each fluid and the resultant component sizes are
compared. The cost estimates obtained from the alternative methods are also compared to real ORC application.
Based on this, a hybrid costing method is proposed and applied to an ORC system design, in order to obtain the
specific investment cost (SIC). The results indicate that as the heat source temperature increases, the power output
increases, resulting in larger and more expensive components. Nevertheless, the SIC drops from 17 GBP/W for low-
power outputs to 2.1 GBP/W for high-temperature/high-power outputs.
Keywords:
Organic Rankine cycle; Cogeneration; Optimisation; Component sizing; Thermoeconomics; Energy efficiency.
1. Introduction
Distributed combined heat and power (CHP) generation has been gaining growing interest, due to the
higher overall efficiency of the system, in comparison to the separate provision of heat and power. This
results in lower energy consumption and costs for the user, whilst the system has overall lower
environmental impact, than the traditional heating systems and the centralised power generation. Typical
small-medium scale CHP systems are comprised of an internal combustion engine (ICE) coupled with a
generator for electricity production. The exhaust gas stream, after the power generation, is used for heating
(or other processes), or in case there is no heating load, it is released to the atmosphere as waste heat. The
release of unusable heat to the atmosphere reduces the efficiency of the system. The amount of waste heat
can vary significantly, depending on the heating demand. A case in the point is that in the industry, studies
have shown that waste heat corresponds up to 50% of the overall heat generated [1].
Organic Rankine cycle (ORC) units can utilise the waste heat of CHP systems for generating additional
power, increasing the power-to-heat ratio of the system, especially in periods of the year when the heating
demand is low. The power-to-heat ratio of CHP systems is defined as the ratio of the power generated over
the thermal output available. The lower the heating demand, the higher the power-heat ratio should be to
minimise the heat being wasted, which reduces the overall system efficiency. ORC engines operate using
the conventional Rankine thermodynamic cycle, but the working fluid is an organic compound (refrigerant,
hydrocarbon, etc.). By selecting the appropriate working fluid given the heat source conditions (in this
case the ICE waste heat), the ORC can be optimised for maximum power output. Several studies can be
found in the literature analysing the ORC thermodynamic performance for different working fluids and
heat sources. Maraver et al. [2] have optimised thermodynamically ORC units for six working fluids, for
both high temperature waste heat sources and low temperature geothermal systems. Aljundi [3] and
Oyewunmi et al.[4] have done a parametric analysis for a range of working fluids including hydrocarbons,
refrigerants, and mixtures for geothermal applications. Li [5] have analysed the performance of alternative
ORC architectures for solar, geothermal and waste heat recovery applications, for 15 alternative working
fluids. Less documented is however the coupling of ORC units to CHP systems, with limited examples
found in Lecompte et. al[1] and Shokati et. al [6]. Based on a review of the extended literature, it can be
concluded that not a single working fluid can be identified as the optimal one. On the contrary, the most
suitable working fluids vary with the application, and the heat source conditions. This finding leads to the
need for a systematic integration of working fluids selection process for ORC engines, for the alternative
applications.
Apart from the system thermodynamic performance, a critical factor for the wider deployment of the
ORC units in the market is the capital expenditure (CAPEX), and the operating and maintenance (O&M)
costs. To obtain credible estimates of the ORC investment cost, the sizing of the main ORC components
is of paramount importance. These estimates form the basis of the cost calculations to be undertaken
when evaluating the financial viability of ORC units’ deployment. In contrast to the prolific literature
related to the thermodynamic analysis of ORCs, there is limited research on ORC components systematic
sizing and costing. Walraven et al. [7] have done a comparison of shell and tube, and plate heat
exchangers design for ORC units, focusing on the equipment sizing only. Thermo-economic analysis of
ORC units recovering geothermal energy can be found in Oyewunmi and Markides [4], for solar driven
ORC in Guarracino et. al [8], and for CHP bottoming cycles in Lecompte et al. [1]. Feng et al. [9] and
Quoilin et al.[10] have done thermo-economic analysis of ORC driven by high grade waste heat,
achieving specific investment cost (SIC) of 2,800 EUR/kW.
These studies have shown the importance of accounting for the components specific design
characteristics and costs, when assessing the feasibility of ORC systems. There is a great range of sizing
methods for the ORC main components (evaporator, condenser, etc.) based on alternative Nusselt
number correlations, such as [11-13]. These correlations vary depending on the type of heat exchangers
(HEXs) selected, the flow regime and the type of evaporation/condensation taking place. In a similar
manner, there is a variety of costing methods available, mostly originating from the chemical industry,
which were traditionally used to provide estimates for chemical plants costs [14]. Typical costing
methods include the module costing technique [15,16].
Based on the above, the aim of this paper is to provide a systematic ORC engine component sizing and
costing methodology. The ORC is first optimised thermodynamically for alternative working fluids, and
then a number of different correlations for components sizing are applied. Next, the best suited
correlation is used to obtain the components cost and the system SIC. The novelty of this work lies in
the fact that: i) it considers alternative sizing methods to come up with credible equipment design
guidelines; and ii) it compares the system cost calculations to real applications, to establish the validity
of the cost estimates. The ORC systems examined in this work are coupled with CHP units driven by
ICE, but the methodology proposed is applicable to any ORC system design. The paper structure is as
follows; firstly, the ORC model set up is presented, along with the optimisation problem. Then, the
thermodynamic optimisation results are discussed. Next, alternative methods for the ORC components
sizing are examined, to obtain the equipment size. The economic analysis of the ORC unit follows.
Finally, conclusions and recommendations for the design of ORC units are discussed.
2. Modelling methodology
2.1. Organic Rankine cycle (ORC) unit
A schematic of an ORC is presented in Fig. 1 along with a typical subcritical non-regenerative cycle on
a T-s diagram. The system is composed of four major components: i) the evaporator, where heat inputs
the cycle; ii) the expander, where power is generated; iii) the condenser, where heat is released; and iv)
2
the circulating pump. Process 1-2 represents liquid pumping, 2-3 the heat addition, 3-4 the expansion of
the working-fluid vapour, and 4-1 the heat rejection. The heat carrier fluid (5-6) and condenser cooling-
water (7-8) temperature changes are also illustrated on the same diagram.
Heat Carrier Fluid 5
Evaporator
3l 3v 3
Working
Fluid G
Expander 6
Electricity 4
Condenser 2 4s
1 4v
8
7
Condenser Water
(a) (b)
Fig. 1. (a) ORC schematic diagram, and (b) subcritical non-regenerative ORC on a T-s diagram.
The HEX selected for the evaporator and the condenser are of tube-in-tube construction, which is a
relatively simple and low cost design, in comparison to shell-and-tube HEXs for example [11]. The
evaporator has been modelled by splitting it into three distinct zones: i) the preheating section, a single
phase liquid zone where the working fluid is heated up to the evaporation saturation temperature (States
2-3l); ii) the evaporating section, a two-phase zone where the phase change occurs (States 3l-3v); and
iii) the superheating section, where the saturated vapour is heated further in the dry vapour zone (States
3v-3). Similarly, the condenser has been modelled by dividing it into two distinct zones: i) the
desuperheating section, a single phase zone where the dry vapour is cooled down to the condensing
saturation temperature (States 4-4v); and ii) the condensing zone, a two-phase zone where the working
fluid changes phase (States 4v-1). The HEX system is sized to maintain turbulent flow in both working
fluid streams to maximise the heat transfer rate. The HEXs have been split into n-segments and in each
i-segment the temperature and the quality of the working fluid are calculated. Based on those, the heat
transfer coefficient, hi, is estimated for each segment, using a number of alternative correlations. Using
the Logarithmic Mean Temperature Difference (LMTD) method [17] the area, Ai, of each segment is
then calculated. By summing the Ai calculated, the total area requirements of the HEX are obtained, for
each working fluid examined and each correlation. More details on the HEX sizing analysis are presented
in subsequent section.
Finally, the expander is modelled by using an isentropic efficiency value of 0.7, as representative of
high-performance reciprocating expanders (for details on the loss mechanisms refer to Sapin et. el [18]),
and the pump used is a centrifugal pump with a typical isentropic efficiency of 0.65 [19]. A reciprocating
expander has been selected due to its wide range of operating volume and pressure ratios.
3
maximise {𝑊̇net }
; (1)
Pevap, Pcon, ṁref, 𝑆𝐻𝐷, 𝑃𝑃evap, 𝑟exp
Subject to: 𝑃con < 𝑃evap < 𝑃crit ; (2)
0 ≤ 𝑆𝐻𝐷 ≤ 1 ; (3)
𝑃𝑃min ≤ 𝑃𝑃 ; (4)
𝑃evap
≤ 𝑟exp 𝛾 ; (5)
𝑃con
𝑇4 ≤ 𝑇4v ; (6)
𝑇lim ≤ 𝑇hs,out . (7)
Equation (2) describes the constraint related to the pressure levels of the cycle; the pressure at the
condenser must be lower than the evaporating pressure, which should be lower than the working fluid
critical pressure, for a subcritical ORC. Equation (3) is the normalised superheating degree restricted
between 0 and 1; it is expressed as the ratio of the superheating degree the cycle actually operates at,
over the maximum allowable, accounting for the pinch point in the evaporator. The SHD is defined as:
3 𝑇 −𝑇3𝑣
𝑆𝐻𝐷 = 𝑇 −𝑃𝑃 . (8)
5 evap −𝑇3
Equation (4) ensures that the minimum pinch point of the HEXs is not violated, while Eq. (5) ensures
that the expansion process is isentropic. The next constraint (Eq. (6)) ensures that the temperature after
the expansion is higher than the saturation condensing temperature, and finally, Eq. (7) has been added
to limit the exhaust gases leaving temperature from the evaporator, to minimise the risk of reaching the
dew-point temperature. For exhaust gases from natural gas combustion, the dew point can vary from
60 °C (373 K) to as low as 35 °C (308 K), for very high oxygen concentration [20,21]. Other researchers
report typical exhaust gases dew point temperature of approximately 50-70 °C (323-343 K) [22-24].
Typical CHP units with natural gas ICE cool the exhaust gases down to approximately 100-120 °C
(373-393 K) [2,25] to ensure that no condensation occurs. In this study for the design of the ORC unit,
the heat carrier fluid temperature exiting the evaporator (𝑇lim ) has been restricted to 80 °C (353 K),
which is a temperature well above the reported dew point levels and close to the current state of the art
figures reported in the CHP system design.
(a) (b)
Fig. 3. ORC unit results for different working fluids and heat-source temperatures: (a) maximum power
output, and (b) operating pressure ratio.
Looking at the other working fluids in Fig. 3a, Pentane and R1233zd have the highest power output (up to
130 kW for a 623 K (350 °C) heat-source temperature), followed by Butane and Hexane (111-112 kW),
and Toluene (96 kW). However, from Fig. 3(b) it can also be seen that Pentane and Hexane generally
operate at higher cycle pressure ratios (PRs). This is due to the higher gamma values of these fluids (up to
1.3 for high temperatures) in comparison to 1.1-1.15 of the refrigerants. For the isentropic expansion
assumed in this study the high gamma values result in high pressure ratios across the expander. Butane,
which also generates similar power output as Pentane and Hexane, operates however in much lower PR.
The difference can be explained by looking at: i) the evaporating temperature, once the maximum
allowable evaporating pressure is reached; and ii) at the gamma values of Butane. For the peak evaporating
pressure of the cycle operating with Butane, the saturation temperature is 420 K (147 °C) (for Pevap = 36
bar), so while the heat source temperature increases the system increases the superheating degree, rather
than increasing the pressure at the evaporator further, in order to increase the enthalpy difference across
5
the expander. For fluids such as Hexane on the contrary, the respective evaporating temperature at high
pressure is 505 K (232 °C), allowing for much lower degree of superheating. Adding to this, the gamma
value of Butane is lower than those of Pentane and Hexane, resulting in lower PR.
So depending on the fluid selection, different types of expanders will be more suitable. For fluids such
as R245fa and Butane, expanders operating at low expansion ratios will be suitable, whilst expanders
with high expansion ratios will be required for fluids such as Pentane and Hexane.
In Fig. 4, the first and second law efficiency of the ORC for every working fluid is presented. In line
with the results for all fluids while the heat source temperature increases up to 500 K (232 °C)
approximately the thermal efficiency increases up to 9%-14% depending on the fluid, and then stays
constant, while the heat carrier fluid temperature increases further. The only exemption is Toluene for
which the thermal efficiency constantly increases, while the heat carrier fluid temperature increases,
although is much lower than the other fluids until the heat source temperature reaches 600 K (327 °C).
These results indicate that some fluids are more suitable for low temperature heat sources (e.g. R1233zd),
than others which maximise their performance at high temperatures (e.g. Toluene).
Fig. 4. Optimum ORC thermal and exergy efficiencies for different working fluids and heat-source temperatures.
The exergy efficiency shows a different trend to the thermal efficiency, with the former increasing as the
heat-source temperature increases up to approximately 470 K (200 °C) and then drops (Fig. 4). The highest
exergy efficiency is 43% for R1233zd and Pentane. The drop in the exergy efficiency implies that the
additional heat input is not being utilised as efficiently by the cycle, although the power output increases.
Finally, the improvement of the overall CHP-ORC system thermal efficiency and power-to-heat ratio is
shown in Fig. 5, using the optimum ORC results for Ths,in of 623 K (350 °C). The total system efficiency
improves by up to 5%, whereas the power-to-heat ratio shows significant increase of up to 65%, for working
fluids such as R1233zd and Pentane. These findings illustrate that the CHP system efficiency can be
decoupled from the heating demand of the building by using an ORC unit, maximising the system
performance.
+64% +65% +63% +64% +65%
1.65 CHP-only +62% +61%
+57% +58%
CHP-ORC R245fa
1.45 CHP-ORC R1233zd
CHP-ORC R152a
1.25 CHP-ORC R1234ze
CHP-ORC R1234yf
1.05 Base-line
CHP - ORC Toluene
CHP - ORC Butane
0.85
CHP - ORC Pentane
0.25
η el,total Power-to-Heat ratio
Fig. 5. CHP-ORC efficiency and power-to-heat ratio variation for different working fluids.
6
4. Equipment sizing analysis
In what follows, component sizing is performed for the optimum ORC systems identified in Section 3.
(a) (b)
Fig. 6. Heat exchanger sizing results for: (a) the evaporating two-phase zone, and (b) the entire evaporator.
For each fluid and zone, it is observed that the area requirements peak at some operating points and then
drop, while the heat source temperature increases. This is explained by two key trends: i) the LMTD in the
preheating/superheating sections increases significantly for high heat carrier fluid temperatures, resulting
in lower surface area requirements; and ii) the HTC increases while the mass flow rate of the working fluid
increases. In the two-phase zone, apart from these two phenomena, the transition to nucleate boiling
conditions results in high HTC and low area requirements.
4.2.3. Condenser
The condensing section surface area requirements for R245fa are presented in Fig. 7a, for different
correlations. Correlations that account for both gravity and shear forces driven condensation result in
lower surface area requirements than the gravity driven only condensation. It should be noted that based
on the flow conditions in this study, the flow regime is such that falls within the shear condensation
regime. Similar results, for the condensing section are found for all working fluids investigated. In
contrast with the evaporator results, the two-phase condensing zone area is much higher than the single
phase (desuperheating) area for all working fluids examined. This is explained by the fact that the
optimiser selects the lowest condensing saturation pressure feasible, without violating the constraints,
therefore there is high latent heat load to be rejected in the condensing zone. Adding this the optimum
cycles for all working fluids selected have minimum superheating degree.
(a) (b)
Fig. 7. Heat exchanger sizing results for: (a) the condensing two-phase zone, and (b) the entire condenser.
8
The average (total) condenser area requirements are presented in Fig. 7b for the best performing working
fluids, derived by using all five correlation results to obtain an average value. The area requirements
increase, while the heat source temperature increases for all working fluids. This is in-line with the
increase of the condenser heat load being rejected in the condenser water circuit. It should be highlighted
that Hexane has the lowest condenser area requirements among the fluids investigated. This is attributed
to the fact that the saturation condensing temperature of Hexane at 101 kPa, is 343 K (70 °C) and it is
the highest among the fluids investigated. The higher saturation temperature results in a high LMTD
across the HEX, reducing the heat transfer area requirements.
5. Economic analysis
Based on the equipment sizing results, the mean surface area of the two-phase zone has been used for
the equipment costing exercise, for both the evaporator and the condenser. For the components costing,
alternative methods found in the literature have been reviewed, and those with the best fit to real
applications data have been used for the rest of the study.
(a) (b)
Fig. 8. For the best-performing working-fluids investigated: (a) optimum ORC-unit SIC (GBP/kW), and (b)
equipment purchase cost (GBP).
The absolute costs of each component for R1233zd and Pentane are shown in Fig. 8b. The expander
costs dominate the total purchase costs at high temperatures (high pressure ratios), amounting to
approximately 50% of the ORC unit purchase cost (for Ths = 630 K). The condenser is the second most
expensive component (up to 30% of the total), followed by the evaporator and the pump. These findings
are in agreement with the costs data reported for a heat recovery ORC facility in Belgium of 375 kWe
[14]. When the oil circuit and installation costs are excluded, the expander and the pump are responsible
for approximately 60% of the investment cost, followed by the condenser (22%), and the evaporator
(13%) [14]. For lower power outputs (low temperature and pressure ratios) the expander costs are
comparable to the cost of the condenser and the evaporator (Fig. 8b), corresponding to 27%, 42%, and
31% respectively (for Ths = 450 K). Based on these findings, it is concluded that for low-medium
temperatures, and low pressures, the cost of the HEXs is significant, therefore it is of high importance
to design them to maximise the heat transfer. In this study, tube-in-tube HEXs have been used for both
the evaporator and the condenser, so the results might vary in case other types of HEXs are used. For
higher power outputs, on the contrary, the selection and design of the expander and then of the condenser
is key factor for reducing the ORC costs. Finally, it should be noted, that the cost correlations, when
used for very small capacities, should be treated with caution, because these loads are close to the low
end of the range of applicability of those correlations.
10
Firstly, thermodynamic optimisation of the ORC unit has been performed for maximising the power
output, given the exhaust gases conditions. A range of working fluids has been examined and the best
performing fluids, namely R1233zd and Pentane, were found to generate up to 130 kW of additional
power. This results in an increase of the power-to-heat ratio of the system of up to 65%, decoupling the
CHP performance from variations on the heating demand side. Adding to this, depending on the fluid
selection, the optimum ORC cycle operates with different pressure levels, and superheating degree,
influencing the components selection. A case in the point is that, for fluids, such as R1233zd, R245fa
and Butane, expanders operating at low expansion ratios will be suitable, whilst expanders efficient at
high expansion ratios will be required for fluids such as Pentane and Hexane.
Next, the individual components sizing has been performed, with particular focus on the evaporator and
condenser HEX design. Key for the sizing of HEXs is the surface area requirements calculation, which in
turn depends on the estimation of the HTC. There is a plethora of correlations for describing the heat
transfer phenomena in HEXs, with the most complex related to the 2-phase zone. In this work, multiple
Nusselt number correlations have been compared. Results for the evaporator have shown that for high
temperature levels- where nucleate boiling prevails- all correlations seem to result in similar surface area
requirements, whilst for lower temperatures the existence of combined convection and nucleate boiling
can reduce the HTC. Looking at the condenser, the majority of the correlations result in similar surface
area requirements, with the exemption of correlations for gravity driven condensation.
Following the system sizing, an economic evaluation of the ORC system has been performed. This work
illustrates that alternative costing methods can be found in the literature, resulting in different cost
estimations. Therefore, it is of great importance to compare the costing calculation results, to real
applications costs. However, this has been proved to be a very onerous task, due to the lack of publicly
available cost data for ORC installations. In this paper, a hybrid costing method has been used,
combining well established cost correlations, and the results were compared to a limited number of real
large scale installation data. The cost estimates are in good agreement with the real ORC units costs,
however a broader range of ORC units and components data should be used in the future to establish the
validity range of the method. While the ORC units’ capacity increases with high heat sources
temperature, the SIC cost drops exponentially, reaching up to 2,100 GBP/kW for the best performing
fluids investigated in this study (R1233zd and Pentane). Depending on the unit capacity, the HEXs will
form between 40%-75% of the total investment cost. Therefore, the HEX sizing has significant impact
on the ORC units cost and financial viability.
To conclude, this work has established the need for a holistic approach when designing ORC units,
accounting for both the thermodynamic and economic aspects. Depending on the application, the most
suitable working fluids, and components design may vary significantly. The cost correlations used to-
date, originate from the chemical industry, and should be used for comparing alternative designs, where
the relative results are more important that the exact cost figures obtained. Finally, the findings reveal
there is need for validating the cost calculations against real ORC applications, to establish a validity
range for the cost estimates. Having validated the cost estimates of the ORC system, optimisation can
then be performed on the basis of minimising the SIC of the project.
Acknowledgments
The authors would like to thank the Imperial College President’s PhD Scholarship Scheme, and the
Climate-KIC PhD Added Programme for funding this research. This work was supported by the UK
Engineering and Physical Sciences Research Council (EPSRC) [grant number EP/P004709/1]. Data
supporting this publication can be obtained on request from [email protected].
References
[1] Lecompte S., Huisseune H., van den Broek M., De Schampheleire S., De Paepe M., Part load based thermo-
economic optimization of the Organic Rankine Cycle (ORC) applied to a combined heat and power (CHP)
system. Appl Energy 2013;111:871-81.
11
[2] Maraver D., Royo J., Lemort V., Quoilin S., Systematic optimization of subcritical and transcritical organic
Rankine cycles (ORCs) constrained by technical parameters in multiple applications. Appl Energy
2014;117:11-29.
[3] Aljundi I.H., Effect of dry hydrocarbons and critical point temperature on the efficiencies of organic Rankine
cycle. Renew Energy 2011;36(4):1196-202.
[4] Oyewunmi O., Markides C.N., Thermo-economic and heat transfer optimization of working-fluid mixtures
in a low-temperature Organic Rankine Cycle system. Energies 2016;9(448):1-21.
[5] Li G., Organic Rankine cycle performance evaluation and thermoeconomic assessment with various
applications Part I: Energy and exergy performance evaluation. Renew Sustain Energy Rev 2016;53:477-99.
[6] Shokati N., Mohammadkhani F., Farrokhi N., Ranjbar F., Thermodynamic and heat transfer analysis of heat
recovery from engine test cell by Organic Rankine Cycle. Heat Mass Transf 2014;50(12):1661-71.
[7] Walraven D., Laenen B., D’haeseleer W., Comparison of shell-and-tube with plate heat exchangers for the
use in low-temperature organic Rankine cycles. Energy Convers Manag 2014;87:227-37.
[8] Guarracino I., Markides C.N., Mellor A., Ekins-Daukes N.J., Dynamic coupled thermal-and-electrical
modelling of sheet-and-tube hybrid photovoltaic/thermal (PVT) collectors. Appl Therm Eng 2016;101.
[9] Feng Y., Hung T., Greg K., Zhang Y., Li B., Yang J., Thermoeconomic comparison between pure and
mixture working fluids of organic Rankine cycles (ORCs) for low temperature waste heat recovery. Energy
Convers Manage 2015;106:859-72.
[10] Quoilin S., Declaye S., Tchanche B.F., Lemort V., Thermo-economic optimization of waste heat recovery
Organic Rankine Cycles. Appl Therm Eng 2011;31(14):2885-93.
[11] Hewitt G.F, Shires GL, Bott T.R. Process heat transfer. CRC Press; 1994.
[12] Dobson M.K., Wattelet J.P, Chato J.C. Optimal Sizing of Two-Phase Heat Exchangers. 1993.
[13] Shah M.M., A general correlation for heat transfer during film condensation inside pipes. Int J Heat Mass
Transf 1979;22(4):547-56.
[14] Lemmens S., Cost engineering techniques and their applicability for cost estimation of organic Rankine cycle
systems. Energies 2016;9(485):1-18.
[15] Turton R., Bailie R.C., Whiting W.B., Shaelwitz J.A., Analysis, Synthesis and Design of Chemical Processes.
Pearson Education, Inc. Rights and Contracts Department 501 Boylston Street, Suite 900 Boston, MA 02116;
2009.
[16] Seider WD., Seader JD., Lewin DR., Product and Process Design Principles - Synthesis, Analysis, and
Evaluation. Second. John Wiley & Sons, Inc., Hoboken, New Jersey; 2009.
[17] Bergman TL., Lavine AS., Incropera FP., DeWitt DP., Fundamentals of Heat and Mass Transfer. John Wiley
& Sons; 2011.
[18] Sapin P., Taleb A., Barfuss C., White A.J., Fabris D., Markides C.N., Thermodynamic Losses in a Gas Spring:
Comparison of Experimental and Numerical Results. In the proceedings of the 12th International Conference
on Heat Transfer, Fluid Mechanics and Thermodynamics. 2016. p. 172-7.
[19] Freeman J., Hellgardt K., Markides C.N., An assessment of solar-powered organic Rankine cycle systems
for combined heating and power in UK domestic applications. Appl Energy 2015;138:605-20.
[20] Peña F., Blanco J.M., Evaluation of the physical dew point in the economizer of a combined cycle burning
natural gas. Applied Thermal Engineering 2007;27;11;2153-58.
[21] ASHRAE. 2013 ASHRAE Handbook: Fundamentals. Design. ASHRAE, 1791 Tullie Circle, N.E., Atlanta,
GA 30329; 2013.
[22] Lee C-E., Yu B., Lee S., An analysis of the thermodynamic efficiency for exhaust gas recirculation-
condensed water recirculation-waste heat recovery condensing boilers (EGR-CWR-WHR CB). Energy
2015;86:267-75.
[23] Shi Y., Zhang X., Li F., Ma L., Engineering acid dew temperature: the limitation for flue gas heat recovery.
Chinese Sci Bull 2014;59(33):4418–25. - Available at: http://dx.doi.org/10.1007/s11434-014-0577-y.
[24] Golman B., Julklang W., Simulation of exhaust gas heat recovery from a spray dryer. Appl Therm Eng
2014;73(1):899-913.
[25] ENER-G. ENER-G CHP Range Guide. 2016 - Available at: http://www.energ-group.com/combined-heat-
and-power/information-centre/technical-information [accessed 2016 Dec 15].
12
[26] Quoilin S., Broek M Van Den., Declaye S., Dewallef P., Lemort V., Techno-economic survey of Organic
Rankine Cycle (ORC) systems. Renew Sustain Energy Rev 2013;22:168-86.
[27] Chatzopoulou M.A., Markides C.N., Modelling of advanced combined heat and power systems. ASTFE
2017. In the Proceedings of the 2nd International Thermal and Fluids Engineering Conference (TFEC)
ASTFE; April 2-5, 2017.
[28] Gnielinski V., New Equations for Heat and Mass Transfer in Turbulent Pipe and Channel Flow. Int Chem
Eng 1976;(16):359-68.
[29] García-Cascales J.R., Vera-García F., Corberán-Salvador J.M., Gonzálvez-Maciá J., Fuentes-Díaz D.,
Assessment of boiling heat transfer correlations in the modelling of fin and tube heat exchangers. Int J Refrig.
2007;30(6):1004-17.
[30] Verein Deutscher Ingenieure V., VDA Heat Atlas. VDI Heat Atlas. Second. Springer; 2010.
[31] XE., XE Currency table. 2016 - Available at: http://www.xe.com/currencytables/?from=GBP&date=2001-
12-11 [accessed 2016 Dec 10].
[32] Viking Heat Engines, Viking Heat Engines. 2016 - Available at: http://www.vikingheatengines.com
[accessed 2017 Jan 20].
13