Operating Instructions v2.0
Operating Instructions v2.0
Instructions
HAEFELY TEST AG
2293
Winding Analyser
Version 1.9
4842186
Title Operating Instructions
2293 Winding Analyser
Date 07-2011
Authors MM, LWA, SG, SM
Layout LWA
Part number 4842186
Revision History
V0.9 06/2011 LWA Initial release of the document
V1.0 07/2011 SG Additional features added, manual completed
V1.1 03/2012 MM Remote control chapter added
V1.2 06/2012 LWA 3rd LED added, CE with new address
V1.3 04/2013 SM, LWA, MM Turns Ratio, graphical updates, connection hints
V1.4 06/2013 SM, LWA Cooling curve & Temperature Rise added
V1.5 02/2014 SM Magnetic Balance, dry type temperature rise added
V1.6 06/2014 SM, LWA, MM, SG License screen updated, Additional Demag information
V1.7 07/2014 SM Magnetic Balance updated
V1.8 09/2014 LW Additional info to temperature probes
V1.9 11/2014 LW Additional info to calibration and classic mode
V2.0 08.2015 SG Tap changer and short circuit impedance added. Interlock
connection explanation. CT connection description
WARNING
Before operating the instrument, be sure to read and fully
understand the operating instructions. This instrument
produces hazardous voltages. It is the responsibility of the user
to ensure that the system is operated in a safe manner.
HAEFELY TEST AG and its sales partners refuse to accept any responsibility for consequential or
direct damage to persons and/or goods due to none observance of instructions contained herein or due
to incorrect use of the equipment.
Further be aware that safety is the responsibility of the user!
Any correspondence regarding this instrument should include the exact type number, instrument serial
number and firmware version number. With the exception of the firmware version number, this
information can be found on the registration plate on the right panel of the instrument. The firmware
version specified in the miscellaneous folder under the setup menu.
Unauthorized opening of the unit may damage the EMI protection of the system and will reduce its
resistance to interference and transients. It may also cause the individual unit to be no longer compliant
with the relevant EMC emission and susceptibility requirements. If the unit has been opened, the
calibration will be rendered invalid.
Note
HAEFELY TEST AG has a policy of continuing improvement on all their products. The design of this
instrument will be subject to review and modification over its life. There may be small discrepancies
between the manual and the operation of the instrument, particularly where software has been
upgraded in the field.
HAEFELY TEST AG retains the right to modify the functionality, specification or operation of the
instrument without prior notice.
All rights reserved. No section of this manual may be reproduced in any form, mechanical or
electronic without the prior written permission of HAEFELY TEST AG.
Indicates hazards.
There is a risk of equipment damage or personal injury or death. Carefully read and follow
the instructions. Be sure to follow any safety instructions given in addition to those for the
site at which tests are being performed.
Foreword
Welcome as a new user of the “Winding Analyzer 2293”. Thank you for placing your confidence in our
product.
With the purchase of this measuring instrument you have opted for all the advantages that have built a
world-wide reputation for a Tettex Instrument: robustness, performance and quality is assured. As a
result this instrument provides a solution which achieves the optimal combination of traditional know-
how and leading edge technology.
This operating manual is designed for completeness and easy location of the required information.
Customers who already have experience with this kind of equipment will find this document to be of
assistance as an extended help.
If you find a mistake or inconsistency in the operating manual then please feel free to inform our
Customer Support department with your corrections so that other users may benefit.
Abbreviations, definitions
Wherever possible the corresponding IEC definitions are used. The following abbreviations and
definitions are used in this manual:
Introduction I
Contents
1 Introduction 9
1.1 Receiving Instructions .................................................................................. 9
1.2 General ........................................................................................................ 9
1.3 Scope of Supply ........................................................................................... 9
1.3.1 Standard scope of supply ................................................................ 9
1.3.2 Options and accessories ............................................................... 10
1.4 Optional features........................................................................................ 10
1.5 Technical Data ........................................................................................... 12
1.5.1 Standard Features......................................................................... 12
1.5.2 Physical and Environmental Specifications ................................... 12
1.5.3 Resistance Measurement.............................................................. 12
1.5.4 Ratio Measurement ....................................................................... 13
1.5.5 Temperature Measurement ........................................................... 14
1.5.6 User Interface System ................................................................... 14
1.5.7 Printer paper Specification ............................................................ 14
1.5.8 Tap Changer Interface .................................................................. 14
1.5.9 Interlock Interface (optional) .......................................................... 15
1.5.10 Covered Standards ....................................................................... 15
2 Safety 16
2.1 General ...................................................................................................... 16
2.2 Essential Safety Recommendations .......................................................... 17
2.3 Interlock connection ................................................................................... 17
2.4 Summary.................................................................................................... 18
3 Theory 20
3.1 General Resistance Measuring Principle ................................................... 20
3.2 Power Supply Modes ................................................................................. 21
3.2.1 Parallel Mode on HV-side 16A ¦ 100V (A1) or 32A ¦ 50V (A2) ....... 21
3.2.2 Parallel Mode on LV-side 16A ¦ 100V (B1) or 32A ¦ 50V (B2) ....... 22
3.2.3 Individual Mode 2x 16A ¦ 50V (C) .................................................. 24
3.2.4 YNdx Mode 2x 16A ¦ 50V (D) ........................................................ 26
3.3 Measuring sequences ................................................................................ 27
3.3.1 Example 1 ..................................................................................... 27
3.3.2 Example 2 ..................................................................................... 28
3.3.3 Example 4 ..................................................................................... 28
3.3.4 Example 5 ..................................................................................... 29
4 Front Panel 30
II Introduction
5.1 Connection Cables..................................................................................... 32
5.1.1 Cable extensions (optional) ........................................................... 33
5.2 Connecting the Instrument ......................................................................... 33
5.2.1 Connection without extenders ....................................................... 34
5.2.2 Connection with extenders ............................................................ 34
5.2.3 Connection in Automated mode to a 3 phase transformer ............ 35
5.2.4 Connection in Automated mode to a 1 phase transformer ............ 36
5.2.5 Connection in Classic mode .......................................................... 37
5.3 USB Type A Host Port ............................................................................... 38
6 User Interface 40
6.1 Startup ....................................................................................................... 40
6.2 Structure .................................................................................................... 41
6.3 Define DUT (Top Bar) ................................................................................ 41
6.3.1 Selection of DUT Type .................................................................. 42
6.3.2 DUT data definition........................................................................ 43
6.3.3 Tap Changer configuration ............................................................ 45
6.3.4 Test Name..................................................................................... 48
6.4 Applications (Side Bar) .............................................................................. 48
6.5 Active Window ........................................................................................... 49
6.6 Function Keys (Bottom Bar) ....................................................................... 49
6.7 Device Information ..................................................................................... 50
6.8 Data Handling ............................................................................................ 50
6.8.1 File management........................................................................... 50
6.8.2 Printing results. ............................................................................. 51
6.8.3 Exporting measurement results. .................................................... 51
6.8.4 Webserver access / Ethernet interface.......................................... 53
7 Resistance Measurement 54
7.1 Operating modes ....................................................................................... 54
7.2 Automated mode........................................................................................ 54
7.2.1 General ......................................................................................... 54
7.2.2 Function keys during resistance in automated mode .................... 56
7.2.3 Active Window ............................................................................... 56
7.3 Performing a test using Automated mode .................................................. 57
7.3.1 Measurement steps ....................................................................... 57
7.3.2 Set up DUT data ........................................................................... 58
7.3.3 Test current selection .................................................................... 58
7.3.4 Test current recommendations ...................................................... 59
7.3.5 Tap sequence ............................................................................... 59
7.3.6 Auto recording configuration ......................................................... 60
7.3.7 Tap Control ................................................................................... 61
7.3.8 Temperature correction ................................................................. 62
7.3.9 Measurement ................................................................................ 62
7.4 Classic mode ............................................................................................. 65
7.4.1 Generalities ................................................................................... 65
7.4.2 User Interface structure ................................................................. 65
7.4.3 Active window ............................................................................... 66
Introduction III
7.5 Performing a test using Classic mode ........................................................ 67
7.5.1 Test object connection on classic mode ........................................ 67
7.5.2 Set up DUT data ........................................................................... 67
7.5.3 Temperature correction ................................................................. 67
7.5.4 Test current selection .................................................................... 68
7.5.5 Auto recoding configuration ........................................................... 69
7.5.6 Measurement ................................................................................ 69
7.6 Temperature Measurement........................................................................ 72
8 Demagnetization 74
8.1 Theory ........................................................................................................ 74
8.2 User interface............................................................................................. 75
8.2.1 Active Window ............................................................................... 75
8.3 Performing a demagnetization ................................................................... 76
8.3.1 Measurement steps ....................................................................... 76
8.3.2 Parameters definition .................................................................... 76
8.3.3 Demagnetizing .............................................................................. 78
8.4 Application hints ......................................................................................... 78
IV Introduction
11 Transformer configuration Detection 97
11.1 Overview .................................................................................................... 97
11.2 User Interface ............................................................................................ 97
11.2.1 Active Window ............................................................................. 100
11.2.2 Function keys .............................................................................. 100
11.3 Performing a Detection ............................................................................ 101
11.3.1 Measurement steps ..................................................................... 101
11.3.2 Parameters definition .................................................................. 101
11.3.3 Detection ..................................................................................... 101
11.3.4 Export results .............................................................................. 103
Introduction V
13.5.1 Measurement steps ..................................................................... 135
13.5.2 Set up DUT data ......................................................................... 135
13.5.3 Data handling definitions ............................................................. 136
13.5.4 Test Voltage Selection ................................................................ 136
13.5.5 Test frequency selection ............................................................. 137
13.5.6 Magnetic Imbalance selection ..................................................... 137
13.5.7 Delta Winding Configuration selection......................................... 137
13.5.8 Measuring ................................................................................... 138
13.5.9 Exporting and printing results ...................................................... 140
13.6 Application hints ....................................................................................... 141
13.6.1 Core Magnetization ..................................................................... 141
13.6.2 Winding short-circuits .................................................................. 141
VI Introduction
15.4.8 Miscellaneous ............................................................................. 165
15.4.9 Measuring ................................................................................... 165
15.4.10 Measurement results ................................................................... 166
15.4.11 Exporting and printing ................................................................. 167
19 Troubleshooting 174
19.1 Warning and Error Messages .................................................................. 174
19.1.1 Polarity reverse or HV and LV reverse ........................................ 174
19.1.2 Current to small ........................................................................... 174
19.1.3 OVP - Overvoltage Protection ..................................................... 174
19.1.4 OCP - Over current Protection .................................................... 174
19.1.5 OTP - Over temperature Protection............................................. 174
19.1.6 Hardware Error ............................................................................ 175
19.2 Firmware Update ..................................................................................... 175
19.3 Unit locks up and/or does not discharge completely ................................ 176
Introduction VII
22 Remote Control 182
22.1 Ethernet Connection ................................................................................ 182
22.1.1 RJ45 Socket ................................................................................ 182
22.1.2 Direct connection......................................................................... 182
22.1.3 Switched Network........................................................................ 184
22.1.4 Routed Network / Internet ........................................................... 184
22.2 Protocol .................................................................................................... 185
22.2.1 Instructions .................................................................................. 186
22.3 Command Reference ............................................................................... 187
22.4 Programming examples ........................................................................... 201
22.4.1 Resistance Measurement............................................................ 201
22.4.2 Tap Changer Control ................................................................... 203
22.4.3 Heat Run ..................................................................................... 204
22.4.4 Demagnetization ......................................................................... 205
22.5 File & Data Transfer ................................................................................. 208
23 Miscellaneous 209
23.1 Care and Maintenance ............................................................................. 209
23.1.1 Cleaning the Instrument .............................................................. 209
23.1.2 Instrument Calibration ................................................................. 209
23.1.3 Changing Fuses .......................................................................... 209
23.2 Instrument Storage .................................................................................. 209
23.3 Packing and Transport ............................................................................. 210
23.4 Recycling ................................................................................................. 210
25 Appendix 212
25.1 Declaration of Conformity......................................................................... 213
25.2 Application Note “Temperature Measurement” ........................................ 214
25.2.1 1. Flat Surface ............................................................................. 214
25.2.2 2. Round Surface (Tube) ............................................................. 217
25.3 Application Note “Unit calibration” ............................................................ 222
VIII Introduction
1 Introduction
1.2 General
The Tettex 2293 is the result of extensive research and years of experience testing transformers.
It incorporates a fast and highly advanced procedure to measure winding resistance. A simple
one-time-connection system together with the simultaneous winding magnetization method
drastically reduces measuring time.
The simultaneous winding magnetization (SWM) method guarantees fast and reliable
measurements even on large power transformers with delta windings on the low voltage side,
where stable measurements can be seldom reached using traditional winding resistance
measurement instruments.
In addition, the new demagnetization function eliminates the magnetic remanence in the core
after the application of a DC voltage. This feature can be used before performing other tests such
as frequency response analysis (FRA), transformer turns ratio measurement (TTR) or recovery
voltage measurement (RVM) which are adversely affected by remanence effects.
The transformer is discharged by a state-of-the-art discharge circuit in a fraction of the time taken
by other instruments. The discharging function and the “Caution” indicator continue to operate
even when line power is lost.
Qty Description
Introduction 9
1 2293 Winding Analyzer Instrument
1 High voltage side (H) measuring adaptor, 0.5m
1 Low voltage side (X) measuring adaptor, 0.5m
4 High voltage side (H) measuring cables, 4 units, (U, V, W, N) with clamp, 10m
4 Low voltage side (X) measuring cables, 4 units, (u, v, w, n) with clamp, 10m
1 Mains cable
1 Operating Instructions
1 carrying bag for cables and accessories
1 Spare kit (Printer paper roll, Fuses)
Once receipt of the unit check that all items have been delivered. Also check that the correct
power cord for your location has been supplied. In the event of missing or damaged parts please
contact you local sales representative stating the serial number and type of the instrument and
the sales order number.
Additional features will be added to the device regularly, for a complete list or for questions please
check in our web page (www.haefely-hipotronics.com).
To activate the additional features (software keys) please read chapter 16- Optional Features
activation, of this manual.
10 Introduction
Trial licenses for a number of tests are available under
request. Contact our sales department to get a trial
code.
Introduction 11
1.5 Technical Data
12 Introduction
320 μ … 32 k 0.1%
32 k … 320 k 1%
Current
25V
32A 50V
16A
3.2A
±
320mA
0.
±0.1%
5%
100V
1mV
32mA
10mV
3.2mA
±1%
320μA
320mΩ
640mΩ
Resistance
320μΩ
3.2mΩ
640μΩ
32mΩ
3.2kΩ
32μΩ
320Ω
32kΩ
320k
3.2Ω
32Ω
General
Max. Supply Current AC 1 APeak ≈ 700 mARMS
Max. Meas. Voltage AC 95 VPeak ≈ 67 VRMS
Range 1.0 … 10’000
Ratio Accuracy at highest measuring voltage
1.0 … 100 0.05%
100 … 2’000 0.1%
2’000 … 20’000 1%
20’000 … 100’000 5%
Phase (AC Meas.) Typical Accuracy at highest measuring voltage
1.0 … 500 ±0.10°
500 … 10’000 ±1.00°
Phase (Clock Number) Accuracy at highest measuring voltage
1.0 … 500 ±0.05°
Introduction 13
1.5.5 Temperature Measurement
Built-in Channels 6
Max. Meas. Channels 30 (6 internal + 3x external 8CH box “2293T”)
Sensor Probe PT100 Class A
Temperature Accuracy
-20°C … +150°C ± (0.41°C + 0.2% TMeas)
Printer: Thermal
14 Introduction
1.5.9 Interlock Interface (optional)
CE mark Compliant
Standards IEC 61010, General IEC 61326-1, IEC 61000-4-X,
61000-3-X, EN 55011, ANSI/IEEE C37.90
Safety VDE 0411/part 1a , IEC/EN 61010-1:2002
Introduction 15
2 Safety
Remember:
Hazardous voltage can shock, burn or cause death !
The unit should only be operated after carefully reading the user manual which is an
integral part of the instrument.
Haefely Test AG and its sales partners refuse to accept any responsibility for consequential
or direct damage to persons and/or goods due to none observance of instructions
contained herein or due to incorrect use of the equipment.
Further be aware that Safety is the responsibility of the user!
2.1 General
Safety is the most important aspect when working on or around high voltage electrical equipment.
Personnel whose working responsibilities involve testing and maintenance of the various types of
high voltage equipment must have understood the safety rules written in this document and the
associated safety practices specified by their company and government. Local and state safety
procedures should also be consulted. Company, regional or national regulations must be fulfilled
beyond Tettex recommendations.
If the instrument is damaged or it is possible that damage has occurred, for example during
transportation, do not apply any voltage. The instrument may only be used under dry operating
conditions.
Do not open the unit, it contains no user replaceable parts.
People with heart pacemakers should not be in the vicinity of this system during operation.
Safety is the responsibility of the user. Always operate the equipment in accordance with
the instructions, always paying full attention to local safety practices and procedures.
This equipment must be operated only by trained and competent personnel who are
aware of the dangers and hazards involved in testing transformers.
Do not operate the 2293 from a variable power supply. The 2293 adjusts to the local line
voltage at start-up. Changing the line voltage while the unit is in operation may cause
damage to the unit and to the test object
16 Safety
2.2 Essential Safety Recommendations
Before connecting the instrument ensure that the transformer to be tested is completely
de-energized and isolated from both line and load. Every terminal should be checked and
verified before connection of the instrument. Ground connections may be left in place.
Never exchange connections to the HV and LV sides of the transformer. The red
connections must always be connected to the High Voltage side of the transformer. The
black connections must always be connected to the Low Voltage side of the transformer.
Interchanging any or all of the connections may result in damage to the transformer or the
instrument and represents a significant safety hazard for personnel.
Never operate the equipment in an explosive environment or where there are flammable
gases or fumes
The instrument must always be connected to a grounded power outlet (i.e. a safety earth).
It must never be operated in a non-grounded configuration as this may result in electrical
shock to the user or damage to the instrument.
Please be aware that any inductive voltage (L M) applied, is transformed to any other
winding on the transformer according to the turns ratio. For high ratios, high voltages can
appear on the DUT!
Never open the current path of the measuring circuit while the current flowing is higher
than 5mA warning LED is on! The current flowing in the magnetizing inductance (LM >>
1H) of the transformer can generate high voltages and electrical flashes. High risk of
electrical shock!
Safety 17
To avoid damaging the device due to induced overvoltage’s or wrong connections, the Interlock
input of the 2293 has to be connected to the safety circuit only by using a relay contact trough
short screened cables.
Opening the Interlock doesn’t mean a safe situation by itself, as the test object
(transformer) has been charged while measuring and stored energy has to be removed.
Once Interlock is opened the instrument will start the discharging of the test and special
caution has to be taken not to go into the test area until the red LEDS (14) are off.
2.4 Summary
Note: Many accidents that happen around high voltage equipment involve personnel who are
familiar, and perhaps too familiar, with high voltage equipment. Staying alert and ever watchful
requires constant training and awareness of the inherent hazards. The greatest hazard is the
18 Safety
possibility of getting on a live circuit. To avoid this requires constant vigilance - for oneself and for
one's fellow workers.
In addition to the obvious dangers, personnel should be alert to recognize subtle dangers as well.
For example, during transformer excitation-current tests, the floating terminals may have
significant voltages induced in them by simple transformer action. Therefore, all terminals of a
device under test, unless grounded, should be considered to be live while the test is in
progress.
When potential transformers or any transformers are interconnected, voltage can be back-fed
through the secondary windings to produce high voltage on the primary although the primary is
seemingly isolated from the power system. This entail a second important rule - all terminals of
a device under test should be completely isolated.
Safety 19
3 Theory
DUT
Instrument
+ R1 R2
ideal
U
- LM
I N1 : N2
20 Theory
3.2 Power Supply Modes
The 3 programmable power supplies in the 2293 can operate in different configurations. These
configurations will be explained in this chapter.
3.2.1 Parallel Mode on HV-side 16A ¦ 100V (A1) or 32A ¦ 50V (A2)
This supply mode is selected, when a phase on the high voltage side of the transformer has to
be measured without the corresponding phase on the low voltage side. The three supplies are
connected in parallel and the range is selected according to the desired measuring current as
follows:
I ≤ 16.0A 16A ¦ 100V
I > 16.0A 32A ¦ 50V
A a
U1
I1 N n
32A / 50V
or
16A / 100V
C B c b
The following diagram shows the operating area for the power supply in mode A1 and B1 - 16A ¦
100V:
Theory 21
Current
32A
Active Load Supply
Region Region
24A (Discharging) (Charging)
800W
16A
400W
8A
4A
Voltage
-100V
-50V
+25V
+75V
-75V
-25V
+50V
+100V
0V
The following diagram shows the operating area for power supply in mode A2 and B2 - 32A ¦
50V:
Current
32A
Active Load
800W
Region
24A (Discharging)
Supply
Region
16A (Charging)
400W
8A
4A
Voltage
-100V
-25V
+25V
+75V
-75V
-50V
+50V
+100V
-12.5V
0V
3.2.2 Parallel Mode on LV-side 16A ¦ 100V (B1) or 32A ¦ 50V (B2)
This supply mode is selected, when a phase on the low voltage side of the transformer has to be
measured without the corresponding phase on the high voltage side. The three supplies are
connected in parallel and the range is selected according to the desired measuring current as
follows:
I ≤ 16.0A 16A ¦ 100V
I > 16.0A 32A ¦ 50V
22 Theory
I2
A a
U1 U2
N n
32A / 50V
or
16A / 100V
C B c b
It is possible that the overvoltage protection of the device triggers on transformers with a
high turns ratio. In this case the user must disconnect the cables from the high voltage
terminals of the DUT to perform a measurement in this mode (B1 or B2).
Theory 23
3.2.3 Individual Mode 2x 16A ¦ 50V (C)
This supply mode is selected, when two the corresponding phases of the high and low voltage
side of the transformer have to be measured. The three power supplies are split to the HV and LV
side. The measuring current must be selected as follows:
I1 ≤ 16.0A
I2 ≤ 16.0A
B C b I2
16A / 50V
16A / 50V
N U2 c
U1
A
I1 a
The following diagram shows the operating area for each power supply in mode C – 2x 16A ¦
50V:
Current
32A
Active Load Supply
Region Region
24A (Discharging) (Charging)
400W
16A
200W
8A
4A
Voltage
2A
-100V
-50V
+25V
+75V
-75V
-25V
+50V
+100V
-12.5V
0V
24 Theory
Theory 25
3.2.4 YNdx Mode 2x 16A ¦ 50V (D)
This supply mode is selected, when two the corresponding phases of the high and low voltage
side of an YNdx (x = 1, 3, 5, 7, 9, 11) transformer have to be measured. This mode is on
applicable to YNd transformers. It is intended to ideally magnetize and saturate the core, to
achieve a faster current balancing in the delta winding. The three power supplies are split to the
HV and LV side. The measuring current must be selected as follows:
I1 ≤ 16.0A
I2 ≤ 16.0A
I1
B C b I2
2
I1
2
16A / 50V
8A / 50V
8A / 50V
N U2 c
U1
A
I1 a
The operating area for the power supplies is the same as in mode C.
26 Theory
3.3 Measuring sequences
This section describes how the device selects the measuring mode depending on the user
settings done in the user software. The coloring of the drawings is equivalent to the user software:
- Violet Phase to be measured
- Red Phase currently measuring
- Blue Phase already measured
- Grey Nothing measured nor to be measured
General Rules
1. If the measuring current selected on any winding is greater than 16.0A, a single winding
measurement will be performed for each winding and phase Mode A2, B2.
2. Mode C is used only when the two corresponding phases on HV and LV are selected to
be measured and the current is less or equal 16.0A.
3. Mode D is used only when the two corresponding phases on HV and LV are selected to
be measured, the DUT is an YNd transformer and the current is less or equal 16.0A. YNd
measuring mode must be set to “without Rn (Ph-Ph)”:
The following examples show the measuring sequence generated by the 2293 depending on the
measurement settings. For simplicity an YNyn0 transformer was chosen as DUT in most
examples.
3.3.1 Example 1
Settings:
A a
16A 16A
YNyn0 N n
C B c b
Sequence:
C
16A 16A
50V 50V
Theory 27
3.3.2 Example 2
Settings:
A a
16A 17A
YNyn0 N n
C B c b
Sequence:
A1 B2
16A 17A
100V 50V
Example 3
Settings:
A a
5A 5A
YNyn0 N n
C B c b
Sequence:
A1 B1
5A 5A
100V 100V
3.3.3 Example 4
Settings:
A a
16A 16A
YNyn0 N n
C B c b
28 Theory
Sequence:
C C C
16A 16A 16A 16A 16A 16A
50V 50V 50V 50V 50V 50V
3.3.4 Example 5
Settings:
A
a
16A 16A
YNd11 N
c b
C B
Sequence:
D or C A1 B1
16A 16A 16A 16A
50V 50V 100V 100V
Theory 29
4 Front Panel
1 Connector for LV cable “X” connection, Black (to Low voltage side of DUT)
2 Connector for HV cable “H” connection, Red (to High voltage side of DUT)
3 I/O connector (for cascading of additional temperature interfaces)
4 Tap Changer connector (for optional Tap Changer Remote interface TAP/2293 )
5 6 Temperature probes connectors
6 Power inlet with integrated mains switch and fuse holder
7 Printer
8 Touch screen display
9 USB (Host)
10 USB (Device)
11 Ethernet (LAN)
12 Emergency Stop button with (optional) interlock connector
13 Cooling air outlet / inlet
14 Caution indication. The two red LEDs on top are lit to indicate a current is flowing.
30 Front Panel
The third green LED on the bottom indicates a safe state.
15 Additional PE (Protective Earth) connector. (Parallel to the PE pin of the power inlet
connector) Can be used when power inlet cable is not connected to Earth.
Front Panel 31
5 Connection and Setup
Neutral N (blue)
Adaptors:
Colour code has been defined in the cables and must be followed to guarantee the
proper device connection. Red is used for the connections to the DUT’s High
Voltage side “H”, Black is used for the connections to the DUT’s Low voltage side
“L”.
During a 32A test the cables are operating at their maximum specification and it’s
normal operation that they get warm.
Before attempting to connect to the test object make sure that it is fully
disconnected and de-energized.
Make sure that you don’t shortcut the specially designed 4-wire measurement Kelvin clamp. Only
use the designated teeth in the front of the clamp.
For a normal transformer, connection is done following the labels in the cable; means connecting
transformer phases with corresponding labeled cables as shown in the bellow diagram.
If only one side of a transformer has to be measured it’s possible to connect only
that side.
For a normal transformer, connection is done following the labels in the cable; means connecting
transformer phases with corresponding labeled cables as shown in the bellow diagram.
To connect the device to a test object different from a transformer, connections must be done as
following.
1 Resistance
Terminal A positive of the high current power supply
Terminal N negative of the high current power supply
Terminal B positive of the voltage measurement
Terminal C negative of the voltage measurement
Instrument is equipped with two voltage measuring channels, therefore two resistances can be
measured simultaneously, connect the equipment according bellow table to measure both
resistances.
2 Resistances
Terminal A positive of the high current power supply
Terminal N negative of the high current power supply
Please note that the USB Type A Standard specifies a maximum of 1500 mating cycles. 10
mating cycles per day would easily lead to connector degradation within 1 Year.
6.1 Startup
To start the device, turn on the main switch and wait until the warning screen arises. Booting can
take some seconds.
Read carefully the warning messages and click OK when understood. Read also carefully the
safety warnings at the beginning of this manual before operating the instrument.
40 User Interface
6.2 Structure
The device is equipped with an intuitive interface, and all parameters are selected through its
touch screen.
Use the finger or a non sharp object to operate the touch screen.
Using sharp or metallic pointers can damage the screen!
Def Test
ine Na
DU me
T &
(To Cloc
p k
Applic
Bar ations
)Active (Side
Windo
w Bar)
Func
tion
Key
(Bott
om
Bar)
DUT Definition:
HV winding configuration
LV winding configuration
Phase displacement HV / LV
TV winding configuration
User Interface 41
Phase displacement HV / TV
Selection of the HV winding Selection of the LV winding Selection of the phase shift
The tertiary winding, when existing, can also be configured by touching the corresponding icon
Examples
42 User Interface
Example for a setup of a single phase transformer with no phase shift
The selected transformer is then shown on a graphical mode in the main screen. In case tertiary
winding has been selected two arrows in the right side will indicate that a tertiary winding has
been configured. By clicking in the arrows either the low voltage winding or the tertiary winding
actual configuration appears in the screen. The other winding appears as a small grey icon in the
button right of the screen.
General information is necessary to identify the test and a proper reporting generation. Following
fields are available in the device software.
Type
Enter here the Serial number and Type of the device
under Test (DUT) and – if existing – also the Tap
Changer information.
This info is then also used to name the test files and
later on to easy classify measuring data.
User Interface 43
Specification
Here the definition about Nominal Voltages of
windings have to be entered (used for desired value
of ratios and as limits)
Labels
Here the user can define the Terminals labelling
according to his country or standards.
These Labels then will be used in all displaying and
recording of measuring data.
Notes
Long text field where any information regarding the
DUT, test conditions, remarks, etc. can be added.
Above information is included in the measurement results file as well as in the printed report.
44 User Interface
6.3.3 Tap Changer configuration
In case the transformer is equipped with a tap changer, it can be easily configured in the device to
allow automation of the measuring procedure and complete test reports generation. The tap
changer configuration screen is accessed selecting the DUT configuration i button in the upper
DUT Top Bar, and selecting the specific folder.
Minimum tap
number
1 or 3 nominal taps
selection
For tapped transformers it is necessary to define each tap voltage. The button has to be
clicked and the following dialog will appear:
User Interface 45
Total number of
tap changer
Actu
positions
al tap
chan First position
ger number
confi
gurati Select if if when
Non more than 1
o nominal
m position, the
i numbers are
n consecutive
Select if the
a Number of intermediate
l nominal taps are
positions reachable and
p can be
o measured
s
i
t
i
o Enter each theoretical tap voltage in
n the voltage column.
46 User Interface
The bottom & top option will
automatically populate the voltage
values when apply is pressed. In this
example, the bottom tap is 11kV and
the top tap is 18kV. The apply button
calculates each tap voltage in
proportion to the number of taps.
Nominal Tap
Nominal tap is indicated by the symbol
“<<>>” beside the number, in case 3
nominal taps are selected, the other 2
nominal taps are marked with the symbol
“<>”. Selection of the nominal tap is done by
clicking beside the number.
Tap Naming
In case the tap changer positions are not
consecutive, or are not numbers, the new
character/characters to define each position can be
introduced manually by clicking in the “Name” cell of
the row that will be modified. The following example
shows a tap changer defined by letters instead
numbers.
User Interface 47
6.3.3.2 Tap changer configuration examples
Example 1
Example 2
The first line shows the name of actual test. Yellow colour means no file name
has been defined yet.
The second line shows the actual time.
The application bar (right side bar) allows the selection of the actual
measurement application (e.g. Resistance or Demagnetization).
The DUT settings in the top bar are valid for all applications. The bottom
function key changes depending on the selected application.
48 User Interface
6.5 Active Window
In the centre of the display graphical information and measuring status of the current application
is shown. The screen change depending of the operating mode or the application selected.
Automated mode main screen Classic mode main screen Demagnetization screen
Specialised keys for the single applications see single application chapters
User Interface 49
6.7 Device Information
The device information is accessible over Setup button in the bottom bar of each application.
Select the “Miscellaneous” folder. Here you will find the system info.
The device information is accessible over Setup button in the bottom bar of each
application.
Select the “Miscellaneous” folder. Here you will find the system info.
The device can print in the included printer, store in the internal memory and export measurement
results. All these operation are done in the file management popup menu
50 User Interface
Open a new test based in the actual data
It is possible to export All test saved in the device memory, or only the actual test. In addition
following options are available:
Select “All Files” if all tests stored in the device memory want to be
exported
Select “Actual File” if only the actual test wants to be exported.
User Interface 51
Select if the device under test data (DUT) and the setup data want to be
exported to the memory stick
52 User Interface
6.8.4 Webserver access / Ethernet interface
To access the files that have been written to the internal webserver storage, a network connection
between the device and your office computer must be established. Please refer to the “Remote
Control” section of this manual for further help.
You can find the IP address configuration of your device in the “Setup” – “Miscellaneous” dialog:
Please make sure that these settings are compatible with the settings on your office computer. As
an example in this case, the IP address of your office computer could be configured to
192.168.1.50. Then you can access the WebServer on the WA2293 using your Internet Browser
(e.g. “Internet Explorer” or “Mozilla” or “Chrome”). Simply type the IP address of the WA2293 into
the address line:
You can download your saved report files by clicking on the file in the browser.
User Interface 53
7 Resistance Measurement
During resistance measurement the device can be used in two operating modes: the “classic
mode” and the “automated mode”.
Automated mode is used for measuring resistance on power transformer, as the unit is equipped
with an internal relay matrix that perform the test in all phases of a three phase transformer
without any reconnection.
Classic mode is used for measuring resistances or any test object different from a transformer.
7.2.1 General
On automated mode, the unit will perform all necessary steps to measure all resistances on a
transformer automatically.
54 Resistance Measurement
Automatic mode selection is selected in
the measurement folder, clicking
Resistance Measurement 55
7.2.2 Function keys during resistance in automated mode
While in automated resistance measurement mode, following actions are available in the button
key. The buttons are case sensitive, i.e. they change according to the actual status.
56 Resistance Measurement
Status bar (actual
procedure step, Temp
timer, etc) eratu
Safe re
State Statu
indicator s with
SC
Selected current
with SC
Active
windings to
measure
with SC
Before operating the instrument, make sure that the safety rules have been fully
read and understood. It is the responsibility of the end user to ensure that the
system is operated in a safe manner.
Resistance Measurement 57
DUT general data
Configuration of the
Selection of the automatic
corresponding DUT temperature
main parameters correction
Selection of the
desired test current
Configuration of the
tap changer (when
existing)
Auto recording
selection
Winding material
selection
Measuring
Exporting and
printing results
Selection of measuring currents above the transformer nominal current can end
in the transformer break down.
58 Resistance Measurement
The measuring current must be introduce
independent for each winding and is done in
the “measurement” folder clicking over the
Setup button in the function key bar.
It is recommend to use 16A maximum. This way two windings of the transformer can be
measured simultaneously, which speeds up the measurement process a lot!
Generally the resistance of the transformer winding to be measured is a good indicator for the
required measurement current:
Resistance Measurement 59
If the transformer is equipped with tap changer and it has been configured in the device, the tap
changer measuring sequence should be defined. Different options are available in the Tap
Control folder, selecting the setup in the main menu.
60 Resistance Measurement
Value is stable and therefore recorded when a change of 0.0003% per second,
or 0.003% per 10 seconds or 0.03% per 100 seconds is achieved.
Value is stable and therefore recorded when a change of 0.003% per second,
or 0.03% per 10 seconds or 0.3% per 100 seconds is achieved.
User can manually introduce any stabilization parameter, the value introduced
is the slope of the change, and is defined as value (in percentage) per second
Sequence:
Select which taps have to be measured
(single extremes, all)
Operation:
Define if the tap changer is operated
manually (the unit gives a message to
change and waits for confirmation) or
automated together with the “Remote Tap
Switch” cable.
Set as timeout the time which is maximum
needed to change the tap (used if no
feedback signal is available from the tap
changer)
Type:
Off Load the unit will be discharged
before changing a tap
On Load The unit stays charged while
tap changing.
Example: When “All Taps” and “On Load” is selected the sequence is as follows:
First phase – test all taps – next phase etc., tap changing in charged state and the
measurements on multiple windings are performed sequential.
Resistance Measurement 61
See also chapter “Tap Changer Interface” for more details and connection advice.
Reference temperature
selection
7.3.9 Measurement
Performing a measurement on a transformer is quite simple. Once all transformer and options
have been introduced; just click the start button. The instrument will perform all operations
automatically.
During the measuring and while in graphical mode the parts of the circuit being measured will
become red and the actual measured value will be shown bellow the label.
62 Resistance Measurement
Before starting the test, a screen showing the tap position
that will be measured arises. Tap changer must be
positioned in this position. Measurement sequence depends
on the tap changer configuration menu.
Measurement results
Click start button to initiate the Automatic measurement running Measurement results
test
If auto recording is active, instrument will record the value and stop the measurement when the
stabilization condition has been reached.
Windings to be measured are selected by clicking on them. Purple color means that this winding
will be measured; blue color means that this winding will not be measured. If a previous
measurement on this winding and tap position has been done, results are shown in blue, but
measurements can be repeated.
Resistance Measurement 63
All phases will be measured Only HV side will be measured Only phase AC in the HV
winding will be measured
Measurements will be automatically saved after each test. Data storage options can be selected
in the Data folder, clicking in the setup button of the function key bar.
64 Resistance Measurement
7.4 Classic mode
7.4.1 Generalities
On classic mode, the unit work as a standard low resistance measuring bridge using the Kelvin
method. The unit includes one current power supply and 2 voltage measuring channels (for
measuring up to 2 resistances simultaneously), This mode can be used for measuring test objects
different from transformers, as well as for calibration purposes.
Classic mode is available by selecting this mode in the
measurement folder, clicking setup in the function key
bar.
Selection between 1, 2 or 3 resistances can also be done in the main screen by clicking on
the drawing.
Func
tion
Key
(Bott
om
The function key bar is adapted to this measurement method. The buttons are case sensitive, i.e.
Bar)
they change according to the actual status.
Start the measurement or Record the actual value (only available during
measurement)
Stop the measurement
Resistance Measurement 65
Open data handling functions
Test object status. Be advised that the external red lamp is the safety
master (14 in the front panel description). The test object can not be
touched or disconnected only when this lamp is still on.
For the correct cable connection in classic mode see also in chapter
“5.2.5 Connection in Classic Mode”
66 Resistance Measurement
7.5 Performing a test using Classic mode
Before operating the instrument, make sure that the safety rules have been fully
read and understood. It is the responsibility of the end user to ensure that the
system is operated in a safe manner.
Selection of the
Selection of the desired test current
corresponding DUT
main parameters
Auto recording
selection
Material selection
Measuring
Configuration of the
automatic
temperature
correction Exporting and
printing results
Resistance Measurement 67
Select the winding material
Reference temperature
selection
If temperature correction is active, then the main screen will show the actual temperature and the
reference temperature.
68 Resistance Measurement
7.5.5 Auto recoding configuration
Measurement can be done in auto stop mode
(value is automatically recorded when stable)
or in manual mode (unit stays measuring until
the operator click the stop button), selection
between both operations modes is done in the
setup screen, Data folder.
Value is stable and therefore recorded when a change of 0.0003% per second,
or 0.003% per 10 seconds or 0.03% per 100 seconds is achieved.
Value is stable and therefore recorded when a change of 0.003% per second,
or 0.03% per 10 seconds or 0.3% per 100 seconds is achieved.
User can manually introduce any stabilization parameter, the value introduced
is the slope of the change, and is defined as value (in percentage) per second
7.5.6 Measurement
Measurement starts just after clicking the start button in the main screen. During the measuring
and while in graphical mode the measured value will become red and the actual measured value
will be shown bellow the label
Resistance Measurement 69
Charging
Resistance
measurement
Discharging
Measurement
results
If auto recording is active, instrument will record the value and stop the measurement when the
stabilization condition has been reached. Otherwise the stop button has to be pushed to stop the
test. Values can be recorded manually using the record button.
Measurements will be automatically saved after each test. Data storage options can be selected
in the Data folder, clicking in the setup button of the function key bar.
70 Resistance Measurement
Results can also be shown as a table list, selecting
the list button in the function key bar.
Resistance Measurement 71
7.6 Temperature Measurement
If temperature correction is active, then the main screen will show the
actual temperature and the reference temperature.
72 Resistance Measurement
Actual reading of the six temperature channels. To be added to the
medium temperature they should be selected. A description (text) can be
added to every temperature channel.
By clicking on a sensor line in this list you enter the temperature probe
definition dialog:
Select the position where the sensor is mounted on the DUT by clicking.
On the “Temp:” column of the specific probe.
In resistance measurement only the simple average temperature of the
activated sensors is taken. In the heat run measurements, the standard
based calculations are implemented with respect to specific probe
positions. (see related heat run chapters)
Here an additional text for the sensor can be added (e.g. when an
external sensor is used on a cooler fan)
The Text input field can also be accessed directly by clicking in the
specific “Description” column in the parent dialogue.
With these arrows you can toggle trough the single probes definitions
Resistance Measurement 73
8 Demagnetization
8.1 Theory
After disconnecting a transformer from the grid or performing a winding resistance measurement
with direct current, the transformer core will be magnetized. The following figure shows a
transformer core hysteresis curve with a possible magnetization M0. M0 can be anywhere on the
y-axis within the hysteresis loop.
B=μ·(H+M)
+ΦR
ΔΦCheck+
M0
H=N·I
-IDemag
MDemag +IDemag
ΔΦCheck-
-ΦR
The magnetization M0 can influence various measurements like turns ratio or frequency
-1
response. For these measurements the magnetization should be M0 ≈ 0 Am , otherwise the
results can be wrong or not comparable. Further, connecting a magnetized transformer to the grid
can cause high inrush currents.
The common method to demagnetize a transformer core is to apply nominal AC voltage to the
transformer and slowly decrease its amplitude to zero. But this method requires a very large and
not portable controllable AC voltage source.
With the 2293 demagnetization function, the hysteresis loop of the transformer is calculated using
a special algorithm, later using an iterative procedure running in several cycles the
demagnetization status is reached
74 Demagnetization
8.2 User interface
The demagnetization procedure is done automatically. Few parameters have to be selected
before proceeding to demagnetize the transformer. Parameters selection and function are
accessible in the demagnetization function.
To access to this application, select
demagnetize function in the applications bar
(side bar)
While in demagnetization application, following actions are available in the button key bar. The
buttons are case sensitive, i.e. they change according to the actual status.
Demagnetization 75
Change display to graphic mode
Demagnetizing
Before operating the instrument, make sure that the safety rules have been fully
read and understood. It is the responsibility of the end user to ensure that the
system is operated in a safe manner.
76 Demagnetization
Injection Phase and Winding
Selection of winding and phases to be used for the demagnetization.
It is recommended to use the high voltage side and the center limb of the
transformer.
If the Rel.Res.Flux is set to 5% (e.g. 30Wb x 5% = 1500mWb), the unit does usually stops
based on that higher value. Instead at its technical limit (Abs.Res.Flux) of 20mWb.
Demagnetization 77
8.3.3 Demagnetizing
Click the start button and the instrument will perform the demagnetization.
Repeating the demagnetization function more than once does theoretically not result in a
much better demagnetization of the transformer because the procedure starts with a
maximal magnetisation to get a defined initial condition of the core.
Please verify that the measured "Winding Resistance" "R" matches the real winding
resistance with good accuracy (e.g. 1%-2%). Otherwise the demagnetization will eventually
not be performed reliable.
78 Demagnetization
9 Heat Run – Cooling Curve
9.1 Theory
The purpose of this test is to establish the top oil temperature rise in steady-state condition with
dissipation of total losses and to establish the average winding temperature rise at rated current
and with the top oil temperature rise specified before.
This target is achieved in two main steps:
First the top oil and average oil temperature rises are established when the transformer is
subjected to a test voltage such that the measured active power is equal to the total losses of the
transformer. The oil temperature and the cooling medium temperature are monitored, and the test
is continued until a steady-state oil temperature is reached. When the top oil temperature has
been established, the test shall immediately continue with the test current reduced to the rated
current for the connected winding. This condition is maintained for a certain time (normally 1h).
Following the first part of the procedure (heating), resistance has to be measured after a quick
disconnection of the power supply. The values of average temperature of the two windings are
determined from the resistances change along the time, known as cooling curve.
While in heat run application, following actions are available in the button key bar. The buttons
are case sensitive, i.e. they change according to the actual status.
Start the timer after disconnecting the power supply (zero time).
Has to be started when the Rated current Supply is switched OFF
Start the resistance measurement when the connection cables are mounted.
When started this button becomes the “Break” function
Measuring Parameters
Measuring values definition
recording interval
Measuring
Before operating the instrument, make sure that the safety rules have been fully
read and understood. It is the responsibility of the end user to ensure that the
system is operated in a safe manner.
Selection of measuring currents above the transformer nominal current can end in the
transformer break down.
A shortcut for current selection is available in the main screen; clicking in the
current by winding drawing.
With these arrows you can toggle trough the single probes
definitions without closing this dialog window.
The temperature settings are common for the Temperature Rise and Cooling Curve functions
Measurement consist on two steps, initiate the timer when the power supply is disconnected, and
then, after connecting the instrument by clicking the start button.
Start the timer when power supply When instrument connected, click All measurement points recorded,
is disconnected by clicking Start Start Meas, a reading is stored measurement finalized, last
Timer, timer starts to count. every defined time interval. measurement value is shown.
Stops the resistance measurement but NOT the timer (with “Start Meas” the
measurement can be reactivated)
Measurement consist on two steps, initiate the timer when the power supply is disconnected, and
then, after connecting the instrument by clicking the start button.
Start the timer when power supply When instrument is connected, Auxiliary measurements of the
is disconnected by clicking Start click Start Meas. Auxiliary selected second phase are
Timer, timer starts to count. measurements of the selected recorded every second.
phase are recorded every
second.
Auxiliary measurements of the The main measurement. A All measurement points recorded,
selected third phase are recorded reading is stored every defined measurement finalized, last
every second. time interval. measurement value is shown.
To see the measured results, select the List in the function key bar.
Measured results are shown in a table mode
by selecting the list button.
10.1 Overview
The 2293 is equipped with an optional temperature rise function. This optional feature is enabled
using the license manager. This process only needs to be completed the first time temperature
rise is used.
See chapter “Heat Run Cooling Curve” for a description of the theory of this test. Temperature
rise performs the total loss injection and rated current injection phase of the heat run test before
switching to the cooling curve function to perform the final phase of the heat run test.
Measuring parameters
definition
Continue test
Measuring
Measuring
The temperature settings are common for the Temperature Rise and Cooling Curve functions
Click Start for temperature A warning message is displayed The latest readings are shown on
recording to begin when total loss as a reminder that temperature the screen and the graph shows
injection is applied. rise and cooling curve must be all the measurements from when
setup before clicking Continue the test was started.
When the temperature rise When the temperature rise has Apply the rated current injection
reaches the setup value the been maintained for the required and then click Continue to start
status changes to green and the time, the total loss injection is phase 2 of the test.
phase 1 timer starts to complete. Click OK to start the
countdown. If the setup value is next phase of the test.
exceeded, the countdown will
reset
Measurement consists of only two steps. Firstly start the test when HV is applied to the
transformer. Second continue to the cooling curve application before the HV supply is switched
off.
Click Start for temperature A warning message is displayed The latest readings are shown on
recording to begin when HV as a reminder that temperature the screen and the graph shows
injection is applied. rise and cooling curve must be all the measurements from when
setup before clicking Continue the test was started.
When the winding/core When the temperature rise has Click Continue to switch
temperature rise reaches the been maintained for the required automatically from Temperature
setup value the status changes to time, the test is complete. Click Rise to Cooling Curve application.
green and the step 1 timer starts OK
to countdown. If the setup value is
exceeded, the countdown will
reset
11.1 Overview
The unit can perform automatic detection of the transformer winding configuration and the phase
displacement. Typically this is used to check the winding connections of a known transformer type
or to find out the configuration of an unknown type.
To access to this feature, the equipment must be equipped with the Turns ratio option, see
chapter 12Turns Ratio Measurement
The function energises and measures the transformer using various different connections and
shorting to determine the phase displacement. Further energisation and measurements are
performed to determine whether there is a neutral connection on either the primary or secondary
winding. Finally the likely transformer configurations are presented in the results grid. Less likely
zig-zag configurations are also shown in a different color.
he function includes a user selectable threshold to control how close the reported phase angle
must be to a perfect clock number phase shift. This allows differentiation of arbitrary phase shift
transformers from standard phase shifts.
Transformer configuration 97
Detection
Select the Miscellaneous folder and then
press the License Manager button.
98 Transformer configuration
Detection
You may need to press the up/down arrow buttons to view
the detection button depending on which other functions
are enabled.
Trial licenses for detection are available
which permit a limited number of tests to be
performed. The remaining number of tests is
displayed on the license screen.
Removing the trial license key will remove
the detection function from the application
bar.
Transformer configuration 99
Detection
11.2.1 Active Window
The detection function main screen components are described below.
Parameters
definition
Detection
Export and
printing results
Before operating the instrument, make sure that the safety rules have been fully
read and understood. It is the responsibility of the end user to ensure that the
system is operated in a safe manner.
11.3.3 Detection
Voltage applied and detection Phase angle measurements are Neutral measurements are
measurements are running. The completed. The grid shows a completed. The grid shows the
grid shows all transformer reduced set of possible likely transformer configuration in
configurations are possible. transformer configurations and green and less likely
phase displacement of 1. configurations in yellow.
12.1 Overview
The unit can perform ratio measurements on all types of objects, but has been specially designed
to measure ratios on highly inductive objects (as for example transformer’s windings, generators
windings, etc).
This optional feature is enabled using the license manager. This process only needs to be
completed the first time magnetic balance is used. For instruction how to enable a feature please
read Chapter 16 Optional Features activation.
12.2 Theory
12.2.1 Definitions
The term “Turns Ratio” (TR) is defined as the theoretical voltage ratio, the term “Voltage Ratio”
(VR) as the ratio of the rated voltages (“boilerplate voltages”).
As a rule, the voltage ratio of three-phase transformers can be measured using a single-phase
supply, as long as the distribution of magnetic flux in the core is taken into consideration. Only
windings, winding segments and winding combinations which have the same magnetic flux
applied, can be compared with one another. The measuring circuit can be derived from the
phasor diagram of the test transformer's vector group. The two voltages which are to be
compared must be in phase and have the same orientation.
But –depending on the winding configuration and phase rotation of the transformer - it’s not
possible to have always phase voltages which are being compared. The WA22293 therefore
internally corrects the measurement with the “TR/(VA/Va)” factor and displays automatically the
correct ratio value.
The TR/(VA/Va) factor determines how the turns ratio is calculated from the ratio of the
energizing voltage to the output voltage of the winding. The ratio of the measured voltages
are multiplied by this factor to give the turns ratio for that winding/tap.
VR H1-H2H3 X1-X2
2/√3 √3/2
• No H2-H3H1 X2-X3
1.15470 0.86603
TR:VR H3-H1H2 X3-X1
H1-H0 X1-X0
1 1 Directly
N N Yes H2-H0 X2-X0
1.00000 1.00000 measured
H3-H0 X3-X0
H1-H0 X1-X2
√3 1/√3 Directly
N Yes H2-H0 X2-X3
1.73205 0.57735 measured
H3-H0 X3-X1
VR H1-H2H3 X1-X2
2/√3 √3/2
N • No H2-H3H1 X2-X3
1.15470 0.86603
TR:VR H3-H1H2 X3-X1
H1-H2 X0-X2
1/√3 √3 Directly
N Yes H2-H3 X0-X3
0.57735 1.73205 measured
H3-H1 X0-X1
H1-H2 X1-X2
1 1 Directly
Yes H2-H3 X2-X3
1.00000 1.00000 measured
H3-H1 X3-X1
VR H1-H2H3 X1-X2
1 3/2
• No H2-H3H1 X2-X3
1.00000 1.50000
TR:VR H3-H1H2 X3-X1
VR H1-H2H3 X1-X2
2/√3 2/√3
• No H2-H3H1 X2-X3
1.15470 1.15470
TR:VR H3-H1H2 X3-X1
VR H1-H2H3 X1-X2
N 2/√3 2/√3
• No H2-H3H1 X2-X3
1.15470 1.15470
TR:VR H3-H1H2 X3-X1
VR H1-H2H3 X1-X2
1 2/3
• No H2-H3H1 X2-X3
1.00000 0.66666
TR:VR H3-H1H2 X3-X1
VR H1-H2H3 X1-X2
1 1
• No H2-H3H1 X2-X3
1.00000 1.00000
TR:VR H3-H1H2 X3-X1
You may need to press the up/down arrow buttons to view the
turns ratio button depending on which other functions are enabled.
Configuration of
Selection of the displayed results
corresponding DUT main
parameters
Selection of the desired
Configuration of the tap test voltage
changer (when existing)
Measuring mode
selection
Configuration of the
nominal and tap
voltages Measuring
Before operating the instrument, make sure that the safety rules have been fully
read and understood. It is the responsibility of the end user to ensure that the
system is operated in a safe manner.
Care has to be taken to ensure that the current transformer is connected correctly
otherwise there is a risk of damage to the CT and Instrument. There is also the risk of
injury.
When testing CT’s, care has to be taken to ensure that the energization voltage does not
cause saturation of the transformer core. It is recommended that the test voltage is limited
to 5 VAC unless it is certain that the CT can tolerate a higher voltage.
If the CT saturates at 5VAC try using lower voltages. This is a problem that is more likely to
be encountered with smaller transformers with a ratio of 20:1 or less, or with small cores
such as “wedding ring” CTs..
CTs are measured by energizing the secondary and measuring on the primary. connect the
system as follows:
8. Connecting to a CT
For core type current transformers, the “H” connections should be made to the secondary (Low
current side) and the “X” connections made to the primary (High current side). The transformer
can then be tested using single phase.
If the transformer is equipped with a tapped secondary, it is also possible to test the secondary by
connecting it as an autotransformer to evaluate the relationship between the individual taps.
Printout:
Phase Display:
Compensated mode (High accuracy): This is an advanced method for determining the
Transformer Turns Ratio. It increases the accuracy of Turns Ratio measurements of Power and
Distribution Transformers where the actual Turns Ratio matches the No-Load Voltage Ratio. This
method performs multiple Classic Ratio Measurements per Phase. Using the results of these
measurements the components of a transformer equivalent circuit can be calculated. The
purpose of this equivalent circuit is to compensate non-linear effects affecting Ratio Measurement
accuracy at lower test voltages. In the manner described the turns ratio (N1:N2) can be calculated
more accurate compared to the classic method, because the voltage ratio is physically a slight
non-linear function of the excitation voltage.
(This is not an appropriate method for measuring PTs, because they have a Turns Ratio which
differs from their No-Load Voltage Ratio to compensate for their losses).
Classic Mode:
on main screen
12.4.9 Measuring
Performing a measurement on a transformer is quite simple. Once all transformer and options have been
introduced; just click the start button. The instrument will perform all operations automatically.
Discharging the
transformer
Measurement results
Click start button to initiate the Automatic measurement running Measurement results
test
If auto recording is active, instrument will record the value and stop the measurement when the
stabilization condition has been reached.
The white box shows the measured turns ratio and the
turns ratio deviation between the measured result and
the theoretical value.
the symbol.
Measurements will be automatically saved after each test. Data storage options can be selected
in the Data folder, clicking in the setup button of the function key bar.
12.7.1 Setup
To access the arbitrary phase
feature, select turns ratio function
in the applications bar (side bar).
Set the DUT winding types. Select in the phase displacement drop down list the closest clock
number and also activate there the “Arbitrary” button in the lowest position.
The arbitrary measuring mode is activated now. This is stated in the DUT phase displacement
info as clock number.x° (e.g. 7.x°)
See the chapter Turns Ratio Measurement User Interface for information about the function keys.
DUT and test setup is similar to making a turns ratio measurement and so the chapters Turns
Ratio Measurement Setup DUT Data and Data Handling Definitions give details of this.
12.7.4 Measuring
13.1 Overview
The unit can perform magnetic balance measurements on transformers. This particularly useful
for checking the balance after a DC test current has been applied to the transformer during a
resistance measurement which may have caused the core to become magnetized.
This optional feature is enabled using the license manager. This process only needs to be
completed the first time magnetic balance is used. For instruction how to enable a feature please
read Chapter 16 Optional Features activation.
13.2 Theory
The Magnetic Balance test is conducted on Transformers to identify inter-turn faults, magnetic
imbalance or the flux distribution.
It can be conducted either in HV side or LV side of the transformer.
On the HV side, a voltage is applied across 2 phases (say 1U and 1V) and the voltage across the
other phases is measured (between U-W and V-W). The test is repeated for each of the three
phases.
Result: The sum of the two measured voltages will be equal to the applied voltage.
1U1V = 1U1W + 1V1W
The voltages obtained in the secondary will also be proportional to the voltages above.
This indicates that the transformer is magnetically balanced. If there is any inter-turn short circuit
that may result in the sum of the two voltages not being equal to the applied voltage.
You may need to press the up/down arrow buttons to view the
magnetic balance button depending on which other functions are
enabled.
Configuration of
Selection of the displayed results
corresponding DUT main
parameters
Selection of the desired
Configuration of the tap test voltage
changer (when existing)
Measuring mode
selection
Measuring
Before operating the instrument, make sure that the safety rules have been fully
read and understood. It is the responsibility of the end user to ensure that the
system is operated in a safe manner.
Recording:
on main screen
13.5.8 Measuring
Performing a measurement on a transformer is quite simple. Once all transformer and options
have been introduced; just click the start button. The instrument will perform all operations
automatically.
It is recommended to perform transformer demagnetization before measuring the magnetic
balance, as residual magnetism can influence the test results.
Click start button to initiate the Automatic measurement running Measurement results
test
If auto recording is active, instrument will record the value and stop the measurement when the
stabilization condition has been reached.
Measurements will be automatically saved after each test. Data storage options can be selected
in the Data folder, clicking in the setup button of the function key bar.
Magnetic Balance results are sensitive to Transformer Core Magnetization. To get reproducible
results, make sure to properly demagnetize the transformer core (directly) before performing a
magnetic balance test:
In a lot of cases, the built-in demagnetization function of the WA2293 will deliver good result.
In some cases, especially for larger power transformer (>50MVA), it can be necessary to use a
High Voltage AC power supply to properly demagnetize the transformer. Usually 110% of the
nominal winding voltage is necessary.
The following example shows an YNyn0 DryType Transformer in two cases:
The upper results show a proper measurement (green box) Balance is nearly 50%/50% on the
middle phase.
The lower results show a measurement with a magnetized transformer core (red box) Balance
is bad on the middle leg (26.3%/72.8%).
14.1 Overview
The unit can perform the short circuit impedance test of a transformer at reduced voltages, the
short circuit impedance in a transformer is quite linear with the voltage and therefore an
extrapolation to the nominal voltage can be perform for comparison.
This optional feature is enabled using the license manager. This process only needs to be
completed the first time magnetic balance is used. For instruction how to enable a feature please
read Chapter 16 Optional Features activation.
14.2 Theory
14.2.1 Definitions
The short-circuit impedance (Zshort-circuit) is defined as the impedance corresponding to the voltage
(Ucc) that must be connected to one pair of terminals of a transformer, with terminals of other side
shorted, which causes rated current (Irated) to flow on the two sides of the transformer.
HV LV
Irated
UCC
U cc
Z CC
I rated
For single phase transformers, the sort circuit impedance in % ( cc) can be easily calculated after
the Zcc has been measured according the formula
S
cc Z m 100
U2
Where:
1 S
cc ( Z m12 Z m13 Z m 23 ) 100
6 U2
Where:
Zm12 = Short circuit impedance phase a to b
Zm13 = Short circuit impedance phase a to c
Zm23 = Short circuit impedance phase b to c
You may need to press the up/down arrow buttons to view the
magnetic balance button depending on which other functions are
enabled.
14.4 Measurement
Before operating the instrument, make sure that the safety rules have been fully
read and understood. It is the responsibility of the end user to ensure that the
system is operated in a safe manner.
As the resistance is multiplied with the square of the ratio while measuring from the
other transformer side, it is critical to keep the short circuit connection resistance as
low as possible to avoid adding unnecessary error to the measuring circuit.
The instrument will supply the target voltage or current first reached. In order to guarantee
that a test is done at a particular voltage or current, fix the other parameter to the
maximum possible.
Storage:
Recording:
14.4.7 Miscellaneous
For information about the tap control window, refers to Chapter 6.7 Device Information
Click start button to initiate the Automatic measurement running Measurement results
test
If auto recording is set to Auto, once a phase is being measured, instrument will automatically
measure the other phases and shot the results.
Short circuit Imp () Single phase short circuit impedance calculation
After all phases are completed, then a calculation of the transformer overall values is done based
in the single phase measurements
Short circuit Imp () Calculated three phases short circuit impedance
15.1 Overview
The unit can perform optionally the Dynamic resistance measurement a transformer.
This optional feature is enabled using the license manager. This process only needs to be completed
the first time Dynamic Resistance (Tap changer) feature is used. For instruction how to enable a feature
please read Chapter 16 Optional Features activation.
15.2 Theory
A standard current curve while measuring dynamic resistance would show following shape.
tFall [mS]: Time from the staring of the tap changer movement (drop in current) until the
minimum current is reached
tRise [mS]: Time from minimum current reached until current becomes stable
Delta: Current drop from stabilization to the minimum while changing tap
You may need to press the up/down arrow buttons to view the
magnetic balance button depending on which other functions are
enabled.
Click “All ” button to change Click “List” to change Click “Single” Button to change
Y
e
Static resistance parameters
s
introduction Tap Changer -> Manual
Set tap position to required Tap
Y
e
See results on the screen s
Export or save results
Before operating the instrument, make sure that the safety rules have been fully
read and understood. It is the responsibility of the end user to ensure that the
system is operated in a safe manner.
Short circuit done externally (not recommended). In case last test done was Short circuit
impedance and short circuit is already available. It would avoid reconnecting the instrument.
To set up the steps with DUT related data: see related chapters in the “User Interface” part.
To access the measuring parameters, click setup button in the bottom of the screen, and then
select “Measurement” folder.
The test current and transformer connection
can be selected
15.4.8 Miscellaneous
For information about the tap control window, refers to Chapter 6.7 Device Information
15.4.9 Measuring
The measurement procedure will slightly differ if the remote tap changer accessory is available
and connected to the transformer or not.
As the tap changer test includes lot of tap changer operations, it is recommended to
acquire and connect this accessory
Performing a measurement on a transformer is quite simple. Once all transformer and options
have been introduced; just click the start button. The instrument will perform all operations and
indicate the operator the next step.
The direction of the tap change movement (move up or move down) is defined by the arrow in the
button right of the screen as following.
The following steps are performed while measuring the tap changer. Steps 3 to 5 will be repeated
for all taps selected in the settings. Step 6 is only necessary if the tap changer accessory is not
available.
Click start button to initiate the Instrument will then require the Instrument will charge and
test operator to drive the tap changer stabilize
to a starting position, normally
position one
If static resistance is selected, The instrument will be waiting for Only if tap changer accessory is
then it will be measured a tap changer, operator have to not connected !
change the transformer tap
position Operator change the tap
position, instrument record the
curve.
tFall [mS]: Time from the staring of the tap changer movement (drop in current) until the
minimum current is reached
For explanation about these parameters, see 15.2.2 Dynamic resistance test
The above parameters should be similar for all taps, deviations between one tap and the others
are an indication of tap changer problem.
See the chapter 6.8 Data Handling for information about exporting and printing results.
17.1 General
Tap changer interface allows the remote control of a motorized tap changer, as well as the remote control
of the 2293 when operator is placed in front of the tap changer and far away from the device.
The contacts have to be connected to the corresponding input signals located in the transformer control
box. No output voltage is supplied by the device, therefore the necessary power to move the tap changer
motor has be connected separately.
Once remote operation is selected, the instrument will try to change the position by closing the contacts up
and down, and will wait for the feedback signal to start the new measurement. Procedure is as following
Unit will measure one position and discharge the transformer
The corresponding signal up/down to increase/decrease a position will be sent to the tap changer trough
the tap changer adaptor.
The instrument will wait until the feedback signal come back or the time out expires (whichever happen
first), in addition the tap changer remote control is also equipped with a small switch that will send the
feedback signal to the device manually when pushed.
Steps one to three will be repeated for all positions to be measured.
In case the transformer is equipped with an on-load tap changer, a special operation mode is also available
by selecting the on load tap changer option. During this mode the unit will not discharge the transformer
after the measurement and will continue supplying current while the signal to change position to the tap
changer is sent.
If on load tap changer is selected, and the measuring circuit is interrupted by any reason,
overvoltage will appear in the tap changer contacts that can end in damaging this
component. The on-load operation mode has to be used carefully.
The 2293 unit supports 6 internal and max. 24 external PT100 Class A sensors.
Sensors for magnetic surface (a) or for liquids (b) are available. See also chapter “Accessories”.
(a)
(b)
By a wrong probe handling or a not proper probe setup or connection, large temperature
errors can be the result!
Apply pressure to the probe in order to properly contact the surface (spring is
loaded only on magnetic surfaces!
Isolate the temperature sensor from the ambient air in order to avoid unwanted
cooling or heating of the sensor. This is especially important if the temperature
difference between surface and ambient air is high (e.g. >10°C)
18.3 Operation
The additional connected probes in the list can now be set up as the standard ones connected on the front
panel. See related chapter.
174 Troubleshooting
19.1.6 Hardware Error
If the device detects a hardware problem, it will pop up this message. If this message persists, the device
should be completely rebooted. If this did not help, there is probably a hardware failure.
In case a newer version found on the USB stick, following dialog will be opened for confirmation
(xx.xx.xx: actual version number, yy.yy.yy: new version number found on the USB stick)
By clicking Yes, the updating will be started until all processes finished automatically.
Troubleshooting 175
19.3 Unit locks up and/or does not discharge
completely
The device features an emergency button to safely discharge the transformer in case of any
problem. This works independent of the software!
The user MUST always observe the red LEDs on the front panel (they work even if there is
no mains supply!)
The user MUST only disconnect the clamps, if there is NO red LED illuminated!
176 Troubleshooting
20 Printer Operation
Cable set for the High Voltage side (red clamps)”. Cables
are equipped with special Kelvin clamps.
Routed
Network
or
Internet
Address: 132.20.196.55
Subnet: 255.255.0.0
Gateway: 132.20.0.1
22.2 Protocol
The device accepts exactly 1 incoming TCP connection on port 50000 for remote controlling. When a
connection to a client has been established, the device will accept further connections, but it will
immediately close these connections. Commands must be sent as TCP data. The protocol stack looks as
follows:
Ethernet IP TCP [Command][?] [Parameter1],[Parameter2],…<CR><LF>
All characters (letters and symbols) must be sent as 1 Byte wide (8 Bit) ASCII characters. All instructions
are case insensitive, but the syntax of instructions and commands must strongly be met. Extra white
spaces (<SP>) must be avoided. Otherwise the instruction will be discarded upon reception of the next
termination sequence (<CR><LF>). The following control characters are used:
- Query: *IDN?
• GTL
Sets the device to local controlled mode. This function will unlock the local touch panel.
• REN
Sets the device to remote controlled mode. This function will lock the local touch panel.
The device
will only accept remote commands, if a REN command has been issued.
• Mode
- Query: Mode?
Local ¦ Remote
• RemoteToLocal
Transfers the remote device configuration to the local device configuration. This command
must
always be issued for any remote settings to become effective.
• Meas:App
- Query: Meas:App?
[App]
• Meas:Start
• Meas:Stop
• Meas:Continue
Continues any ongoing measurement which is waiting for user interaction in certain states
(e.g. manual
recording resistance measurement).
• Meas:State
- Query: Meas:State?
Standby ¦ Initializing ¦ Charging ¦ Measuring ¦
Discharging
¦ Reset ¦ Interlock ¦ OffsetNulling ¦ DemagAnalyzing ¦
DemagCycleInit
Returns any errors that have occurred during measuring. Errors are reset by the
Meas:Start
command.
- Query: Meas:Error?
PolarityReverse ¦ HVLVReverse ¦ OverVoltageProtection
¦
HardwareFail ¦ Interlock ¦ OverTemperature ¦
RemanenceTooSmall ¦ CurrentTooSmall ¦ CurrentTooHigh ¦
ACSupplyOffset ¦ UnknownError
• DUT:Set:Vectorgroup
Sets and returns the winding configuration and phase shift of the DUT.
- Set: DUT:Set:Vectorgroup
[WindHV],[WindLV],[ClockLV],[WindTV],[ClockTV]
[Winding] = D ¦ Y ¦ YN ¦ Z ¦ ZN ¦ I ¦ -
[Clock] = 0 ¦ 1 ¦ 2 ¦ 3 ¦ 4 ¦ 5 ¦ 6 ¦ 7 ¦ 8 ¦ 9 ¦ 10 ¦ 11
- Query: DUT:Set:Vectorgroup?
[WindHV],[WindLV],[ClockLV],[WindTV],[ClockTV]
• DUT:Set:TempCoeff
Sets and returns the temperature coefficient for the three windings (HV, LV and TV). The
coefficient is
used for temperature correction of the winding resistance value.
- Query: DUT:Set:TempCoeff?
[Coeff]
• TC:Move
Sends and up or down impulse to the remote controlled tap changer which is connected
to the 2293
tap changer interface.
Resets or returns the state of the tap changer feedback signal. This signal indicates
wheter the
button on the tap changer interface handheld has been pressed or the connected tap
changer signaled
ready.
- Query: TC:Feedback?
[FB] = 0 ¦ 1
• TC:ButtonLED
Controls the state of the LED of the Button on the tap changer interface handheld.
Returns the current temperature value measured by the temperature measuring channels
in xxx.xx°C.
-100.00 indicates that no sensor is connected.
- Query: Temp:Values?
[Temp1],[Temp2],[Temp3],[Temp4],[Temp5],[Temp6]
Temp:Values? [Channel]
[Temp[Channel]]
• Res:Set:Mode
- Query: Res:Set:Mode?
[Mode]
• Res:Set:YNMode
Sets and returns the method used for measuring YN connected windings (Phase-to-
Phase or
Phase-to-Neutral Supply).
- Query: Res:Set:YNMode?
[YNMode]
• Res:Set:ConnClassic
Sets and returns the connection method used in Classic Resistance Measurement mode
(separate or
combined supply clamps/cables).
-Query: Res:Set:ConnClassic?
[ConnClassic]
• Res:Set:Data:Recording
- Query: Res:Set:Data:Recording?
[Recording]
• Res:Set:Data:Stability
Sets and returns the value in %/s (percent change of resistance value per second) used
to determine if
a resistance value is considered stable or not.
- Query: Res:Set:Data:Stability?
[Stability]
Sets and returns the reference temperature in °C used for temperature dependent
resistance
correction.
- Query: Res:Set:Mode?
[Mode]
• Res:Set:Temp:Man
Sets and returns the manual value for the temperature of the DUT used for temperature
correction.
- Query: Res:Set:Temp:Man?
[Temp]
• Res:Set:Temp:Use
Sets and returns which temperature channels are used to calculate the average
temperature of the
DUT for temperature correction.
- Set: Res:Set:Temp:Use
[Ch1],[Ch2],[Ch2],[Ch4],[Ch5],[Ch6],[ChManual]
[Ch] = 0 ¦ 1
- Query: Res:Set:Temp:Use?
[Ch1],[Ch2],[Ch2],[Ch4],[Ch5],[Ch6],[ChManual]
• Res:Set:Temp:Enable
Sets and returns whether the temperature correction of the resistance is enabled or not.
- Query: Res:Set:Temp:Enable?
[TempEnable]
• Res:Set:Winding:Select
- Query: Res:Set:Winding:Select?
[WindingPair]
• Res:Set:Phase:Select
Sets and returns the selection of the phases to be measured for all three windings. The 4 argument
style command lets the user explicitly choose which phases on which windings have to be measured.
Using the 1 argument style command, the software automatically selects the corresponding phases on
HV, LV and TV (one phase per winding). Phase assignment:
Res:Set:Phase:Select [Phase]
[Phase] = 1 ¦ 2 ¦ 3
- Query: Res:Set:Phase:Select?
HV,[Ph1],[Ph2],[Ph3];LV,[Ph1],[Ph2],[Ph3];TV,[Ph1],[Ph2],[Ph3]
• Res:Set:Current
Sets and returns the measuring current in Ampere for the three different windings (HV, LV
and TV).
- Query: Res:Set:Current?
HV,[Current];LV,[Current];TV,[Current]
Res:Set:Current? [Winding]
[Current]
Returns the recorded value for all or certain windings and phases as 1.23456e-3
Resistance (R), Voltage (U), Current (I) or Temperature (T)
- Query: Res:Data:R?
[ResHV1],[ResHV2],[ResHV3],[ResLV1],[ResLV2],[ResLV3],
[ResTV1],[ResTV2],[ResTV3]
Res:Data:R? LV
[ResLV1],[ResLV2],[ResLV3]
Res:Data:R? TV,2
[ResTV2]
• Res:Meas:R ¦ Res:Meas:U
- Query: Res:Meas:R?
[R1],[R2],[R3],[R4]
Res:Meas:R? 2
[R2]
• Res:Meas:I
Returns the currently measured current values as 1.23456e-3. In automatic mode I1 and
I2 are the
values of HV and LV, respectively the values of HV and TV, depending on which windings
are
selected. In classic mode I1 is the measuring current for all resistors.
- Query: Res:Meas:I?
[I1],[I2]
Res:Meas:I? 1
[I1]
Returns the currently measured average temperature value as 1.23456e-3. This value
depends on
which temperature channels are marked for average calculation.
- Query: Res:Meas:T?
[TAverage]
• Res:Meas:Sequence
Returns the current measuring sequence for the started resistance measurement. The
parameter
winding describes whether no (-) or only primary (1) or only secondary (2) or both (D)
windings will be
measured. Mode defines which supply mode will be used. In case that no measurement
will be
performed for a sequence step, mode will be set to “Nop”. And phase describes between
which
terminals the resistance will be measured for primary and secondary winding.
- Query: Res:Meas:Sequence?
[Winding],[Mode],[PhasePri],[PhaseSec];
[Winding],[Mode],[PhasePri],[PhaseSec];
[Winding],[Mode],[PhasePri],[PhaseSec];
[Winding],[Mode],[PhasePri],[PhaseSec];
[Winding],[Mode],[PhasePri],[PhaseSec];
[Winding],[Mode],[PhasePri],[PhaseSec];
[Winding1] = - ¦ 1 ¦ 2 ¦ D
[Mode] = Nop ¦ 32A/50V ¦ 16A/100V ¦ 16A/50V ¦ YdnMode ¦
Classic2R ¦ UnknownOperation
[Phase] = A-N ¦ B-N ¦ C-N ¦ N-A ¦ N-B ¦ N-C ¦
A-B ¦ B-C ¦ C-A ¦ B-A ¦ C-B ¦ A-C
• Res:Meas:State
Returns the current resistance measurement state. SeqNo indicates which measurement
out of the
sequence described above is currently performed. An RxStable is set to 1 if the measured
resistance
value is stable according to the Res:Set:Data:Stability criterion.
- Query: Res:Meas:State?
[SeqNo],[R1Stable],[R2Stable],[R3Stable]
• HR:Set:Interval
Sets and returns the interval time in seconds between two resistance values.
- Query: HR:Set:Interval?
[Time]
• HR:Set:NumPoints
Sets and returns the number of points to be recorded for the heat run cooling curve.
- Query: HR:Set:NumPoints?
[NPoints]
Sets and returns the phase selection for the heat run test. Issuing the set command with
only a phase
argument selects the corresponding two phases of the currently selected windings. By
adding a
winding argument, the selection can be reduced to only one phase on only one winding.
HR:Set:Phase:Select [Phase]
[Phase] = 1 ¦ 2 ¦ 3
- Query: HR:Set:Phase:Select?
HV,[Ph1],[Ph2],[Ph3];LV,[Ph1],[Ph2],[Ph3];TV,[Ph1],[Ph2],[Ph3]
[Ph] = 0 ¦ 1
• HR:Data
Returns a measurement set (Time [t] in seconds, Resistance [R], Voltage [U], Current [I],
Temperature
[T]) for a given winding, phase and index. The index is used to access various points
recorded. Each
successful query returns [IndexCurrent] which shows the amount of points recorded so
far. When
[IndexCurrent] has reached [NPoints] the heat run recording is finished and the device will
discharge
the DUT.
[IndexCurrent],[t],[R],[U],[I],[T1],[T2],[T3],[T4],[T5],[T6]
[IndexCurrent],- (No data for this index available)
- (No data for this winding and phase available)
• Dem:Set:Phase
Sets and returns the phase on which the demagnetizazion shall be performed.
- Query: Dem:Set:Phase?
[Winding],[Phase]
• Dem:Set:Tolerance:Abs
Sets and returns the absolute stop criterion for demagnetization in V·s respectively Wb.
- Query: Dem:Set:Tolerance:Abs?
[TolAbs]
• Dem:Set:Tolerance:Rel
Sets and returns the relative stop criterion for demagnetization in % of maximum
remanence.
- Query: Dem:Set:Tolerance:Rel?
[TolRel]
Sets and returns the maximum number of cycles to be performed when demagnetizing.
- Query: Dem:Set:Cycles?
[NCycles]
• Dem:Meas
Returns the current set of measurements used in the demagnetization process. The
current
demagnetization cycle [CycleAct], the remanence flux determined during analysis
[FluxRemanence],
the current magnetic flux [FluxAct], the induced voltage [UInduced], the current [I] and the
winding
resistance [R].
- Query: Dem:Meas?
[CycleAct],[FluxRemanence],[FluxAct],[UInduced],[I],[R]
REN
Meas:Set:App RES
Res:Set:Mode Auto
Res:Set:YNMode PhPh
DUT:Set:Vectorgroup YN,YN,0,D,5
DUT:Set:TempCoeff CopperANSI,CopperIEC,Aluminium
Res:Set:Temp:Man 18.9
Res:Set:Temp:Ref 75.0
Res:Set:Temp:Use 0,1,0,0,0,0,1
Res:Set:Temp:Enable 1
Res:Set:Current HV,2.2
RemoteToLocal
Meas:Start
will start the resistance measuring sequence. After the measurement has started, the measuring
sequence and mode can be obtained using
Res:Meas:Sequence?
The result of this query helps to find out which winding and phase the device is currently
measuring. Further
Res:Meas:State
Shows which sequence step is currently performed and if a stable resistance reading is reached.
Meas:State
Has to be used to find out in which state within a sequence step the device currently is. For
resistance measurement the state flow will typically look like
When “Data Recording” is set to auto, the device will automatically continue from Measuring to
Discharging. When “Data Recording” to manual, the device stays in the Measuring state until
Meas:Stop
One can observe the current measured values during the whole process using
Res:Meas:R?
Res:Meas:U?
Res:Meas:I?
Res:Meas:T?
Temp:Values?
Res:Data:R?
Res:Data:U?
Res:Data:I?
Res:Data T?
If a measuring process aborts unexpectedly or the system state is Reset or Interlock, one
can get an error message using
Meas:Error
TC:Move Up ¦ Down
This operation is only valid if the system state is either Measuring or Standby. Further only an
On-Load Tap Changer could be operated during Measuring. NEVER operate an Off-Load Tap
Changer during Measuring. An Off-Load Tap Changer must be operated ALWAYS during
Standby. After issuing a TC:Move command the Tap Changer Feedback will be set to 0. When
the Tap Changer movement completed, the feedback will be set to 1. This status can be obtained
using
TC:Feedback?
Meas:Set:App HR
Res:Set:YNMode PhPh
DUT:Set:Vectorgroup YN,YN,0,D,5
Res:Set:Current HV,2.2
Res:Set:Current LV,8.9
Res:Set:Current TV,13.2
HR:Set:Phase:Select 2
Res:Set:Winding:Select HV-LV
HR:Set:Interval 5
HR:Set:NumPoints 100
RemoteToLocal
Meas:Start
will start the Heat Run sequence. The start command will only start the timer when switching the
transformer heating supply off. When the 2293 is connected to transformer and everything is
ready for cooling curve acquisition, the command
Meas:Continue
will start the actual resistance measuring process. After the measurement has started, the
measuring sequence and mode can be obtained using
Res:Meas:Sequence?
The result of this query helps to find out which winding and phase the device is currently
measuring.
Meas:State
Has to be used to find out in which state within a sequence step the device currently is. For
cooling curve measurement the state flow will typically look like
When the device has reached the Measuring state, it will immediately start to record data sets.
The sequence can be stopped anytime by sending
Meas:Stop
One can observe the current measured values during the whole process using
Res:Meas:R?
Res:Meas:U?
Res:Meas:I?
Res:Meas:T?
Temp:Values?
HR:Data? HV,2,1
HR:Data? LV,2,1
HR:Data? HV,2,2
HR:Data? LV,2,2
HR:Data? HV,2,3
HR:Data? LV,2,3
…
If a measuring process aborts unexpectedly or the system state is Reset or Interlock, one
can get an error message using
Meas:Error
22.4.4 Demagnetization
First, start with REN. This will enable remote controlling and it will transfer the current local set of
settings to the remote set of settings. Then send all settings to the device and at the end call
RemoteToLocal to transfer the remote settings to the local settings.
REN
Meas:Set:App DEM
DUT:Set:Vectorgroup YN,YN,0,D,5
RemoteToLocal
Meas:Start
Meas:State
Has to be used to find out in which state the device currently is. For the demagnetization process
the state flow will typically look like
In the state DemagCycleInit the system decides whether the transformer is still
magnetized (next cycle) or already demagnetized (no more cycles).
One can observe the current measured values during the whole process using
Dem:Meas?
If a measuring process aborts unexpectedly or the system state is Reset or Interlock, one
can get an error message using
Meas:Error
NoError
Miscellaneous 209
23.3 Packing and Transport
The packing of the 2293 instrument provides satisfactory
protection for normal transport conditions. Nevertheless, care
should be taken when transporting the instrument. If return of the
instrument is necessary, and the original packing crate is no
longer available, then packing of an equivalent standard or better
should be used.
Whenever possible protect the instrument from mechanical
damage during transport with padding. Mark the container with the
pictogram symbols "Fragile“ and “Protect from moisture“.
23.4 Recycling
When the instrument reaches the end of its working life it can, if required, be disassembled and recycled.
No special instructions are necessary for dismantling.
The instrument is constructed of metal parts (mostly aluminum) and synthetic materials. The various
component parts can be separated and recycled, or disposed of in accordance with the associated local
rules and regulations.
210 Miscellaneous
24 Customer Support
All error messages appear on the display of the 2293 measuring instrument. If persistent problems or
faulty operation should occur then please contact the Customer Support Department of HAEFELY TEST
AG or your local agent.
The Customer Support Department can be reached at the following address:
HAEFELY TEST AG
Customer Service - Tettex
Birsstrasse 300
CH-4052 Basel
Switzerland
We prefer contact via email. Then the case is documented and traceable. Also
the time zone problems and occupied telephones do not occur.
212 Appendix
25.1 Declaration of Conformity
Appendix 213
25.2 Application Note “Temperature
Measurement”
▪ Setup
To check the performance of different types of surface temperature measurement probes for flat
surfaces, the setup depicted in figure 1 was constructed:
The surface to be measured is a flat and 4.5mm thick steel plate, which was heated by 2 power
resistors located at the bottom side of the plate. For reference temperature measurement 2
Thermocouples Type were used. Ech of them were sticked in a hole (d = 1.5mm, h = 2mm) filled
with thermal compound for optimal thermal conduction. The thermocouples are the two black
cables in figure 1. The probes under test were located near to the thermocouple probes.
The thermal contact is quite good in this setup for both types of probes.
214 Appendix
▪ Probes under Test
Appendix 215
▪ Measurements
216 Appendix
25.2.2 2. Round Surface (Tube)
▪ Setup
During the HeatRun, the Radiator top and bottom (outlet and inlet) temperatures must be
measured. Usually there are tubes, which are not very easy to measure. To check the
performance of different types of surface temperature measurement probes for round surfaces,
the setup depicted in figure 2 was constructed.
The steel tube to be measured has a diameter of 50mm and a thickness of 5mm. The tube was
heated using 3 power resistors circularly arranged inside the tube . For reference temperature
measurement 2 Thermocouples Type J were used. Each of them were sticked in a hole (d =
1.5mm, h = 2mm) filled with thermal compound for optimal thermal conduction. The
thermocouples are the two black cables in figure 2. The probes under test were located near to
the thermocouple probes.
The thermal contact is not very good for the OF/E-14 and even worse for the Tettex probe.
Appendix 217
1. Tettex magnetically Surface Temperature Measurement Probe Box (PT100)
See figure 2, the probe with the black plastic handle.
2 Fühlersysteme OF/E-14/10-4 (PT100)
See figure 1, the probe with the red horseshoe magnet and the spring loaded sensor
tip.
218 Appendix
▪ Measurements
Appendix 219
Figure 3: OF/E-14 placement on tube
3. Further Accuracy Improvement
The main Application issue, when measuring the temperature of a surface, is heat transfer from
the surface to the probe. The surface will heat or cool the probe tip and the ambient air will do the
opposite (cool or heat). Unless ambient air and surface temperature are equal, there will always
be thermal flow at the probe. In order to reduce the thermal effect of the ambient air, it is strongly
recommend isolating the temperature probe from the ambient. This can easily be achieved using
an EPS foam box or similar.
See figure 4 as a reference design:
220 Appendix
Figure 4: Thermal isolation using a piece of EPS foam
Appendix 221
25.3 Application Note “Unit calibration”
If calibration with a common standard resistor is performed, one has to isolate the voltage
(sense) line from the current jaw to avoid failures by additionally measure the internal connection
lead to the standard resistor part itself.
222 Appendix