Installer Manual-0
Installer Manual-0
Modulating operation
1 Declarations................................................................................................................................................................................ 3
5 Installation ................................................................................................................................................................................ 20
5.1 Notes on safety for the installation ............................................................................................................................ 20
5.2 Handling .................................................................................................................................................................... 20
5.3 Preliminary checks .................................................................................................................................................... 20
5.4 Operating position ..................................................................................................................................................... 21
5.5 Removal of the locking screws from the shutter........................................................................................................ 21
5.6 Preparing the boiler ................................................................................................................................................... 21
5.6.1 Boring the boiler plate ............................................................................................................................................... 21
5.6.2 Blast tube length........................................................................................................................................................ 21
5.7 Securing the burner to the boiler ............................................................................................................................... 22
5.8 Access to head internal part...................................................................................................................................... 22
5.9 Probe-electrode position ........................................................................................................................................... 22
5.10 Combustion head adjustment.................................................................................................................................... 23
5.11 Gas feeding ............................................................................................................................................................... 24
5.11.1 Gas feeding line ........................................................................................................................................................ 24
5.11.2 Gas train.................................................................................................................................................................... 25
5.11.3 Gas train installation.................................................................................................................................................. 25
5.11.4 Gas pressure............................................................................................................................................................. 25
5.12 Electrical wiring ......................................................................................................................................................... 26
5.12.1 Supply cables and external connections passage .................................................................................................... 27
1 GB 20160897
Contents
7 Maintenance ..............................................................................................................................................................................47
7.1 Notes on safety for the maintenance .........................................................................................................................47
7.2 Maintenance programme ...........................................................................................................................................47
7.2.1 Maintenance frequency..............................................................................................................................................47
7.2.2 Safety test - with gas feeding closed .........................................................................................................................47
7.2.3 Checking and cleaning...............................................................................................................................................47
7.2.4 Measuring the ionisation current ................................................................................................................................48
7.2.5 Safety components ....................................................................................................................................................48
7.3 Opening the burner ....................................................................................................................................................48
7.4 Closing the burner......................................................................................................................................................48
20160897
2 GB
Declarations
1 Declarations
The quality is guaranteed by a quality and management system certified in accordance with ISO 9001:2015.
Manufacturer's Declaration
RIELLO S.p.A. declares that the following products comply with the NOx emission limits specified by German standard “1. BIm-
SchV revision 26.01.2010”.
Product Model Type Output
Forced draught gas burner RS 810/E BLU S032T1 1200 - 8000 kW
Legnago, 19.05.2021 Research & Development Director
RIELLO S.p.A. - Burner Department
Mr. F. Maltempi
3 GB 20160897
Information and general warnings
DANGER: BURNING
This symbol indicates the risks of burns due to
high temperatures.
20160897
4 GB
Information and general warnings
2.1.4 Delivery of the system and the instruction The system supplier must carefully inform the user about:
manual – the use of the system;
– any further tests that may be required before activating the
When the system is delivered, it is important that:
system;
the instruction manual is delivered to the user by the system
– maintenance, and the need to have the system checked at
manufacturer, with the recommendation to keep it in the
least once a year by a representative of the manufacturer
room where the heat generator is to be installed.
or another specialised technician.
The instruction manual shows:
To ensure a periodic check, the manufacturer recom-
– the serial number of the burner;
mends the drawing up of a Maintenance Contract.
.........................................................................................
.........................................................................................
.........................................................................................
.........................................................................................
5 GB 20160897
Safety and prevention
3.1 Introduction
The burners have been designed and built in compliance with the type and pressure of the fuel, the voltage and frequency of the
current regulations and directives, applying the known technical electrical power supply, the minimum and maximum deliveries for
rules of safety and envisaging all the potential danger situations. which the burner has been regulated, the pressurisation of the
It is necessary, however, to bear in mind that the imprudent and combustion chamber, the dimensions of the combustion cham-
clumsy use of the equipment may lead to situations of death risk ber and the room temperature must all be within the values indi-
for the user or third parties, as well as the damaging of the burner cated in the instruction manual.
or other items. Inattention, thoughtlessness and excessive confi- Modification of the burner to alter its performance and desti-
dence often cause accidents; the same applies to tiredness and nations is not allowed.
sleepiness. The burner must be used in exemplary technical safety con-
ditions. Any disturbances that could compromise safety must
It is a good idea to remember the following:
be quickly eliminated.
The burner must only be used as expressly described. Any
Opening or tampering with the burner components is not
other use should be considered improper and therefore dan-
allowed, apart from the parts requiring maintenance.
gerous.
Only those parts envisaged by the manufacturer can be
replaced.
In particular:
The manufacturer guarantees safety and proper
it can be applied to boilers operating with water, steam, diather-
functioning only if all burner components are intact
mic oil, and to other users expressly named by the manufacturer;
and positioned correctly.
WARNING
The user is the person, body or company that has acquired the In addition:
machine and intends to use it for the specific purpose. He is re-
the user must take all the measures neces-
sponsible for the machine and for the training of the people work-
sary to prevent unauthorised people gaining
ing around it.
access to the machine;
The user: the user must inform the manufacturer if
undertakes to entrust the machine exclusively to suitably faults or malfunctioning of the accident pre-
trained and qualified personnel; vention systems are noticed, along with any
undertakes to inform his personnel in a suitable way about presumed danger situation.
the application and observance of the safety instructions. Personnel must always use the personal pro-
With that aim, he undertakes to ensure that everyone knows tective equipment envisaged by legislation
the use and safety instructions for his own duties; and follow the indications given in this man-
Personnel must observe all the danger and caution indica- ual.
tions shown on the machine.
Personnel must not carry out, on their own initiative, opera-
tions or interventions that are not within their province.
Personnel must inform their superiors of every problem or
dangerous situation that may arise.
The assembly of parts of other makes, or any modifications,
can alter the characteristics of the machine and hence com-
promise operating safety. The manufacturer therefore
declines any and every responsibility for any damage that
may be caused by the use of non-original parts.
20160897
6 GB
Technical description of the burner
Range: R
Size
Voltage of auxiliaries:
230/50/60 230V / 50-60Hz
110/50/60 110V / 50-60Hz
7 GB 20160897
Technical description of the burner
(1) Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(2) Pressure at the test point 21)(Fig. 4 on page 11) with zero pressure in the combustion chamber and at maximum burner output.
(3) Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output. The sound
power is measured with the “Free Field” method, as per EN 15036, and according to an “Accuracy: Category 3” measuring accuracy, as set out in
EN ISO 3746.
20160897
8 GB
Technical description of the burner
The maximum dimensions of the burner are shown in Fig. 1. The maximum dimensions of the open burner are indicated by
Bear in mind that inspection of the combustion head requires the the A and R positions.
burner to be opened and the rear part turned on the hinge. The l position is reference for the refractory thickness of the boiler
door.
20162256
P T L
I G M
N
E
C F
A
R
A
Fig. 1
mm A C D E F G I L M N P R S T
RS 810/E BLU 1197 173 363 585 DN80 577 405 990 413 260 1345 1055 420 558
Tab. E
4.7 Burner equipment
9 GB 20160897
Technical description of the burner
20161991
Combustion chamber
pressure - mbar
The burner/boiler combination does not pose any problems if the The firing rates were obtained in special test boilers, according to
boiler is EC approved and its combustion chamber dimensions EN 676 regulations.
are similar to those indicated in the diagram (Fig. 3). In Fig. 3 you can see the diameter and length of the test combus-
If the burner must be combined with a boiler that has not been EC tion chamber.
approved and/or its combustion chamber dimensions are clearly Example:
smaller than those indicated in the diagram, consult the manufac- Output 7000 kW - diameter 120 cm - length 6 m.
turer.
Combustion chamber
m
D2448
Fig. 3
20160897
10 GB
Technical description of the burner
2 1 1 3 4 5 6
7
17 18
16
14 13 12 11 9 8
15
19
20162260
20 21 22 23 24 25
10
27 26
Fig. 4
1 Lifting rings
The burner can be opened to the right or to the left
2 Cover for electrical panel
without links to the fuel supply side.
3 Lever for combustion head movement
4 Air pressure test point for combustion head When the burner is closed, the hinge can be refit-
CAUTION
5 Combustion head ted on the opposite side.
6 Shutter
7 Flame stability disc
8 Gas inlet flange
9 Maximum gas pressure switch
10 Gas servomotor
11 Hinge for burner opening
12 Protection
13 Air inlet for fan
14 Air damper control lever
15 Protection for viewing port
16 Reset button
17 Ignition electrode
18 Flame sensor probe
19 Fan motor
20 Gasket for boiler fixing
21 Gas pressure test point for combustion head
22 Pipe coupling
23 Air pressure test point for combustion head
24 Pressure test point for air pressure switch “+”
25 Air pressure switch
26 Fan
27 Servomotor for air dampers
11 GB 20160897
Technical description of the burner
12
14
6
13
2
4
20162606
11
1
15
21 16
4 5
24
3
26
22 27
23 25
4
20
18 19
4 5 8
9
10
Fig. 5
1 Electrical control box
2 ON/OFF selector
3 Output regulator
4 Earth terminal
5 Supply cables and external connections passage. See sec-
tion “Electrical wiring” on page 26
6 Bracket for applying the kits
7 Main terminal supply board
8 Relay with clean contacts for signalling the burner is in lock-
out
9 Relay with clean contacts for signalling the burner is operat-
ing
10 Auxiliary circuits fuse (includes a spare fuse)
11 Air pressure switch
12 Ignition transformer
13 Ionisation probe cable
14 Operator panel with LCD display
15 Light signalling burner lockout
16 Reset button
17 Control terminal board 4-20 mA
18 Star/triangle start-up line contactor
19 Thermal relay (with RESET button)
20 Triangle contactor
21 Star contactor
22 Auxiliary contacts
23 Timer for star/triangle start up
24 Sheath for maximum gas pressure switch
25 Sheath for air servomotor
26 Sheath for gas servomotor
27 Sheath for motor cables
20160897
12 GB
Technical description of the burner
Warnings
To avoid accidents, material and/or environmental
damage, observe the following instructions!
The control box is a safety device! Avoid opening
WARNING
or modifying it, or forcing its operation. Riello
S.p.A. cannot assume any responsibility for dam-
age resulting from unauthorised interventions!
Risk of explosion!
An incorrect configuration can provoke fuel over-
charging, with the consequential risk of explosion!
The operators must be aware that the incorrect
setting of the visualisation and operation control
box, and of the positions of the fuel and/or air ac-
tuators, can cause dangerous conditions during
burner operation.
The control box is a system to check the burners, based on a mi-
croprocessor and equipped with components to adjust and su-
pervise medium and large capacity forced draught burners. D8266
The control box contains the following components:
Fig. 6
– burner management system with valve leak detection control
device; The connections to the actuators do not provide a secure
– electronic device to check the fuel/air ratio with a maximum separation from the mains voltage.Before connecting or
of 2 actuators; changing the actuators the system should be off to avoid any
– Modbus interface. conditions that could cause the formation of condensation or
humidity. Otherwise, before switching on again, make sure
For the safety and reliability of the control box,
that the entire control box is perfectly dry!
comply with the following instructions:
Static charges must be avoided since they can damage the
WARNING control box’s electronic components when touched.
All interventions (assembly and installation operations,
assistance, etc.) must be carried out by qualified personnel.
Before carrying out any checks on the wiring, fully isolate the
system from the electric mains (omnipolar separation).
Check the system is not powered and cannot be accidentally
reconnected. Failure to do this will lead to the risk of electro-
cution.
Protection against electrocution from the control box and all
connected electric components is obtained with the correct
assembly.
After every intervention (assembly and installation opera-
tions, assistance, etc.), ensure the wiring is in order and that
the parameters are correctly set, then perform the safety
checks.
Falls and collisions can negatively affect the safety func-
tions. In this case, the control box must not be operated,
even if it displays no evident damage.
During the programming of the air-fuel ratio control curves,
the technician should constantly observe the quality of the
combustion process (for example using a gas analyser) and,
in the event of inadequate combustion values or dangerous
conditions, should take appropriate action, for example shut-
ting down the system manually.
The plugs of the connection cables or other accessories can
be disconnected when the system has been switched off.
13 GB 20160897
Technical description of the burner
Technical data
Control box Mains voltage AC 230 V -15% / +10%
Mains frequency 50 / 60 Hz ±6%
Power absorption < 30 W
Safety class I, with components in compliance with II and III, ac-
cording to DIN EN 60730-1
Load on Fuse on the control box (can be inspected) 6.3 AT
‘input’ terminals Undervoltage
– Safety switch-off from operating position to mains < AC 186V
voltage
– Restart when mains voltage picks up > AC 195V
Cable length – Main line AC 230 V Max. 100 m (100 pF / m)
– Control load (TL1-TL2) Max. 20 m (100 pF/m)
– External reset button (RS) Max 20 m (100 pF/m)
– Load exit (DC 0/2...10V) Max. 10 m (100 pF/m)
– Fuel valve Max. 3 m (100 pF/m)
– Other lines Max. 3 m (100 pF/m)
Environmental Storage DIN EN 60721-3-1
conditions – Climatic conditions Class 1K3
– Mechanical conditions Class 1M2
– Temperature range -20 ... +60 °C
– Humidity < 95% RH
Transport DIN EN 60721-3-2
– Climatic conditions Class 2K2
– Mechanical conditions Class 2M2
– Temperature range -30 ... +60 °C
– Humidity < 95% RH
Operation DIN EN 60721-3-3
– Climatic conditions Class 3K3
– Mechanical conditions Class 3M3
– Temperature range -20 ... +60 °C
– Humidity < 95% RH
Tab. F
Condensation, the formation of ice and the entry
of water are prohibited!
WARNING
20160897
14 GB
Technical description of the burner
Operation Checking of
Start-up Switching off seal
t1 TSA1
Phase number
Timer 2 (parameters)
Thermostat/pressure switch
X3-04 Pin 1/2
safety TS
Thermostat/pressure switch
X5-03 Pin 1/4
indicator TL
X10-05 Pin 2 Pin 3/4
X10-06 Pin 1/2 Ionisation probe ION
INPUT SIGNALS
Transformer of
X4-02 Pin 2/3
TA ignition
OUTPUT SIGNALS
90°
Nominal load
Pos. of post-purging
Fuel
90°
Nominal load
Pos. of post-purging
X53 Ignition load
Air
Low flame
Pos. without load
0°
S8870
Fig. 7
Signal ON
Signal OFF
15 GB 20160897
Technical description of the burner
Ignition transformer
powered Valve powered
Fan motor powered Flame presence
Pre-heater active
Lockout
only for light oil burners
Heat request Lock-out lamp
20160897
16 GB
Technical description of the burner
17 GB 20160897
Technical description of the burner
Warnings
To avoid accidents, material or environmental
damage, observe the following instructions!
Do not open, modify or force the actuators.
WARNING
All interventions (assembly and installation
operations, assistance, etc.) must be carried
out by qualified personnel.
Before modifying the wiring of the servomotor
in the connection area, fully disconnect the
burner control device from the power supply
(omnipolar separation).
To avoid the risk of electrocution, protect the
connection terminals in a suitable manner
and correctly fix the cover.
After every intervention (assembly and instal-
lation operations, assistance, etc.), ensure D8271
Fig. 10
the wiring is in order, then make the safety
checks. Technical data
Falls and collisions can negatively affect the Model SQM33.5...
safety functions. In this case, the servomotor
Operating voltage AC / DC 24V ± 20%
must not be operated, even if it displays no
evident damage. Safety class 2 according to EN 60 730
Power absorption Max. 10 W
Assembly notes Protection level IP54 in compliance with EN 60 529-1
The connection between the actuator command Cable connection RAST2,5, connectors
shaft and the control element must be rigid, with-
WARNING
out any mechanical play. Rotation direction - GAS servomotor: clockwise
- Air servomotor: anticlockwise
Installation notes
The rotation direction is set in the
The static torque is reduced when the electrical supply of the
factory using the control box param-
actuator is switched off.
eter REC ...
WARNING
During the maintenance or replacement of the Rated torque (max.) 3 Nm
actuators, be careful not to invert the connec-
tors. Static torque (max.) 3 Nm
WARNING
Running time for 90° 5 s.
Weight approx. 1.4 kg
Environmental conditions:
Operation DIN EN 60 721-3-3
Climatic conditions Class 3K5
Mechanical conditions Class 3M4
Temperature range -20...+60°C
Humidity < 95% rh
Tab. H
20160897
18 GB
Technical description of the burner
19 GB 20160897
Installation
5 Installation
After carefully cleaning all around the area where the burner will
The installation of the burner must be carried out
be installed, and arranging the correct lighting of the environ-
by qualified personnel, as indicated in this manual
ment, proceed with the installation operations.
and in compliance with the standards and regula-
WARNING tions of the laws in force.
All the installation, maintenance and disassembly
operations must be carried out with the electricity Combustion air inside the boiler must be free from
supply disconnected. hazardous mixes (e.g.: chloride, fluoride, halo-
DANGER
gen); if present, it is highly recommended to carry
DANGER out cleaning and maintenance more frequently.
5.2 Handling
20160897
20 GB
Installation
2
1 D12015 3
Fig. 14
21 GB 20160897
Installation
20162275
Fig. 17
Fig. 18
20160897
22 GB
Installation
5
6
These output values may not match with the actual values as the
combustion conditions change according to the plant.
The factory regulation corresponds to the minimum output (cou-
pling position: 1).
Coupling position Output (kW) Fig. 19
3 3500
4 4333
5 5166
6 6000
6 8010
Tab. J
20166577
Combustion head
Output (kW)
Fig. 20
23 GB 20160897
Installation
6C Includes Fig. 22
– safety valve
– working valve
DMV “flanged or threaded”
6D Includes:
– safety valve
– working valve
7 Minimum gas pressure switch
8 Leak detection control, provided as an accessory or integrat-
ed, based on the gas train code. In compliance with the EN
676 standard, the leak detection control is compulsory for
burners with maximum outputs over 1200 kW.
9 Gasket, for “flanged” versions only
10 Pressure adjuster
P2 Up-line pressure of valves/adjuster
P3 Upstream pressure of the filter 20065609
Fig. 23
L Gas train, supplied separately
L1 The responsibility of the installer CB “flanged or threaded”
20065707
Fig. 24
20160897
24 GB
Installation
5.11.2 Gas train Calculate the approximate maximum output of the burner in this
Approved according to standard EN 676 and provided separately way:
from the burner. – subtract the combustion chamber pressure from the gas
pressure measured at test point P1) (Fig. 25).
– Find, in the table Tab. K related to the burner concerned, the
5.11.3 Gas train installation pressure value closest to the result of the subtraction.
– read the corresponding output on the left.
Disconnect the electrical power using the main
system switch. Example for RS 810/E BLU with G20 natural gas:
DANGER Maximum output operation
Gas pressure at test point P1)(Fig. 25) = 27.6 mbar
Pressure in combustion chamber = 2 mbar
Check that there are no gas leaks. 27.6 - 2 = 25.6 mbar
A pressure of 25.6 mbar, column 1, corresponds in the table Tab.
K to an output of 5750 kW.
Beware of train movements: danger of crushing of This value serves as a rough guide; the effective output must be
limbs. measured at the gas meter.
To calculate the required gas pressure at test point P1) (Fig. 25),
set the MAX output required from the burner operation:
Make sure that the gas train is properly installed – find the nearest output value in the table Tab. K for the burner
by checking for any fuel leaks. in question.
– read, on the right (column 1), the pressure at the test point
P1)(Fig. 25).
The operator must use appropriate tools for instal- – Add this value to the estimated pressure in the combustion
lation. chamber.
1 p (mbar) 2 p (mbar)
kW
G 20 G 25 G 20 G 25
3500 9.5 14.0 0.4 0.6
4250 14 20.6 0.6 1.0
5000 19.4 28.5 0.9 1.4
P1 P4
5750 25.6 37.7 1.2 1.8
Fig. 25
6500 32.7 48.1 1.5 2.3
7250 40.7 59.9 1.9 2.9
5.11.4 Gas pressure 8010 49.7 73.0 2.3 3.5
Tab. K indicates the minimum pressure drops along the gas sup- Tab. K
ply line, depending on the maximum burner output.
The values shown in Tab. K refer to:
– Natural gas G 20 NCV 9.45 kWh/Sm3 (8.2 Mcal/Sm3)
– Natural gas G 25 NCV 8.13 kWh/Sm3 (7.0 Mcal/Sm3)
Column 1
Pressure drop on combustion head.
Gas pressure measured at the test point P1) (Fig. 25), with:
• Combustion chamber at 0 mbar;
• Burner working at maximum output;
• Combustion head adjusted as in page 23.
Column 2
Pressure loss at gas butterfly valve 10)(Fig. 23) with maximum
opening: 90°.
25 GB 20160897
Installation
If the cover is still present, remove it and proceed with the electri-
cal wiring according to the wiring diagrams.
Use flexible cables in compliance with the EN 60 335-1 standard.
20160897
26 GB
Installation
A Fan motor
B Maximum gas pressure switch
C GAS servomotor
D AIR servomotor
20076574
Fig. 26
27 GB 20160897
Start-up, calibration and operation of the burner
20160897
28 GB
Start-up, calibration and operation of the burner
Air/fuel synchronisation is carried out with the relevant air and 6.4.4 Output upon ignition
gas servomotors by logging a calibration curve by using the elec- Ignition must occur at a lower output than the max. operation out-
tronic cam. put. Regulations provide that the ignition output of this burner
It is advisable, to reduce the loss and for a wide calibration field, must be equal to or less than 1/3 of the MAX operation output.
to adjust the servomotors to the maximum of the output used, the Example:
nearest possible to the maximum opening (90°). MAX operation output of 8010 kW.
The choking of the air, taking into account the maximum combus- The ignition output must be equal to or less than 2670 kW with ts
tion output, takes place by varying the adjustment of the combus- = 3s
tion head (See “Combustion head adjustment” on page 23.). In order to measure the ignition output:
On the gas butterfly valve, the fuel step according to the burner disconnect the plug-socket on the ionisation probe cable
output required, with servomotor completely open, is carried out (the burner will fire and then go into lockout after the safety
by the pressure stabiliser on the gas train. time has elapsed);
perform 10 consecutive ignitions with lockouts;
6.4.1 Air adjustment for maximum output on the meter, read the quantity of gas burned:
Adjust the servomotor to maximum opening (nearly 90°) so This quantity must be equal to, or lower than, the quantity
that the air butterfly valves are entirely open. given by the formula, for ts = 3s:
29 GB 20160897
6.5 Final adjustment of the pressure switches
1 kPa = 10 mbar
WARNING
PGM
D3856
Fig. 30
20160897
30 GB
6.5.3 Minimum gas pressure switch
Adjust the minimum gas pressure switch (Fig. 31) after perform-
ing all the other burner adjustments with the pressure switch set
to the start of the scale.
With the burner operating at maximum output, increase adjust-
ment pressure by slowly turning the relative knob clockwise until
the burner stops.
Now turn the knob anticlockwise by 0.2 kPa (2 mbar) and repeat
burner start-up to ensure it is uniform.
If the burner locks out again, turn the knob anticlockwise again by
0.1 kPa (1 mbar).
D3855
Fig. 31
6.5.4 PVP pressure switch kit
Adjust the pressure switch for the leak detection control (PVP kit)
(Fig. 32) according to the instructions supplied with the kit.
1 kPa = 10 mbar
WARNING
D3855 Fig. 32
31 GB 20160897
6.6 Visualisation and programming mode
6.6.1 Normal mode 6.6.1.4 Error state message, display of the errors and
The Normal mode is the standard operation mode visualised on information
the operator panel display. It is the main level of the menu. The display visualises alternately the error code (in the example
Visualises the operation conditions and allows you to modify c: 12) and the relative diagnostic (in the example d: 0).
the operation point of the burner manually. The system goes into safety mode and the message shown in the
It does not require any use of the keys of the Operator next figure appears.
Panel.
It allows access to the other visualisation and programming
modes. P
From Normal mode you can access other levels:
D9005
– Info mode (InFo)
– Service mode (SEr) V h min s %
– Parameter mode (PArA)
Some examples in the standard conditions are given below. P
D9006
6.6.1.1 Burner in stand-by display
The burner is in the heat request waiting mode, or the selector “0- V h min s %
1” (Fig. 28 on page 28) is at “0”.
The burner goes into lockout.
The display visualises alternately the lockout code (in the exam-
P
ple alongside c: 4) and the relative diagnostic (in the example d:
3). The red lockout lamp is on.
D9002
V h min s %
P
6.6.1.2 Display during starting / stopping
D9007
The display visualises the various phases of the start-up, ignition
and switch-off of the burner. V h min s %
In the example, the display indicates that the burner is in
Phase 30 (see diagram Fig. 33) and there are 12 seconds until
the next phase. P
D9008
P
V h min s %
The burner is working in the requested load position (in the exam-
ple alongside, 78.4%). V h min s %
P
P
D9004
D9010
V h min s %
V h min s %
20160897
32 GB
Start-up, calibration and operation of the burner
6.6.1.5 Reset procedure Releasing the “F” key, the standard visualisation appears, with
The burner is in lockout when the red indicator light on the oper- the current load percentage flashing: this means that the burner
ator panel is lit up, and the display visualises the lockout code (in is working in Manual mode (any outside adjustment is excluded
the example alongside c: 4) and the relative diagnostics (in the and only the safety devices are active).
example d: 3) alternately.
D9016
P
V h min s
D9007
V h min s % Keep the “F” key pressed and, with the keys “+” or “–”, increase
or decrease the load percentage.
P
D9008 P
D9017
V h min s %
V h min s
To reset, press the “i/reset” key for 1 s: the display will show “rE-
SEt”. When the key is released, the lockout signal will disappear To exit manual mode, press the keys “+” and “-” (ESC) simulta-
and the red indicator light will switch off. neously for 3 seconds: the burner will work in Automatic mode
The control box is reset. and the output will depend on the thermostat/adjustment pres-
sure switch (TR).
ESC
P
D9013
/reset V h min s %
6.6.2 Info mode
6.6.1.6 Manual lockout procedure The Info mode (InFo) visualises general system information. To
If necessary, it is possible to manually block the control box and, access this level you must:
consequently, the burner, by pressing the key “i/reset” simulta- press the “i/reset” key for 1-3 s.
neously with any other key of the operator panel. Release the key immediately when the display shows
“InFo”.
With the selector “0-1” (Fig. 28 on page 28), the
burner does not stop immediately, but the switch-
off phase is activated. P
CAUTION
D9019
6.6.1.7 Manual operation procedure
/reset V h min s %
After the adjustment of the burner and the setting of the points on
the modulation curve, it is possible to manually check the opera- The list of parameters (in the sequence in which they are dis-
tion of the burner along the entire curve. played) is shown in Tab. L.
Example:
No. Parameter
the burner is working at the requested load percentage: 20%.
Volumetric delivery of fuel in the unit of measurement
167
selected
P 162 Operation time with flame
163 Operation time
D9014
33 GB 20160897
Start-up, calibration and operation of the burner
D9020
ter you will see 7 dashes, the first one flashing.
/reset V h min s %
The list of parameters (in the sequence in which they are dis- VSD
P
played) is shown in Tab. M.
D9025
No. Parameter F A
954 Flame intensity (%) V h min s %
960 Actual fuel which passes in units of volume / h
(m³/h, l/h, ft³/h, gal/h)
P
121 Manual setting of output
D9026
Not defined = automatic operation
922 Position of the servomotors (expressed in de- V h min s %
grees, symbol )
0 = fuel With the keys “+” and “–” select the first character of the pass-
1 = air word (letter or number), and confirm by pressing the key “i/re-
161 Number of errors set”.
701÷725 Log of the errors: 701-725.01, Code
Tab. M P
D9027
6.6.3.1 Operating mode on Info Mode and Service Mode
After access to these levels, the display visualises the number of V h min s % /reset
the parameter (flashing) on the left, and the corresponding value
on the right. Once you have confirmed, the sign “–” will appear.
Continue in the same way for the other characters.
After inserting the last character of the password, confirm by
P pressing the key “i/reset”: if the password inserted is correct you
will see “PArA” for a few seconds, then you can access the var-
D9021
P
D9024
V h min s %
20160897
34 GB
Start-up, calibration and operation of the burner
D9022
Setting of air/fuel adjustment points
V h min s %
500: ParA Positioning of servomotors
Select the group of parameters with keys “+” and “-”, and con- Choice of positions of the air/fuel servomotors in
firm by pressing the key “i/reset”. the various phases.
Within the group you have chosen, scroll through the list with the 600: ParA Servomotors
keys “+” and “-”. At the end of the list, the display visualises Setting and addressing of the servomotors.
“End”. 700: HISt Log of the errors:
To return to Normal visualisation mode, simultaneously press the Choice of different visualisation modes for the er-
keys “+” and “-” (ESC) twice. rors log.
900: dAtA Process information
Visualisation of information for the remote man-
ESC
agement of the burner.
Tab. N
/reset All the parameters are checked in the factory.
Modification/tampering may compromise the
good operation of the burner and cause injury to
WARNING people or damage to things. In any case, modifi-
cations must be carried out by qualified person-
nel.
P V h mi s % /reset
D9028
To return to the list of parameters, press the keys “+” and “-”
h min s % (ESC) simultaneously.
P
D9029
/reset V h min s %
Press the key “+” and increase the value to 25 seconds (flash-
ing). Press the key “i/reset” to confirm and store.
35 GB 20160897
Start-up, calibration and operation of the burner
6.7.0.1 Procedure for inserting and adjusting points on Select another point, or exit this area by pressing the keys “+”
the modulation curve and “-” (ESC) simultaneously.
Nine adjustment/calibration points (P1 ÷ P9) can be inserted in
ESC
the control box for each servomotor, varying their position by de-
grees and, consequently, the quantity of air and fuel introduced.
The ignition point P0 is independent of the minimum modulation
value. This means that, in the event of difficulty, it is possible to
switch on the burner at a value other than the modulation mini- 6.7.0.2 CALC function
mum (P1). The diagram (Fig. 33) shows how the fuel modulation curve is
To access the Parameter mode (group 400) referring to the Ac- modified if the values of point “P5” are changed.
cess procedure with password. By keeping the “+” key pressed for more than 3 s, the points
from “P6” to “P8” are recalculated.
To insert or adjust a point, proceed as follows.
By keeping the “-” key pressed for more than 3 s, the points
Using the keys “+” and “-” insert/select the curve point you want from “P4” to “P2” are recalculated.
and wait for it to flash: this means that the servomotors are now
positioned on the values shown on the display and which corre-
D7908
spond to the point previously set. 100
It is now possible to insert/modify the position by degrees. 90
Original
80
curve
The set value does not require confirmation. el
Fu
Angle (degrees)
70
WARNING
60
50 CALC+
P
40
D9032
V h min s % 30
For the fuel servomotor, keep the key “F” pressed (the position 20 CALC-
in degrees flashes) and press the keys “+” or “-” to increase or 10
decrease the value. Recalculation
0
P0 P1 P2 P3 P4 P5 P6 P7 P8 P9
P Point of the curve
Fig. 33
D9033
F The diagram of Fig. 34 shows the fuel modulation curve when, af-
s %
ter the modification of point “P5”, the recalculation of all the other
For the air servomotor, keep the key “A” pressed (the position in points is not carried out.
degrees flashes) and press the keys “+” or “-” to increase or de- D7909
crease the value. 100
90
P 80
el
Fu
D9034
70
A
Angle (degrees)
V h min 60
VSD 20
P
10
D12135
F A
0
V h min %
P0 P1 P2 P3 P4 P5 P6 P7 P8 P9
Point of the curve
Fig. 34
20160897
36 GB
Start-up, calibration and operation of the burner
Check that the operator panel display shows the heat request Otherwise, modify the ignition point (see the sectionProcedure
and “OFF Upr”: this means it is necessary to set the modulation for inserting and adjusting points on the modulation curve.
curve of the burner.
P
P
D9032
D9035
V h min s %
V h min s %
Access the Parameters Level referring to Access procedure with The values shown in the figure are purely for indi-
password. cation purposes.
The display screen displays the parameters group 400. WARNING
Phase 38:
P The ignition phase begins and the spark goes off.
D9023
Phase 40:
V h min s % The gas valves open (the count of the safety time begins). Using
the appropriate visor check there is a flame and that the combus-
Confirm with the key “i/reset”
tion parameters are correct. if necessary, vary the degrees of
opening/closing of the air and fuel servomotors.
If the control box goes into lockout, press the keys “+” and “-”
(ESC) simultaneously: the display visualises alternately the lock-
out code for flame absence c: 4) and the relative diagnostic (d:
/reset 3).
The display shows “run”
D9007
20064414
V h min s %
D9008
The phases are listed in the section List of phases.
V h min s %
Phase 22:
Solve the problem, referring to the paragraph Ignition failure.
Start of the fan motor.
To unlock, see Reset procedure. The display visualises “OFF
Phase 24: Upr”.
The burner goes to the pre-purging position, the air servomotor Repeat the “Start-up procedure”.
opens the damper at 90°.
Phases 80, 81, 82, 83: The values previously inserted remain stored.
These phases relate to the valve seal test. WARNING
Once the ignition has occurred (point “P0”), proceed with the
Phase 30:
calibration of the modulation curve.
The count of the pre-purging time pre-set in the factory begins.
Phase 36:
The burner goes to its switch-on position, point “P0”, defined in
Tab. O on page 38: the display shows a flashing “P0” indication.
If the value proposed is adequate, confirm using the “+” but-
ton.
37 GB 20160897
Start-up, calibration and operation of the burner
Press the button “+”: the display visualises the indicator “P1” If you want to make the burner work on just a part of the modula-
flashing and proposes the same settings as point “P0”. tion curve, modify the parameters “546” and “545” according to
Press button “+” again: the display shows “CALC” for a few sec- the Parameter modification procedure.
onds. Press the keys “+” and “-” (ESC) simultaneously twice, the dis-
play will show the current load position.
P
ESC P
D9041
D9014
V h min s %
V h min s %
The control box will automatically report the same values set in
points “P0” and “P1” at points “P2” to “P8”. At the end of the “Start-up procedure” it is nec-
The purpose of this is to reach point “P9” to regu- essary to carry out a “Backup”, which is used to
late/determine the maximum operation output. memorise the parameters and the data in the con-
WARNING trol box within the display RDI21…
Press “+” until point “P9” is reached.
This operation allows the parameters and the
Once point “P9” is reached wait for the display to show the flash- points of the modulation curve to be restored in
ing indicator “P9” proposing the same settings as point “P0”. the event of problems.
Now it is possible to change this value to obtain the maximum op- It is advisable to perform a backup every time that
erating power desired. a parameter is changed!
If the gas pressure is insufficient, despite opening the gas servo- For the procedure see Backup.
motor to a maximum of 90°, it is necessary to use the gas valve
stabiliser. Factory settings
Burner
P0
After adjusting point “P9” keep the “-” key on the display pressed RS 810
for about 5 seconds, “CALC” appears for a few seconds. air 15°
gas 22°
P Tab. O
D9041
V h min s %
The control box will automatically calculate the points from “P8”
to “P2”, distributing them in a straight line. These are theoretical
and must be checked.
Check that the settings of point “P8” are adequate.
If not, modify the point.
Proceed in sequence, with the “-” button, up to point “P1”.
It is possible to modify point “P1” to obtain a minimum modulation
point different to the ignition point (“P0”).
Before moving on from one point to the next, wait
for the servomotors to reach the position visual-
ised on the display.
During the adjustment of each point, work on the air and gas ser-
vomotors, without modifying the position of the gas valve stabilis-
er.
Halfway through the procedure (i.e. around point P4 or P5), you
are advised to measure gas delivery and check that the output is
about 50% of the maximum output.
If this is not the case, work also on the gas valve stabiliser: in this
case however, it is necessary to revise the calibrations of all the
points previously set.
Once the calibration of point “P1” is completed, confirm by press-
ing the keys “+” and “-” (ESC) simultaneously: parameter “546”
will appear.
If you want to make the burner work on the entire modulation
curve, press the “+” and “-” (ESC) keys simultaneously: in this
way, parameter “546” will automatically be assigned the value of
100% and parameter “545” will have a value of 20%.
20160897
38 GB
Start-up, calibration and operation of the burner
6.9.1 Backup
To perform the backup, proceed as follows: confirm with the key “i/reset”:
access the Parameters Level referring to Access procedure
with password.
The display screen displays the parameters group 400.
/reset
P
The display screen shows the following value:
D9023
V h min s %
P
With the key “-”:
D12143
V h min s %
P
The value will be set to 1. Value 1 is flashing:
D12140
h min s %
P
The 000 parameter blinks, confirm using the “i/reset” key:
D12144
V h min s
P /reset
D12141
V h min s %
P
P
D12142
D12143
V h min s %
V h min s %
39 GB 20160897
Start-up, calibration and operation of the burner
NOTE:
If an error occurs during the backup process, the display It is advisable to perform a backup every time
screen shows a negative value. that a parameter is changed, after checking
Refer to diagnostic code 137 to determine the cause of the that the modification carried out is correct.
WARNING
error (see section List of parameters).
6.9.2 Restore
The parameter bAC_UP appears on the display screen:
Use this procedure when replacing equipment
with a parts code. In this way it is possible to have
the default parameters already memorised or
P
WARNING those memorised during the start-up.
D12142
This procedure cannot be carried out on
equipment coming from other burners. V h min s %
To perform the restore procedure, proceed as follows:
access the Parameters Level referring to Access procedure With the key “+”
with password.
The display screen displays the parameters group 400.
select therEStorE parameter
P
D9023
D12146
V h min s %
P /reset
The display shows the following value.
D12140
h min s %
P
The 000 parameter blinks, confirm using the “i/reset” key:
D12143
V h min s %
P
D12144
h min s %
Confirm with the key “i/reset”: V h min s
/reset
/reset
20160897
40 GB
Start-up, calibration and operation of the burner
D12145
V h min s % At the end of the restore process, it is neces-
sary to check the sequence of functions and
After approx 8 seconds (it depends on the duration of the pro- the list of parameters.
gramme), the 0 value appears on the display screen, this is to in-
dicate that the restore process has been completed correctly.
V h min s % D12143
41 GB 20160897
Start-up, calibration and operation of the burner
20160897
42 GB
Start-up, calibration and operation of the burner
43 GB 20160897
Start-up, calibration and operation of the burner
20160897
44 GB
Start-up, calibration and operation of the burner
Tab. P
6.10 Operation
Burner without modulating operation kit The burner stops when the heat request is less than the heat
Once the start-up cycle is completed, the servomotor command supplied by the burner at MIN output.
moves on to the thermostat/pressure switch TR that controls the The thermostat/pressure switch TL opens, the control box
pressure or the temperature in the boiler. carries out the switching off phase.
If the temperature or the pressure is low (so the thermostat/ The air damper closes completely to reduce heat losses to a
pressure switch TR is closed), the burner progressively minimum.
increases the output as far as the MAX value (point “P9”). As an alternative to control through TR, the command for burner
If the temperature or the pressure increases as far as the modulation can be made also using a 4-20 mA signal.
opening of the thermostat/pressure switch TR, the burner
progressively reduces the output as far as the MIN value Burner with modulating operation kit
(point “P1”). The sequence repeats endlessly. See manual enclosed with the adjuster kit.
If the burner does not switch on, there is a lockout within 3s of the
In the event the burner stops, in order to prevent
electrical supply reaching the gas valve.
any damage to the installation, do not unblock the
It may be that the gas does not arrive at the combustion head burner more than twice in a row.
within the safety time of 3s. WARNING
If the burner locks out for a third time, contact the
In this case increase gas ignition flow rate.The arrival of gas to customer service.
the pipe coupling is displayed on the pressure gauge, as shown
in (Fig. 27 on page 28). In the event there are further lockouts or faults
with the burner, the maintenance interventions
must only be carried out by qualified, authorised
DANGER personnel, in accordance with the contents of this
manual and in compliance with the standards and
regulations of current laws.
If the flame should go out during operation, the burner will lockout
within 1s.
45 GB 20160897
Start-up, calibration and operation of the burner
The burner can be stopped by: There are now two possibilities:
intervening on the disconnecting switch of the electrical sup- – using the operator panel according to the manual lockout pro-
ply line, located on the boiler panel; cedure on page 32;
removing the transparent protection after unscrewing the rel- – using the switch 0-1 of Fig. 28 on page 28.
ative screw.
Disconnect the connector of the ionisation probe The burner must stop in lockout due to ignition failure
Tab. Q
20160897
46 GB
Maintenance
7 Maintenance
The periodic maintenance is essential for the good operation, Before carrying out any maintenance, cleaning or checking oper-
safety, yield and duration of the burner. ations:
It allows you to reduce consumption and polluting emissions and
to keep the product in a reliable state over time. Disconnect the electrical supply from the burner
The maintenance interventions and the calibration by means of the main system switch.
DANGER
of the burner must only be carried out by qualified,
authorised personnel, in accordance with the con-
DANGER tents of this manual and in compliance with the
Close the fuel interception tap.
standards and regulations of current laws.
DANGER
47 GB 20160897
Maintenance
Disconnect the electrical supply from the burner Wait for the components in contact with heat
by means of the main system switch. sources to cool down completely.
DANGER
Refit following the steps described but in reverse order; refit all
burner components as they were originally assembled. Carry out all maintenance work and mount the
casing again.
20160897
48 GB
Faults - Possible causes - Solutions
Error
Diagnostic code Meaning of the REC 37.400A2 system Recommended measures
code
No communication between REC 37.400A2 and Check the wiring between the control box REC 37.400A2 and
No Comm
RDI21… display RDI21…
2 # No flame at the end of TSA1
1 No flame at the end of safety time 1 (TSA1)
2 No flame at the end of safety time 2 (TSA2)
No flame at the end of safety time 1 (TSA1)
4
(software version V02.00)
3 # Air pressure error
0 Air pressure switch off
1 Air pressure switch on
4 Air pressure on – Lockout alarm at start
20 Air pressure, fuel pressure on - Alarm lock at start
68 Air pressure, POC on – Alarm lockout at start
84 Air pressure, fuel pressure, POC on - Alarm lockout at start
4 # Extraneous light
0 Extraneous light during start-up
1 Extraneous light during switch-off
2 Extraneous light during start-up – Lockout alarm at start
Extraneous light during start-up, air pressure - Alarm
6
lockout at start
Extraneous light during start-up, fuel pressure - Alarm
18
lockout at start
Extraneous light during start-up, air pressure, fuel pressure
24
- Alarm lockout at start
Extraneous light during start-up, POC – Alarm lockout at
66
start
Extraneous light during start-up, air pressure, POC - Alarm
70
lockout at start
Extraneous light during start-up, fuel pressure, POC -
82
Alarm lockout at start
Extraneous light during start-up, air pressure, fuel pressure,
86
poc - Alarm lockout at start
7 # Loss of flame
0 Loss of flame
3 Flame loss (software version V02.00)
The diagnostics covers the period between the closure of the fuel
3…255 Flame loss during TÜV test (flame loss test) valve to the point the flame loss is detected (resolution 0.2 s
12 # Valve leak detection control
Leak test
0 V1 leaks Check if the valve on the side of the gas has any leaks.
Check the wiring and make sure that the circuit is open.
49 GB 20160897
Faults - Possible causes - Solutions
Error
Diagnostic code Meaning of the REC 37.400A2 system Recommended measures
code
Leak test
Check if the valve on the side of the burner has any leaks.
1 V2 leaks Check if the pressure switch for the leak test (PGVP) is closed
when gas pressure is not present.
Check the wiring and check if there is a short circuit.
The valve leak detection is active, but the minimum gas
2 Valve leak detection test not possible pressure switch is selected as input for X9-04 (check
parameters 238 and 241).
The valve leak detection is active, but no input has been
3 Valve leak detection test not possible
assigned (check parameters 236 and 237).
Valve leak detection is active, but 2 inputs have already been
4 Valve leak detection not possible assigned (configure parameter 237 or maximum gas Pressure
switch or POC).
The valve leak detection is active, but 2 inputs have been
5 Valve leak detection not possible
assigned (check parameters 236 and 237).
14 # POC
0 POC Open Check if the closure contact of the valve is closed.
Check the wiring.
1 POC Closed Check if the closure contact of the valve opens when the valve
is checked.
Check the wiring.
64 POC Open - Alarm lockout at start
Check if the closure contact of the valve is closed.
Check that the pressure switch is closed when no pressure is
19 80 Fuel pressure, POC - Alarm lockout at start present from the fuel.
Check that there are no short-circuits.
20 # Pmin
0 Minimum gas/oil pressure absent Check that there are no line interruptions.
1 Scarcity of gas - Alarm lockout at start Check that there are no line interruptions.
21 # Pmax/POC
Pmax: Max. gas/oil pressure exceeded Check the wiring.
0
POC: POC open (software version V02.00) POC: check whether the closure contact of the valve is closed.
Check the wiring.
1 POC closed (software version V02.00) Check if the closure contact of the valve opens when the valve
is checked.
Check the wiring.
POC Open - Lockout alarm at the start (software version
64 Check if the contact of the valve opens when the valve is
V02.00)
checked.
22
# Safety circuit/Burner flange
OFF S
0 Safety circuit open /Burner flange open
Safety circuit open /Burner flange open - Alarm lockout at
1
start
Safety circuit open /Burner flange open, extraneous light -
3
Alarm lockout at start
Safety circuit open /Burner flange open, extraneous light -
5
Alarm lockout at start
Safety circuit open /Burner flange open, extraneous light -
17
Alarm lockout at start
Safety circuit open /Burner flange open, extraneous light -
19
Alarm lockout at start
Safety circuit open /Burner flange open, extraneous light -
21
Alarm lockout at start
Safety circuit open /Burner flange open, extraneous light,
23
air pressure, fuel pressure - Alarm lockout at start
Safety circuit /Burner flange open, POC - Alarm lockout at
65
start
Safety circuit open /Burner flange open, extraneous light,
67
POC - Alarm lockout at start
Safety circuit open /Burner flange open, air pressure, POC
69
- Alarm lockout at start
Safety circuit open /Burner flange open, extraneous light,
71
air pressure, POC - Alarm lockout at start
Safety circuit open /Burner flange open, fuel pressure, POC
81
- Alarm lockout at start
Safety circuit open /Burner flange open, extraneous light,
83
air pressure, POC - Alarm lockout at start
20160897
50 GB
Faults - Possible causes - Solutions
Error
Diagnostic code Meaning of the REC 37.400A2 system Recommended measures
code
80 # VSD control range limit 2. The VSD train times are not shorter than those of the
standard unit (parameters 522, 523).
3. The VSD characteristic is not linear. The VSD voltage input
configuration must correspond with that of the standard unit
(parameter 645).
4. The VSD does not follow the changes of the standard unit
quickly enough. Check the VSD settings (input filter, slide
compensation, different latent speeds).
1 Lower control range limit The VSD speed was too high.
2 Upper control range limit The VSD speed was too low.
Excessive electromagnetic interference on the sensor line ->
81 1 Interruption in speed limit input
improve the EMC.
82 # Error during VSD speed standardisation
Time-out at the end of the standardisation, during deceleration
Standardisation time-out (the descent time of the VSD train of VSD.
1
is too long) 1. The VSD train times are not shorter than those of the
standard unit (parameter: 523).
Error during the logging of the standardised speed ---> block the
2 Logging of the standardised speed not successful
standard unit, reset it and repeat the standardisation.
51 GB 20160897
Faults - Possible causes - Solutions
Error
Diagnostic code Meaning of the REC 37.400A2 system Recommended measures
code
The standard unit does not receive pulses from the speed
sensor:
1. The motor does not turn.
3 Speed sensor circuit open
2. The speed sensor is not connected.
3. The speed sensor is not activated by the sensor disc (check
the distance).
The motor has not reached a stable speed after acceleration.
1. The VSD train times are not shorter than those of the
standard unit (parameters 522, 523).
2. The VSD characteristic is not linear. The VSD voltage input
configuration must correspond with that of the standard unit
Variation in speed / VSD acceleration time too long / speed
4 (parameter 645).
below the minimum limit for standardisation
3. The VSD does not follow the changes of the standard unit
quickly enough. Check the VSD settings (input filter, slide
compensation, different latent speeds).
4. The VSD speed is below the minimum for standardisation
(650 rpm).
The motor rotation direction is incorrect.
1. The motor does not rotate in the correct direction ---> modify
5 Incorrect rotation direction the parameterisation of the rotation direction, or invert 2 phases.
2. The sensor disc is incorrectly assembled ---> turn the sensor
disc.
The required pulse pattern (60°, 120°, 180°) has not been
correctly identified.
1. The speed sensor does not detect all the noses of the sensor
disc ---> check the distance.
6 Implausible speed sensor signals 2. When the motor turns, other metal parts are detected along
with the noses.
---> improve the assembly.
3. Electromagnetic interference on the sensor lines ---> check
the cable path, improve the EMC.
The standardised speed measured is not within the allowed
7 Standardised speed not valid range.
1. The motor turns too slowly or too quickly.
Microcomputer speeds 1 and 2 have an excessive deviation.
This may be caused by incorrect standardised speeds (e.g.
15 Speed deviation µC1 + µC2
after the reintegration of a set of data in a new unit)
---> repeat the standardisation and check the air/fuel ratio.
The standardisation was performed in the wrong phase.
20 Incorrect phase of the phase controller The only phases allowed are 12 ---> controller OFF, restart
the standardisation.
The safety loop or burner flange is open ---> repeat the
21 Safety loop/burner flange open
standardisation with the safety loop closed.
The air actuator has no reference, or has lost it.
1. Check whether the reference position can be approached.
22 Pneumatic actuator without reference 2. Check whether the actuators have been swapped over.
3. If the error only arises after the start of standardisation, the
actuator may be overloaded and unable to reach its destination.
The standardisation was started with the VSD deactivated --->
23 VSD deactivated
activate the VSD and repeat the standardisation.
The standardisation was started without a valid operation mode
24 No valid operation mode ---> activate a valid operation mode and repeat the
standardisation.
The standardisation was started with a pneumatic control of the
25 Pneumatic control of the air/fuel ratio air/fuel ratio ---> it is not possible to carry out the standardisation
with a pneumatic control of the air/fuel ratio.
The VSD is controlled but not standardised ---> perform the
128 Run command without prior standardisation
standardisation.
The motor turns but is not standardised ---> perform the
255 No standardised speed available
standardisation.
83 # VSD speed error The required speed has not been reached.
The speed was not reached because the control range limit was
Bit 0
Lower control range limit activated.
Valence 1
---> for the measurements, see error code 80.
Bit 1 The speed was not reached because the control range limit was
Greater control range limit
Valence 2...3 activated ---> for the measurements, see error code 80.
The speed has not been reached because there are too many
Bit 2
Stop caused by electromagnetic interference electromagnetic interferences on the sensor line. For the
Valence 4...7
measurements, see error code 81.
20160897
52 GB
Faults - Possible causes - Solutions
Error
Diagnostic code Meaning of the REC 37.400A2 system Recommended measures
code
The speed was not reached because the curve was too steep.
1. With a train REC3... of 20 s, the speed variation between 2
points of the curve (in modulating mode) cannot exceed 10%.
With a train REC3... of 10 s, the speed variation between 2
points of the curve (in modulating mode) cannot exceed 20%.
Bit 3 With a train REC3... of 5 s, the speed variation between 2 points
Curve too steep in terms of train speed
Valence 8 of the curve (in modulating mode) cannot exceed 40%.
---> Between the ignition point (P0) and the low flame point (P1),
the speed in modulating mode may vary by a maximum of 40%,
regardless of the train REC3….
2. The VSD train must be about 20% faster than the train of the
standard unit (parameters 522, 523).
No speed detected, despite the control.
1. Check whether the motor turns.
Bit 4
Speed signal interruption 2. Check whether the speed sensor provides a signal (LED /
Valence 16
check the distance from the sensor disc).
3. Check the VSD wiring.
For about 1 s, the speed deviation was >10% outside the
Bit 5 envisaged range.
Quick switch-off due to excessive speed deviation
Valence 32 1. Check the train times of REC3.... and VSD.
2. Check the VSD wiring.
84 # Servomotors curve slope
1. With a train REC3... of 20 s, the speed variation between
points of the curve (in modulating mode) cannot exceed 10%.
.With a train REC3... of 10 s, the speed variation between points
of the curve (in modulating mode) cannot exceed 20%.
2. With a train REC3... of 5 s, the speed variation between
Bit 0
VSD: Curve too steep in terms of train speed points of the curve (in modulating mode) cannot exceed 40%.
Valence 1
---> Between the ignition point (P0) and the low flame point (P1),
the speed in modulating mode may vary by a maximum of 40%,
regardless of the train REC3….
The VSD train must be about 20% faster than the train of the
standard unit (parameters 522, 523).
Bit 1 The slope of the curve can correspond to a maximum position
Fuel servomotor: Curve too steep in terms of train ratio
Valence 2..3 variation of 31° between 2 points of the modulation curve.
Bit 2 The slope of the curve can correspond to a maximum position
Air servomotor: Curve too steep in terms of train ratio
Valence 4..7 variation of 31° between 2 points of the modulation curve.
85 # Reference error of a servomotor
The reference of the fuel servomotor was not successful.
It was not possible to reach the reference point.
0 Reference error of the fuel servomotor
1. Check if the servomotors have been inverted.
2. Check if the servomotor is blocked or overloaded.
The reference of the air servomotor was not successful.
It was not possible to reach the reference point.
1 Reference error of the air servomotor
1. Check if the servomotors have been inverted.
2. Check if the servomotor is blocked or overloaded.
The parameterisation of an actuator (e.g. the reference position)
Bit 7
Reference error owing to parameter modification has been modified. This error will be visualised to start up a new
Valence 128
reference.
86 # Fuel servomotor error
It was not possible to reach the target position within the
0 Position error required range ---> Check to see if the servomotor is blocked or
overloaded.
Open circuit detected on the connection of the servomotor
Bit 0
Circuit open ---> Check the wiring (voltage between pins 5 or 6 and 2 of the
Valence 1
X54 connector should be > 0.5 V).
Bit 3 The slope of the curve can correspond to a maximum position
Curve too steep in terms of train ratio
Valence 8 modification of 31° between 2 points of the modulation curve.
Overloading of the servomotor or servomotor subjected to
mechanical torsion.
Bit 4
Deviation of section compared with the last reference 1. Check if the servomotor is blocked in any point along its
Valence 16
range of action.
2. Check if the torque is sufficient for the application.
87 # Air servomotor error
It was not possible to reach the target position within the
0 Position error requested tolerance range.
1. Check if the servomotor is blocked or overloaded.
Open circuit detected on the connection of the servomotor
Bit 0
Circuit open ---> Check the wiring (voltage between pins 5 or 6 and 2 of the
Valence 1
X54 connector should be > 0.5 V).
53 GB 20160897
Faults - Possible causes - Solutions
Error
Diagnostic code Meaning of the REC 37.400A2 system Recommended measures
code
20160897
54 GB
Faults - Possible causes - Solutions
Error
Diagnostic code Meaning of the REC 37.400A2 system Recommended measures
code
55 GB 20160897
Faults - Possible causes - Solutions
Error
Diagnostic code Meaning of the REC 37.400A2 system Recommended measures
code
252 (-4) After restoration, the pages are still in INTERRUPTION Repeat the reset and backup.
253 (-3) The restoration cannot currently be carried out Repeat the reset and backup.
254 (-2) Interruption owing to transmission error Repeat the reset and backup.
255 (-1) Interruption owing to time-out during the restoration Carry out a reset, check the connections and repeat the backup.
146 # Time-out of the system automation interface Refer to the Modbus User Documentation (A7541).
1 Modbus time-out
150 # TÜV test
1 (-1) Invalid phase The TÜV test can only be started in phase 60 (operation).
The output of the TÜV test must be lower than the minor output
2 (-2) The TÜV test default output is too low
limit.
The output of the TÜV test must be greater than the upper
3 (-3) The TÜV test default output is too high
output limit.
4 (-4) Manual interruption No error: Manual interruption of the TÜV test by the user.
No flame loss after the fuel valves have been closed
1. Check for any extraneous lights.
5 (-5) TÜV test timeout
2. Check that there are no short-circuits.
3. Check whether one of the valves is leaking.
165 # Internal error
166 0 Watchdog reset internal error
167 # Manual lockout The control box has been manually blocked (no error).
1 Manual lockout from remote reset command
2 Manual lockout from RDI21…
3 Manual lockout from PC interface
During a regulation of the curve via the operating panel
Manual lockout from RDI21… RDI21…the timeout for the operating menu is passed (setting
8
Timeout/interrupted communication via the 127 parameter), or else the communication between
REC 37.400A2 and RDI21... has been interrupted.
During an adjustment of the curve via the PC interface, the
Manual lockout from PC interface
9 communication between REC 37.400A2 and the operator panel
Communication interrupted
has been interrupted for more than 30 seconds.
Manual lockout after the PC tool has performed a tentative The PC tool has performed a tentative reset, even if the system
33
reset has worked correctly.
Carry out a reset; if the error arises repeatedly, replace the
168 ÷ 171 # Internal error management
control box.
200 OFF # System free of errors No error.
201 OFF
# Lockout or error at start Lockout or error due to lack of unit parameter settings.
UPr
Bit 0
No valid operation mode
Valency 1
Bit 1
No fuel train defined
Valency 2..3
Bit 2
No curve defined
Valency 4..7
Bit 3
Standardisation speed not defined
Valency 8..15
Bit 4
Backup / Reset impossible
Valency 16..31
202 # Selection of internal operation mode Redefine the operation mode (parameter 201).
Redefine the operation mode (parameter 201)
203 # Internal error Carry out a reset; if the error arises repeatedly, replace the
control box.
204 Phase number Program stop The program stop is active (no error).
Carry out a reset; if the error arises repeatedly, replace the
205 # Internal error
control box.
Combination of control box and operator panel not
206 0
allowed
207 # Compatibility of control box with operator panel
0 Obsolete version of control box
1 Obsolete version of operator panel
Carry out a reset; if the error arises repeatedly, replace the
208 - 209 # Internal error
control box.
The selected operating mode is not released for the
210 0 Select an operating mode released for the standard unit.
standard unit
20160897
56 GB
Faults - Possible causes - Solutions
Error
Diagnostic code Meaning of the REC 37.400A2 system Recommended measures
code
Tab. T
57 GB 20160897
Appendix - Accessories
A Appendix - Accessories
UV sensor kit
Burner Code
RS 810/E BLU 20077814
20160897
58 GB
Appendix - Electrical panel layout
1 Index of layouts
2 Indication of references
2 Indication of references
/1.A1
Sheet no.
Co-ordinates
59 GB 20160897
20160897
-
)**+
,- ,- ,-
/ /
.
/ /
,-
$!
60 GB
,-
,-!
)**+ )**+
$!
$!
0
$!
!
0
0
!
$!
0
0 #
0
20 /3
0
1
!""#! "$%!& '%%""#%$ !" #"(!!"(! !"""#! !$"!
"&
'
"&
'
(
(
(
(
(
(
(
(
(
61 GB
Appendix - Electrical panel layout
"& "&
"& "& "&
"& "& "&
"& "& "&
)
"
"
"
%)#
"%
*"+"#
*)"*"
"* #%)#!#"#!%"#!"#! -)!"!-"!-"!
)!"
"!"*! #) !"#!" !"#!, #)!"!#"!#"!# $)!"$"!"! !)!#"
!"!#"
!
)!!"!*"!!"! !)!"!"!#"! )
"
"
"
#)!"#
"!"#
#%)#
" !"%
*"#!"+" !"#
"#!
!
"!#
!"
!!$!
% !!!
!
!!!
"!#
20160897
20160897
#!+++
%&#
)3#7 $#,*)) $*&#
+(& + 8!(9 ## -+
-+
*
#
1
.
! !
/ 0
.
#
-
+
62 GB
*
*
-+" -+"
& &
-
+# -+"
" "
-+
-+
&
*
Appendix - Electrical panel layout
. .
# #
. / .
. ! . !
. !
:
&
*
$ %2 *%- *%#- *#%- *% ,#2(**)-,#**)3-4%&#-#* 32 (&!)-3(#- *&!-3#( ,2(()-#,-(-% 62%!##-%6%)(#-%6%)(#-%( *% $
2&#)- *!-&)(-!3' &2#"#-##&-#-5& )2&!()-)&#-)&#-)&# 2)-(&-)#-) 2#&)-(*#-#&-(* #
&2)&#- )3&-)&- %& "2))-#"-)%#-) 2()*#)-()*#-()*#-()*# "2))-)*"-)-)*" &,#2(**)-#"#-,#**)3-##&-4%&#-#-#* -%&
!#$%&'()&*##!+++ #!+++)#()&**,)% #(# !##!+++ !#$)&!()&*#!+++
&&&
0 &&&& , 0&&&& )
) )') )
'!! -
- 0&&&& )
) )') )
'&
*
&
'&
'&
( ( $ $
$
'&
'&
'&
63 GB
'& '&
'& '&
)
$
)
)
! $+$'$ ' $' $ +- ' ,'. $ '- ,"+ '," ' ', -+--'- '-'- $ 0+$" '$0$ '$0$ '$ $ !
+ ' ''", % -+) '- ') '-/ -+ ' - ' - ' - + '' ' + - ') ' - '
+# ','# ' $ +' '$- ' )+) ') ') ') -+'-''- - +- ') ' ,'- '. $ ') '- '-$
" # !$% &&& &&& $ " # &&& " # ! &&&
20160897
20160897
& ***
&
&
(
&
( &(
(
(+ (+ + + $( &+ (+ (+ + + $( &+ $(
/ / &4 $(
&4 &/-***
/4 $( &4
-*
$
% % %
%& /***
/4 4 %&
:.<88"99#;.<9"
$
& !"# &
& ***
(
&
/0 $(
%
$(
(
,
$(
(
,
$
$
64 GB
/
/
$(
$(
(+
(+
(+
(+
$(
/
/
+
+
+
+
&+
&+
.89#:;
% %
%
Appendix - Electrical panel layout
78
4 & %
.##
%
***/0 %&
1--- 1$-2-3(-$ 2'1(&-2'-(&-2 $1$
$-$
-$
-$
61
&'-
6-
6-
,
,1(
-&,-(
-&'2
) $(14
-$
(-4
-$
5( $1
(&-
($-
($-
($ ,1
-(,-
-
1
$(-4
-
$(-
(1
(-
2(-
(-
(
1
-
-
$-
414-4-4-4 $1
-$-
-$ $(1$-4
-2-$
(-3(-4
-$-$
(
&' ()(
& ***
& ***
(
&'
& *** &' (&(
& ***
*
*
* *
+,
*
*-
+,
**
*
+,
+,
+,
65 GB
.
.
)
)
-
*
%
%
.
%)
.
$*,,,
#/#+#+#+# 0/+0$+1#+ $&/+$&++$ 0/+0++# )/#&+#)#+#)#+#%#
%/+%++&$ /2++2+' /+++ %/+%++ /+2++
/+$++# /++#+ 2/2+2+2+2 /+++ 0/+2+0$++1#+2++#
20160897
( /
20160897
" !+.
(
(
(
'5
.68 .68 9
.&
,#
* .!# ! *
'#
+
* *
"( &( (
& "
((:"
( !
(
.
!
'5
(
! !& #! # !0!&&#!3 '#4&
'
66 GB
! "'(
) ! +!
(
(
!
(
*#
*#
*&
*!
*
Appendix - Electrical panel layout
!
(
( '
* *
*!!!
*&&!#'
*&! !
*& !.&!2 !
>*'&!*!!
* *&&
*&! &
* *&
. *&?*&+*&+*&+*& ? + "+@&!+* "'?*! +"'+*!+" ? + ++& 4?&'+&4& +&4& +&*& .
*?! +*+! +'"2 !?+!++1! ?! + !+ !+ ! ? +!+ + ?! ++!+*
*!?# !+* "!+# !+*&! ? ++ &+ ? + + + ? + + + ! ? ++ "+!+@&!++*+&!
#!&0! !! !* ! !'1 #!&&2&.1'! #!34&..&30!&
( /
1 "1% "
"
1 "/0 "
"
1 "/
0
2
,-.
,-.
+
+
"
*
*
+
67 GB
4" 6
4" 6
!
!!"
"4"
"%"
"
1 "6
"4"
"%"
"
1 "6
" ")4" "" "6 ")4" "" "6
$" & 4" " 6 & 4" " 6
Appendix - Electrical panel layout
%!
%%&
%"&%
"3"4"4"4" $3 4$145"4 1%341%441 $3 4 $4 4 " *3"%4"*"4"*"4""
3444%1( 3'4 4'4 & 34 4 4
34
44 3 4'4 4
3!414!4" 344" 4 '3'4'4'4' 34 44 $3 4'4$14 45"4'4 4 "
!"# $ %&'!""("&% !)*"")
#"
20160897
$ % ! & '
20160897
!"#####
(
(
(
(
(
(
(
(
$
") "
"":$": " " "
6/6.09-:3:- 6/6.09-:3:-
!"##### "" $####":
-:3938,4 -3CB/98--038,8 -3CB/234.138,8
/0B/-9/-98/" % /0B/-9/-98/
;%%##<
;
%=<
(
(
$
68 GB
==
==
;%<
=)=;
<
=)=;<
(
Appendix - Electrical panel layout
";$<": "; <%" "
,-./01234.1 3784./0138,8
86/7:,-.8- 6/6.09
30/3:-" """ 2/9B/98--038,8 2/9B/234.138,8
53--.06789- ";$<":" "
$)%:
;%%##< ;%%##< ;%%#!< ;%%##< ;%%##<
>
)
)
)
>()
)@
)(
>
)
)
)
(>(()(
)()( >
)
)
)?
?>
)
?))* (>
)(
)
)(A (>)(
)(
)(
?>)?)
) >(
)
)(
)
>
)
))
>)
)(
) >
)
)
)
(>)())( (
>()
)
)(
)@
)
)(
)(
(
)
(
* )
(
(()((
(
(
+
)
(
$ % ! & '
Appendix - Electrical panel layout
69 GB 20160897
RIELLO S.p.A.
I-37045 Legnago (VR)
Tel: +39.0442.630111
http:// www.riello.it
http:// www.riello.com
Subject to modifications