Compactlogix 5370 Controllers: User Manual
Compactlogix 5370 Controllers: User Manual
Compactlogix 5370 Controllers: User Manual
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably
trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of
this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with
any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
These labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Identifies information that is useful and can help to make a process easier to do or easier to understand.
Rockwell Automation recognizes that some of the terms that are currently used in our industry and in this publication are not in alignment
with the movement toward inclusive language in technology. We are proactively collaborating with industry peers to find alternatives to such
terms and making changes to our products and content. Please excuse the use of such terms in our content while we implement
these changes.
Preface
About This Publication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Download Firmware, AOP, EDS, and Other Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Summary of Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Chapter 1
CompactLogix 5370 Controllers CompactLogix 5370 Control System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Overview Controller Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Support for Integrated Motion over an EtherNet/IP Network . . . . . . . . . . . . . . . . . 16
Electronic Keying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
More Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Example System Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
EtherNet/IP Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
DeviceNet Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Chapter 2
Install the CompactLogix 5370 Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
L1 Controller CompactLogix 5370 L1 Controller Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Install the Secure Digital Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Install the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Mount the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Ground the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Install the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Install the Removable Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Connect Power to the Controller (Series B and C). . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Connect to the Controller Via a USB Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Connect the Controller to an EtherNet/IP Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Connecting to Different EtherNet/IP Network Topologies. . . . . . . . . . . . . . . . . . . . 37
Chapter 3
Install the CompactLogix 5370 Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
L2 Controller CompactLogix 5370 L2 Controller Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Install the Secure Digital Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Install the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Mount the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Ground the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Install the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Remove and Replace the Removable Terminal Block. . . . . . . . . . . . . . . . . . . . . . . . 51
Wire the Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Wire Size and Terminal Screw Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Connect Power to the Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Connect to the Controller Via a USB Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Connect the Controller to an EtherNet/IP Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Chapter 4
Install the CompactLogix 5370 Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
L3 Controller CompactLogix 5370 L3 Controller Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Install the Secure Digital Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Install the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Assemble the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Remove and Replace the Removable Terminal Block. . . . . . . . . . . . . . . . . . . . . . . . 65
Wire the Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Wire Size and Terminal Screw Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Mount the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Ground the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Connect Power to the Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Connect to the Controller Via a USB Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Connect the Controller to an EtherNet/IP Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Connecting to Different EtherNet/IP Network Topologies. . . . . . . . . . . . . . . . . . . . 72
Chapter 5
Complete Software Tasks Set the IP Address of a Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Required at CompactLogix 5370 Use the BOOTP Server to Set the IP Address of the Controller . . . . . . . . . . . . . . . . 75
Use the DHCP Server to Set the IP Address of the Controller . . . . . . . . . . . . . . . . 80
Controller Installation
Use RSLinx Classic Software to Set the Controller IP Address . . . . . . . . . . . . . . . . 81
Use the Logix Designer Application to Set the IP Address of the Controller . . . . . 82
Use the SD Card to Set the IP Address of the Controller . . . . . . . . . . . . . . . . . . . . . 85
Change the IP Address of a Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Change the Network IP Address with RSLinx Classic Software. . . . . . . . . . . . . . . . 87
Change the Network IP Address with Logix Designer Application . . . . . . . . . . . . . 88
Change the Network IP Address with an SD Card . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Load the Controller Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Use the ControlFLASH Software to Load Firmware. . . . . . . . . . . . . . . . . . . . . . . . . . 90
Use AutoFlash to Load Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Use the Secure Digital Card to Load Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Select the Operating Mode of the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Chapter 6
Communicate Over Networks EtherNet/IP Network Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Available Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
EtherNet/IP Network Functionality. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Nodes on an EtherNet/IP Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
EtherNet/IP Network Topologies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Socket Interface with CompactLogix 5370 Controllers . . . . . . . . . . . . . . . . . . . . . 108
Quality of Service (QoS) and I/O Module Connections. . . . . . . . . . . . . . . . . . . . . . . 109
EtherNet/IP Network Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
DeviceNet Network Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Available Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Compact I/O 1769-SDN DeviceNet Scanner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Power Supply Distance Rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Current Capacity in CompactLogix 5370 L3 Control Systems . . . . . . . . . . . . . . . . 116
Chapter 7
Use I/O Modules with Select I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
CompactLogix 5370 Connect Field Power to I/O Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Embedded I/O Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
L1 Controllers
Local Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Distributed I/O Modules over an EtherNet/IP Network. . . . . . . . . . . . . . . . . . . . . . 130
Validate I/O Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Set the Number of Local Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Empty Slots and Removal and Insertion Under Power Situations. . . . . . . . . . . . . 131
Estimate Requested Packet Interval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Module Faults Related to RPI Estimates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Calculate System Power Consumption. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Physical Placement of I/O Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Use the Event Task. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Configure I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Common Configuration Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
I/O Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Configure Distributed I/O Modules on an EtherNet/IP Network . . . . . . . . . . . . . . . . . . 140
Monitor I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Bus Off Detection and Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Chapter 8
Use I/O Modules with Select I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
CompactLogix 5370 Embedded I/O Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Determine Embedded Module Update Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
L2 Controllers
Channel Update Times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Embedded Analog I/O Modules Data Arrays. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 162
Input Array . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Output Array. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Configuration Array. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Local Expansion Modules - Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
Distributed I/O Modules over an EtherNet/IP Network. . . . . . . . . . . . . . . . . . . . . . 173
Distributed I/O Modules over a DeviceNet Network . . . . . . . . . . . . . . . . . . . . . . . . 174
Chapter 9
Use I/O Modules with Select I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
CompactLogix 5370 Local Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Distributed I/O Modules over an EtherNet/IP Network. . . . . . . . . . . . . . . . . . . . . . 191
L3 Controllers
Distributed I/O Modules over a DeviceNet Network . . . . . . . . . . . . . . . . . . . . . . . . 191
Validate I/O Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Estimate Requested Packet Interval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Module Fault Related to RPI Estimates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Calculate System Power Consumption. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
Physical Placement of I/O Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Power Supply Distance Rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Configure I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Common Configuration Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
I/O Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Configure Distributed I/O Modules on an EtherNet/IP Network . . . . . . . . . . . . . . . . . . 203
Configure Distributed I/O Modules on a DeviceNet Network. . . . . . . . . . . . . . . . . . . . 206
Monitor I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
End Cap Detection and Module Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Chapter 10
Develop Applications Elements of a Control Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Task Priority . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
Scheduled and Unscheduled Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
Routines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Extended Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Access Extended Properties in Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Programming Languages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
Add-On Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
Access the Module Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Create the Add-On Instruction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Monitoring Controller Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
6 Rockwell Automation Publication 1769-UM021K-EN-P - May 2023
Table of Contents
Chapter 11
Develop Integrated Motion Over Motion Axes Support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
an EtherNet/IP Network AXIS_VIRTUAL Axis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
AXIS_CIP_DRIVE Axis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Application
Maximum Number of Position Loop-configured Drives . . . . . . . . . . . . . . . . . . . . . . . . . 233
Position Loop-configured Drive Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
Time Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
Configure Integrated Motion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Enable Time Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Add a Drive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
Scalability in Applications Using Integrated Motion . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
1769-L18ERM-BB1B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
1769-L27ERM-QBFC1B Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
Chapter 12
Use a Secure Digital Card Store or Load a Project with the Secure Digital Card. . . . . . . . . . . . . . . . . . . . . . . . . . . 242
Store a Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
Load a Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Appendix A
Troubleshoot the Module Use Logix Designer Application for Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
Fault Type Determination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
Use the CompactLogix 5370 Controllers Status Indicators . . . . . . . . . . . . . . . . . . . . . . 250
Appendix B
Replacement Considerations Product Comparison. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
Power Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
Embedded DC Input Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
Firmware Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254
Power Supply Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Series B and C Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Series A Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
Appendix C
Connect Power to the Series A Connect External Power to Series A L1 Controllers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
CompactLogix 5370 L1 Connect Field Power to Series A L1 Controllers for I/O Devices . . . . . . . . . . . . . . . . . . 261
Controllers
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
About This Publication This manual describes the necessary tasks to install, configure, program, and operate a
CompactLogix™ 5370 controller. This manual is intended for automation engineers and control
system developers.
CompactLogix 5370 controllers are designed to provide solutions for small and medium-sized
applications.
Rockwell Automation recognizes that some of the terms that are currently used in our industry
and in this publication aren’t in alignment with the movement toward inclusive language in
technology. We’re proactively collaborating with industry peers to find alternatives to such
terms and making changes to our products and content. Please excuse the use of such terms
in our content while we implement these changes.
Download Firmware, AOP, Download firmware, associated files (such as AOP, EDS, and DTM), and access product release
notes from the Product Compatibility and Download Center at rok.auto/pcdc.
EDS, and Other Files
Summary of Changes This publication contains the following new or updated information. This list includes
substantive updates only and is not intended to reflect all changes.
Topic Page
Added conformal coated controller catalog numbers Throughout
Updated to include CompactLogix 5370 L1 series C controller information Throughout
Updated to include CompactLogix 5370 L2 series B controller information Throughout
Updated CompactLogix 5370 L3 controller information Throughout
Added information regarding battery-less, embedded Energy Storage Module (ESM) 35, 54, 71
The CompactLogix™ 5370 controllers offer state-of-the-art control, communication, and I/O
elements in a distributed control package. This product family includes the following
CompactLogix 5370 controllers:
• 1769-L16ER-BB1B
• 1769-L18ER-BB1B
• 1769-L18ERM-BB1B, 1769-L18ERM-BB1BK
• 1769-L19ER-BB1B, 1769-L19ER-BB1BK
• 1769-L24ER-QB1B
• 1769-L24ER-QBFC1B, 1769-L24ER-QBFC1BK
• 1769-L27ERM-QBFC1B
• 1769-L30ER, 1769-L30ERK
• 1769-L30ERM, 1769-L30ERMK
• 1769-L30ER-NSE
• 1769-L33ER, 1769-L33ERK
• 1769-L33ERM, 1769-L33ERMK
• 1769-L33ERMO
• 1769-L36ERM
• 1769-L36ERMO
• 1769-L37ERM, 1769-L37ERMK
• 1769-L37ERMO(1)
• 1769-L38ERM, 1769-L38ERMK
• 1769-L38ERMO(1)
Among the features the CompactLogix 5370 controllers support, are dual EtherNet/IP™ ports
on each controller and support for Integrated Motion over an EtherNet/IP network on some
CompactLogix 5370 controllers.
CompactLogix 5370 Control This table describes the components a CompactLogix 5370 controller uses in a typical
control system.
System Components
Product Family
System Component
CompactLogix 5370 L1 Controllers CompactLogix 5370 L2 Controllers CompactLogix 5370 L3 Controllers
Controller One of the controllers that is documented in this publication
One of the following 1769 Compact I/O™
External power supply that is connected to power supplies:
External power supply that is connected to the • 1769-PA2, 1769-PA2K
the embedded 24V DC nominal input of the
Power supply embedded 24V DC input of the controller, isolated
controller, nonisolated power supply. The • 1769-PB2, 1769-PB2K
power supply
power supply has a 10…28.8 input range. • 1769-PA4, 1769-PA4K
• 1769-PB4, 1769-PB4K
Any of the following: Any of the following:
• EtherNet/IP network via built-in EtherNet/ • EtherNet/IP network via built-in EtherNet/IP network ports
Communication
networks components IP network ports • DeviceNet® network via a 1769-SDN module
• USB connection only for programming and
firmware updates • USB connection only for programming and firmware updates
• One of the following:
– RSLogix 5000® software, version 20.xx.xx, - For CompactLogix 5370 controllers that are using firmware revision 20.xxx
– Logix Designer application, version 21.00.00 or later, - For CompactLogix 5370 controllers that are using firmware revision 21.000 or later
Software • RSLinx® Classic software, version 2.59.xx or later
• RSNetWorx™ for DeviceNet software, version 11.00.00 or later
IMPORTANT: This software isn’t used with CompactLogix 5370 L1 controllers because they do not offer DeviceNet connectivity.
Secure Digital (SD) • 1784-SD1 card - Ships with CompactLogix 5370 controller and offers 1 GB of memory
card for external
nonvolatile memory • 1784-SD2 card - Available for separate purchase and offers 2 GB of memory
• 16 embedded 24V DC digital input points
• 16 embedded 24V DC digital input points -
The nominal input voltage is 24V DC but • 16 embedded 24V DC digital output points
the operating range is 10…28.8V DC. • Only 1769-L24ER-QBFC1B and
1769-L27ERM-QBFC1B controllers • Local expansion modules- 1769 Compact I/
• 16 embedded 24V DC digital output points O modules
- The nominal input voltage is 24V DC but – Four embedded high-speed counters
I/O modules the operating range is 10…28.8V DC. – Four embedded universal analog input points • Distributed I/O - Multiple I/O module
– Two embedded analog output points product lines over DeviceNet and
• Local expansion modules- 1734 POINT I/O™ EtherNet/IP networks
modules • Local expansion modules- 1769 Compact
I/O modules
• Distributed I/O - Multiple I/O module
product lines over an EtherNet/IP network • Distributed I/O - Multiple I/O module product lines
over DeviceNet and EtherNet/IP networks
Reset button If held in during controller power-up, it clears the user program from the internal memory of the controller.
Controller Functionality This table describes the functionality available with CompactLogix 5370 controllers.
Controller Programs EtherNet/IP
Internal Energy Power Supply Onboard User Local I/O Module
Cat. No. Tasks Supported Per Network
Storage Solution Topology Support Distance Rating Memory Size Support
Supported Task
As many as six
1769-L16ER-BB1B 384 KB 1734 POINT I/O
modules(1)
1769-L18ER-BB1B
NA
1769-L18ERM-BB1B, 512 KB As many as eight
1769-L18ERM-BB1BK 1734 POINT I/O
1769-L19ER-BB1B, modules(1)
1 MB
1769-L19ER-BB1BK
1769-L24ER-QB1B
768 KB As many as four
1769-L24ER-QBFC1B,
1769-L24ER-QBFC1BK See footnote(2) Compact I/O
modules
1769-L27ERM-QBFC1B Support the 1 MB
1769-L30ER, 1769-L30ERK following
Yes - Eliminating topologies: As many as eight
1769-L30ER-NSE 32 1000 the need for a • Device Level 1 MB Compact I/O
1769-L30ERM, 1769-L30ERMK battery Ring (DLR) modules
1769-L33ER, 1769-L33ERK • Linear As many as 16
• Traditional star Compact I/O
1769-L33ERM, 1769-L33ERMK 2 MB modules
1769-L33ERMO —
4 As many as 30
1769-L36ERM Compact I/O
3 MB modules
1769-L36ERMO
1769-L37ERM, 1769-L37ERMK
4 MB
1769-L37ERMO(3) —
1769-L38ERM, 1769-L38ERMK
5 MB
1769-L38ERMO(3)
(1) IMPORTANT: You can use up to the maximum number of 1734 POINT I/O modules with the CompactLogix 5370 L1 controllers that are listed in the table in Chapter 2, page 24. This applies only
as long as the total current that the modules draw does not exceed the available POINTBus™ backplane current of 1 A. If you must use more local expansion modules than the POINTBus
backplane current supports, you can install a 1734-EP24DC POINT I/O expansion power supply between local expansion modules to increase the POINTBus backplane power and meet your
system requirements.
(2) CompactLogix 5370 L2 controllers have an embedded power supply. Therefore, you do not need to consider the power supply distance rating when installing the controller. The Compact I/O
modules that are used as local expansion modules in a CompactLogix 5370 L2 control systems operate on a CompactBus. These Compact I/O modules also have a power supply distance
rating that you must consider when installing those modules.
For more information on power supply distance rating regarding how to use Compact I/O modules in a CompactLogix 5370 L2 control system, see Chapter 8, page 177.
(3) Available at software version 31 and firmware revision 31.
The 1769-L30ER-NSE controller is intended for use in applications that require the installed
controller to deplete its residual stored energy to specific levels before transporting it into or
out of your application.
IMPORTANT The Real Time Clock (RTC) does not retain its time and date when the
power is off.
Some applications require that the installed controller to deplete its residual stored energy to
specific levels before transporting it into or out of your application. This requirement can
include other devices that also require a wait time before removing them. See the
documentation of those products for more information.
For more information on how to use CompactLogix 5370 controllers in applications that
require Integrated Motion over an EtherNet/IP network, see Chapter 11, page 231.
Electronic Keying Electronic Keying reduces the possibility that you use the wrong device in a control system. It
compares the device that is defined in your project to the installed device. If keying fails, a
fault occurs.
Electronic Keying Attributes
Attribute Description
Vendor The device manufacturer.
Device Type The general type of the product, for example, digital I/O module.
Product Code The specific type of the product. The Product Code maps to a catalog number.
Major Revision A number that represents the functional capabilities of a device.
Minor Revision A number that represents behavior changes in the device.
Carefully consider the implications of each keying option when selecting one.
More Information
For more detailed information on Electronic Keying, see Electronic Keying in Logix 5000™
Control Systems Application Technique, publication LOGIX-AT001.
EtherNet/IP Network
Kinetix 5500
PowerFlex® 525
PanelView™ Plus 7
• 1769-AENTR
Stratix 5700 • 1769 Compact I/O 1769-L33ERM Control System
Kinetix 5500
PanelView Plus 7
Kinetix 5500
1734-AENTR POINT I/O 1794-AENTR FLEX I/O
DeviceNet Network
E3 Electronic
Overload Relay
For more information on how to use the CompactLogix 5370 L2 or L3 controllers on DeviceNet
networks, see Chapter 6, page 111.
Before You Begin The CompactLogix™ 5370 L1 series B and C controller redesign occurred to provide an option
to use one external power supply for system power and field side power.
There are differences between the CompactLogix 5370 L1, series A and B, controllers, which
are detailed throughout the sections of this manual.
Consider the details in this section before installing a CompactLogix 5370 L1 controller.
• The control system includes the controller, an embedded power supply, and embedded
I/O points.
• The embedded power supply for the series A L16ER, L18ER, or L18ERM controller is a 24V
DC nominal, non-isolated power supply with an input range of 10…28.8V DC. You wire
the embedded power supply via a removable connector.
• The embedded power supply for the series B and C L16ER, L18ER, and L18ERM
controllers, and the series A and C L19ER controller is a 24V DC nominal, isolated
power supply. The input range of the power supply is 10…28.8V DC. You wire the
embedded power supply via a removable connector.
IMPORTANT You must use the latest series and firmware revision for all 1734
POINT I/O modules in the local expansion slots to make sure that
your application operates as expected. Use of an older firmware
revision renders the entire 1734 bus inoperable.
This table lists local expansion module support by controller catalog number.
Local Expansion Module Support for CompactLogix 5370 L1 Controllers
Cat. No. 1734 POINT I/O Modules Supported, Max
1769-L16ER-BB1B 6
1769-L18ER-BB1B
1769-L18ERM-BB1B,
1769-L18ERM-BB1BK 8
1769-L19ER-BB1B,
1769-L19ER-BB1BK
See Chapter 7, page 117 for further information about the I/O modules.
ATTENTION: Do not discard the end cap. Use this end cap to cover the
exposed interconnections on the last mounting base on the DIN rail. Failure to
do so could result in equipment damage or injury from electric shock.
For more information on how to terminate the end of your system, see
page 31.
1734 POINT I/O modules support removal and insertion under power.
Install the Secure The CompactLogix 5370 L1 controller is shipped from the factory with the 1784-SD1 SD card
installed.
Digital Card
Complete these steps to reinstall an SD card that has been removed from the controller back
into the controller or to install a new SD card into the controller.
We recommend that you leave the SD card in the controller, even when it isn’t used. If the
controller experiences a major non-recoverable fault, extended fault information is saved to
the card.
WARNING: W ? hen you insert or remove the SD card while power is on, an electric
arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
1. Verify that the SD card is locked or unlocked according to your preference.
Consider that, if the card is unlocked, the controller can write data to it or read data
from it.
Unlocked Locked
We recommend that you keep the SD card door closed during normal system operation.
For more information on how to use the SD card, see Chapter 12, page 241.
Install the System Complete these steps to install the CompactLogix 5370 L1 control system.
ATTENTION: This product is grounded through the DIN rail to chassis ground.
Use zinc plated chromate-passivated steel DIN rail to assure proper
grounding. The use of other DIN rail materials (for example, aluminum or
plastic) that can corrode, oxidize, or are poor conductors, can result in
improper or intermittent grounding. Secure DIN rail to mounting surface
approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be
sure to ground the DIN rail properly. Refer to Industrial Automation Wiring and
Grounding Guidelines, Rockwell Automation publication 1770-4.1, for more
information.
You can mount the CompactLogix 5370 L1 controller on these DIN rails:
• EN 50 022 - 35 x 7.5 mm (1.38 x 0.30 in.)
• EN 50 022 - 35 x 15 mm (1.38 x 0.59 in.)
Minimum Spacing
Maintain spacing from enclosure walls, wireways, and adjacent equipment. Allow 50 mm (2 in.)
of space on all sides, as shown. This spacing provides ventilation and electrical isolation.
50 mm
Top (2 in.)
50 mm 50 mm
CompactLogix 5370 L1
(2 in.) (2 in.)
Embedded Power
Controller with
End Cap
Side Side
Bottom 50 mm
(2 in.)
System Dimensions
CompactLogix 5370 L1 Control System Dimensions
105 mm 100.00 mm
(4.13 in.) (3.94 in.)
130.00 mm
(5.11 in.)
144.00 mm
(5.67 in.)
CompactLogix 5370 L1 Control System Dimensions with Expansion I/O Modules Installed
12.00 mm
(0.47 in.)
105 mm 100.00 mm
(4.13 in.) (3.94 in.)
130.00 mm
(5.11 in.)
144.00 mm
(5.67 in.)
2. Slide the controller into position on the DIN rail and push the locking tabs in.
3. If you aren’t using local expansion modules, use the tongue-and-groove slots on the
right side of the controller to slide a protective covering onto the controller. The
protective cover ships with the controller.
The covering covers the exposed interconnections on the right side of the controller.
Failure to use a protective covering can result in equipment damage or injury from
electric shock.
If you’re using local expansion modules, see Chapter 7, page 127 for more information
on how to install them in a CompactLogix 5370 L1 control system.
D tus ork
Sta etw
N
E:
O
N
le
t p
pu ou
In oc
erm
IMPORTANT This section describes how to power the controller via the VDC+ and
VDC- terminals.
Connections to the VDC+ and VDC- terminals do not provide power to
input or output devices that are connected to the embedded I/O
modules of the controller or local expansion modules. Power must be
connected to the FP+ and FP- terminals to provide power to input or
output devices that are connected to the embedded I/O modules of the
controller or local expansion modules.
The external power supply can be used to power both the VDC+/- and
FP+/- terminals on the series B and C L1 controllers.
For more information on how to provide power to input or output
devices that are connected to the embedded I/O modules of the
controller and local expansion modules, see Chapter 7, page 117.
WARNING: Do not connect directly to line voltage. Line voltage must be supplied
by a suitable, approved isolating transformer or power supply having short
circuit capacity not exceeding 100VA maximum or equivalent. The controller
power requirement is 30VA.
Power is connected to the controller via a removable connector that is connected to the front
of the controller. This graphic shows the connector.
IMPORTANT The controller is grounded once it’s installed on a DIN rail as described
on page 28.
Complete these steps to connect power to the CompactLogix series B and C L16ER, L18ER, and
L18ERM controllers, and series A and C L19ER controllers.
1. Verify that the external 24V DC power source isn’t powered.
2. Mount the external 24V DC power source on a DIN rail.
The external 24V DC power source can be installed on the same DIN rail as the controller
or a separate DIN rail.
3. Connect wires to the 24V DC+ and 24V DC- connections on the external 24V DC power
source.
WARNING: I?f you connect or disconnect wiring while the field-side power is on,
an electric arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before
proceeding.
5. Connect the wire that is connected to the 24V DC+ terminal on the external 24V DC
power source to the VDC+ terminal. The VDC+ terminal is the top terminal on the
removable connector.
6. Connect the wire that is connected to the 24V DC- terminal on the external 24V DC
power source to the VDC- terminal. The VDC- terminal is the second from the top on the
removable connector.
This graphic shows an external 24V DC power source that is connected to a CompactLogix
5370 L1 controller.
Connect to the Controller The controller has a USB port that uses a Type B receptacle. The port is USB 2.0-compatible
and operates at 12 Mbps.
Via a USB Cable
Use a USB cable to connect your computer to the USB port. With this connection, you can
update firmware and download programs to the controller directly from your computer.
ATTENTION: The USB port is intended only for temporary local programming
purposes and not intended for permanent connection.
The USB cable isn’t to exceed 3.0 m (9.84 ft) and must not contain hubs.
Connect the RJ45 connector of the Ethernet cable to one of the Ethernet ports on the
controller. The ports are on the bottom of the controller.
Bottom of Controller
Port 1 - Front
Port 2 - Back
IMPORTANT This example shows how to connect the controller to the network
through one port. Depending on the network topology of your
application, you can connect both ports of the controller to the
EtherNet/IP™ network.
There are connection and configuration requirements for each EtherNet/IP network topology.
Notes:
Before You Begin Consider these details before installing a CompactLogix™ 5370 L2 controller:
• The control system includes a controller, an embedded power supply, embedded I/O
points, and a 1769-ECR/1769-ECRK right end cap.
• The embedded power supply is a 24V DC input, isolated power supply
This graphic shows an example CompactLogix 5370 L2 controller.
1769-L24ER-QBFC1B Control System
End Cap
Embedded Power
Supply Terminals
ATTENTION: You must use an external power supply that is Class 2 or SELV-
listed for series A L1 controllers.
For example, you can use a 1606-XLSDNET4, standard switched-mode power supply, as
shown in this chapter.
• The controllers have embedded I/O points. You wire the input and output points via a
removable connector.
• The controller supports the use of up to four Compact I/O™ modules on the local 1769
CompactBus backplane as local expansion modules.
For more information on how to use embedded I/O points and local expansion modules,
see Chapter 8, page 145.
• You must terminate the end of the CompactBus via a 1769-ECR/1769-ECRK right end cap
as shown in step 6 on page 50.
• You can’t remove nor install Compact I/O modules while the controller is powered.
Install the Secure The CompactLogix 5370 L2 controller is shipped from the factory with the 1784-SD1 SD card
installed.
Digital Card
Complete these steps to reinstall an SD card that has been removed from the controller back
into the controller or to install a new SD card into the controller.
We recommend that you leave the SD card in the controller, even when it isn’t used. If the
controller experiences a Major Non-recoverable Fault, extended fault information is saved to
the card.
WARNING: When you insert or remove the SD card while power is on, an electric
arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous
before proceeding.
1. Verify that the SD card is locked or unlocked according to your preference.
Consider that, if the card is unlocked, the controller can write data to it or read data
from it.
Unlocked Locked
L24ER
QBFC1B
L24ER
QBFC1B
L24ER
QBFC1B
We recommend that you keep the SD card door closed during normal system operation.
For more information on how to use the SD card, see Chapter 12, page 241.
Install the System Complete these tasks to install the CompactLogix 5370 L2 control system.
You can mount the CompactLogix 5370 L2 controller on these DIN rails:
• EN 50 022 - 35 x 7.5 mm (1.38 x 0.30 in.)
• EN 50 022 - 35 x 15 mm (1.38 x 0.59 in.)
ATTENTION: This product is grounded through the DIN rail to chassis ground.
Use zinc-plated chromate-passivated steel DIN rail to assure proper
grounding. The use of other DIN rail materials (for example, aluminum or
plastic) that can corrode, oxidize, or are poor conductors, can result in
improper or intermittent grounding. Secure DIN rail to mounting surface
approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be
sure to ground the DIN rail properly. Refer to Industrial Automation Wiring and
Grounding Guidelines, Rockwell Automation publication 1770-4.1, for more
information.
Minimum Spacing
Maintain spacing from enclosure walls, wireways, and adjacent equipment. Allow 50 mm (2 in.)
of space on all sides, as shown. This spacing provides ventilation and electrical isolation.
50 mm
Top (2 in.)
50 mm 50 mm
(2 in.)
CompactLogix 5370 L2
(2 in.)
Embedded Power
End Cap
Side Side
Bottom 50 mm
(2 in.)
System Dimensions
1769-L24ER-QB1B Controller System Dimensions
27.65 mm
3.06 mm 59.70 mm
(1.09 in.)
(0.12 in.) (2.35 in.)
105 mm
(4.13 in.)
118.00 mm
(4.65 in.)
2.8 mm 115.00 mm
(0.12 in.) (4.53 in.)
35.00 mm 18.00 mm
25.00 mm
(1.38 in.) (0.71 in.)
(0.98 in.)
105 mm 115.00 mm
(4.13 in.) (4.53 in.)
118.00 mm 126.6 mm
(4.65 in.) (4.98 in.)
118.00 mm
(4.65 in.)
2.8 mm 140.00 mm
(0.12 in.) (5.51 in.)
126.6 mm
118.00 mm (4.98 in.)
(4.65 in.)
18.00 mm
(0.71 in.)
3.06 mm 27.65 mm
84.70 mm
(0.12 in.) (1.09 in.)
(3.33 in.)
105 mm
(4.13 in.)
118.00 mm
(4.65 in.)
2.8 mm 140.00 mm
(0.12 in.) (5.51 in.)
118.00 mm 126.6 mm
(4.65 in.) (4.98 in.)
18.00 mm
(0.71 in.)
6. If you aren’t using local expansion modules, slide the 1769-ECR/1769-ECRK end cap onto
the right side of the controller.
IMPORTANT You must install an end cap onto the right side of the
CompactLogix 5370 L2 controller system either at the end of the
controller. You must also install an end cap at the end of any
local expansion modules that can be installed onto the controller.
7. Secure the end cap onto the controller by pushing the locking mechanism to the left.
If you’re using local expansion modules, see Chapter 8, page 172 for more information
on how to install them in a CompactLogix 5370 L2 control system.
3 1
Item Description
1 Wiring the fingersafe cover
2 Lower retaining screws
3 Upper retaining screws
WARNING: Do not connect directly to line voltage. Line voltage must be supplied
by a suitable, approved isolating transformer or power supply having short
circuit capacity not exceeding 100VA maximum or equivalent.
For example purposes, this section uses a 1606-XLDNET4, standard switched-mode power
supply.
IMPORTANT The 1606-XLDNET4 power supply isn’t certified for use in all
applications, for example, you can’t use it in hazardous locations.
Complete these steps to connect power to the CompactLogix 5370 L2 control system.
1. Verify that the external 24V DC power source isn’t powered.
2. Mount the external 24V DC power source on a DIN rail.
The external 24V DC power source can be installed on the same DIN rail as the controller
or a separate DIN rail.
3. Connect the wires to the 24V DC+ and 24V DC- connections on the external 24V DC
power source.
WARNING: If you connect or disconnect wiring while the field-side power is on,
an electric arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before
proceeding.
4. Strip 8 mm (0.31 in.) insulation from the end of the wire that you connect to the +24V DC
terminal on the controller.
5. Connect the wire from the 24V DC+ terminal on the external 24V DC power source to the
+24V DC terminal on the controller.
6. Strip 8 mm (0.31 in.) insulation from the end of the wire that you connect to the COM
terminal on the controller.
7. Connect the wire from the 24V DC- terminal on the external 24V DC power source to the
COM terminal on the controller.
This graphic shows an external 24V DC power source that is connected to a CompactLogix
5370 L2 controller.
IMPORTANT When you remove power from the CompactLogix 5370 L2 controller to
cycle power, the OK status indicator of the controller remains lit briefly
as the controller passes through its shutdown sequence.
Do not reapply power from the external power supply to the embedded
power supply of the CompactLogix 5370 L2 controller until after the OK
status indicator of the controller is off.
Connect to the Controller The controller has a USB port that uses a Type B receptacle. The port is USB 2.0-compatible
and operates at 12 Mbps.
Via a USB Cable
Use a USB cable to connect your computer to the USB port. With this connection, you can
update firmware and download programs to the controller directly from your computer.
ATTENTION: The USB port is intended only for temporary local programming
purposes and not intended for permanent connection.
The USB cable isn’t to exceed 3.0 m (9.84 ft) and must not contain hubs.
Connect the RJ45 connector of the Ethernet cable to one of the Ethernet ports on the
controller. The ports are on the bottom of the controller.
ATTENTION: Do not plug a DH-485 network cable or a NAP cable into the
Ethernet port. Undesirable behavior and/or damage to the port can result.
Bottom of Controller
Port 1 - Front
Port 2 - Back
IMPORTANT This example shows how to connect the controller to the network
through one port. Depending on the network topology of your
application, you can connect both ports of the controller to the
EtherNet/IP™ network.
There are connection and configuration requirements for each EtherNet/IP network topology.
For more information about EtherNet/IP Network Topologies, see Chapter 6, page 104.
Before You Begin Consider these details when planning your CompactLogix™ 5370 L3 control system:
• The controller is the leftmost device in the system.
• Only one controller can be used on a local 1769 CompactBus. The controller supports the
local bank and up to two more banks.
• The controller has a power supply distance rating of four. This rating means that the
controller must be within four slots of the power supply. You can install as many as
three modules between the power supply and the controller, as shown in this graphic.
• The controllers support this many local expansion modules across multiple I/O banks.
Number of Local Expansion Modules Supported Across Multiple I/O Banks
Cat. No. Local Expansion Modules Supported, Max
1769-L30ER
1769-L30ERK
1769-L30ERM 8
1769-L30ERMK
1769-L30ER-NSE
1769-L33ER
1769-L33ERK 16
1769-L33ERM
1769-L33ERMK
1769-L33ERMO —
1769-L36ERM 30
1769-L36ERMO —
1769-L37ERM, 1769-L37ERMK 31
1769-L37ERMO(1) —
1769-L38ERM, 1769-L38ERMK 31
1769-L38ERMO(1) —
(1) Available at software version 31 and firmware revision 31.
For graphics of CompactLogix 5370 L3 control systems that use one bank or multiple
banks, see page 66.
Install the Secure The CompactLogix 5370 L3 controllers ship from the factory with the 1784-SD1 SD card
installed.
Digital Card
Complete these steps to reinstall an SD card that has been removed from the controller back
into the controller or to install a new SD card into the controller.
We recommend that you leave the SD card in the controller, even when it isn’t used. If the
controller experiences a Major Non-recoverable Fault, extended fault information is saved to
the card.
WARNING: When you insert or remove the Secure Digital (SD) Card while power is
on, an electric arc can occur. This could cause an explosion in hazardous
location installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
1. Verify that the SD card is locked or unlocked according to your preference. Consider the
following when deciding to lock the card before installation:
- If the card is unlocked, the controller can write data to it or read data from it.
Unlocked Locked
We recommend that you keep the SD card door closed during normal system operation. For
more information on how to use the SD card, see Chapter 12, page 241.
Install the System Complete these steps to install the CompactLogix 5370 L3 control system.
You can attach an adjacent Compact I/O module or 1769 Compact I/O power supply to a
CompactLogix 5370 L3 controller before or after mounting. For mounting instructions, see
page 66 or page 69.
WARNING: Remove power before removing or inserting this module. If you insert
or remove the module while backplane power is on, an electric arc can occur.
This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
Complete these steps to install the controller. This example describes how to attach a 1769
Compact I/O power supply to the controller.
1. Verify that line power is disconnected.
2. Make sure that the bus lever of the 1769 Compact I/O power supply is in the unlocked
position. The bus lever leans to the right in the unlocked position.
3. Use the upper and lower tongue-and-groove slots to secure the controller and power
supply together.
Tongue-and-groove Slots
4. Move the power supply back along the tongue-and-groove slots until the bus
connectors align with each other.
5. Use your fingers or a small screwdriver to push the bus lever of the power supply back
slightly to clear the positioning tab.
6. Move the bus lever of the power supply fully to the left until it clicks, which makes sure
that it locks.
7. If your system does not use any local expansion modules, use the tongue-and-groove
slots that were previously described to attach a 1769-ECR Compact I/O end cap
terminator to the last module in the system.
IMPORTANT You must install an end cap onto the right side of the
CompactLogix 5370 L3 controller system either at the end of the
controller. You must also install an end cap at the end of any
local expansion modules that can be installed onto the controller.
8. Wire the 1769 Compact I/O power supply according to the directions in the Compact I/O
Expansion Power Supplies installation instructions, publication 1769-IN028.
If you’re using local expansion modules, see Chapter 9, page 189.
3 1
2
.
Item Description
1 Wiring the fingersafe terminal block
2 Lower retaining screws
3 Upper retaining screws
ATTENTION: During panel or DIN rail mounting of all devices, be sure that all
debris (such as metal chips or wire strands) is kept from falling into the
controller. Debris that falls into the controller could cause damage while the
controller is energized.
A CompactLogix 5370 L3 control system must be mounted so that the modules are horizontal
to each other. If you separate modules into multiple banks, the banks can be vertical or
horizontal to each other.
Example CompactLogix 5370 L3 Control Systems with Local Expansion Modules Installed
Horizontal Orientation
Bank 1
1769-CRRx Cable
Vertical Orientation
Bank 2
Before you mount a CompactLogix 5370 L3 control system, consider these requirements.
Minimum Spacing
Maintain spacing from enclosure walls, wireways, and adjacent equipment. Allow 50 mm (2 in.)
of space on all sides, as shown. This spacing provides ventilation and electrical isolation.
Top 50 mm
(2 in.)
50 mm 50 mm
CompactLogix 5370 L3
(2 in.) (2 in.)
Power Supply
Compact I/O
Compact I/O
End Cap
Module
Side Side
Controller
Bottom 50 mm
System Dimensions
55 mm 70 mm 35 mm
(2.17 in.) (2.76 in.) (1.38 in.)
132 mm
(5.20 in.)
118 mm
(4.65 in.)
52.5 mm 35 mm 35 mm 35 mm 35 mm
(2.07 in.) (1.38 in.) (1.38 in.) (1.38 in.) (1.38 in.)
105 mm
(4.13 in.)
CompactLogix 5370 L3 controllers and the Compact I/O modules have power supply distance
ratings. Power supply distance ratings determine how many slots in a bank that a device can
be from the power supply.
For example, a product with a power supply distance rating of four can only have up to three
slots between it and the power supply.
Device Power Supply Distance Rating
CompactLogix 5370 L3 controller 4
1769 Compact I/O DeviceNet® scanner
4…8, depending on module
For more information about the power supply distance rating
Compact I/O module for a Compact I/O module, see CompactLogix Selection
Guide, publication 1769-SG001
CompactLogix 5370 L3 controllers must be the leftmost device in the control system, and the
system only enables up to three modules between the controller and the power supply. This
graphic shows an example configuration.
Use two M4 or #8 pan head screws to mount the controller. Mounting screws are required on
many modules. Use the assembled modules as a template to drill holes in the panel, as follows:
IMPORTANT Due to module mounting hole tolerance, it’s important to follow this
procedure.
1. On a clean work surface, assemble no more than three modules.
2. Use the assembled modules as a template and carefully mark the center of all module-
mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including any previously
mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel and check for proper hole alignment.
The grounding plate, that is, where you install the mounting screws,
grounds the module when it’s panel-mounted.
6. Use the mounting screws to attach the modules to the panel.
If you’re mounting more modules, mount only the last one of this group and
put the others aside. This process reduces remounting time when you are
drilling and tapping the next group of modules.
7. Repeat steps 1… 6 for any remaining modules.
Connect to the Controller The controller has a USB port that uses a Type B receptacle. The port is USB 2.0-compatible
and operates at 12 Mbps.
Via a USB Cable
Use a USB cable to connect your computer to the USB port. With this connection, you can
update firmware and download programs to the controller directly from your computer.
ATTENTION: The USB port is intended only for temporary local programming
purposes and not intended for permanent connection.
The USB cable isn’t to exceed 3.0 m (9.84 ft) and must not contain hubs.
Plug the USB cable into the CompactLogix 5370 L3 controller as shown.
Connect the RJ45 connector of the Ethernet cable to one of the Ethernet ports on the
controller. The ports are on the bottom of the controller.
ATTENTION: Do not plug a DH-485 network cable or a NAP cable into the
Ethernet port. Undesirable behavior or damage to the port can result.
Bottom of Controller
Port 1 - Front
Port 2 - Rear
IMPORTANT This example shows how to connect the controller to the network
through one port. Depending on the Ethernet network topology of your
application, you can connect both ports of the controller to the
EtherNet/IP™ network.
To complete the tasks that are described in this chapter, you must have the software that is
described in the following table installed on your computer.
Software Required Version
2.59.00 or later
CompactLogix™ 5370 L2 controllers require RSLinx Classic software,
RSLinx® Classic version 2.59.01 or later.
The 1769-L19ER-BB1B controller requires RSLinx Classic software, version
3.74.00
20 - For CompactLogix 5370 controllers using firmware revision 20.
RSLogix 5000® RSLogix 5000 software does not support the 1769-L19ER-BB1B controller.
21 or later - For CompactLogix 5370 controllers using firmware revision 21
Studio 5000 Logix Designer® or later.
28 or later - For the 1769-L19ER-BB1B controller.
BOOTP-DHCP server Most current version is installed with RSLinx Classic software installation
Installed with the installation of one of the following:
• RSLogix 5000 software, version 20
ControlFLASH™ • Studio 5000® environment, version 21 or later
• Studio 5000 environment, version 28 or later for 1769-L19ER-BB1B
controllers
CompactLogix 5370 controllers require a network Internet Protocol (IP) address to operate on
an EtherNet/IP™ network.
The IP address uniquely identifies the controller. The IP address is in the form xxx.xxx.xxx.xxx
where each xxx is a number from 000… 254 with some exceptions for reserved values. These
numbers are examples of reserved values that you can’t use:
• 000.xxx.xxx.xxx
• 127.xxx.xxx.xxx
• 224 to 255.xxx.xxx.xxx
Set the IP Address of You must set the IP address of a CompactLogix 5370 controller when the controller powers up
for the first time, that is, when commissioning the controller for the first time. You aren’t
a Controller required to set an IP address each time the controller cycles power.
You can use these tools to set the IP address of a CompactLogix 5370 controller:
• Bootstrap Protocol (BOOTP) server
• Dynamic Host Configuration Protocol (DHCP) server
• RSLinx Classic software
• Studio 5000 Logix Designer® application
• SD card
IMPORTANT Each tool has connection requirements to set the IP address of the
controller via that tool. For example, your computer must be connected
to the controller via a USB cable to set the initial IP address of the
controller with RSLinx Classic software or the application.
This figure describes how to set the IP address of your CompactLogix 5370 controller on a
power cycle during initial installation or after operation has begun.
No
Is the controller Is the controller
DHCP-enabled? BOOTP- enabled?
Yes
Yes Yes
There are two conditions in which the CompactLogix 5370 controllers use the BOOTP servers
to set the IP address of the controller:
• Initial powerup - Because the CompactLogix 5370 controller ships with BOOTP-
enabled, when it is first powered up, the controller sends a request for an IP address on
the EtherNet/IP network. You can use the BOOTP server to set the IP address, as
described later in this section.
• Powerup after controller operation has begun - When controller power is cycled
after operation has begun, the BOOTP/DHCP server sets the IP address if one of these
conditions exists:
- Controller is BOOTP-enabled - You set the IP address manually with the BOOTP
server.
- Controller is DHCP-enabled - The IP address is set automatically via the DHCP server.
IMPORTANT Before you start the BOOTP/DHCP utility, make sure that you have the
hardware (MAC) address of the controller. The hardware address is on
the front of the controller and uses an address in a format similar to the
following: 00:00:BC:2E:69:F6
Complete these steps to set the IP address of the controller with the
BOOTP/DHCP server.
IMPORTANT To use the BOOTP server, your computer and the controller must be
connected to the same EtherNet/IP network.
1. Start the BOOTP/DHCP software.
2. From the Tools menu, select Network Settings.
The Gateway address, Primary or Secondary DNS address, and Domain Name fields are
optional.
4. Select OK.
The Request History panel appears with the hardware addresses of all devices that
issue BOOTP requests. This process can take some time to complete.
5. Select the appropriate module.
8. Select OK.
9. To assign this configuration to the controller, wait for the controller to appear in the
Relation List panel and select it.
When power is cycled, the controller uses the assigned configuration and does not
issue a BOOTP request.
If you select Disable BOOTP/DHCP and it does not disable BOOTP/DHCP, use RSLinx Classic
software or the Studio 5000 environment to disable BOOTP/DHCP.
8. Select OK.
To disable BOOTP/DHCP from the Studio 5000 environment, perform the following:
1. Start the application.
2. Open the project.
3. Right-click on the controller and select Properties.
4. On the Controller Properties dialog box, select the Internet Protocol tab.
5. Select Manually configure IP settings.
6. Select OK.
7. When prompted to confirm the IP address setting, select Yes.
Be cautious when using DHCP software to configure a module. A BOOTP client, such as the
EtherNet/IP communication modules, can start from a DHCP server only if the DHCP server is
written to handle BOOTP queries. This requirement is specific to the DHCP software package
used. Consult your system administrator to see if a DHCP package supports BOOTP commands
and manual IP allocation.
Be cautious when using the DHCP server to configure a controller. A BOOTP client, such as the
CompactLogix 5370 controllers, can start from a DHCP server only if the DHCP server is written
to handle BOOTP queries. This requirement is specific to the DHCP server used. Consult your
system administrator to see if a DHCP server supports BOOTP commands and manual IP
allocation.
If you use the Rockwell Automation BOOTP or DHCP server in an uplinked subnet where a DHCP
server exists, a controller can procure an address from the enterprise server before the
Rockwell Automation utility even sees the controller. Disconnect from the uplink to set the
address and configure the controller to retain its static address before reconnecting to the
uplink, if necessary.
IMPORTANT To set the IP address, that is, assign an IP address to a controller that
does not have one, for a CompactLogix 5370 controller via RSLinx
Classic software, you must be connected to your controller via the
USB port.
Complete these steps to set the IP address of the controller with RSLinx Classic software.
IMPORTANT These steps show a 1769-L36ERM controller. The same steps also apply
to all CompactLogix 5370 controllers with slight variations in screens.
1. Make sure that a USB cable is connected to your computer and the controller.
2. Start RSLinx Classic software.
After several seconds, an RSWho dialog box appears.
3. If no RSWho dialog box appears, from the Communications pull-down menu, select
RSWho.
The RSWho dialog box appears and includes the USB driver.
4. Right-click the EtherNet/IP module and select Module Configuration.
6. For Network Configuration Type, select Static to assign this configuration to the port.
IMPORTANT If you select Dynamic, on a power cycle, the controller clears the
current IP configuration and starts to send BOOTP requests.
7. Enter the new IP address and Network Mask.
8. Select OK.
As with all configuration changes, if desired, make sure that you’re using the SD card in a way
that does not overwrite the IP address at the next controller power cycle.
For more information on how to use the SD card, see Chapter 12, page 241.
IMPORTANT These steps show a 1769-L18ERM-BB1B controller. The same steps also
apply to all CompactLogix 5370 controllers with slight variations
in screens.
1. Start the application.
2. Set the Project Path.
a. Select RSWho.
3. Select Download.
The new project is downloaded to the controller and the project goes online, in Remote
Program or Program mode.
5. Right-click the controller name and select Properties.
6. On the Controller Properties dialog box, select the Internet Protocol tab.
The IP Settings Configuration values show that the controller has no IP address that is
assigned to it.
IMPORTANT To set the IP address from an SD card, software isn’t required during
the power-up process. However, you must have previously saved the
project to the SD card.
The IP address of the CompactLogix 5370 controller is automatically
configured at power-up as long as you’ve configured an IP address,
stored the program onto a controller, and set the SD card to the Load
Image parameter set to On Power Up.
The option to set the IP address of a CompactLogix 5370 controller via
an SD card at power-up is only one part of the process to load an entire
project to the controller from the SD card.
Use this option carefully. For example, the SD card can contain a
desirable IP address as part of an undesirable project, for example, a
project that is older than the project currently used on the controller.
These requirements apply when using the SD card to set the IP address on a CompactLogix
5370 controller:
• A project must be stored on the SD card.
• The project that is stored on the SD card is configured with the Load Image parameter
set to On Power Up.
For more information on how to use the SD card, see Chapter 12, page 241.
Change the IP Address of a You can change the IP address of a CompactLogix 5370 controller after system operation has
begun. In this case, the controller has an IP address that is assigned to it, but you must change
Controller that IP address.
IMPORTANT You can’t use any of these tools to change the IP address of a
controller:
• Bootstrap Protocol (BOOTP) server
• Dynamic Host Configuration Protocol (DHCP) server
Consider these factors when you determine how to change the IP address of a controller:
• Network isolation from, or integration into, the plant/enterprise network
• Network size - For large, isolated networks, it can be more convenient and safer to use
a BOOTP/DHCP server rather than the Logix Designer application or RSLinx Classic
software. A BOOTP/DHCP server limits the possibility of duplicate IP address
assignment.
However, you can only use the BOOTP/DHCP server to set the IP address of the
controller and not to change it. If you decide to change the IP address of the controller
and want to use a BOOTP/DHCP server to limit the possibility of duplicate IP address
assignment, you must first clear the IP address.
After clearing the IP address, use the steps for using the BOOTP Server on page 75 or
the DHCP Server on page 80 to set the IP address of the controller.
• Company policies and procedures that deal with plant floor network installation and
maintenance
• Level of involvement by IT personnel in plant-floor network installation and
maintenance
• Type of training that is offered to control engineers and maintenance personnel
IMPORTANT The steps on page 81 describe how to use RSLinx Classic Software to
assign an IP address for a CompactLogix 5370 controller that does not
have an IP address.
The steps in this section describe how to use RSLinx Classic Software to
change the IP address on a CompactLogix 5370 controller that has an IP
address that is assigned to it.
The graphics in this section show how to change the IP address for a 1769-L36ERM controller.
The same steps also apply to all other CompactLogix 5370 controllers with slight variations in
screens.
1. Right-click the controller and select Module Configuration.
2. Select the Port Configuration tab when the Module Configuration dialog box appears.
The controller has an IP address and Network Configuration Type.
3. Enter a new IP address and make any other desired changes.
4. To assign this configuration to the controller, select Static in the Network Configuration
Type section of the dialog box.
IMPORTANT If you select Dynamic, on a power cycle, the controller clears the
current IP configuration and starts to send BOOTP or DHCP
requests, depending on the controller configuration.
5. Select OK.
IMPORTANT The steps on page 82 describe how to use the Logix Designer
Application to assign an IP address for a CompactLogix 5370 controller
that does not have an IP address.
The steps in this section describe how to change the IP address on a
CompactLogix 5370 controller that has an IP address that is assigned
to it.
You can change the IP address of a CompactLogix 5370 controller via Logix Designer
application over a USB or EtherNet/IP network connection.
The graphics in this section show how to change the IP address for a 1769-L18ERM-BB1B
controller over a USB connection. The same steps also apply to all other CompactLogix 5370
controllers with slight variations in screens.
1. Verify that your computer is connected to the controller.
2. Verify that your project is online.
3. Right-click the controller name and select Properties.
You can also right-click the Ethernet node in the I/O Configuration section and
select Properties. The Controller Properties dialog box appears on the Internet Protocol
tab.
4. Change the IP address of the controller.
5. Make other changes where necessary.
6. Select OK.
IMPORTANT To set the IP address from an SD card, software isn’t required during
the power-up process. However, you must have previously saved the
project to the SD card.
These requirements apply when using the SD card to change the IP address on a
CompactLogix 5370 controller:
• A project is stored on the SD card.
• The project that is stored on the SD card includes another IP address for the
CompactLogix 5370 controller than the IP address currently in use on the physical
controller that houses the SD card.
• The project that is stored on the SD card is configured with the Load Image parameter
set to On Power Up.
• Power is cycled to the controller with the SD card installed.
For more information on how to use the SD card, see Chapter 12, page 241.
Load the Controller You must download the current firmware before you can use the CompactLogix 5370
controller.
Firmware
IMPORTANT Do not interrupt a firmware update while it is in process. Firmware
update interruption can cause the firmware revision of the
CompactLogix 5370 controller to revert to its out-of-the-box revision
level, that is, 1.xxx.
To load the firmware, you can use any of the following:
• ControlFLASH software that installs with Logix Designer application
• AutoFlash that launches through the application when you download a project and the
controller does not have the matching firmware revision
• SD card (catalog numbers 1784-SD1 or 1784-SD2) with an image stored on the card
IMPORTANT The controller firmware revision that is loaded via the ControlFLASH
software or the AutoFlash option can be overwritten after future
controller power cycles if the conditions described on page 96 exist.
The firmware is available with the application or you can download it from the support website
at rok.auto/support.
Complete these steps to use the ControlFLASH software to load the firmware.
IMPORTANT These steps show a 1769-L36ERM controller. The same steps also apply
to all other CompactLogix 5370 controllers with slight variations
in screens.
1. Verify that a connection exists between your computer and the CompactLogix 5370
controller.
2. Select Start>All Programs>FLASH Programming Tools>ControlFLASH.
IMPORTANT If you expand the controller, that is, expand the network beyond
the first instance in which it appears on the left side of the
screen, you receive the following message:
The target device isn’t in the proper mode to accept an update in
ControlFLASH.
7. Select the revision level to which you want to update the controller and select Next.
Before the firmware update begins, you see the following dialog box. Take the required
action for your application. In this example, the update continues when OK is selected.
After the controller is updated, the status dialog box displays the message Update
complete.
9. Select OK.
10. To close the ControlFLASH software, select Cancel and Yes.
Let the update complete without interruption. If you interrupt a firmware update that is in
process, you’re alerted that an error has occurred. In this case, cycle power to the controller.
The firmware revision level reverts to the 1.xxx revision level and you can begin the update
process again.
Complete these steps to use the AutoFlash utility to load the firmware.
IMPORTANT These steps show a 1769-L36ERM controller. The same steps also apply
to all CompactLogix 5370 controllers with slight variations in screens.
1. Make sure that the network connection is made and your network driver is configured
in RSLinx Classic software.
2. Create a controller project.
3. To specify the controller path, select RSWho.
You can also select to select Update Firmware to complete this process. If you do so,
skip to step 6.
A dialog box appears to indicate that the project revision and controller firmware
revision are different.
6. Use the checkbox and pull-down menu to select your controller and firmware revision.
7. Select Update.
Before the firmware update begins, you can be warned about your controller missing its
SD card. Take the required action, typically select OK, and the firmware update will
begin.
9. When the firmware update is complete, the Download dialog box appears and you can
continue by downloading your project to the controller.
Your application requires the following to load the firmware from an SD card at power-up:
• You must have saved the project to the SD card before the power cycle.
• The firmware revision in the project that is stored on the SD card differs from the
firmware revision on the CompactLogix 5370 controller.
For more information on how to use the SD card, see Chapter 12, page 241.
Select the Operating Mode CompactLogix 5370 controllers have slightly different front designs and mode switch
placements.
of the Controller
WARNING: When you change switch settings while power is on, an electric arc
can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before
proceeding.
Mode Switch Placement on a CompactLogix 5370 L1 Controller
Use the mode switch on the controller to set the operating mode of the CompactLogix 5370
controller.
Mode Switch Position Description
You can perform these tasks:
• Upload projects.
• Run the program and enable outputs.
You can’t perform these tasks:
• Update controller firmware.
Run • Create or delete tasks, programs, or routines.
• Create or delete tags or edit online.
• Import a program to the controller.
• Change the port configuration of the controller, advanced port configuration, nor network configuration settings.
• Change controller configuration parameters that are directly set for operation on a Device Level Ring (DLR) network topology.
You can perform these tasks:
• Update controller firmware.
• Disable outputs.
• Upload/download projects.
Prog
• Create, modify, and delete tasks, programs, or routines.
• Change the port configuration of the controller, advanced port configuration, nor network configuration settings.
You can’t perform these tasks:
• Use the controller to execute (scan) tasks.
You can perform these tasks:
• Upload/download projects.
• Change the port configuration of the controller, advanced port configuration, nor network configuration settings.
• Change between Remote Program, Remote Test, and Remote Run modes through the application.
• The controller executes (scans) tasks.
Remote Run • Enable outputs.
• Edit online.
Rem • Update controller firmware.
• Disable outputs.
• Create, modify, and delete tasks, programs, or routines.
Remote Program
• Download projects.
• Edit online.
• The controller does not execute (scan) tasks.
• Execute tasks with outputs disabled.
Remote Test
• Edit online.
All CompactLogix 5370 controllers also support temporary connections from your computer
via a USB connection.
EtherNet/IP Network The EtherNet/IP network offers a full suite of control, configuration, and data collection
services by layering the Common Industrial Protocol (CIP™) over the standard Internet
Communication protocols, such as TCP/IP and UDP. This combination of well-accepted standards provides the
capability that is required to support information data exchange and control applications.
The CompactLogix 5370 controllers use socket interface transactions and conventional
communication over the EtherNet/IP network to communicate with Ethernet devices that do
not support the EtherNet/IP application protocol.
Available Software
Use the software listed in this table with a CompactLogix 5370 controller on an EtherNet/IP
network.
Version 20 - For CompactLogix 5370 controllers that are • Configure the CompactLogix project.
RSLogix 5000 using firmware revision 20. • Define EtherNet/IP communication.
• Change IP address for devices on network,
Studio 5000 Logix Designer® Version 21 or later - For CompactLogix 5370 controllers including the CompactLogix 5370
application that are using firmware revision 21 or later. (1) controller. Yes. Studio 5000 Logix Designer
application, version 28 or later -
For 1769-L19ER-BB1B controllers
2.59.00 or later • Assign or change IP addresses to devices
CompactLogix 5370 L2 controllers require RSLinx on an EtherNet/IP network.
RSLinx® Classic Classic software, version 2.59.01 or later. • Configure communication devices.
The 1769-L19ER-BB1B controller requires RSLinx Classic • Provide diagnostics.
software, version 3.74.00. • Establish communication between devices.
IMPORTANT While CompactLogix 5370 controllers offer the option of using Ethernet
node count to effectively design a control system, the controllers do
have connection limits on an EtherNet/IP network.
For more information on how to design EtherNet/IP network use in your
CompactLogix 5370 control system, see these resources:
• The EtherNet/IP Capacity Tool Wizard embedded in the Integrated
Architecture® Builder (IAB) software from Rockwell Automation: https://
www.rockwellautomation.com/en-us/support/product/product-
selection-configuration/integrated-architecture-builder.html
The EtherNet/IP Capacity Tool Wizard helps you in the initial layout of
your EtherNet/IP network.
• Ethernet Design Considerations Reference Manual, publication
ENET-RM002.
Any devices that you add directly to the local Ethernet I/O configuration are counted toward
the node limitation of the controller. The following are example devices that are added to the I/
O configuration section in your project and must be counted:
• Remote communication adapters
• I/O modules that are directly connected to the EtherNet/IP network, for example the
1732E-IB16M12R ArmorBlock® EtherNet/IP module
• Motion devices, such as drives
• Remote controllers
• HMI devices that are included in the I/O configuration section, for example, PanelView™
Plus terminals
• Linking devices, such as the 1788-EN2DNR, Ethernet-to-DeviceNet linking device or
1788-EN2DNROM, On-Machine™ Ethernet-to-DeviceNet linking device
• Third-party devices that are directly connected to the EtherNet/IP network
When considering the Ethernet node limitation of a CompactLogix 5370 controller, you do not
count Ethernet devices that exist on the EtherNet/IP network but aren’t added to the I/O
configuration section of the project.
The following devices aren’t added to the I/O configuration section in your project and aren’t
counted among the total number of nodes:
• Computer
• HMIs that aren’t added to the I/O configuration section, for example, PanelView™ Plus
terminals
• MSG instructions
• Devices the CompactLogix 5370 controllers use a socket interface to communicate
with.
For example, the following devices require communication via a socket interface:
- Modbus TCP/IP device
- Barcode scanners
A DLR network topology is a single-fault tolerant ring network that is intended for the
interconnection of automation devices. A DLR network is composed of Supervisor (Active and
Backup) nodes and Ring nodes.
DLR network topologies automatically convert to linear network topologies when a fault is
detected. The conversion to the new network topology maintains communication of data on
the network. The fault condition is typically easily detected and corrected.
CompactLogix 5370 controllers connect directly to a DLR network topology, that is, without
requiring a 1783-ETAP tap to connect to the network. The controllers can function in any of the
roles on a DLR network topology, that is, active supervisor node, back-up supervisor node or
ring node.
IMPORTANT The topology graphics that are shown in this section are examples of
applications that use only DLR network topologies.
We recommend that you exercise caution if you consider designing an
application that includes the connection of a DLR topology with a linear
or star network topology.
For more information on using a DLR network topology, see the EtherNet/IP Embedded Switch
Technology Application Guide, publication ENET-AP005.
Example 1769-L18ERM-BB1B Control System Using DLR Network Topology
Stratix® 5700 1769-L18ERM-BB1B
Kinetix 5500
• 1769-AENTR
Stratix 5700 • 1769 Compact I/O™ 1769-L27ERM-QBFC1B
PowerFlex® 525
PanelView Plus 7
• 1769-AENTR
Stratix 5700 • 1769 Compact I/O 1769-L33ERM Control System
Kinetix 5500
PanelView Plus 7
Kinetix 5500
1734-AENTR POINT I/O 1794-AENTR FLEX I/O
A linear network topology is a collection of devices that are daisy-chained together across an
EtherNet/IP network. Devices that can connect to a linear network topology use embedded
switch technology to remove any need for a separate switch, as required in Star network
topologies.
Example 1769-L18ERM-BB1B Control System Using a Linear Network Topology
1734-AENTR POINT I/O
1734-AENTR FLEX I/O
PanelView Plus
1769-L18ERM-BB1B
• Kinetix 350 • Kinetix 350
• 1783-ETAP • 1783-ETAP
PanelView Plus
LINK 1 LINK 2
AUX POWER
POINT I O
Module
Status
Network
Activity
Network
Status
Point Bus
Link 1 Status
Activity/
Status System
Power
Field
Power
IP ADDRESS
Link 2
Activity/
Status
PanelView Plus
00:00:BC:2E:69:F6
1 (Front)
2 (Rear)
1769-L33ERM
• PowerFlex 525
• 1783-ETAP
Kinetix 5500
A star network topology is a traditional EtherNet/IP network that includes multiple devices that
are connected to each other via an Ethernet switch.
Example1769-L18ERM-BB1B Control System Using a Star Network Topology
1769-L18ERM-BB1B
IP Address:
ENET Address: 00:00:BC:66:0F:C7
Stratix 6000
LINK 1 LINK 2
PanelView Plus
1732E-IB16M12R 8 7
6 5
4 3
2 1
1769-L27ERM-QBFC1B
1769-L33ERM
00:00:BC:2E:69:F6
1 (Front)
2 (Rear)
4 3
2 1
IMPORTANT Keep the following in mind when using sockets with CompactLogix 5370
controllers:
• A significant difference between CompactLogix 5370 controllers and
other Logix 5000™ controllers is the communication path.
CompactLogix 5370 controllers do not require a separate EtherNet/IP
network communication module, for example, a 1756-EN2T module. In
the case of the CompactLogix 5370 controllers, the MSG is sent to the
controller itself by using the path ‘1,0’.
• All CompactLogix 5370 controllers must use unconnected MSG
instructions for socket servers. When you configure a message for a
CompactLogix 5370 controller, make sure that the Connected checkbox
on the Message Configuration dialog box is cleared.
For more information on socket interface, see EtherNet/IP Socket Interface Application
Technique, publication ENET-AT002.
You indirectly determine the number of connections the controller uses by configuring the
controller to communicate with other devices in the system.
Connections are allocations of resources that provide more reliable communication between
devices than unconnected messages.
DeviceNet Network The CompactLogix 5370 L2 and L3 controllers communicate with other devices over the
DeviceNet network via a Compact I/O 1769-SDN DeviceNet scanner. The DeviceNet network
Communication uses the Common Industrial Protocol (CIP) to provide the control, configuration, and data
collection capabilities for industrial devices.
Available Software
The software applications that are listed in this table are required when using a CompactLogix
5370 L2 or L3 controller on a DeviceNet network.
Software Required Version Functions
RSLogix 5000® 20 - For CompactLogix 5370 controllers using firmware revision 20.
21 or later - For CompactLogix 5370 controllers using firmware revision 21 or later. Configure the CompactLogix project
Studio 5000® environment Studio 5000 environment, version 28 or later - For 1769-L19ER-BB1B controllers.
• Configure communication devices
RSLinx Classic 2.59.00 or later(1), (2), (3) • Provide diagnostics
• Establish communication between devices
One of the following:
• Configure DeviceNet devices
RSNetWorx™ for DeviceNet • 11.00.00 or later if used with RSLogix 5000 software, version 20.xx.xx
• Define the scanlist for the DeviceNet network
• 21.00.00 or later if used with the Studio 5000 environment, version 21.00.00 or later
(1) CompactLogix 5370 L2 controllers require RSLinx Classic software, version 2.59.01 or later.
(2) We recommend that you use RSLinx Classic software, version 3.51.00 or later, with the Studio 5000 environment, version 21.00.00 or later.
(3) RSLinx Classic software, version 3.74.00 is recommended for use with the 1769-L19ER-BB1B controller.
• 1769-L24ER-QB1B
DeviceNet Connection • 1769-SDN Scanner
• 1769-L24ER-QB1B
DeviceNet Connection • 1769-SDN Scanner
Power supply distance rating is the number of slots a 1769-SDN scanner can be installed away
from the power supply. The 1769-SDN scanner has a power supply distance rating of four.
Therefore, your CompactLogix 5370 L2 or L3 control system can include up to three modules
between the 1769-SDN scanner and the power supply.
The power supply distance rating of the 1769-SDN scanner as a design consideration differs by
CompactLogix L2 controller catalog number.
In a CompactLogix 5370 L2 control system, you can install a 1769-SDN scanner on the right side
of the control system. The controller has an embedded power supply, which disallows the
installation of 1769-SDN scanners between the controller and the power supply.
Additionally, the controller has embedded I/O modules that disallow installation of the 1769-
SDN scanner directly to the right of the embedded power supply. CompactLogix 5370 L2
control systems have one or two embedded I/O modules, described as follows:
• 1769-L24ER-QB1B controller - One embedded I/O module
• 1769-L24ER-QBFC1B, 1769-L24ER-QBFC1BK, and 1769-L27ERM-QBFC1B controllers - Two
embedded I/O modules
While the embedded I/O modules aren’t considered local expansion modules, you must still
include each embedded I/O module in the module slot count when determining where to install
the 1769-SDN scanner as a local expansion module.
The farthest local expansion module slot where you can install the 1769-SDN scanner in a
CompactLogix 5370 L2 control system is module slot number two or three as determined by
the controller catalog number that is used in the control system.
This table lists the farthest local expansion module slot where you can install a 1769-SDN
scanner and meet its power supply distance rating requirement.
1769-L24ER-QB1B 1
Three modules between the power supply and the 1769-SDN scanner. With this controller catalog number, you can only
install up to two local expansion modules between the controller and the 1769-SDN scanner.
The embedded I/O modules are the first two modules in the module count. At its maximum power supply
distance rating, the 1769-SDN scanner can be installed in slot 2 of the local expansion modules, as shown in
the following graphic.
Three modules between the power supply and the 1769-SDN scanner. With this controller catalog number, you can only
install one local expansion module between the controller and the 1769-SDN scanner.
CompactLogix 5370 L3 control systems do not have embedded I/O modules. You begin
counting local expansion slots with the first Compact I/O module installed next to the power
supply when determining where to install a 1769-SDN scanner and meet its power supply
distance rating.
In CompactLogix 5370 L3 control systems, you can install 1769-SDN scanners to the left or right
side of the power supply. You can also use local and extra banks in CompactLogix 5370 L3
control systems, with each allowing the inclusion of a 1769-SDN scanner.
In the local bank, the controller must be the leftmost device in the system and you can only
install up to three modules between the controller and the power supply. Therefore, any 1769-
SDN scanners that are installed to the left of the power supply in the local bank, are in a
module slot that meets the power supply distance rating requirements of the module.
CompactLogix 5370 L3 control systems also support the use of extra banks for the local
expansion modules of the system. Each additional bank requires a 1769 Compact I/O power
supply. The bank can be designed with local expansion modules on either side of the power
supply.
In this case, you must install the 1769-SDN scanner with no more three Compact I/O modules
between the scanner and the power, regardless of whether the modules are installed to the
left or right of the power supply.
This graphic shows 1769-SDN scanners that are installed in a 1769-L36ERM control system that
meet the power supply distance rating of the module.
Local Bank
Extra Bank
For example, if a bank uses a 1769-PA2 Compact I/O power supply, each side of the bank has a
current capacity of 1 A at 5V DC and 0.4 A at 24V DC. Because a
Select I/O Modules This chapter details the I/O module options that CompactLogix™ 5370 L1 control systems offer.
IMPORTANT You must connect a separate external power source to the FP+ and FP-
terminals on the removable connector on the controller to power the
field-side circuitry of the embedded I/O modules and the local
expansion modules for only series A L1 controllers. See Appendix C,
page 257 for further information.
Power connections to the FP+ and FP- terminals provides power to input and output devices
that are connected to the embedded I/O modules or local expansion modules of the controller.
For example, input or output devices, such as a barcode scanner.
The embedded I/O of the controller and the field-side power of the local expansion modules is
24V DC nominally with an input range of
10…28.8V DC.
IMPORTANT The controller is grounded once it’s installed on a DIN rail as described
in Chapter 2, page 28.
IMPORTANT Do not use the following steps to connect power to the CompactLogix
5370 series A L16ER, L18ER, and L18 ERM controllers. Appendix C,
page 257 provides steps to connect power to the CompactLogix 5370
series A L16ER, L18ER, and L18 ERM controllers. The steps are also an
optional way to connect power to a series B or C L1 controller.
Complete these steps to connect power to CompactLogix 5370 series B and C L16ER, L18ER, or
L18ERM controllers, and series A and C L19 controllers.
1. Verify that the separate external 24V DC power source that powers the CompactLogix
5370 L1 controller isn’t powered.
2. Connect the wires to the + and - connections on the external 24V DC power source.
WARNING: If you connect or disconnect wiring while the field-side power is on,
an electric arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before
proceeding.
3. Loosen the screws that secure the removable connector to the CompactLogix 5370 L1
controller and pull the connector off the controller.
Wires that are connected between external
24V DC power source and VDC+ and VDC-
terminals on the removable connector.
4. Connect the wire that is connected to the + terminal on the external 24V DC power
source to the FP+ terminal. The FP+ terminal is the fourth terminal from the top on the
removable connector.
5. Connect the wire that is connected to the - terminal on the external 24V DC power
source to the FP- terminal. The FP- terminal is the fifth terminal from the top on the
removable connector.
8. Turn on power to the separate external 24V DC power source connected to the
removable connector.
The following graphic shows separate external 24V DC power supply that is connected to the
VDC+/VDC- and FP+/FP- terminals on the removable connector, respectively.
The following diagram shows the wiring terminals on the embedded I/O module.
Consider the following when you connect input or output devices to the embedded I/O modules
of your CompactLogix 5370 L1 controller:
• You must connect an external 24V DC power source to the FP+ and FP- terminals on the
removable connector on the controller to the power input and output devices that are
connected to the embedded I/O modules on the controller:
- Series A for L16ER, L18ER, and L18ERM controllers require an extra external 24V DC
power source for the FP+ and FP- terminal connections. For more information on
how to connect an extra external power source for a series A L1 controller to the FP+
and FP- terminals, see Appendix C, page 257.
- Series B and C controllers use the external 24V DC power source that is connected to
the VDC+ and VDC- terminals on the controller for the FP+ and FP- terminal
connections. Series B and C controllers can also use an extra external 24V DC power
source for the FP+ and FP- terminal connections. See Appendix C, page 257 for more
information on how to connect the extra external power source to the FP+ and FP-
terminals. For more information on how to connect the external power source to the
FP+ and FP- terminals on the series B and C controllers, see page 118.
The field-side power requirement of the embedded I/O modules of the controller is 24V
DC nominally with an input range of 10…28.8V DC.
• The available RPI range of the I/O points is 1.0 ms… 750.0 ms and can be changed by 0.5
ms increments. The default setting is 20 ms.
IMPORTANT • If you attempt to use an RPI value that is not valid, the application
automatically rounds the value down to the closest 0.5 ms
increment when you apply the change.
For example, if you set the RPI = 1.75 ms, when you select Apply
or OK, the value is rounded down to 1.5 ms and applied.
• The RPI value for embedded I/O module is intended to establish a
time interval at which data is transmitted. However, the
configuration of your CompactLogix 5370 L1 control system can
affect the actual time interval of data transmission.
For more information, see Estimate Requested Packet Interval
on page 132.
Complete these steps to wire the input and output points on the CompactLogix 5370 L1
controller.
1. Verify that the control system isn’t powered.
2. Use a small screwdriver to push the spring release clip and insert the wire.
3. With the wire in place, pull the screwdriver off the spring release clip.
4. Repeat step 2 for all embedded I/O wires that are needed in your application.
Complete these steps to remove and replace and I/O module connector.
1. Verify that the control system isn’t powered.
2. Use a small screwdriver to loosen the screws that secure the connector to the module.
3. Pull the connector out from the I/O module to remove it.
4. Disconnect any wires from the connector.
5. Connect any wires to the replacement connector.
6. Push the replacement connector back into the I/O module.
7. Secure the connector to the I/O module with the small screwdriver.
The embedded input points on the CompactLogix 5370 L1 controllers support 2-wire and 3-
wire input devices. You can wire the input devices to be powered in one of the following
methods:
• By using an external power supply, as shown in Figure 2 on page 124 - In this case, you
can monitor the input devices even if field power is interrupted, for example, by the
Master Control Relay (MCR).
This method is required if you must continue reading data from the input devices when
the embedded output terminals are disabled, for example, when the use of an MCR
disrupts output power.
• By using the V terminal on the embedded I/O module, as shown in Figure 4 on page 125
- In this case, you can’t monitor the input devices even if field power is interrupted, for
example, by the MCR.
Figure 2 on page 124 and Figure 3 on page 124 show examples of how to power 2-wire and 3-
wire input devices in your application.
IMPORTANT When using Figure 2 on page 124 and Figure 3 on page 124, use the
following guidelines:
• With this wiring configuration, you can monitor the input devices even if
field power is interrupted, for example, by the MCR. The FP- connection
must be maintained as a reference for inputs to function.
• With this wiring configuration, the controller does not help protect field-
side devices from overcurrent draw conditions.
• Design your application so that power consumption does not exceed the
power supply ratings.
• The following figure is a wiring example that complies with the National
Electrical Code (NEC) standard for isolation between system and field
power.
• The FP+ terminal on the removable connector is the voltage connection.
• The FP- terminal on the removable connector is the common
connection.
• The MCR must be closed for the removable connector to provide power
to the embedded I/O module.
• Install a user-replaceable fuse with overcurrent protection of
4…6 A @ 52.5…68.25 I²t in line between the incoming power and the FP+
terminal.
For series A L1 controllers only, you must use a separate, dedicated
Class 2 power supply for the CompactLogix 5370 L1 controller and a
separate power supply for the embedded I/O module (see Appendix C,
Connect Field Power to Series A L1 Controllers for I/O Devices ).
Figure 2 - CompactLogix 5370 L16ER, L18ER, and L18ERM Controllers with Input Devices Powered by
External Power Supplies (Series A [Alternate Series B and C])
Power
Supply 1
MCR
Figure 3 - CompactLogix 5370 L1 Controllers with Input Devices Powered by External Power Supplies
(Series B and C)
MCR
Figure 4 on page 125 and Figure 5 on page 126 shows examples of how to power 2-wire and 3-
wire input devices in your application with connections to a V terminal.
IMPORTANT When using Figure 4 on page 125 and Figure 5 on page 126, use the
following guidelines:
• With this wiring configuration, the input devices lose power if the
removable connector does not power the embedded I/O modules.
• With this wiring configuration, the controller does not help protect field-
side devices from overcurrent draw conditions.
• Design your application so that power consumption does not exceed the
power supply ratings.
• The following figure is a wiring example that complies with the National
Electrical Code (NEC) standard for isolation between system and field
power.
• The FP+ terminal on the removable connector is the Voltage connection.
• The FP- terminal on the removable connector is the Common
connection.
• The MCR must be closed for the removable connector to provide power
to the embedded I/O module.
• Install a user-replaceable fuse with overcurrent protection of 4…6 A in
line between the incoming power and the FP+ terminal.
For series A L1 controllers only, you must use a separate, dedicated
Class 2 power supply for the CompactLogix 5370 L1 controller and a
separate power supply for the embedded I/O module (see Appendix C,
Connect Field Power to Series A L1 Controllers for I/O Devices ).
Figure 4 - CompactLogix 5370 Series B and C L16ER, L18ER, and L18ERM Controllers, and series A and
C L19 Controllers with Input Devices Powered by a V Terminal on Embedded I/O Module
(Series A [Alternate Series B and C])
Power
Supply 1
MCR
MCR
Power
Supply
The embedded output points on the CompactLogix 5370 L1 controllers support 2-wire systems.
The embedded power supply in the controller powers the embedded output points over the
POINTBus backplane.
This figure shows examples of how to connect 2-wire systems to embedded output points
0…7. The same wiring connections can be used with output points 8…15.
IMPORTANT Do not exceed the per point output current rating or the total output
module current rating.
CompactLogix 5370 L1 Controllers Embedded Digital Output Point Wiring Diagram
Load
Load
Load
Load
Load
Load
Load
Load
This figure shows an example of how to connect 2-wire systems to embedded output points
0…4 and use an external terminal block with a bus connector strip.
IMPORTANT Do not exceed the per point output current rating or the total output
module current rating.
CompactLogix 5370 L1 Controllers Embedded Digital Output Point Wiring Diagram
Load
Load
Load
Load
Load
IMPORTANT For a full description of how to use 1734 POINT I/O modules, see the
POINT I/O Digital and Analog Modules and POINTBlock I/O Modules,
publication 1734-UM001.
IMPORTANT Do not put more than three of the 1734-IT2I or 1734-IR2 modules
on the POINT I/O bus that draws power from the same power
source. This restriction includes power sources such as from
communication adapters or the 1734-EPAC or 1734-EP24DC
expansion power supply modules. The inrush current exceeds
the current limit of the DC to DC converter in the power source.
Based on the configuration of your application, you can use one of the following devices
to make more POINTBus backplane current or field power current available:
- 1734-EP24DC POINT I/O Expansion Power Supply - An expansion power supply is
installed between embedded I/O modules and local expansion modules or between
local expansion modules.
The expansion power supply breaks the available POINTBus backplane current
between the modules to its left and right. With the expansion power supply installed,
the modules to its left can draw up to 1 A of POINTBus backplane current. The
modules to the right of the expansion power supply can draw as much current as is
provided by the expansion power supply.
Additionally, the expansion power supply breaks the available field power current
between the modules to its left and right. With the expansion power supply installed,
the modules to its left can draw up to 3 A of field power current. The modules to the
right of the expansion power supply can draw as much field power current as
allowed by the expansion power supply.
For example, if you need six 1734-IR2 modules as local expansion modules for a 1769-
L18ER-BB1B controller application, you must include the 1734-EP24DC expansion
power supply in the local expansion-module installation.
For more information on the 1734-EP24DC expansion power supply, see the POINT I/O
24V DC Expansion Power Supply Installation Instructions, publication 1734-IN058.
- 1734-FPD POINT I/O Field Power Distributor Module - A field power distributor
module can also be installed between embedded
I/O modules and local expansion modules or between local expansion modules.
The field power distributor module breaks the available field power current between
the modules to its left and right. With the field power distributor module installed, the
modules to its left can draw up to 3 A of field power current. The modules to the right
of the field power distributor module can draw as much field power current as
allowed by the field power distributor.
For more information on the 1734-FPD POINT I/O Field Power Distributor module, see
the POINT I/O Field Power Distributor Module Installation Instructions, publication
1734-IN059.
IMPORTANT Remember, the field power distributor module changes only the
level of field power current available in the system. It does not
affect the level of POINTBus backplane current available.
• You must connect an external 24V DC power source to the FP+ and FP- terminals on the
removable connector on the controller. This connection provides power to input and
output devices that are connected to the local expansion modules.
- Series A controllers require an extra external 24V DC power source for the FP+ and
FP- terminal connections. For more information on how to connect an extra external
power source for series A L1 controller to the FP+ and FP- terminals, see Appendix C,
Connect Field Power to Series A L1 Controllers for I/O Devices
- Series B and C controllers use the external 24V DC power source that is connected to
the VDC+ and VDC- terminals on the controller for the FP+ and FP- terminal
connections. Series B and C controllers can also use an extra external 24V DC power
source for the FP+ and FP- terminal connections.
The field-side power requirement of the local expansion modules of the controller is
24V DC nominally with an input range of 10…28.8V DC.
For more information on how to connect a power source to the FP+ and FP- terminals,
see page 117.
• We recommend that you update all 1734 POINT I/O modules that are designated as local
expansion modules to the most current firmware revision before installing them in a
CompactLogix 5370 L1 system.
• The available RPI range of each local expansion module is 1.0… 750.0 ms and can be
changed by 0.5 ms increments. The default setting is module-dependent.
You can configure RPI values for each local expansion module in your control system.
However, the complete I/O configuration has an impact on the rate at which data is
transmitted in a CompactLogix 5370 L1 control system. For more information, see
page 132.
• Before installing a 1734 POINT I/O module into a CompactLogix 5370 L1 control system,
make sure the I/O module is set to Autobaud. 1734 POINT I/O modules are set to
Autobaud by default.
If you must return a 1734 POINT I/O module to Autobaud, see the POINT I/O Digital and
Analog Modules and POINTBlock I/O Modules, publication 1734-UM001.
• When possible, use specialty 1734 POINT I/O modules to meet unique application
requirements.
• Make sure that there are no empty slots between the controller and local expansion
modules or between local expansion modules.
• The Expansion I/O parameter in the project of the controller must match the number of
local expansion modules that are installed in the system. This requirement is so the
controller can establish connections to the local expansion modules.
• You must use a 1734-232ASC, firmware revision 4.002 or later, to access an RS-232
network in your CompactLogix 5370 L1 controller application.
IMPORTANT Field power is required for the 1734-232ASC module. The module
can’t receive adequate power without the application of
field power.
Validate I/O Layout You must validate the layout of 1734 POINT I/O modules in your CompactLogix 5370 L1 control
system. Consider the points detailed in this section when validating I/O layout placement.
Each time the controller is powered up, it compares the number of local expansion modules
present on the POINTBus backplane to the Expansion
I/O value. The controller does not allow any I/O connections until the number of local
expansion modules present equals the Expansion I/O value.
Follow these rules for I/O system configuration and RIUP of I/O modules.
• When you remove an I/O module that has an active connection from the controller, the
controller I/O status indicator flashes green to indicate the condition.
The CompactLogix 5370 L1 controllers attempt to scan an I/O module at the configured RPI
rate. For individual I/O modules, a module RPI overlap minor fault (further described on
page 133) occurs if there are enough I/O modules with RPI rates set too fast that they can’t all
be serviced in the allotted interval.
The configuration parameters for a system determine the impact on actual RPI rates. These
configuration factors can affect the effective scan frequency for any individual module:
• Other 1734 POINT I/O module RPI rate settings
• Number of other 1734 POINT I/O modules in the system
• Types of other 1734 POINT I/O modules in the system
• Application user task priorities
IMPORTANT When considering digital I/O modules, remember that they can
be the embedded I/O module on the controller or 1734 POINT I/O
modules that are used as Local Expansion Modules. Therefore,
the consideration for using two modules can be the embedded
I/O module and a 1734 POINT I/O module or two 1734 POINT I/O
modules.
• For specialty and analog I/O modules (except 1734-485ASC modules):
- One module can be scanned at 20 ms.
- For each additional module, add 20 ms.
For example, if a CompactLogix 5370 L1 control system uses two analog modules, the
module can be scanned in 40 ms.
• For 1734-485ASC modules, the total data size for all ASC modules determines the RPI
rates:
- For total data size less than 20 bytes, each module can be scanned in 20 ms.
- For data size greater than 20 bytes, use the size value as the RPI.
For example, if the total data size is 40 bytes, each ASC module can be scanned in 40
ms.
You aren’t required to set individual RPI values of 1734 POINT I/O modules to the values listed
previously. For example, if your application scans one or two modules, you do not have to use
RPI rates of 2 ms. Remember, though, that higher RPI rates result in less frequent data scans.
The RPI shows how quickly modules can be scanned, not how quickly an application can use
the data. The RPI is asynchronous to the program scan. Other factors, such as program
execution duration, affect I/O throughput.
Some systems that follow the guidelines can experience minor faults that are described in this
table.
The embedded power supply provides 1 A @ 5V DC to the POINTBus backplane to power all
system components, including local expansion modules, in most system configurations. Local
expansion modules include 1734 POINT I/O modules.
In some circumstances, you can configure a system that requires more current than the
embedded power supply of the system provides. This type of configuration results from using
a combination of local expansion modules that, when combined with current consumption of
the rest of the system, exceeds 1 A @ 5V DC.
In this case, you can take any of the following actions to make sure that your system
configuration has enough power:
• Insert a 1734-EP24DC POINT I/O expansion power supply between local expansion
modules to increase the POINTBus backplane power.
• Insert a 1734-FPD POINT I/O Field Potential Distribution module between local expansion
modules to renew field power or change the field power from DC to AC. The Field
Potential Distribution module separates DC I/O modules from AC I/O modules on the
same POINTBus.
IMPORTANT The 1734-FPD POINT I/O Field Power Distributor is required if the
devices connected to the local expansion modules consume
more than 3 A.
Use the Event Task The CompactLogix 5370 L1 controllers support the use of an Event task with their embedded
input points. You can configure embedded input point terminals to trigger an Event task if a
change of state (COS) occurs.
IMPORTANT When using the Event task with the CompactLogix 5370 L1 controllers,
consider these points:
• You can use the Event task only with Logix Designer application, version
21.00.00 and later.
• You can use the Event task only with the embedded input points of the
controller. You can’t use the Event task with input points in the local
expansion modules, for example, a 1734-IB4 module.
• You can use the Event task only if the input point has an input data
state change.
• An event is recognized only when it maintains the same state for at least
the duration of the input filter time specified.
• Configure the Event task at a rate that stops task overlap conditions.
• Configure the Event task at a rate that is likely to succeed.
A 2 ms signal width is the minimum pulse width that can be used at
which the Event task succeeds.
You can configure multiple embedded input points to trigger an Event task. However, we
recommend that you enable COS for only one point. If you enable COS for multiple points, a
task overlap of the Event task can occur.
You can configure an Event task to trigger if one of these events occurs:
• An event occurs on one point on an input module.
• A trigger event does not occur in a time interval.
You configure whether the task updates output modules at the end of the task. After the task
executes, it does not execute again until the event occurs again. Each Event task requires a
trigger.
This table describes the triggers for an Event task available in a CompactLogix 5370 L1 control
system.
Trigger Description
The input point triggers the Event task that is based on the change of state (COS)
Input Data State Change configuration for the point. The COS configuration is set on the Module Definition
dialog box.
Only one consumed tag can trigger an Event task. Use an Immediate Output (IOT)
Consumed Tag instruction in the producing controller to signal the production of new data.
Axis Registration 1 or 2 A registration input triggers the Event task.
Axis Watch A watch position triggers the Event task.
The coarse update period for the motion group triggers the execution of the motion
Motion Group Execution planner and the Event task. Because the motion planner interrupts all other tasks, it
executes first.
EVENT Instruction Multiple EVENT instructions can trigger the same task.
IMPORTANT An event is recognized only when it maintains the same state for
at least the duration of the input filter time specified.
d. Select OK.
Configure I/O Complete these steps to add a 1734 POINT I/O module to your CompactLogix 5370 L1 control
system.
1. Right-click PointIO and select New Module.
I/O Connections
A CompactLogix 5370 L1 control system uses connections to transmit I/O data. This table
describes the connection types.
IMPORTANT You can only use direct connections with the local expansion modules
in a CompactLogix 5370 L1 control system.
Configure Distributed I/O Your CompactLogix 5370 L1 control system can use distributed I/O modules on an EtherNet/IP
network.
Modules on an EtherNet/IP
Network IMPORTANT When adding distributed I/O modules, remember to count the remote
Ethernet adapter to remain within the maximum number of EtherNet/IP
network nodes limitation for your controller.
The distributed I/O modules that are connected to the controller via the
remote Ethernet adapter aren’t counted toward the maximum Ethernet
node limit for the controller.
For example, a 1769-L16ER-BB1B controller supports up to four Ethernet
nodes. You can add up to four remote Ethernet adapters to the I/O
Configuration section because each remote adapter counts against the
node count. However, you can add as many remote I/O modules to the
chassis of the adapter as necessary. Remote I/O modules do not count
against the node count.
For more information on node limitations, see page 102.
Complete these steps to configure distributed I/O modules on an EtherNet/IP network.
1. Right-click Ethernet and select New Module.
7. To add all desired distributed I/O modules to the project, repeat these steps.
1794-AENT FLEX™ I/O Adapter Connected via 1734-AENTR POINT I/O Adapter with
a 1783-ETAP EtherNet/IP Tap POINT I/O Modules
Monitor I/O Modules With CompactLogix 5370 L1 controllers, you can use the following options to monitor I/O
modules:
• QuickView™ Pane below the Controller Organizer
• Connection tab in the Module Properties dialog box
• Programming logic to monitor fault data so you can act
When a fault occurs on an I/O module, a yellow triangle on the module listing in the Controller
Organizer alerts you to the fault.
The following graphic shows the Quick View Pane, which indicates the type of fault.
To see the fault description on the Connection tab in Module Properties dialog box, complete
these steps.
1. In the I/O Configuration, right-click the faulted I/O module and select Properties.
2. To diagnose the issue, select the Connection tab and use the fault description, in the
Module Fault section.
3. To close the dialog box and remedy the issue, select OK.
Complete these steps to identify the source of the BUS OFF minor fault.
1. Make sure the number of local expansion modules in the project matches the number of
modules that are physically installed in the system.
2. Make sure that all mounting bases are locked and I/O modules are securely installed on
mounting bases.
3. Make sure all 1734 POINT I/O modules are configured to use the Autobaud rate.
IMPORTANT You can’t change the Autobaud setting for a 1734 POINT I/O when
the module is installed in a CompactLogix 5370 L1 control
system.
If you must return a 1734 POINT I/O module to Autobaud, see the
POINT I/O Digital and Analog Modules and POINTBlock I/O
Modules, publication 1734-UM001.
If these steps do not remedy the fault condition, contact Rockwell Automation® technical
support.
Select I/O Modules This chapter details the I/O module options CompactLogix™ 5370 L2 control systems offer.
IMPORTANT Remember the following when using the embedded I/O modules on
CompactLogix 5370 L2 controllers:
• 1769-L24ER-QB1B controller - The digital input points and digital output
points are on one embedded I/O module. Therefore, the
1769-L24ER-QB1B controller is considered to have one embedded I/O
module.
• 1769-L24ER-QBFC1B, 1769-L24ER-QBFC1BK, and 1769-L27ERM-QBFC1B
controllers - The digital input points and digital output points are on one
embedded I/O module. The high-speed counter input/output points,
universal analog input points, and analog output points are on another
single embedded I/O module. Therefore, the 1769-L24ER-QBFC1B, 1769-
L24ER-QBFC1BK, and 1769-L27ERM-QBFC1B controllers are considered to
have two embedded I/O modules.
You configure an RPI rate for the embedded I/O modules to establish the time intervals at
which data is transmitted between the controller and each embedded I/O point. The available
RPI range of the embedded I/O points is 0.5… 750.0 ms and can be changed by 0.5 ms
increments. The default setting is 20 ms.
IMPORTANT • If you attempt to use an RPI value that is not valid, the application
automatically rounds the value down to the closest 0.5 ms increment
when you apply the change.
For example, if you set the RPI = 1.75 ms, when you select Apply or OK,
the value is rounded down to 1.5 ms and applied.
• The RPI value for an embedded I/O module is intended to establish a
time interval at which data is transmitted. However, the configuration of
your CompactLogix 5370 L2 control system can affect the actual time
interval of data transmission.
For more information regarding estimating the RPI value, see page 175.
The embedded digital I/O module on CompactLogix 5370 L2 contains 16 24V DC sinking inputs
and 16 24V DC sourcing outputs. The inputs can be configured to use digital filtering by input
group. Filter times can be specified for OFF to ON and ON to OFF.
Group 0 is used to configure inputs 0…7. Group 1 is used to configure inputs
8…15. The default filter time for each group is 8 ms. You can adjust the filter times to 0.0 ms,
0.1 ms, 0.5 ms, 1.0 ms, 2.0 ms, and 4.0 ms, as shown in this graphic.
IMPORTANT The embedded digital I/O points on the 1769-L24ER-QBFC1B and 1769-
L27ERM-QBFC1B controllers are organized and wired the same.
CompactLogix 5370 L2 Controllers Embedded Digital I/O Module Wiring Termination Points
Digital Input
Points
Digital Output
Points
+ DC (Sinking)
- DC (Sourcing)
24V DC
- DC (Sinking)
+ DC (Sourcing)
+ DC
24V DC
- DC
IMPORTANT The embedded analog I/O points are available on only the
1769-L24ER-QBFC1B and 1769-L27ERM-QBFC1B controllers.
This table lists the available embedded analog input channel types and ranges for the channel
type. The configuration choices are made on the Input Configuration tab of the Module
Properties dialog box, as shown.
Input Types and Ranges
Input Type Input Ranges Project Configuration
• Type -50…+50 mV
• Type -100…+100 mV
• 0…5V
Voltage
• 1…5V
• 0…10V
• -10V…10V
• 0…20 mA
Current
• 4…20 mA
• J
• K at 1370…1372 °C (2498…2501.6 °F)
• K at -200…+1370 °C (-328…+2498 °F)
• T
• E
Thermocouple • S and R at 0…1768 °C (32…3214.4 °F)
• S and R at -50…0 °C (-58…+32 °F)
• B at 300…1820 °C (572…3308 °F)
• B at 250…300 °C (482…572 °F)
• N
• C
• 100 Platinum 385
• 200 Platinum 385
• 500 Platinum 385
• 1000 Platinum 385
• 100 Platinum 3916
• 200 Platinum 3916
RTD
• 500 Platinum 3916
• 1000 Platinum 3916
• 10 Copper 426
• 120 Nickel 618
• 120 Nickel 672
• 604 Nickel-Iron 518
• 0…150
• 0…500
Resistance
• 0…1000
• 0…3000
This figure shows the embedded analog I/O points and how each termination point is used
with different analog input types.
IMPORTANT The embedded analog I/O points on the 1769-L24ER-QBFC1B and 1769-
L27ERM-QBFC1B controllers are organized and wired the same.
1769-L27ERM-QBFC1B Controller Embedded Analog I/O Wiring Termination Points
Thermocouple Input Type Connections RTD and Resistance Input Type Connections
This figure shows an example of ungrounded and grounded thermocouple wiring diagrams on
a 1769-L27ERM-QBFC1B controller.
1769-L27ERM-QBFC1B Controller Thermocouple Wiring Diagrams
IMPORTANT For both input types, we recommend that you use Belden #8761
or equivalent cable.
This figure shows an example of devices with single-ended connections that are wired to the
embedded analog inputs on a 1769-L27ERM-QBFC1B controller when it’s operating with voltage
or current input types.
1769-L27ERM-QBFC1B Controller Single-ended Connections Wiring Diagrams
Earth Earth
This figure shows an example of 2-wire, 3-wire, and 4-wire RTD/Resistance wiring diagrams
on a 1769-L27ERM-QBFC1B controller.
1769-L27ERM-QBFC1B RTD/Resistance Wiring Diagrams
2-wire Device
Wiring Diagram
Earth
3-wire Device
Wiring Diagram
Earth
4-wire Device
Wiring Diagram
IMPORTANT For all wiring diagrams, we recommend that you use Belden
#83503 or 9533 cable.
This table lists the available embedded analog output channel types and ranges for the
channel type. The configuration choices are made on the Output Configuration tab of the
Module Properties dialog box, as shown in the table.
Output Types and Ranges
Output Type Output Ranges Project Configuration
• -10…10V
• 0…5V
Voltage
• 0…10V
• 1…5V
• 4…20 mA
Current
• 0…20 mA
This figure shows an example of wiring input devices to the analog output points on the 1769-
L27ERM-QBFC1B controller when it’s operating in voltage or current mode.
1769-L27ERM-QBFC1B Controller Analog Output Wiring Diagrams
Voltage
Load Current
Load
The L2 embedded high-speed counters operate like the 1769-HSC module. See 1769-UM006 for
further information.
Each counter uses differential inputs that are compatible with standard differential-line driver
output devices and single-ended devices. This shows the embedded high-speed counter input
points.
This figure shows an example of a differential encoder that is wired to the embedded high-
speed counter inputs on a 1769-L27ERM-QBFC1B controller.
1769-L27ERM-QBFC1B Controller Differential Encoder with High-speed Counter Input Wiring Diagram
Cable
External
Power Shield
Supply
Earth
Shield/Housing
Only connect if housing is
electronically isolated from the motor
This figure shows an example of a single-ended encoder that is wired to the embedded high-
speed counter inputs on a 1769-L27ERM-QBFC1B controller.
1769-L27ERM-QBFC1B Controller Single-ended Encoder with High-speed Counter Input Wiring
Diagram
Cable
Shield
External
Power
Supply
Earth
Shield/Housing
Only connect if housing is electronically
isolated from the motor and ground.
The embedded high-speed counter also supports four output points. This figure shows a
wiring diagram for the embedded high-speed counter output points.
+DC
5/24V DC
-DC
Complete these steps to wire the input and output points on the CompactLogix 5370 L2
controller.
1. Verify that the control system isn’t powered.
2. Strip 10 mm (0.39 in.) insulation from the end of the wire.
3. Push the wire into the open terminal until it’s secure.
If your wire is too thin to push into the open terminal for secure placement, we
recommend that you connect the wire to a ferrule and insert it into the open terminal.
4. Repeat step 3 for all embedded I/O wires that are needed in your application.
You can use a continuity tester to determine if the connection point is operating correctly, that
is, the connection point is a complete circuit. You use a continuity tester if any issues arise
with a removable connector and you suspect that a connection point can no longer be
functioning as a complete circuit.
The indication mechanism, for example, a light that illuminates on the tester, varies by
continuity tester. The following example graphic shows a continuity tester with one
connection point. In this case, if the circuit is operating correctly, the indicator light turns on.
Insert a continuity tester into the suspected I/O connection point as shown in the following
graphic.
Continuity Tester
Small hole on
opposite from
termination point
in removable
connector.
Complete these steps to remove and replace an embedded I/O module connector.
1. Verify that the control system isn’t powered.
2. Compress the small release clips at the top and bottom of the connector and tilt the top
of the connector away from the module.
3. Pull the connector away from the module and disconnect any wires.
4. Connect the wires to the replacement connector.
5. Push the connector back into the module and engage the clips to secure the connector.
Determine Embedded
Module Update Time IMPORTANT This section applies to the 1769-L24ER-QBFC1B and 1769-L27ERM-
QBFC1B controllers because only those controllers have
embedded universal analog input points.
The module update time is the time that the module requires to sample and convert the input
signals of all enabled analog input channels and provide the resulting data values to the
controller.
You calculate the module update time by adding the update times for each enabled analog
input channel on the module. Each channel update time calculation is the result of several
configuration choices that are described in the following section.
When you enable an embedded analog input channel, you must select an input type and a filter
frequency for that input. The selections that you make determine the value that is required
when calculating channel update time.
IMPORTANT Each channel input type has multiple ranges or types. For example, a
voltage input type can use one of six voltage ranges. Regardless of which
voltage range the channel uses, the channel update time remains the
same.
This table shows the channel update times for each channel input type and filter frequency
selection.
Channel Update Times
Channel Update Times Based on Input Type Selection
Filter Frequency
Selection(1) Voltage, Current, or Thermocouple Resistance or RTD Input Type
Input Type
10 Hz 307 ms 614 ms
50 Hz 67 ms 134 ms
60 Hz 57 ms 114 ms
250 Hz 19 ms 38 ms
500 Hz 13 ms 26 ms
1 kHz 11 ms 22 ms
(1) Filter frequency selections are made on the Input Configuration tab of the Module Properties dialog box.
You must account for more voltage at the junction of the thermocouple field wires and the
input point. This condition applies when you use any of the thermocouple input types on your
embedded analog input. More voltage can alter the input signal on that point and, therefore,
affect the update time of that channel.
The process to account for increased voltage at an input point by using a thermocouple type
input is cold junction compensation (CJC). You enable CJC for a given channel on the Input
Configuration tab of the Module Configuration dialog box, as shown in the following graphic.
By default, CJC is disabled. You must clear the Disable Cold Junction Compensation checkbox
to use CJC for a given channel.
You aren’t required to enable CJC for a channel by using the thermocouple input type. If you
enable CJC and select Update Cold Junction Compensation every other scan, an extra update
time exists on the channel. This extra update time increases the overall channel update time.
The filter frequency selection for the channel determines the CJC update time. This table
shows the CJC update times that are based on filter frequency selections.
Channel Update Times
Filter Frequency Selection(1) CJC Update Time
10 Hz 614 ms
50 Hz 134 ms
60 Hz 114 ms
250 Hz 38 ms
500 Hz 26 ms
1 kHz 22 ms
(1) Filter frequency selections are made on the Input Configuration tab of the Module Properties dialog box.
IMPORTANT Keep the following in mind when calculating the CJC update time:
• If multiple input channels are configured to use a thermocouple input
type and another filter value is selected for each, the filter frequency
selection with the slowest update time determines the CJC update time.
For example, if one input channel uses a thermocouple input with a 50
Hz filter frequency and another input channel uses a thermocouple
input with a 60 Hz filter frequency, the CJC channel update time is 134
ms.
• The CJC update time that increases overall module update time is only
used once regardless of the number of input channels on a module that
have CJC enabled to scan every other scan.
In other words, if your module uses a filter frequency selection of 250
Hz and includes three channels with CJC enabled to scan every other
scan, you add only one instance of CJC update time to the overall
equation. Instead of including 38 ms for each channel, you include 38
ms once.
Open circuit detection is used to verify that the field wiring is physically connected to the
embedded analog input point. If this feature is enabled and the field wiring is disconnected
from the input, the application alerts you to the condition and an open wire bit is set for the
respective input channel in the tags for the project.
Open circuit detection can be enabled or disabled on any channel input type except for an
input channel that is configured to use the 0…20 mA input range. The configuration selection
is made on the Input Configuration tab on the Module Properties dialog box, as shown in the
following graphic. The configuration choice, that is, enabled or disabled, is the result of an
Open Circuit Response selection for the channel.
To disable open circuit detection, select Disable. To enable open circuit detection, select any
of the other four options.
This table describes the module response that is associated with each enable selection.
Open Circuit Detection Response Definitions
Response Option Definition
Sets the input data value to the full upper-scale value of the channel data word. The
Upscale selected input type and data format determines the full-scale value.
Sets the input data value to full lower-scale value of channel data word. The selected input
Downscale type and data format determines the low scale value.
Last State Sets the input data value to the last input value before the detection of the open-circuit.
Zero Sets the input data value to 0 to force the channel data word to 0.
When you enable open circuit detection for an input channel, an extra update time is used to
calculate the overall channel type. The increase in channel update time is 11 ms for each
channel that enables open circuit detection response.
This table lists example module update times that are based on channel configurations.
Example Module Update Times
Example Enabled Analog Input Module Update
Channel Update Time Calculations
Channel Configuration Time
• Channel 0:
– Input type = Current 57 ms 57 ms
– Filter Frequency Selection = 60 Hz
• Channel 0:
– Input type = Current
– Filter Frequency Selection = 60 Hz Channel 0 update time + Channel 2 update time 171 ms
• Channel 2: 57 ms + 114 ms
– Input type = RTD
– Filter Frequency Selection = 60 Hz
• Channel 0:
– Input type = Voltage
– Filter Frequency Selection = 60 Hz (Channel 0 update time + Open Circuit Detection
– Open Circuit Detection = Enabled time) + Channel 2 update time 682 ms
• Channel 2: (57 ms + 11 ms) + 614 ms
– Input type = RTD
– Filter Frequency Selection = 10 Hz
• Channel 0:
– Input type = RTD
– Filter Frequency Selection = 10 Hz
– Open Circuit Detection = Enabled
• Channel 2: (Channel 0 update time + Open Circuit Detection
– Input type = Thermocouple time) + (Channel 2 update time + Open Circuit
– Filter Frequency Selection = 60 Hz Detection time) + (Channel 3 update time + Open
Circuit Detection time) + CJC Update time 831 ms
– CJC = Enabled
– Open Circuit Detection = Enabled (614 ms + 11 ms) + (57 ms + 11 ms)
• Channel 3: + (13 ms + 11 ms) + 114 ms(1)
– Input type = Thermocouple
– Filter Frequency Selection = 500 Hz
– CJC = Enabled
– Open Circuit Detection = Enabled
(1) If you select multiple thermocouples for your system, use the largest CJC Update time for your calculations.
Embedded Analog I/O The section describes the data table structures for the embedded analog I/O modules on the
CompactLogix 5370 L2 controllers. The embedded analog
Modules Data Arrays I/O modules have arrays for the following data:
• Input data
• Output data
• Configuration data
You can access the data via the tags in the application.
IMPORTANT The analog I/O modules data structures apply to only the
1769-L24ER-QBFC1B, 1769-L24ER-QBFC1BK, and 1769-L27ERM-QBFC1B
controllers.
The 1769-L24ER-QB1B controller does not have an embedded analog
I/O module.
Input Array
The input data array for the embedded analog I/O module contains 11 words as described in
this table. This array is read-only and the default value for all bits is 0.
CompactLogix 5370 L2 Controller Embedded Analog I/O Module Input Data Array
Bit
Word
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 S Analog Read (Input) Data Value Channel 0
1 S Analog Read (Input) Data Value Channel 1
2 S Analog Read (Input) Data Value Channel 2
3 S Analog Read (Input) Data Value Channel 3
4 Nu Timestamp Value
5 Nu UI4 OI4 OC4 OC3 OC2 OC1 OC0 Nu SI4 SI3 SI2 SI1 SI0
6 LI3 HI3 UI3 OI3 LI2 HI2 UI2 OI2 LI1 HI1 UI1 OI1 LI0 HI0 UI0 OI0
7 S Cold Junction Compensation Value
8 S Output Data Loopback/Echo Channel 0
9 S Output Data Loopback/Echo Channel 1
10 Nu UO1 OO1 Nu UO0 OO0 Nu SO1 SO0
Analog Read (Input) Data Value Channel x is the data that is read from the field device that is connected to the channel.
Timestamp Value is the timestamp of when data was received at the corresponding channel.
Cold Junction Compensation value is the converted CJC data. The data is calculated in the following manner:
• If the CJC is open, the converted value is 25 °C (77 °F).
• If the CJC isn’t opened and the Update CJC sensor every other scan option is disabled, the converted value is 25 °C (77 °F).
• If the CJC isn’t opened and the Update CJC sensor every other scan option is enabled, the converted value is the measured temperature.
S Sign bit
Nu Bit not used
SIx General status bit for an input channel. Bits 0…3 are for input channels. Bit 4 is for CJC. If the bit is 0, the channel is operating normally. If the bit is 1, a fault has
occurred on the channel.
Overrange alarm bit for an input channel.
OIx 0 = Channel is operating normally
1 = Input signal is over normal range.
Underrange alarm bit for an input channel.
UIx 0 = Channel is operating normally
1 = For bits 0…3, that is, input channels, the input signal is under the normal range. For bit 4, that is, channel using the thermocouple/mV, RTD/Resistance input
type, the input value equals the minimum value of the range.
Where:
High alarm bit for an input channel 0.
HIx 0 = Channel is operating normally
1 = Input signal is above the user-defined range
Low alarm bit for an input channel 0.
LIx 0 = Channel is operating normally
1 = Input signal is below the user-defined range.
Open circuit detection bit.
OCx 0 = Channel isn’t experiencing an open circuit condition
1 = Channel is experiencing an open circuit condition
General status bit for output channel 0 or 1.
SOx 0 = Channel operating normally
1 = A fault has occurred on the channel
Overrange alarm bit for output channel 0 or 1.
OOx 0 = Channel is operating normally
1 = Output signal is over the normal range
Underrange alarm bit for output channel 0 or 1.
UOx 0 = Channel is operating normally
1 = Output signal is below the normal range
Output Array
The embedded analog I/O output image array of the module contains four words as described
in this table. This array is write-only and the default value for all bits is 0.
CompactLogix 5370 L2 Controller Embedded Analog I/O Module Output Data Array
Bit
Word
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 S Analog Output Data Value Channel 0
1 S Analog Output Data Value Channel 1
CL CH CL CH CL CH CL CH
2 Nu I3 I3 I2 I2 I1 I1 I0 I0
CL CH CL CH
3 Nu O1 O1 O0 O0
Analog Output Data Value Channel x is the data that is written to the channel.
S Sign bit
Nu Bit not used
Use this bit to cancel High Process Alarm Latch functionality for an input.
CH 0 = Do not cancel
Ix 1 = Cancel the alarm latch
Use this bit to cancel Low Process Alarm Latch functionality for an input.
Where: CL 0 = Do not cancel
Ix 1 = Cancel the alarm latch
Use this bit to cancel High Process Alarm Latch functionality for an output.
CH 0 = Do not cancel
Ox 1 = Cancel the alarm latch
Use this bit to cancel Low Process Alarm Latch functionality for an output.
CL 0 = Do not cancel
Ox 1 = Cancel the alarm latch
Configuration Array
The embedded analog I/O configuration image array of the module contains 43 words as
described in this table.
CompactLogix 5370 L2 Controller Embedded Analog I/O Module Configuration Image Array
Bit
Word
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 Real Time Sample Value
1 ETS Nu
2 EC Nu EA AL EI EO Open Circuit Ch0 0V Adj Filter Setting ChI0
3 Wire & CLCD TU ChIo Nu Inpt Dta Fm ChI0 Nu Inpt Tp/RngeSel ChI0
4 S Process Alarm High Data Value Universal Input Channel 0
5 S Process Alarm Low Data Value Universal Input Channel 0
6 S Alarm Dead Band Value Universal Input Channel 0
7 Nu
8 EC Nu EA AL EI EO Open Circuit ChI 1 0V Adj Filter Setting ChI1
9 Nu TU ChI1 Nu Inpt Dta Fm ChI1 Nu Inpt Tp/RngeSel ChI1
10 S Process Alarm High Data Value Universal Input Channel 1
11 S Process Alarm Low Data Value Universal Input Channel 1
12 S Alarm Dead Band Value Universal Input Channel 1
13 Nu
14 EC Nu EA AL EI EO Open Circuit ChI 2 0V Adj Filter Setting ChI2
15 Wire & CLCD TU ChI1 Nu Inpt Dta Fm ChI2 Nu Inpt Tp/RngeSel ChI2
16 S Process Alarm High Data Value Universal Input Channel 2
17 S Process Alarm Low Data Value Universal Input Channel 2
CompactLogix 5370 L2 Controller Embedded Analog I/O Module Configuration Image Array (Continued)
Bit
Word
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
18 S Alarm Dead Band Value Universal Input Channel 2
19 Nu
20 EC Nu EA AL EI EO Open Circuit ChI 3 0V Adj Filter Setting ChI3
21 Nu TU ChI1 Nu Inpt Dta Fm ChI3 Nu Inpt Tp/RngeSel ChI3
22 S Process Alarm High Data Value Universal Input Channel 3
23 S Process Alarm Low Data Value Universal Input Channel 3
24 S Alarm Dead Band Value Universal Input Channel 3
25 Nu
26 CJC Ses Cycle Nu CJC WP Nu TU CJC
Calib
27 Nu
28 EC NU EHI ELI LC ER FM PM Nu PFE
29 Nu Outpt Fm ChI0 Nu Outpt Tp/RngeSel Ch0
30 S Fault Value Channel 0
31 S Program (Idle) Value Channel 0
32 S Clamp High Data Value Channel 0
33 S Clamp Low Data Value Channel 0
34 S Ramp Rate Channel 0
35 Nu
36 EC Nu EHI ELI LC ER FM PM Nu PFE
37 Nu Outpt Fm ChI1 Nu Outpt Tp/RngeSel ChI1
38 S Fault Value Channel 1
39 S Program (Idle) Value Channel 1
40 S Clamp High Data Value Channel 1
41 S Clamp Low Data Value Channel 1
42 S Ramp Rate Channel 1
CompactLogix 5370 L2 Controller Embedded Analog I/O Module Configuration Image Array (Continued)
Bit
Word
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Use to enable or disable a channel. Each channel can be individually enabled.
EC 0 = Disable
1 = Enable
Inpt Dta Use this bit to select the form in which the analog data is returned to the controller and used in the control program.
FM CHIx
Use this bit to enable or disable the process alarms of a channel.
EA 0 = Disable
1 = Enable
Use this bit to enable or disable alarm latching on the process alarm of a channel.
AL 0 = No latch
1 = Latch
Use this bit to enable or disable interrupts on the process alarms of a channel.
EI 0 = Disable
1 = Enable
Use this bit to enable or disable Open Circuit functionality on a channel.
EO 0 = Disable
1 = Enable
Use to set the Open Circuit Response for a channel.
Where: Open 0 = Upscale
Circuit 1 = Downscale
Chx 2 = Last State
3 = Zero
CJC is performed by default by taking the CJC sensor temperature value for a given channel, converting that to a thermocouple voltage, and adding
OV that voltage from the measured value before converting to a user value. If this bit is set for a given channel, the signal value is directly converted
adjust to a user value (No cold junction compensation performed).
Use to set the wire mode. The combination of values in bits 14 and 15 determine the mode, as listed in the following table.
Table 1 -
Wire & Bit 15 Value Bit 14 Value Mode
CLCD
0 0 3-wire and cycle lead compensation - Enable
0 1 3-wire and cycle lead compensation - Disable
1 0 2-wire (No lead compensation)
1 1 4 i (N l d ti )
Use to set the temperature units.
TU Chx 0 = Degrees Celsius
1 = Degrees Fahrenheit
CompactLogix 5370 L2 Controller Embedded Analog I/O Module Configuration Image Array (Continued)
Bit
Word
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Use these bits to select the form the analog input data is presented to the controller and used by the controller. The combination of multiple
Inpt Dta selections in words and bits determines this value.
Fm ChIx For more information on what selections determine the input data form that is used, see the Analog Input Data Format table on page 169.
Inpt Tp / Use these bits to select the input type and operating range for a channel. For more information on what selections determine the input type and
Rnge Sel operating range for a channel, see the Analog Input Type and Operating Range table on page 170.
ChIx
Filter
Setting Use these bits to select the filter setting for a channel. For more information on what selections determine the filter settings for a channel, see the
Input Filter Selections table on page 169.
Chx
Process
Alarm
High
Data Use to configure the Process Alarm High value for a channel. Configuration is done by using words 4, 10, 16, and 22 to set the Alarm High value.
Value
Channel
x
Process
Alarm
Low
Data Use to configure the Process Alarm Low value for a channel. Configuration is done by using words 5, 11, 17, and 23 to set the Low High value.
Value
Channel
x
Alarm
Dead
Where Band
(cont.) Data Use to configure the Alarm Deadband value for a channel. Configuration is done by using words 6, 12, 18, and 24 to set the deadband alarm value.
Value
Channel
x
Use to enable or disable the timestamping function on the module.
ETS 0 = Disable
1 = Enable
Real
Time Use to set the Real Time Sample value. The available range = 0…5000 ms.
Stamp
Value
Use this bit to enable or disable a CJC sensor.
UpdateC • If enabled, the CJC is read once every other module scan, and its value is updated in the CJC status word. This value is also used for
JCComp thermocouple cold junction compensation.
ensatio • If disabled, the CJC sensor value isn’t acquired, and the CJC temperature is fixed at 25 °C (77 °F) for all channels. The CJC is also fixed at 25 °C
nEn (77 °F) for all channels if it’s determined to be broken (short or open circuit).
0 = Disable
1 = Enable
Use this bit to enable Cycle Calibration.
• If enabled, the internal calibration of the module occurs once every 5 minutes.
Cycle • If disabled, the internal calibration of the module occurs only once at power on/ reset.
Calib Cycle Calibration enables the module to readjust for environmental changes such as variations in temperature. However, the module throughput is
slightly reduced during the calibration operation.
0 = Disable
1 = Enable
CompactLogix 5370 L2 Controller Embedded Analog I/O Module Configuration Image Array (Continued)
Bit
Word
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Use this bit to enable or disable the CJC Weighted Profile.
• If enabled, the CJC temperature for each channel is scaled by multiplying the single CJC reading by a predefined scale factor that is derived from
lab measurements of the stable temperature of each terminal block pin. In this condition, all channel data is overridden with the
CJC temperature of that channel.
CJC WP
• If disabled, the single CJC reading is applied directly to all channels. If the CJC sensors are installed in a remote terminal block, the weighted
profile must be disabled. In this condition, channel data is presented in the input table as normal.
0 = Disable
1 = Enable
Use this bit to select whether data from the Program/Idle m ode or the Fault Enable mode is applied.
PFE 0 = Program/Idle mode data applied
1 = Fault mode data applied
Use this bit to enable or disable ramping for each channel.
ER 0 = Disable
1 = Enable
Use this bit to enable or disable the output channel interrupt function when a High Clamp alarm is set.
EHI 0 = Disable
1 = Enable
Use this bit to enable or disable the output channel interrupt function when a Low Clamp alarm is set.
ELI 0 = Disable
1 = Enable
Use this bit to set data a channel uses when it is in Program/Idle mode.
Where PM 0 = Hold Last State value
(cont.) 1 = User-defined value
Use this bit to set the data a channel uses when it is in Fault mode.
FM 0 = Hold Last State value
1 = User-defined value
Use this bit to enable or disable latch functionality when Low/High clamp and Under/Over range alarm conditions exist on a channel.
LC 0 = Disable
1 = Enable
Outpt Use these bits to select the form the analog output data is presented to the controller and used by the controller. The combination of multiple
Dta Fm selections in words and bits determines this value.
ChIx For more information on what selections determine the output data form that is used, see the Analog Output Data Format table on page 171.
Outpt Tp Use these bits to select the output type and operating range for a channel. For more information on what selections determine the input type and
/ Rnge operating range for a channel, see the Analog Output Type and Operating Range table on page 171.
Sel ChIx
Fault
Value Use this bit to configure the Fault mode value for a channel.
Channel
x
Program
(Idle)
Value Use this bit to configure the Program/Idle mode value for a channel.
Channel
x
ClampHi
gh Data
Value Use this bit to configure the Clamp High data value for a channel.
Channel
x
Clamp
Where Low
(cont.) Data Use this bit to configure the Clamp Low data value for a channel.
Value
Channel
x
Ramp
Rate Use this bit to set the Ramp Rate value for a channel.
Channel
x
This table lists the bit value combinations that you can use to select a filter setting for a
channel. You use bits 0…3 in words 2, 8, 14, and 20 to make this selection.
Input Filter Selections
Bit Settings
Filter Value (Words 3, 9, 15, and 21)
Bit 03 Bit 02 Bit 01 Bit 00
60 Hz 0 0 0 0
50 Hz 0 0 0 1
10 Hz 0 0 1
250 Hz 0 0 1 1
500 Hz 0 1 0 0
1 kHz 0 1 0 1
Spare(1) Values 6...15
(1) An attempt to write a non-valid (any Spare value) or Not Used bit configuration into the Input Filter Response Select field
causes a Module Configuration Error (contained in the Mod_Condition Array).
This table lists the bit value combinations that you can use to select the output data format for
analog data that is sent to the controller for a channel. You use bits 8…10 in words 3, 9, 15, and 21 to
make this selection.
Analog Input Data Format
Bit Settings
Analog Output Data Format (Words 3, 9, 15, and 21)
Bit 10 Bit 09 Bit 08
Raw/Proportional Data 0 0 0
Engineering Units 0 0 1
Engineering Units x 10 0 1 0
Scaled for PID 0 1 1
Percent Range 1 0 0
Spare(1) Values 5...7
(1) An attempt to write a non-valid (any Spare value) bit configuration into the Input/Output Data Format Select field causes a
Module Configuration Error (contained in Mod_Condition Array). All bits shown as 0 in this table are set to 0.
This table lists the bit value combinations that you can use to select the input type and
operating range for a channel. You use bits 0…5 in words 3, 9, 15, 21, 29, and 37 to make the
selections.
Analog Input Type and Operating Range
Bit Settings
Input Type and Normal Operating Range (Words 3, 9, 15, and 21)
Bit 05 Bit 04 Bit 03 Bit 02 Bit Bit 00
-10…10V DC 0 0 0 0 0 0
0…5V DC 0 0 0 0 0 1
0…10V DC 0 0 0 0 1 0
4…20 mA 0 0 0 0 1 1
1…5V DC 0 0 0 1 0 0
0…20 mA 0 0 0 1 0 1
-50 mV…50 mv 0 0 0 1 1 0
-100…+100 mV 0 0 0 1 1 1
Thermocouple J 0 0 1 0 0 0
Thermocouple K 0 0 1 0 0 1
Thermocouple T 0 0 1 0 1 0
Thermocouple E 0 0 1 0 1 1
Thermocouple R 0 0 1 1 0 0
Thermocouple S 0 0 1 1 0 1
Thermocouple B 0 0 1 1 1 0
Thermocouple N 0 0 1 1 1 1
Thermocouple C 0 1 0 0 0 0
100 PT 385 0 1 0 0 0 1
200 PT 385 0 1 0 0 1 0
500 PT 385 0 1 0 0 1 1
1000 PT 385 0 1 0 1 0 0
100 PT 3916 0 1 0 1 0 1
200 PT 3916 0 1 0 1 1 0
500 PT 3916 0 1 0 1 1 1
1000 PT 3916 0 1 1 0 0 0
10 CU 426 0 1 1 0 0 1
120 Ni 618 0 1 1 0 1 0
120 Ni 672 0 1 1 0 1 1
604 NiFe 518 0 1 1 1 0 0
150 0 1 1 1 0 1
500 0 1 1 1 1 0
1000 0 1 1 1 1 1
3000 1 0 0 0 0 0
This table lists the bit value combinations that you can use to select the output data format for
analog data that is sent to the controller for a channel. You use bits 8…10 in words 29 and 37 to
make this selection.
Analog Output Data Format
Bit Settings
Analog Output Data Format (Words 29 and 37)
Bit 10 Bit 09 Bit 08
Raw/Proportional Data 0 0 0
Engineering Units 0 0 1
Scaled for PID 0 1 0
Percent Range 0 1 1
Spare(1) Values 4…7
(1) An attempt to write a non-valid (any Spare value) bit configuration into the Input/Output Data Format Select field causes a
Module Configuration Error (contained in Mod_Condition Array). All bits shown as 0 in this table are set to 0.
This table lists the bit value combinations that you can use to select the input type and
operating range for a channel. You use bits 0…5 in words 29 and 37 to make the selections.
Analog Output Type and Operating Range
Bit Settings
Output Type and Normal (Words 29 and 37)
Operating Range
Bit 05 Bit 04 Bit 03 Bit 02 Bit Bit 00
-10…10V DC 0 0 0 0 0 0
0…5V DC 0 0 0 0 0 1
0…10V DC 0 0 0 0 1 0
4…20 mA 0 0 0 0 1 1
1…5V DC 0 0 0 1 0 0
0…20 mA 0 0 0 1 0 1
Complete these steps to install local expansion modules in your CompactLogix 5370 L2 control
system.
1. Attach the Compact I/O modules as described in these publications:
• Compact I/O Modules Installation Instructions, publication 1769-IN088
• Compact I/O DeviceNet® Scanner Module Installation Instructions, publication
1769-IN060
2. Use the tongue-and-groove slots to attach a 1769-ECR Compact I/O end cap terminator
to the last module in the system.
3. Move the lever of the end cap bus terminator fully to the left until it clicks to lock the
end cap bus terminator.
Wire each Compact I/O module that is used as a local expansion module according to the
technical documentation for that module.
You must use the following to use distributed I/O modules over a DeviceNet network in your
CompactLogix 5370 L2 control system:
• Logix Designer application or the Studio 5000® environment - For more information,
see page 182.
• RSNetWorx™ for DeviceNet software - For more information, see page 185.
The following graphic shows a CompactLogix 5370 L2 control system on a DeviceNet network
that uses all three I/O module options.
Embedded I/O Modules Local Expansion Modules
Validate I/O Layout You must validate the layout of I/O modules in your CompactLogix 5370 L2 control system.
Consider the points detailed in this section when validating
I/O layout placement.
The CompactLogix 5370 L2 controllers attempt to scan an I/O module at the configured RPI
rate. The controller scans distributed I/O modules at the configured RPI rates.
With embedded I/O modules and local expansion modules, however, some system
configuration parameters determine the actual rate at which the controller scans the
modules. That is, the controller can be configured to scan an I/O module at one rate but
actually scan the module at another rate.
For individual I/O modules, a module RPI overlap minor fault (further described on page 176)
occurs if there is at least one I/O module that can’t be serviced within its RPI time.
The configuration parameters for a system determine the impact on actual RPI rates. These
configuration factors can affect the effective scan frequency for any individual embedded or
local expansion module:
• Rates at which RPI values are set for embedded I/O modules
• Number of embedded I/O modules that are used in the system
• Types of embedded I/O modules that are used in the system
• Rates at which RPI values are set for Compact I/O modules
• Number of Compact I/O modules in the system
• Types of Compact I/O modules in the system
• Application user task priorities
Requested Packet Interval Rate Guidelines
Type of Module Guidelines(1)
The following guidelines apply:
• 1…2 modules can be scanned in 0.5 ms.
All digital
• 3…4 modules can be scanned in 1 ms.
• 5…30 modules can be scanned in 2 ms.
The following guidelines apply:
Mix of digital • 1…2 modules can be scanned in 0.5 ms.
and analog or all • 3…4 modules can be scanned in 1 ms.
analog • 5…13 modules can be scanned in 2 ms.
• 14…30 modules can be scanned in 3 ms.
The following conditions apply:
• For every 1769-SDN module in the system, increase every RPI by 2 ms for every other module.
Specialty • For every 1769-HSC module in the system, increase every RPI by 1 ms for every other module.
• For every 1769-ASCII module in the system, increase every RPI by 1 ms for every other module.
• For every 1769-SM2 module in the system, increase every RPI by 2 ms for every other module.
(1) The guidelines in this table do not factor in the following items, which affect the CMX5370 controller CPU loading:
I/O RPI timing does not affect the task priority. Event and periodic tasks have higher priority than I/O and user tasks.
IOT (Immediate Output Instruction) Messaging CompactBus browsing such as accessing DeviceNet network through 1769-SDN
using CMX5370 Ethernet or USB connection. Module RPI guidelines can require adjustment (increase of 1 ms or more) if the
CMX5370 controller application includes one or more of the listings in this table. Monitor controller minor faults to determine
if Module RPI overlaps have occurred.
IMPORTANT When considering the number of I/O modules, remember that they can
be the embedded I/O modules on the controller or Compact I/O
modules that are used as local expansion modules.
Therefore, the consideration for using modules can be any of the
following system configurations:
• Only embedded I/O modules
• Only Compact I/O modules
• Some combination of embedded I/O modules and Compact I/O modules
You can set the RPI rates higher for individual Compact I/O modules. The RPI shows how
quickly modules can be scanned, not how quickly an application can use the data. The RPI is
asynchronous to the program scan. Other factors, such as program execution duration, affect
I/O throughput.
The embedded power supply provides the following power to the CompactBus:
• 1769-L24ER-QB1B controller:
- 1.54 A @ 5V DC
- 0.95 A @ 24V DC
• 1769-L24ER-QBFC1B, 1769-L24ER-QBFC1BK, and 1769-L27ERM-QBFC1B controllers:
- 1 A @ 5V DC
- 0.8 A @ 24V DC
The embedded power supply can power any combination of controller, embedded I/O modules,
and local expansion modules that are used in your application.
Power supply distance rating is the number of slots a Compact I/O module can be installed
away from the power supply. If a Compact I/O module has a distance rating of three, you can
include up to two modules between the Compact I/O module and the power supply.
Additionally, the controller has embedded I/O modules that are designed to protect against
installation of a Compact I/O module directly to the right of the embedded power supply.
CompactLogix 5370 L2 control systems have embedded I/O modules in the controller.
CompactLogix 5370 L2 control systems have one or two embedded I/O modules as described
as follows:
• 1769-L24ER-QB1B controller - one embedded I/O module
• 1769-L24ER-QBFC1B, 1769-L24ER-QBFC1BK, and 1769-L27ERM-QBFC1B controllers - two
embedded I/O modules
The embedded I/O modules aren’t considered local expansion modules. However, you must still
include each embedded I/O module in the module slot count when determining where to install
Compact I/O module as a local expansion module.
Because CompactLogix 5370 L2 control systems only allow up to four local expansion modules
in the system, you can install most Compact I/O modules in any local expansion module slot.
Some Compact I/O modules have power supply distance ratings that affect where you can
install them in the CompactLogix 5370 L2 control system.
For example, the 1769-ASCII Compact ASCII and 1769-HSC Compact high-speed counter
modules each have a power supply distance rating of four. The farthest local expansion
module slot where you can install one of these modules in a CompactLogix 5370 L2 control
system is module slot number two or three. The controller catalog number that is used in the
control system determines the slot number.
This table describes the farthest local expansion module slot where you can install a 1769-HSC
high-speed counter module and meet its power supply distance rating requirement.
Example CompactLogix 5370 L2 Control Systems with a 1769-HSC High-speed Counter Module
Number of Embedded 1769-HSC High-speed Counter Module Power Supply Distance Rating Calculation Impact
Controller Cat. No. I/O Modules
The embedded I/O module is the first module in the module count. At its maximum power supply distance rating, the
1769-HSC high-speed counter module can be installed in slot 3 of the local expansion modules, as shown in this graphic.
1769-HSC Module
1769-L24ER-QB1B 1
Three modules between the power supply and the 1769-HSC high-speed counter module. With this controller catalog number, you can
only install up to two local expansion modules between the controller and the 1769-HSC high-speed counter module.
Example CompactLogix 5370 L2 Control Systems with a 1769-HSC High-speed Counter Module (Continued)
Number of Embedded 1769-HSC High-speed Counter Module Power Supply Distance Rating Calculation Impact
Controller Cat. No. I/O Modules
The embedded I/O modules are the first two modules in the module count. At its maximum power supply distance rating,
the 1769-HSC high-speed counter module can be installed in slot 2 of the local expansion modules, as shown here.
1769-HSC High-speed
Module
Three modules between the power supply and the 1769-HSC high-speed counter module. With this controller catalog number, you can
only install one local expansion module between the controller and the 1769-HSC high-speed counter.
IMPORTANT When counting I/O modules to determine the 1769-HSC high-speed counter
module placement in a 1769-L24ER-QBFC1B or 1769-L27ERM-QBFC1B control
1769-L24ER-QBFC1B, system, the embedded I/O module appearance is different between the
1769-L24ER-QBFC1BK, 2 physical appearance and the appearance of the module in the application.
1769-L27ERM-QBFC1B The physical appearance is a shown in the previous graphic. The second
module is two rows of termination points below one set of status indicators.
In the application Controller Organizer, the second embedded I/O module
appears as two modules, each with their own slot number, [2] and [3].
When the 1769-HSC high-speed counter module is installed in the farthest
local expansion module slot possible, that is the fourth module in the
system, it appears with a [5] designation in the Controller Organizer, as
shown in this graphic.
1769-HSC high-speed counter module is shown as module [5] in this location but considered the
fourth module when counting modules to meet power supply distance rating requirements.
For more information about the power supply distance rating for a Compact
I/O module, see CompactLogix Selection Guide, publication 1769-SG001.
Configure Local I/O Modules You can configure one of these types of local I/O modules in the programming software
environment:
2. Select the required tab, make the necessary changes, and select OK.
IMPORTANT You can also use the tags to configure the embedded I/O modules of
the CompactLogix 5370 L2 controller. When attempting to use the tags
to make analog I/O module selections in the input, output, and
configuration data arrays, the options are complicated.
I/O Connections
IMPORTANT You can only use direct connections with the local expansion modules in
a CompactLogix 5370 L2 control system.
A Logix 5000™ system uses connections to transmit I/O data, as described in this table.
I/O Module Connections
Connection Description
A direct connection is a real-time, data-transfer link between the controller and an I/O module. The controller maintains and
monitors the connection. Any break in the connection, such as a module fault, causes the controller to set fault status bits in the
Direct data area that is associated with the module.
Typically, analog I/O modules, diagnostic I/O modules, and specialty modules require direct connections.
For digital I/O modules, you can select rack-optimized communication.
This option is used with distributed I/O modules and the Rack Optimization connection selection is made when configuring the
remote adapter. For example, if your CompactLogix 5370 L2 control system includes distributed digital I/O modules over an
EtherNet/IP and you want to use a rack-optimized connection with those digital I/O modules, you must configure the EtherNet/IP
Rack-optimized adapter of the distributed digital I/O modules to use a connection type of Rack Optimization.
A rack-optimized connection consolidates connection usage between the controller and the digital I/O modules in a remote chassis
or on one DIN rail. Rather than having individual, direct connections for each I/O module, there’s one connection for the entire rack
(or DIN rail).
Configure Distributed I/O Your CompactLogix 5370 L2 control system can use distributed I/O modules on an EtherNet/IP
network.
Modules on an EtherNet/IP
Network IMPORTANT When adding distributed I/O modules, remember to count the remote
Ethernet adapter to remain within the maximum number of EtherNet/IP
network nodes limitation for your controller.
The distributed I/O modules that are connected to the controller via the
remote Ethernet adapter aren’t counted toward the maximum Ethernet
node limit for the controller.
For example, a 1769-L27ERM-QBFC1B controller supports up to 16
Ethernet nodes. You can add up to 16 remote Ethernet adapters to the I/
O Configuration section because each remote adapter counts against
the node count. However, you can add as many remote I/O modules to
the chassis of the adapter as necessary. Remote I/O modules do not
count against the node count.
For more information on node limitations, see Chapter 6, page 102.
Complete these steps to configure distributed I/O modules on an EtherNet/IP network.
1. Right-click Ethernet and select New Module.
This graphic is an example of a 1769-L27ERM-QBFC1B control system that uses distributed I/O
modules over an EtherNet/IP network.
1794-AENTR FLEX™ I/O 1734-AENTR POINT I/O
PanelView™ Plus
Configure Distributed I/O Your CompactLogix 5370 L2 control system can use distributed I/O modules on a DeviceNet
network.
Modules on a DeviceNet
Network Complete these steps to configure distributed I/O modules on a DeviceNet network.
1. If you haven’t done so, install a 1769-SDN Compact I/O DeviceNet scanner into the local
bank of your CompactLogix 5370 L2 control system.
2. Right-click 1769 Bus and select New Module.
6. Use RSNetWorx for DeviceNet software to define the scan list in the 1769-SDN scanner
to communicate data between the devices and the controller through the scanner.
• 1769-L27ERM-QBFC1B
• 1769-SDN
Monitor I/O Modules With CompactLogix 5370 L2 controllers, you can use the following options to monitor I/O
modules:
• QuickView™ pane below the Controller Organizer
• Connection tab in the Module Properties dialog box
• Programming logic to monitor fault data so you can act.
When a fault occurs on an I/O module, a yellow triangle on the module listing in the Controller
Organizer alerts you to the fault, as shown in this graphic.
This graphic shows the Quick View pane, which indicates the type of fault.
To see the fault description on the Connection tab in Module Properties dialog box, complete
these steps.
1. In the I/O Configuration, right-click the faulted I/O module and select Properties.
2. Select the Connection tab and use the fault description, in the Module Fault section, to
diagnose the issue.
Select I/O Modules This chapter details the I/O module options that CompactLogix™ 5370 L3 control
systems offer.
• When possible, use specialty Compact I/O modules to meet unique application
requirements.
• Consider using a 1492 wiring system for each I/O module as an alternative to the
terminal block that comes with the module.
• Use 1492 PanelConnect™ modules and cables if you’re connecting input modules to
sensors.
Complete these steps to install local expansion modules in your CompactLogix 5370 L3 control
system:
1. Attach the 1769 Compact communication or I/O modules as described in these
publications:
• Compact I/O Modules Installation Instructions, publication
1769-IN088
• Compact I/O DeviceNet® Scanner Module Installation Instructions,
publication 1769-IN060
2. If your system uses only a local bank, complete these steps.
a. Use the tongue-and-groove slots to attach a 1769-ECR Compact
I/O end cap terminator to the last module in the system.
b. Move the lever of the end cap bus terminator fully to the left until it clicks to lock the
end cap bus terminator.
3. If your system uses more banks, follow these steps.
a. Install a 1769-CRx Compact I/O communication bus expansion cable at the right end
of the local bank.
b. Connect the 1769-CRx cable to the additional bank as necessary.
How you connect to the first extra bank—on the right or left side of the bank,
determines the expansion cable that is installed at the end of the local bank. See
page 190 for an example of how to connect a local bank to extra banks.
c. Complete the installation of the remaining banks in your system.
IMPORTANT Make sure that you install an end cap at the end of the last bank
in your system.
This figure shows example systems with local expansion modules included.
Figure 6 - Example CompactLogix 5370 L3 Control Systems
Horizontal Orientation
Bank 1
1769-CRRx Cable
Vertical Orientation
Bank 2
Wire each Compact I/O module that is used as a local expansion module according to the
technical documentation for that module.
You must use this software to include distributed I/O modules over a DeviceNet network in
your CompactLogix 5370 L3 control system:
• Logix Designer application or the Studio 5000® environment - for more information, see
page 203.
• RSNetWorx™ for DeviceNet software - for more information, see page 111.
This graphic shows an example 1769-L33ERM control system that uses local expansion
modules and distributed I/O modules over a DeviceNet network.
Validate I/O Layout After you’ve selected your I/O modules, you must validate the system that you want to design.
Consider the points detailed in this section when validating I/O layout placement.
The CompactLogix 5370 L3 controllers attempt to scan an I/O module at the configured RPI
rate. For individual I/O modules, a Module RPI Overlap minor fault (further described on
page 194) occurs if there is at least one I/O module that can’t be serviced within its RPI time.
The configuration parameters for a system determine the impact on actual RPI rates. These
configuration factors can affect the effective scan frequency for any individual module:
• Rates at which RPI rates are set for other Compact I/O modules
• Number of other Compact I/O modules in the system
• Types of other Compact I/O modules in the system
• Application user task priorities
Requested Packet Interval Rate Guidelines
Type of Module Guidelines(1)
The following guidelines apply:
• 1…2 modules can be scanned in 0.5 ms.
All digital
• 3…4 modules can be scanned in 1 ms.
• 5…30 modules can be scanned in 2 ms.
The following guidelines apply:
• 1…2 modules can be scanned in 0.5 ms.
Mix of digital and analog or all analog • 3…4 modules can be scanned in 1 ms.
• 5…13 modules can be scanned in 2 ms.
• 14…30 modules can be scanned in 3 ms.
The following conditions apply:
• For every 1769-SDN module in the system, increase the RPI of every other
module by 2 ms.
• For every 1769-HSC module in the system, increase the RPI of every other
Specialty module by 1 ms.
• For every 1769-ASCII module in the system, increase the RPI of every
other module by 1 ms.
• For every 1769-SM2 module in the system, increase the RPI of every other
module by 2 ms.
(1) The guidelines in this table do not factor in the following items, which affect CMX5370 controller CPU loading:
I/O RPI timing does not affect the task priority. Event and periodic tasks have higher priority than I/O and user tasks.
IOT (Immediate Output Instruction). Messaging CompactBus browsing such as accessing DeviceNet network through
1769-SDN by using CMX5370 Ethernet or USB connection. Module RPI guidelines can require adjustment (increase of 1 ms or
more) if CMX5370 controller application includes one or more of the listings in this table. Monitor controller minor faults to
determine if Module RPI overlaps have occurred.
You can set the RPI rates of individual Compact I/O modules higher than the rates listed. The
RPI shows how quickly modules can be scanned, not how quickly an application can use the
data. The RPI is asynchronous to the program scan. Other factors, such as program execution
duration, affect
I/O throughput.
Current Capacity for Side of Bank Current Capacity for Side of Bank
• The maximum current capacity requirements vary by the power supply that is used in
the bank.
Power Supply Cat. No. Max Current Capacity for Single Bank Max Current Capacity for Each Side of Bank(1)
1769-PA2
2 A at 5V DC and 0.8 A at 24V DC 1 A at 5V DC and 0.4 A at 24V DC
1769-PB2
1769-PA4
4 A at 5V DC and 2 A at 24V DC 2 A at 5V DC and 1 A at 24V DC
1769-PB4
(1) Specification for banks with devices on left and right sides of the power supply.
I/O Module-specific
IMPORTANT: Insert a separate row in this Up to 8 Module-specific Module-specific
Right calculation for each I/O module.
Total Current Required(2):
Total Current Required for Single Bank if Modules Are Installed on Both Sides of the Power Supply(3):
(1) In the local bank, you can only install up to three modules to the left of the power supply. This limitation is because the CompactLogix 5370 L3 controllers have a power supply distance rating
of four and must be within four slots of the Compact I/O power supply. On the right side of the power supply in the local bank and both sides of the power supply in more banks, you can
install up to eight modules. This configuration is possible only if the power supply distance ratings for the modules validate the system design.
(2) This number must not exceed the power supply current capacity for this side of the bank.
(3) This number must not exceed the power supply current capacity for the bank.
IMPORTANT In extra banks, you can install I/O modules to the left side, right side, or
both sides of the power supply.
I/O Modules
Right - Optional in IMPORTANT: Insert a separate row for each Up to 8 Module-specific Module-specific
one bank I/O module.
Total Current Required(2):
Total Current Required for Bank if Modules Are Installed on Both Sides of the Power Supply(3):
(1) You can install up to eight modules in additional banks if the power supply distance ratings for the modules validate the system design.
(2) This number must not exceed the power supply current capacity for this side of the bank.
(3) This number must not exceed the power supply current capacity for the bank.
Consider these factors when determining the physical placement of the I/O modules:
• You can install I/O modules in local and extra banks.
• You can install I/O modules to the left and right of the power supply.
• When a system requires multiple banks, you can install the additional banks horizontally
or vertically, as shown in this graphic.
Horizontal Orientation
Local Bank
Extra Bank
• Each I/O module also has a power supply distance rating and maximum current draw.
Considered jointly, distance ratings and current draw determine where I/O modules can
be placed in a bank and what configuration of modules can be installed in the bank.
For more information on power supply distance ratings, see page 69. For more
information on system power consumption, see page 194.
Local Bank
To validate the local bank design, confirm that the design meets these requirements:
• The controller is the leftmost device in the local bank.
• No more than three modules are installed between the controller and the left side of the
power supply.
• No more than eight modules are installed to the right of the power supply.
• The power consumption of the modules on each side of the power supply does not
exceed the capacity of the power supply for that side.
• The total power consumption by all modules in the bank does not exceed the capacity
of the power supply for the entire bank.
• Modules are installed such that all power supply distance rating and system power
consumption requirements are met.
For example, the 1769-SDN scanner has a power supply distance rating of four. If the
design includes the installation of a 1769-SDN scanner with greater than three modules
between it and the power supply, the design is invalid.
IMPORTANT Make sure that you take power supply distance ratings into
consideration when you design a system. If you install a module that
violates its power supply distance rating specification, the system can
operate normally for a time, but experience operational issues, such as
I/O faults.
Additional Banks
If your application calls for twelve or more I/O modules, at minimum, you must install the
modules in extra banks. The conditions of each application determine the number of extra
banks.
Once the local bank design is validated, you must validate the design for any additional banks.
To validate extra bank designs, confirm that the design meets these requirements:
• Compact I/O communication bus expansion cables are used properly.
Compact I/O expansion cables have the same dimensions as the end caps
regardless of whether they’re installed at the right or left side of the
communication bus.
• No more than eight modules are installed on either side of the power supply.
• The power consumption of the modules on each side of the power supply does not
exceed the capacity of the power supply for that side.
• Modules are installed such that all power supply distance rating requirements are met.
• End caps are installed properly, as shown in the following graphic.
Local Bank
1769-CRRx Cables
Extra Bank
End Cap
In CompactLogix 5370 L3 control systems, you can install Compact I/O modules to the left or
right side of the power supply. You can also use local and extra banks in CompactLogix 5370
L3 control systems, with each allowing the inclusion of Compact I/O modules.
Local Bank
In the local bank, the controller must be the leftmost device in the system and you can only
install up to three modules between the controller and the power supply. Therefore, any
Compact I/O modules that are installed to the left of the power supply in the local bank are in a
module slot that meets the power supply distance rating requirements for the module.
Additional Banks
CompactLogix 5370 L3 control systems also support the use of extra banks for the local
expansion modules of the system. Every additional bank requires a 1769 Compact I/O power
supply. The bank can be designed with local expansion modules on either side of the power
supply.
Most Compact I/O modules have power supply distance rating values that allow you to install
them in any slot on either side of the power supply in extra banks. Some Compact I/O modules
have power supply distance ratings that affect where you can install them in the
CompactLogix 5370 L3 control system.
For example, the 1769-ASCII Compact ASCII and 1769-HSC Compact high-speed counter
modules each have a power supply distance rating of four. These modules can be installed in
local expansion module slots one through three.
In this case, you must install the 1769-ASCII module and 1769-HSC high-speed counter module
with no more three Compact I/O modules between the module and the power. This
requirement is true regardless of whether the modules are installed to the left or right of the
power supply.
This graphic shows 1769-HSC high-speed counter modules that are installed in a 1769-L36ERM
control system that meet the power supply distance rating of the module.
Local Bank
Extra Bank
IMPORTANT The Module Power Consumption Calculation for an Additional Bank table
on page 196 shows example systems with 1769-HSC high-speed counter
modules in each control system because it has a power supply distance
rating of four and can’t be installed as far from the Compact I/O power
supply. Most Compact I/O modules have power supply distance ratings
that allow you to install them anywhere in the local expansion slots of a
CompactLogix 5370 L2 control system.
For more information about the power supply distance rating for a
Compact I/O module, see CompactLogix Selection Guide, publication
1769-SG001.
Configure I/O Complete these steps to add a Compact I/O module to your CompactLogix 5370 L3 control
system and configure it.
1. Right-click the 1769 Bus and select New Module.
I/O Connections
A Logix 5000™ system uses connections to transmit I/O data, as described in this table.
Connection Description
A direct connection is a real-time, data-transfer link between the controller and an I/O module. The controller maintains and
monitors the connection. Any break in the connection, such as a module fault, causes the controller to set fault status bits in the
Direct data area that is associated with the module.
Typically, analog I/O modules, diagnostic I/O modules, and specialty modules require direct connections.
For digital I/O modules, you can select rack-optimized communication.
This option is used with distributed I/O modules and the Rack Optimization connection selection is made when configuring the
remote adapter. For example, if you want to use a rack-optimized connection with digital I/O modules in a remote 1734 POINT I/O
Rack-optimized system, you configure the 1734-AENT(R) module to use a connection type of Rack Optimization.
A rack-optimized connection consolidates connection usage between the controller and the digital I/O modules in a remote chassis
or on one DIN rail. Rather than having individual, direct connections for each I/O module, there’s one connection for the entire rack
(or DIN rail).
Configure Distributed I/O Your CompactLogix 5370 L3 control system can use distributed I/O modules on an EtherNet/IP
network.
Modules on an EtherNet/IP
Network IMPORTANT When adding distributed I/O modules, remember to count the remote
Ethernet adapter to remain within the maximum number of EtherNet/IP
network nodes limitation for your controller.
The remote I/O modules that are connected to the controller via the
Ethernet adapter aren’t counted toward the maximum Ethernet node
limit for the controller.
For more information on node limitations, see Chapter 6, page 102.
Complete these steps to configure distributed I/O modules on an
EtherNet/IP network.
1. Right-click Ethernet and select New Module.
The following graphic is an example of a 1769-L33ERM control system that uses distributed I/O
modules over an EtherNet/IP network.
PanelView™ Plus
Configure Distributed I/O Your CompactLogix 5370 L3 control system can use distributed I/O modules on a DeviceNet
network.
Modules on a DeviceNet
Network Complete these steps to configure distributed I/O modules on a DeviceNet network.
1. If you have not done so, install a 1769-SDN Compact I/O DeviceNet scanner into the local
bank of your CompactLogix 5370 L3 control system.
2. Right-click 1769 Bus and select New Module.
6. Use RSNetWorx for DeviceNet software to define the scan list in the 1769-SDN scanner
to communicate data between the devices and the controller through the scanner.
The following graphic is an example of a 1769-L33ERM control system that uses distributed I/O
modules on a DeviceNet network.
• 1769-L33ERM
• 1769-SDN Scanner
Monitor I/O Modules With CompactLogix 5370 L3 controllers, you can monitor I/O modules in the following ways:
• QuickView™ Pane below the Controller Organizer
• Connection tab in the Module Properties dialog box
• Programming logic to monitor fault data so you can act
When a fault occurs on an I/O module, a yellow triangle on the module listing in the Controller
Organizer alerts you to the fault.
This graphic shows the Quick View Pane, which indicates the type of fault.
To see the fault description on the Connection tab in Module Properties dialog box, complete
these steps.
1. In the I/O Configuration, right-click the faulted I/O module and select Properties.
2. To diagnose the issue, select the Connection tab and use the fault description, in the
Module Fault section.
3. To close the dialog box and remedy the issue, select OK.
Notes:
Develop Applications
Elements of a Control A control application is composed of several elements that require planning for efficient
application execution. This section details the elements of a control application.
Application
Elements of a Control Program
Control Application
Task 32
Task 1
Configuration
Status
Watchdog
Program 1000
Program 1
Program (Local
Main Routine Tags and
Parameters)
Fault Routine
Other
Routines
Controller (global)
Tags I/O Data System-shared Data
Tasks A Logix 5000® controller lets you use multiple tasks to schedule and prioritize the execution of
your programs that are based on criteria. This multitasking allocates the processing time of
the controller among the different operations in your application:
• The controller executes only one task at a time.
• One task can interrupt the execution of another task and take control.
• In any given task, multiple programs can be used. However, only one program executes
at a time.
• You can display tasks in the Controller or Logical Organizer views, as necessary.
Task in a Control Application
Control Application
Task 32
Task 1 Task 1
Contains the following: Configuration
• Configuration Data
Status
• Status Data
• Watchdog Data Watchdog
• Programs Program 1000
Program 1
Program (Local
Main Routine Tags and
Parameters)
Fault Routine
Other Routines
Tasks in Application
Controller Logical Organizer
Main Task
(continuous)
Main Task
(continuous)
Task 2
(periodic)
Task 2
(periodic) Task 3
(event)
Task 3
(event)
A task provides scheduling and priority information for a set of one or more programs.
Configure tasks as continuous, periodic, or event by using the Task Properties dialog box.
Configuring the Task Type
This table explains the types of tasks that you can configure.
The CompactLogix controller supports up to 32 tasks, only one of which can be continuous.
A task can have up to 1000 separate Programs (as described on page 216) per task, each with
its own executable routines and program-scoped tags. Once a task is triggered (activated), all
programs that are assigned to the task execute in the order in which they’re grouped. Multiple
tasks can’t share Programs and Programs appear only once in the Controller Organizer.
Task Priority
Each task in the controller has a priority level. The operating system uses the priority level to
determine which task to execute when multiple tasks are triggered. A higher priority task
interrupts any lower priority task. A periodic or event task interrupts the continuous task,
which has the lowest priority.
You can configure periodic tasks to execute from the lowest priority of 15 up to the highest
priority of 1. Configure the task priority by using the Task Properties dialog box.
Configure the Task Priority
Programs The controller operating system is a pre-emptive multitasking system that is in compliance
with IEC 1131-3. This system provides the following:
• Programs to group data and logic
• Routines to encapsulate executable code that is written in one programming language
Task 32
Task 1
Configuration
Status
Watchdog
Program 1000
Program 1
Program 1 Program (Local
Contains the following: Tags and
Main Routine
• Main Routine Parameters)
• Fault Routine
• Other Routines Fault Routine
• Program Tags
Other Routines
Programs in Application
Controller Organizer Logical Organizer
Program
Program
Program
Program
Unscheduled programs in a task are downloaded to the controller with the entire project. The
controller verifies unscheduled programs but does not execute them.
You must schedule a program in a task before the controller can scan the program. To
schedule an unscheduled program, use the Program/Phase Schedule tab of the Task
Properties dialog box.
Scheduling an Unscheduled Program
Routines A routine is a set of logic instructions in one programming language, such as Ladder Diagram
(ladder logic). Routines provide the executable code for the project in a controller. A routine is
similar to a program file or subroutine in a PLC or SLC™ processor.
Each program has a main routine. This routine is the first routine to execute when the
controller triggers the associated task and calls the associated program. Use logic, such as
the Jump to Subroutine (JSR) instruction, to call other routines.
You can also specify an optional program fault routine. The controller executes this routine if
it encounters an instruction-execution fault in any of the routines in the associated program.
Routines in a Control Application
Control Application
Task 32
Task 1
Configuration
Status
Watchdog
Program 1000
Program 1
Program (Local
Main Routine Tags and
Parameters)
Fault Routine
Other Routines
Routines in Application
Routine
Routine
Routine
Routine
Tags With a Logix 5000 controller, you use a tag (alphanumeric name) to address data (variables). In
Logix 5000 controllers, there’s no fixed, numeric format. For example, as shown in the
following figure, you can use the tag name north_tank_mix instead of a numeric format, such
as N7:0.0.
The tag name itself identifies the data. The tag lets you do the following:
• Organize your data to mirror your machinery.
• Document your application as you develop it.
This example shows data tags that are created in the scope of the Main Program of the
controller.
Tags Example
Controller Organizer - Main Program Parameters and Local Tags
Integer Value
Storage Bit
Counter
Timer
Digital I/O Device
There are several guidelines to create and configure parameters and local tags for optimal
task and program execution. For more information, see the Logix 5000 Controllers and I/O Tag
Data Programming Manual,
publication 1756-PM004.
Extended Properties
The Extended Properties feature lets you define more information, such as limits, engineering
units, or state identifiers, for various components within your controller project.
Component Extended Properties
Tag In the Tag Editor, add extended properties to a tag.
User-defined data type In the Data Type Editor, add extended properties to data types.
In the properties that are associated with the Add-On Instruction definition, add
Add-On Instructions extended properties to Add-On Instructions.
Pass-through behavior isn’t available for limits. When an instance of a tag is created, if limits
are associated with the data type, the instance is copied.
You must know which tags have limits that are associated with them as there’s no indication
in the tag browser that extended properties are defined for a tag. If, however, you try to use
extended properties that haven’t been defined for a tag, the editors show a visual indication
and the routine does not verify.
If an array tag is using indirect addressing to access limits in logic, these conditions apply:
• If the array tag has limits that are configured, the extended properties are applied to
any array element that does not explicitly have that particular extended property
configured. For example, if the array tag MyArray has Max configured to 100, any
element of the array that does not have Max configured inherits the value of 100 when
being used in logic. However, it isn’t visible that the value inherited from MyArray is
configured in the tag properties.
• At least one array element must have a limit that is configured for indirectly referenced
array logic to verify. For example, if MyArray[x].@Max is being used in logic, at least one
array element of MyArray[] must have Max extended property that is configured if
MyArray hasn’t configured Max.
• Under the following circumstances, a data type default value is used:
- Array is accessed programmatically with indirect reference.
- Array tag does not have the extended property configured.
- A member of an array does not have the extended property configured.
For example, for an array of SINT type, when max limit is called in logic for a member,
use the value of 127. If an array element is directly accessed, the element has to have
the extended property defined. If not, verification fails.
Programming Languages The CompactLogix controller supports these programming languages, online, and offline.
CompactLogix Controller Programming Languages
Language Is best-used in programs with
Continuous or parallel execution of multiple operations (not sequenced)
Boolean or bit-based operations
Complex logical operations
Relay ladder Message and communication processing
Machine interlocking
Operations that service or maintenance personnel can have to interpret to
troubleshoot the machine or process
Continuous process and drive control
Function block diagram Loop control
Calculations in circuit flow
High-level management of multiple operations
Repetitive sequence of operations
Sequential function chart (SFC) Batch process
Motion control using structured text
State machine operations
Complex mathematical operations
Structured text Specialized array or table loop processing
ASCII string handling or protocol processing
For information about programming in these languages, see the Logix 5000 Controllers
Common Procedures Programming Manual,
publication 1756-PM001.
Add-On Instructions You can design and configure sets of commonly used instructions to increase project
consistency. Similar to the built-in instructions contained in Logix 5000 controllers, these
instructions you create are called Add-On Instructions. Add-On Instructions reuse common
control algorithms. With them, you can do the following:
• Ease maintenance by animating logic for one instance.
• Protect intellectual property with Source Protection.
• Reduce documentation development time.
You can use Add-On Instructions across multiple projects. You can define your instructions,
obtain them from somebody else, or copy them from another project.
This table explains some of the capabilities and advantages of use Add-On Instructions.
Add-On Instruction Capabilities
Capability Description
With Add-On Instructions, you can combine your most commonly used logic into sets of reusable instructions. You save time
Save Time when you create instructions for your projects and share them with others. Add-On Instructions increase project consistency
because commonly used algorithms all work in the same manner, regardless of who implements the project.
You create Add-On Instructions by using one of three editors:
• Relay Ladder
Use Standard Editors • Function Block Diagram
• Structured Text
Once you have created instructions, you can use them in any editor.
You can export Add-On Instructions to other projects and copy and paste them from one project to another. Give each instruction
Export Add-On Instructions a unique name so that you don’t accidentally overwrite another instruction of the same name.
Context views let you visualize the logic of an instruction for an instant, which simplifies online troubleshooting of your Add-On
Use Context Views Instructions. Each instruction contains a revision, a change history, and an auto-generated help page.
When you create an instruction, you enter information for the description fields in dialogs, information that becomes what is
Create Custom Help known as Custom Help. Custom Help makes it easier for you to get the help you need when implementing the instructions.
As the creator of Add-On Instructions, you can limit users of your instructions to read-only access. You can also bar access to the
Apply Source Protection internal logic or local parameters that are used by the instructions. This source protection lets you stop unwanted changes to
your instructions and protects your intellectual property.
Once defined in a project, Add-On Instructions behave similarly to the built-in instructions in
Logix 5000 controllers. They appear on the instruction toolbar for easy access, as do internal
instructions.
Add-On Instructions
Access the Module Object The MODULE object provides status information about a module. To select a particular module
object, set the Object Name operand of the GSV/SSV instruction to the module name. The
specified module must be present in the
I/O Configuration section of the controller organizer and must have a device name.
You must create a Module Reference parameter when you define the Add-On Instruction to
access the MODULE object data. A Module Reference parameter is an InOut parameter of the
MODULE data type that points to the MODULE Object of a hardware module. You can use
module reference parameters in both Add-On Instruction logic and program logic.
For more information on the Module Reference parameter, see the Logix 5000 Controllers Add-
On Instructions Programming Manual,
publication 1756-PM010, and the Logix Designer application online help.
The MODULE object uses the following attributes to provide status information:
• EntryStatus
• FaultCode
• FaultInfo
• FWSupervisorStatus
• ForceStatus
• Instance
• LEDStatus
• Mode
• Path
The Path attribute is available with Logix Designer application, version 24.00.00 and later. This
attribute provides a communication path to the module.
For more information on the attributes available in the MODULE object, see the Logix 5000
Controllers General Instructions Reference Manual, publication 1756-RM003.
Monitoring Controller Status The CompactLogix controller uses Get System Value (GSV) and Set System Value (SSV)
instructions to get and set (change) controller data. The controller stores system data in
objects. There’s no status file, as in the PLC-5® processor.
The GSV instruction retrieves the specified information and places it in the destination. The
SSV instruction sets the specified attribute with data from the source. The instructions are
available from the Input/Output tab of the Instruction toolbar.
GSV and SSV Instructions for Monitoring
When you add a GSV/SSV instruction to the program, the object classes, object names, and
attribute names for each instruction are displayed. For the GSV instruction, you can get values
for the available attributes. For the SSV instruction, only those attributes you’re allowed to set
are displayed.
Some object types appear repeatedly, so you have to specify the object name. For example,
there can be several tasks in your application. Each task has its own Task object that you
access by the task name.
There are several objects and attributes that you can use the GSV and SSV instructions to
monitor and set the system. For more information about GSV instructions, SSV instructions,
objects, and attributes see the Logix 5000 Controllers General Instructions Reference Manual,
publication 1756-RM003.
Monitoring I/O Connections If communication with a device in the I/O configuration of the controller does not occur in an
application-specific period, the communication times out and the controller
produces warnings.
The minimum timeout period that, once expired without communication, causes a timeout is
100 ms. The timeout period can be greater, depending on the RPI of the application. For
example, if your application uses the default RPI = 20 ms, the timeout period is 160 ms.
For more information about I/O faults, see the Logix 5000 Controllers Major, Minor, and I/O
Faults Programming Manual, publication 1756-PM014.
224 Rockwell Automation Publication 1769-UM021K-EN-P - May 2023
Chapter 10 Develop Applications
For more information about attributes available with the Module object, see the Logix 5000
Controllers General Instructions Reference Manual, publication 1756-RM003.
For more information about attributes available with the Module object, see the Logix 5000
Controllers General Instructions Reference Manual, publication 1756-RM003.
For more information about programming the Controller Fault Handler, see the Logix 5000
Controllers Major, Minor, and I/O Faults Programming Manual, publication 1756-PM014.
System Overhead The controller communicates with other devices at a specified rate (scheduled) or when
there’s processing time available to service the communication.
Time Slice
The system overhead time slice specifies the percentage of time a controller devotes to
service communication. If you have a continuous task, the System Overhead Time Slice
entered in the Advanced tab of the Controller Properties dialog box specifies the continuous
task/service communication ratio. However, if there’s no continuous task, the overhead time
slice has no effect.
This table shows the ratio between the continuous task and service communication at various
system overhead time slices.
If the system overhead time slice is less than or equal to 50%, the duration stays fixed at 1 ms.
The same applies for 66% and higher, except there are multiple 1 ms intervals. For example, at
66% there are two 1 ms intervals of consecutive time and at 90% there are nine 1 ms intervals
of consecutive time.
Notes:
Some of the CompactLogix™ 5370 controllers support Integrated Motion over an EtherNet/IP™
network. This motion solution is on standard, unmodified EtherNet/IP networks with simple
design or configuration as compared to traditional motion applications.
AXIS_VIRTUAL Axis
The AXIS_VIRTUAL axis is an internal axis representation that is not associated with any
physical drives. That is, you can configure the axis but it does not cause any physical motion in
your system.
AXIS_CIP_DRIVE Axis
The AXIS_CIP_DRIVE axis is a motion axis that is used with physical drives to cause physical
motion in your system as determined by your application.
Configuration Types
When adding an axis to your project, you must associate the axis to a drive. Among other
configuration parameters, you must select a configuration type. The axis configuration type is
also considered the drive configuration type.
For example, an AXIS_CIP_DRIVE axis can use a Position Loop configuration and be associated
with a Kinetix 350 drive. The axis is considered a Position Loop-configured axis and the
associated drive is considered a Position Loop-configured drive.
For example, the 1769-L30ERM controller supports a maximum of four Position Loop-
configured drives.
This table lists motion-related specification information for the controllers that support
Integrated Motion over an EtherNet/IP network.
CompactLogix 5370 Controllers Supporting Integrated Motion on the EtherNet/IP Network
Number of Position Loop-
Number of Drives
Controller Type Drive Types Supported configured Drives
Supported, Max Supported, Max
1769-L18ERM-BB1B 8 2
1769-L18ERM-BB1BK
1769-L27ERM-QBFC1B
1769-L30ERM 16 4
1769-L30ERMK
1769-L33ERM
1769-L33ERMK Kinetix 350 32 8
1769-L33ERMO Kinetix 5500
Kinetix 5700
1769-L36ERM Kinetix 6500
1769-L36ERMO PowerFlex 755
1769-L37ERM 48 16
1769-L37ERMK
1769-L37ERMO(1)
1769-L38ERM
1769-L38ERMK 80 16
1769-L38ERMO(1)
(1) Available at software version 31 and firmware revision 31.
If your solution requires more than 16 Position Loop-configured drives, consider using the
ControlLogix® platform. The ControlLogix platform enables up to 100 Position Loop-configured
drives.
Time Synchronization Integrated Motion over an EtherNet/IP network requires Time Synchronization, also known as
CIP Sync™. CIP Sync provides accurate real-time (real-world time) or Coordinated Universal
Time (UTC) synchronization of CompactLogix 5370 controllers and devices that are connected
over an EtherNet/IP network.
CIP Sync is a time-synchronization protocol that can be applied to various applications. This
chapter focuses on how to use the protocol in applications with Integrated Motion over an
EtherNet/IP network.
All controllers and communication modules must have time synchronization enabled to
participate in CIP Sync.
CIP Sync requires that devices in the system function in the following roles:
• Grandmaster, also known as the coordinated system time (CST) master - Sets time for
the entire system and passes the time to a Master
• Master - Sets time for its backplane
• Slave - Uses time set by Master
Configure Integrated Motion To use Integrated Motion on the EtherNet/IP network, complete the steps that are detailed in
this section.
IMPORTANT These steps show a 1769-L36ERM controller. The same steps apply to
other CompactLogix 5370 controllers that support Integrated Motion
over an EtherNet/IP network with slight variations in screens.
IMPORTANT This section assumes that you’ve previously created a project for your
1769-L36ERM controller. If you haven’t, do so before continuing.
Add a Drive
You can only use these drives in an application that uses Integrated Motion over an EtherNet/
IP network:
• Kinetix 350 drive
• Kinetix 5500 drive
• Kinetix 5700 drive
• Kinetix 6500 drive
• PowerFlex 755 AC drive
IMPORTANT These steps show a Kinetix 350 drive in a 1769-L36ERM control system.
The same steps apply to other CompactLogix 5370 controllers that
support Integrated Motion over an EtherNet/IP network with slight
variations in screens.
1. In the I/O configuration tree, right-click the Ethernet network and select New Module.
6. If you must change the configuration for any of the following parameters, select Change
in the Module Definition area:
• Revision
• Electronic Keying
• Connection
• Power Structure
• Verify Power Rating on Connection
The Module dialog box appears.
Scalability in Applications CompactLogix 5370 controllers offer various levels of flexibility and scalability to operate in
control systems that use Integrated Motion on EtherNet/IP networks.
Using Integrated Motion
You can use the following controllers in control systems that require simpler configuration and
complex configuration of Integrated Motion on
EtherNet/IP networks parameters:
• 1769-L30ERM, 1769-L30ERMK
• 1769-L33ERM, 1769-L33ERMK
• 1769-L33ERMO
• 1769-L36ERM
• 1769-L36ERMO
• 1769-L37ERM, 1769-L37ERMK
• 1769-L37ERMO(1)
• 1769-L38ERM, 1769-L38ERMK
• 1769-L38ERMO(1)
1769-L33ERM
Stratix 2000
PowerFlex 755
PanelView™ Plus
Kinetix 350
Complex control systems that use Integrated Motion over an EtherNet/IP network often
include managed switches. This example shows such a configuration with Stratix 6000 switch,
and Kinetix 6500 and PowerFlex 755 drives.
1769-L33ERM
Kinetix 350
Kinetix 6500
POINT I/O™
PowerFlex 755
1769-L18ERM-BB1B
The 1769-L18ERM-BB1B controller is typically used in control systems that require simpler
configuration regarding using Integrated Motion over an EtherNet/IP network.
1769-L18ERM-BB1B
Stratix 2000
PowerFlex 755
PanelView Plus
Kinetix 350
1769-L27ERM-QBFC1B Controller
The 1769-L27ERM-QBFC1B controller is typically used in control systems that require simpler
configuration regarding using Integrated Motion over an EtherNet/IP network.
1769-L27ERM-QBFC1B
Stratix 2000
PowerFlex 755
PanelView Plus
Kinetix 350
For more information on Integrated Motion over an EtherNet/IP network, see the publications
that are listed on page 11.
This chapter describes the primary tasks that are required to store a project on an SD card or
load a project from an SD card to the CompactLogix™ 5370 controller.
CompactLogix 5370 controllers support nonvolatile storage through the following SD cards:
• 1784-SD1 - Ships with CompactLogix 5370 controller and offers 1 GB of memory. You can
order more 1784-SD1 cards if desired.
• 1784-SD2 cards - Available for separate purchase and offer 2 GB of memory.
For information on how to install or remove an SD card from a CompactLogix 5370 controller,
see Chapter 4, page 61
.
IMPORTANT We recommend that you leave the SD card installed in the controller and
the card unlocked. The SD card saves extended diagnostic information
that you can send to Rockwell Automation that provides enhanced
diagnostics of your application and firmware revision if circumstances
require this data.
This section briefly describes how to use the SD card when installed in a
CompactLogix 5370 controller. The section details how to store a
project from the controller to the SD card and how to load a project
from the SD card to the controller.
However, you can complete other tasks by using the SD card, such as
the following:
• Change the image that is loaded from the card
• Check for a load that was completed
• Clear an image from the memory card
• Store an empty image
• Change load parameters
• Read/write application data to the card
For more detailed information on how to use an SD card, see the
Logix 5000™ Controllers Nonvolatile Memory Card Programming Manual,
publication 1756-PM017.
Store or Load a Project with There are several options for when to load the project back into the user memory (RAM) of the
CompactLogix 5370 controller. The controller configuration determines the option that is used.
the Secure Digital Card
This table describes the conditions and necessary configuration settings that are required for
a project to be loaded from an SD card.
Conditions and Settings for Project Loading
Condition to Load
Project from an SD Card Required Setting in
Controller Configuration Notes
into Controller RAM
• During a power cycle, you lose any online changes and
tag values you haven’t stored on the memory card.
• A load from a memory card can also change the firmware
of the controller.
Controller power-up On Power Up
• For more information, see the Logix 5000 Controllers
Nonvolatile Memory Card Programming Manual,
publication 1756-PM017.
• You can use the application to load the project.
• During a power cycle, you lose any online changes and
tag values you haven’t stored on the memory card.
• A load from a memory card can also change the firmware
No project in the of the controller.
controller and you power On Corrupt Memory
up the controller • For more information, see the Logix 5000 Controllers
Nonvolatile Memory Card Programming Manual,
publication 1756-PM017.
• You can use the application to load the project.
You lose any online changes and tag values that you haven’t
Only through application User Initiated stored on the memory card.
Store a Project Follow these steps to store a project. These steps show a 1769-L18ERM-BB1B controller. The
same steps apply for other CompactLogix 5370 controllers.
1. Go online with the controller.
2. Put the controller in Program mode, that is, Remote Program or Program.
3. On the Online toolbar, select the controller properties icon.
6. Select under what conditions to load the project into the user memory of the controller.
Project that is on the memory card of the Project that is in the user memory of the
controller (if any project is there). controller.
If you select On Power Up or On Corrupt Memory, you must also select the mode that you
want the controller to go to after the load:
• Remote Program
• Remote Run
7. In the Automatic Firmware Update box, use the default (disable) or select the Firmware
Supervisor option.
Load a Project Follow these steps to use the application to load the project from an SD card. These steps
show a 1769-L18ERM-BB1B controller. The same steps apply for other CompactLogix 5370
controllers.
1. Go online with the controller.
2. Put the controller in Program mode, that is, Remote Program or Program.
3. On the Online toolbar, select the controller properties icon.
6. Select Load.
Project that is on the memory card of the controller Project that is in the user memory of
(if any project is there). the controller.
After you select Load, the project is loaded into the controller as indicated by the controller
status indicators. These conditions can exist:
• While the load is in progress, the following occurs:
- The controller resets itself.
When the controller is resetting itself, the status indicators execute a sequence of
state changes, for example, a brief time with the OK status indicator in the steady
red state. Wait for the controller to complete the sequence.
- After the controller fully resets itself, the OK indicator is steady green.
The SD indicator is off.
This section explains how to interpret the status indicators on your CompactLogix™ 5370
controllers. All controllers use the status indicators that are described in this table.
Status Indicator Description
RUN Indicates the operating mode of the controller.
FORCE Indicates the force state.
I/O Indicates the current state of communication between the controller and I/O modules.
OK Indicates the state of the controller.
NS Indicates the EtherNet/IP™ network status regarding the controller operating on the network.
LINK 1 Indicates the EtherNet/IP link status for port 1 if the controller.
LINK 2 Indicates the EtherNet/IP link status for port 2 of the controller.
SD Indicates if there’s activity on the SD card.
Use Logix Designer This section details the ways in which the Logix Designer application indicates fault
conditions.
Application for
Troubleshooting Warning signal on the main screen next to the module - This occurs when the connection to
the module is broken. The controller state also indicates Faulted and the Controller fault is
illuminated in red.
On the Module Info tab, in the Status section, the Major and Minor Faults are listed along with
the Internal State of the module.
Notification in the Tag Editor - General module faults are also reported in the Tag Editor.
Diagnostic faults are reported only in the tag editor.
The Major Faults tab indicates the type of fault under Recent Faults. A fault displays here when
you’re monitoring the configuration properties of a module in the Logix Designer application
and receive a Communication fault message.
Use the CompactLogix 5370 This graphic shows the controller status indicators for all CompactLogix 5370 controllers.
Controllers Status
Indicators
Notes:
Replacement Considerations
CompactLogix™ 5370 L1 series B and C controllers are direct replacements of the series A
controllers. The series B and C controllers have an improved power supply circuit to the
isolated power supply so that a second power supply is no longer needed.
Product Comparison This section details certain characteristics to consider when comparing CompactLogix 5370 L1
series A, B, and C controllers.
Power Considerations
CompactLogix 5370 L1 series A, B, and C controllers
Characteristics CompactLogix L1 Series B and C CompactLogix L1 Series A
Power dissipation 11.5 W 12 W
Recommended external short circuit User-provided 4...6 A @
User-provided 4...5 A @ 3.15...5.5 I²t fuse
protection, field power 52.5...68.25 I²t fuse
Embedded power supply 24V DC input, isolated 24V DC input, non-isolated
Line requirement (V DC), min 30VA 50VA
Current draw @ 24V DC, field power, max 3 A @ 24V DC –
Firmware Compatibility
For the latest information regarding firmware compatibility, refer to Rockwell Automation
Product Compatibility and Download Center at: rok.auto/pcdc
Dimensions There are no dimension differences between the series A controller and the series B and C
controllers.
12.00 mm
(0.47 in.)
100.00 mm
(3.94 in.)
105 mm
(4.13 in.)
130.00 mm
(5.11 in.)
144.00 mm
(5.67 in.)
Series A Wiring
Fuse
IMPORTANT: No wires are
connected to the NC terminal.
Examples
In this example:
• Replace a series A controller with a series B or C controller
OR
• Replace a series B controller with a series C controller
Requirements:
Category Tasks
The series B or C controller requires only one power supply,
but the series B or C controller does support two power
Power Supply Wiring supplies. You can retain the current power supply design for
the series A controller and avoid rewiring.
Refer to Rockwell Automation Product Compatibility and
Controller Firmware Download Center (PCDC) at: rok.auto/pcdc.
Install the Studio 5000 environment compatible with the
Programming Software controller firmware obtained from the PCDC.
Use an operating system compatible with the Studio 5000
Personal Computer environment obtained from the PCDC.
This appendix explains how to connect power to series A L1 CompactLogix™ 5370 controllers.
The external power supply must be dedicated to the embedded supply of the controller. The
external power supply converts 115/230V AC power to 24V DC or other application-required DC
voltage that is within the operating range of the controller.
WARNING: Do not connect directly to line voltage. Line voltage must be supplied
by a suitable, approved isolating transformer or power supply having short
circuit capacity not exceeding 100VA maximum or equivalent. The controller
power requirement is 50VA.
Power is connected to the controller via a removable connector that is connected to the front
of the controller. The following graphic shows the connector.
• The external power supply that provides power to the CompactLogix 5370 L1 controller
must be dedicated to power the controller.
• You must use a separate, dedicated external 24V DC power source to connect power to
other terminals on the removable connector and devices in the system, for example, the
FP+ terminal or a barcode scanner, respectively.
• The external 24V DC power source that is connected to the VDC+ and VDC- terminals on
the removable connector must reside in the same enclosure as the CompactLogix 5370
L1 controller.
• Use a power source that most effectively meets your application needs. That is,
calculate the power requirements for your application before choosing a power source
to avoid using a power source that far exceeds your application requirements.
• This section assumes that any DIN rail that you use has been grounded following
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
• The embedded power supply of the CompactLogix 5370 L1 controller provides power to
the controller and POINTBus™ backplane. It does not provide field-side power to the
embedded I/O or local expansion modules.
• Not all Class 2/SELV-listed power supplies are certified for use in all applications, for
example, use in nonhazardous and hazardous environments.
Before installing an external power supply, consult all specification and certification
information to verify that you’re using an acceptable external power supply.
• For example purposes, this section describes how to use a 1606-XLE120E, NEC Class 2
switched-mode power supply. The exact steps for other external power supplies can
vary from the steps that are described here.
Complete these steps to connect power to the CompactLogix 5370 L1 controller. CompactLogix
5370 L1 Series B and C controllers can also be connected to power as instructed in this
procedure.
1. Verify that the external 24V DC power source isn’t powered.
2. Mount the external 24V DC power source on a DIN rail.
The external 24V DC power source can be installed on the same DIN rail as the controller
or a separate DIN rail.
3. Connect the wires to the 24V DC+ and 24V DC- connections on the external 24V DC
power source.
WARNING: If you connect or disconnect the wiring while the field-side power is
on, an electric arc can occur. This could cause an explosion in hazardous
location installations. Be sure that power is removed or the area is nonhazardous
before proceeding.
5. Connect the wire that is connected to the 24V DC+ terminal on the external 24V DC
power source to the VDC+ terminal. The VDC+ terminal is the top terminal on the
removable connector.
6. Connect the wire that is connected to the 24V DC- terminal on the external 24V DC
power source to the VDC- terminal. The VDC- terminal is second from the top on the
removable connector.
Connect Field Power to Complete these steps to connect field power to the CompactLogix 5370 L1 series A controller.
CompactLogix 5370 L1 Series B and C controllers can also be connected to field power as
Series A L1 Controllers for I/ instructed in this procedure.
O Devices 1. Verify that the separate external 24V DC power source that powers the CompactLogix
5370 L1 controller isn’t powered.
2. Verify that the external 24V DC power source that is connected to the FP+ and FP-
terminals isn’t powered.
3. Mount the external power supply that connects to the FP+ and FP- terminals on a DIN
rail.
The external power supply can be installed on the same DIN rail as the controller or a
separate DIN rail.
4. Connect wires to the appropriate + and - connections on the external 24V DC power
source.
WARNING: If you connect or disconnect wiring while the field-side power is on,
an electric arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous before
proceeding.
5. Pull the removable connector off the CompactLogix 5370 L1 controller.
Wires that are connected between external
24V DC power source and VDC+ and VDC-
terminals on the removable connector.
6. Connect the wire that is connected to the + terminal on the external 24V DC power
source to the FP+ terminal. The FP+ terminal is the fourth terminal from the top on the
removable connector.
7. Connect the wire that is connected to the - terminal on the external 24V DC power
source to the FP- terminal. The FP- terminal is the fifth terminal from the top on the
removable connector.
10. Turn on power to the separate external 24V DC power source connected to the VDC+
and VDC- terminals of the removable connector.
11. Turn on power to the external 24V DC power source connected to the FP+ and FP-
terminals of the removable connector.
This graphic shows separate external 24V DC power supplies connected to the VDC+/VDC-
and FP+/FP- terminals on the removable connector, respectively.
FP Power Supply
Notes:
Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the
form at rok.auto/docfeedback.
At the end of life, this equipment should be collected separately from any unsorted municipal waste.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Allen-Bradley, Armor, ArmorBlock, Compact I/O, ControlFLASH, CompactLogix, ControlLogix, DriveLogix, E3 Electronic Overload Relay, expanding human possibility, FLEX I/O, FlexLogix, Integrated
Architecture Builder, Kinetix, Logix 5000, On-Machine, PanelConnect, PanelView Plus, PLC-5, POINT I/O, POINTBus, PowerFlex, QuickView, Rockwell Automation, RSLinx Classic, RSLogix 5000,
RSNetWorx, SLC, SoftLogix, Stratix, Studio 5000, and Studio 5000 Logix Designer are trademarks of Rockwell Automation, Inc.
CIP, CIP Sync, DeviceNet, and EtherNet/IP are trademarks of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur