DIESEL GENERATOR SET

STANDBY
600 ekW 750 kVA
60 Hz 1800 rpm 480 Volts
Caterpillar is leading the power generation
marketplace with Power Solutions engineered
to deliver unmatched flexibility, expandability,
reliability, and cost-effectiveness.
Image shown may not
reflect actual package.

FEATURES
FUEL/EMISSIONS STRATEGY CAT C18 ATAAC DIESEL ENGINE
• Low fuel consumption • Reliable, rugged, durable design
• Field-proven in thousands of applications
DESIGN CRITERIA worldwide
• The generator set accepts 100% rated load in one • Four-stroke-cycle diesel engine combines
step per NFPA 110 and meets ISO 8528-5 transient consistent performance and excellent fuel
response. economy with minimum weight
• Electronic controlled governor
UL 2200
• UL 2200 listed packages available. Certain CAT GENERATOR
restrictions may apply. Consult with your • Matched to the performance and output
Caterpillar Dealer. characteristics of Caterpillar engines
• 2/3 pitch minimizes harmonic distortion and
FULL RANGE OF ATTACHMENTS
facilitates parallel operation
• Wide range of bolt-on system expansion
• Low adjustment module provides engine relief
attachments, factory designed and tested
upon load impact and improves load acceptance
SINGLE-SOURCE SUPPLIER and recovery time
• Fully prototype tested with certified torsional • UL 1446 Recognized Class H insulation
vibration analysis available
CAT EMCP 3 SERIES CONTROL PANELS
WORLDWIDE PRODUCT SUPPORT • Controls designed to meet individual customer
• Caterpillar® dealers provide extensive post sale needs.
support including maintenance and repair • EMCP 3 provides the option for full-featured
agreements power metering and protective relaying
• Caterpillar dealers fill 99.7% of parts orders within • Segregated low voltage, AC/DC accessory box
24 hours provides single point access to accessory
• Caterpillar dealers have over 1,600 dealer branch connections
stores operating in 200 countries • Options to meet UL/CSA/NFPA
• The Cat® S•O•SSM program cost effectively detects • Power Center provides convenient location for
internal engine component condition, even the control panel, optional power terminal strips and
presence of unwanted fluids and combustion optional circuit breakers
by-products
®

STANDBY 600 ekW 750 kVA


60 Hz 1800 rpm 480 Volts

FACTORY INSTALLED STANDARD & OPTIONAL EQUIPMENT

System Standard Optional


Air Inlet • Light Duty Air Cleaner • Single element canister type air cleaner
• Service indicator • Dual element air cleaner
• Heavy-duty air cleaner with precleaner
• Air inlet shutoff
Cooling • Radiator with guard sized for 50° C • Radiator duct flange
• Coolant level sight window • Low Coolant Level Sensor
• Coolant drain line with valve • Radiator removal
• Fan and belt guards
• Caterpillar® Extended Life Coolant
Exhaust • Stainless steel exhaust flex and ANSI weld flange • Industrial, residential and
• Turbo outlet elbow critical mufflers
• 35 dBA muffler
• Engine mounted muffler
• Mounting and through-wall installation kits
• Manifold and turbocharger guards
Fuel • Primary fuel filter with integral water separtor • Dual Wall Integral Fuel Tanks
• Secondary fuel filters • Dual Wall Sub-base Fuel Tanks
• Fuel cooler • Manual Fuel Fill Pump
• Fuel priming pump • Automatic Fuel Fill Options
• Fuel pressure gauge
• Flexible fuel lines
Generator • Self excited or internal excitation • Permanent magnet conversion for self-excited and
• Class H insulation internal excited generators
• Class H Temperature Rise • Oversize and premium generators
• Random wound • Three phase sensing
• R448 Voltage Regulator • Quadrature droop kit
• Power terminal strip connections • Digital voltage Regulator
• IP23 Protection • Space heaters
• Power Center • RFI filter
• 80% & 100% UL Breakers
• IEC compliant 3 or 4-pole
• Floor standing circuit breakers with auxiliary contacts
& cabling kits
Control Panels • EMCP 3.1 (package mounted) • EMCP 3.2
• EMCP 3.3
• Local alarm and remote annunciator modules
• Protective devices
Lube • Lubricating oil and filter • Oil temperature sensor
• Oil drain line with valves • Manual sump pump
• Fumes disposal
• Lube oil level indicator
Mounting • Formed steel narrow base frame • Formed steel wide base frame
• Linear vibration isolators between base and engine • Oil field skid base
generator
Starting/Charging • 45 amp charging alternator • Jacket water heater
• 24 volt starting motor(s) • Block heater
• Batteries with rack and cables • Ether starting aid
• Battery disconnect switch
• Battery charger(5A, 10A)
• Oversized batteries
• Battery removal

2 13 October 2006 11:21 AM


®

STANDBY 600 ekW 750 kVA


60 Hz 1800 rpm 480 Volts

SPECIFICATIONS

CAT GENERATOR CAT CONTROL PANEL

EMCP 3 Series Controls


Frame size.................................................................LC7024F
24 Volt DC Control
Excitation...................................................... Internal Excited
EMCP 3.1 (Standard)
Pitch.............................................................................. 0.6667
• UL/CSA/CE
Number of poles...................................................................4
NEMA 1, IP22 enclosure
Number of bearings...................................... Single Bearing
• Run/Auto/Stop control
Number of leads................................................................. 12
Lockable hinged door (option)
Insulation....................... UL 1446 Recognized Class H with
• True RMS metering, 3-phase
tropicalization and antiabrasion
- Consult your Caterpillar dealer for available voltages • Speed Adjust
IP rating..........................................................Drip Proof IP23 Voltage adjust (optional)
Alignment.............................................................. Pilot Shaft • Digital Indication for:
Overspeed capability...................................... 125% of rated - RPM
Wave form deviation (Line to Line)................................. 2% -Operating hours
Paralleling kit droop transformer.......................... Standard - Oil Pressure
Voltage regulator.3 Phase sensing with selectible volts/Hz -Coolant temperature
Voltage Regulation...........Less than +/- 1/2% (steady state) - System DC volts
Less than +/- 1/2% (w/ 3% speed change) - L-L volts, L-N volts, phase amps, Hz
Telephone Influence Factor.............................. Less than 50 -ekW, kVA, kVAR,kW-hr, %kW, PF (*)
Harmonic distortion......................................... Less than 5% • Shutdowns
CAT ENGINE -Low oil pressure
-High coolant temperature
-Overspeed
C18 ATAAC, I-6, 4-stroke watercooled diesel -Emergency stop
Bore - mm.............................................. 145.00 mm (5.71 in) -Failure to start (overcrank)
Stroke - mm............................................. 183.00 mm (7.2 in) • Programmable protective relaying functions: (*)
Displacement - L................................... 18.13 L (1106.36 in3) -Under and over voltage
Compression ratio........................................................ 14.5:1 -Under and over frequency
Aspiration........................................... Air-to-Air Aftercooled - Reverse power
Fuel system..................................... Electronic unit injection -Overcurrent
Governor type................. Caterpillar ADEM control system • MODUS isolated data link (RS-485 half-duplex) supports
serial communication at data rate up to 115.2 kbaud (*)
(*) Available on EMCP 3.2 & EMCP 3.3
Single location customer connector point
Consult your Caterpillar dealer for available voltages.

3 13 October 2006 11:22 AM


®

STANDBY 600 ekW 750 kVA


60 Hz 1800 rpm 480 Volts

TECHNICAL DATA

Open Generator Set - - 1800 rpm/60 Hz/480 Volts DM7548


Low Fuel Consumption

Generator Set Package Performance


Genset Power rating @ 0.8 pf 750 kVA
Genset Power rating with fan 600 ekW
Fuel Consumption
100% load with fan 162.7 L/hr
75% load with fan 119.8 L/hr
50% load with fan 83.0 L/hr
Cooling System1
Ambient air temperature 52 ° C
Air flow restriction (system) 0.12 kPa
Air flow (max @ rated speed for radiator arrangement) 804 m³/min
Engine Coolant capacity with radiator/exp. tank 81.8 L
Engine coolant capacity 20.8 L
Radiator coolant capacity 61.0 L
Inlet Air
Combustion air inlet flow rate 48.4 m³/min
Exhaust System
Exhaust stack gas temperature 552.8 ° C
Exhaust gas flow rate 141.3 m³/min
Exhaust flange size (internal diameter) 203 mm
Exhaust system backpressure (maximum allowable) 10.0 kPa
Heat Rejection
Heat rejection to coolant (total) 183 kW
Heat rejection to exhaust (total) 640 kW
Heat rejection to aftercooler 145 kW
Heat rejection to atmosphere from engine 107 kW
Heat rejection to atmosphere from generator 41.0 kW
Alternator2
Motor starting capability @ 30% voltage dip 1633 skVA
Frame LC7024F
Temperature Rise 150 ° C
Lube System
Sump refill with filter 38.0 L
Emissions (Nominal)3
NOx g/hp-hr 5.61 g/hp-hr
CO g/hp-hr .47 g/hp-hr
HC g/hp-hr .01 g/hp-hr
PM g/hp-hr .038 g/hp-hr
1
Ambient capability at 300m (984 ft) above sea level. For ambient capability at other altitudes, consult your Caterpillar dealer. Air flow
restriction (system) is added to existing restriction from factory. Generator temperature rise is based on a 40 C (104 F) ambient per NEMA
MG1-32
2
Generator temperature rise is based on a 40° C (104° F) ambient per NEMA MG1-32.
3
Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for
measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77°F, 28.42 in HG and number 2 diesel fuel
with 35° API and LHV of 18,390 btu/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and
engine to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use
values based on a weighted cycle.

4 13 October 2006 11:22 AM


®

STANDBY 600 ekW 750 kVA


60 Hz 1800 rpm 480 Volts

RATING DEFINITIONS AND CONDITIONS

Meets or Exceeds International Specifications: AS1359, Ratings are based on SAE J1349 standard conditions.
AS2789, CSA, EGSA101P, IEC60034, ISO3046, ISO8528, These ratings also apply at ISO3046 standard conditions.
NEMA MG1-32, UL508, 72/23/EEC, 89/336/EEC, 98/37/EEC Fuel rates are based on fuel oil of 35º API [16º C (60º F)]
Standby - Output available with varying load for the gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb)
duration of the interruption of the normal source power. when used at 29º C (85º F) and weighing 838.9 g/liter
Standby power in accordance with ISO8528. Fuel stop (7.001 lbs/U.S. gal.). Additional ratings may be available
power in accordance with ISO3046, AS2789, and BS5514. for specific customer requirements. Consult your
Standby ambients shown indicate ambient temperature Caterpillar representative for details.
at 100 percent load which results in a coolant top tank
temperature just below the shutdown temperature.

5 13 October 2006 11:22 AM


®

STANDBY 600 ekW 750 kVA


60 Hz 1800 rpm 480 Volts

DIMENSIONS

Package Dimensions
Note: Do not use for installation design.
Length 4237.4 mm See general dimension drawings for
Width 1536.0 mm detail (Drawing #2673870).
Height 2165.8 mm
Weight 4001 kg

www.CAT-ElectricPower.com
© 2006 Caterpillar
All rights reserved.
Performance No.: DM7548
Materials and specifications are subject to change without notice.
Feature Code:: C18DE33 The International System of Units (SI) is used in this publication.
CAT, CATERPILLAR, their respective logos, "Caterpillar Yellow," and the
Source:: U.S. Sourced POWER EDGE™ trade dress, as well as corporate and product identity
used herein, are trademarks of Caterpillar and may not be used without
permission.
13 October 2006 8221378