Project Name: EMS APPARELS LIMITED. Area Reference: MOST REMOTE AREA 5th Floor (1500SQFT) OHG2

This document provides hydraulic calculations for a fire sprinkler system design for a project at EMS Apparels Limited in Gazipur, Bangladesh. The system is designed to protect a 1500 square foot area on the 5th floor, classified as Ordinary Hazard Group II. It includes 15 operating sprinkler heads plus one hydrant, with a specified discharge density of 8.20 mm/min. The calculations show the pipe sizes, lengths, diameters, flows, pressures, and heights for the significant pipes in the system. All operating sprinkler heads and the hydrant meet the minimum required pressures and densities.

Uploaded by

NOMAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
43 views8 pages

Project Name: EMS APPARELS LIMITED. Area Reference: MOST REMOTE AREA 5th Floor (1500SQFT) OHG2

This document provides hydraulic calculations for a fire sprinkler system design for a project at EMS Apparels Limited in Gazipur, Bangladesh. The system is designed to protect a 1500 square foot area on the 5th floor, classified as Ordinary Hazard Group II. It includes 15 operating sprinkler heads plus one hydrant, with a specified discharge density of 8.20 mm/min. The calculations show the pipe sizes, lengths, diameters, flows, pressures, and heights for the significant pipes in the system. All operating sprinkler heads and the hydrant meet the minimum required pressures and densities.

Uploaded by

NOMAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Full Hydraulic Calculations Computer Printout Page No 1

Submitted by user number Project: EMS APPARELS LIMITED.


Address: Bhumihin Road (Barenda), Kashimpur, Gazipur.
Number: 01
Area ref: MOST REMOTE AREA 5th Floor(1500SQFT)OHG2
Hazard: ORDINARY HAZARD GROUP-II
Authority: National Fire Protection Association
Source: 2267.6 l/min @ 5.109 bar
Tel: Fax: Printout: 29-July-23 at 19:34

Project Data and Design Parameters


Project name : EMS APPARELS LIMITED.
Area reference : MOST REMOTE AREA 5th Floor(1500SQFT)OHG2
Address / location : Bhumihin Road (Barenda), Kashimpur, Gazipur.
Project number : 01
Installation number(s) : 01
Drawing number(s) : 01
Issue no / date : 29-07-2023
Designers reference : PACIFIC TECH & ENGINEERING LIMITED.
Project Data File : C:\Users\NOMAN\Desktop\EMSAPP~1.FHC
Hazard classification : ORDINARY HAZARD GROUP-II
Design authority : National Fire Protection Association
Insurance company : ---
Specified density of discharge : 8.20 mm/min (l/min/m2)
Assumed maximum area of operation : 138.99 m2
Number of operating sprinkler heads : 15 + 1 hydrant(s)
Maximum area covered per head : 9.27 m2
Highest head / nozzle above source : 25.28 m
Number of pipes in system : 53 from 25 to 200 mm
Pressure loss equation used : Hazen-Williams
Fluid : Water
Pipe Data Table : STD_PIPE.PDT
Maximum fluid velocity : 5.36 m/s in pipe 44 45
Volume of pipework and fittings : 2.96 m3
Elbows are welded for : 50 mm and above
Comment : ---
Checked by & Date :

Source duty = 2267.6 l/min @ 5.109 bar at node no 1

FHC - Hydraulic Analysis Software - Ver: 1.8.4


By CANUTE LLP - Email [email protected] Web www.canutesoft.com
Program FHC
Full Hydraulic Calculations Computer Printout Page No 2
Submitted by user number Project: EMS APPARELS LIMITED.
Address: Bhumihin Road (Barenda), Kashimpur, Gazipur.
Number: 01
Area ref: MOST REMOTE AREA 5th Floor(1500SQFT)OHG2
Hazard: ORDINARY HAZARD GROUP-II
Authority: National Fire Protection Association
Source: 2267.6 l/min @ 5.109 bar
Tel: Fax: Printout: 29-July-23 at 19:34

Operating Sprinkler Heads, Nozzles and Hydrants


Head|Node| Size | 'K' |F l o w|A r e a|Density mm/min|Pressure bar|Heights|Pipe
no | no | mm | factor| l/min | m2 |Req.d Actual| Min Actual| m | no
1 22 15.0 80.00 101.2 9.266 8.20 10.92 0.50 1.600 25.280 21
2 24 15.0 80.00 96.0 9.266 8.20 10.36 0.50 1.441 25.280 23
3 26 15.0 80.00 89.5 9.266 8.20 9.66 0.50 1.253 25.280 25
4 28 15.0 80.00 78.2 9.266 8.20 8.44 0.50 0.955 25.280 27
5 30 15.0 80.00 76.8 9.266 8.20 8.29 0.50 0.921 25.280 29
6 35 15.0 80.00 100.2 9.266 8.20 10.81 0.50 1.568 25.280 34
7 37 15.0 80.00 95.0 9.266 8.20 10.26 0.50 1.412 25.280 36
8 39 15.0 80.00 88.6 9.266 8.20 9.57 0.50 1.227 25.280 38
9 41 15.0 80.00 77.4 9.266 8.20 8.35 0.50 0.936 25.280 40
10 43 15.0 80.00 76.0 9.266 8.20 8.20 0.50 0.902 25.280 42
11 46 15.0 80.00 101.4 9.266 8.20 10.95 0.50 1.607 25.280 45
12 48 15.0 80.00 96.2 9.266 8.20 10.39 0.50 1.447 25.280 47
13 50 15.0 80.00 89.7 9.266 8.20 9.68 0.50 1.258 25.280 49
14 52 15.0 80.00 78.4 9.266 8.20 8.46 0.50 0.959 25.280 51
15 54 15.0 80.00 77.0 9.266 8.20 8.30 0.50 0.925 25.280 53
17 946.0 Hydrant 2.221 24.980 16

0 heads are under the required density / minimum pressures

FHC - Hydraulic Analysis Software - Ver: 1.8.4


By CANUTE LLP - Email [email protected] Web www.canutesoft.com
Program FHC
Full Hydraulic Calculations Computer Printout Page No 3
Submitted by user number Project: EMS APPARELS LIMITED.
Address: Bhumihin Road (Barenda), Kashimpur, Gazipur.
Number: 01
Area ref: MOST REMOTE AREA 5th Floor(1500SQFT)OHG2
Hazard: ORDINARY HAZARD GROUP-II
Authority: National Fire Protection Association
Source: 2267.6 l/min @ 5.109 bar
Tel: Fax: Printout: 29-July-23 at 19:34

Hydraulically Significant Pipes in System


NUMBERS | P I P E | F L O W |DIMENSIONS|ANGLE| VALUES |HEIGHT M|PRESSURES BARS
Pipe|Start|Size Type| L/min | Length VJ|Dir. | Eq.len | Start | Start Frict
no | End |Bore 'C'| Vel m/s |EL T VT|Slope| mbar/m | End | End Static
1 1 200mm MW 2267.6 0.490 Up 0.49 0.000 5.109 -0.000
2 206.40 120 1.1 0 0 90.0 0.7 0.490 5.061 -0.048
2 2 200mm MW 2267.6 5.760 90 11.41 0.490 5.061 -0.008
3 206.40 120 1.1 1 0 GV 0.0 0.7 0.490 5.052 +0.000
3 3 200mm MW 2267.6 2.980 Up 7.30 0.490 5.052 -0.005
4 206.40 120 1.1 1 0 90.0 0.7 3.470 4.755 -0.292
4 4 200mm MW 2267.6 3.930 0 8.25 3.470 4.755 -0.006
5 206.40 120 1.1 1 0 0.0 0.7 3.470 4.749 +0.000
5 5 150mm MW 2267.6 2.950 0 3.90 3.470 4.749 -0.012
6 155.32 120 2.0 0 0 GV 0.0 3.0 3.470 4.737 +0.000
6 6 150mm MW 2267.6 3.520 Up 6.37 3.470 4.737 -0.019
7 155.32 120 2.0 1 0 90.0 3.0 6.990 4.374 -0.345
7 7 150mm MW 2267.6 11.500 270 14.35 6.990 4.374 -0.043
8 155.32 120 2.0 1 0 0.0 3.0 6.990 4.331 +0.000
8 8 150mm MW 2267.6 0.610 Dn 3.46 6.990 4.331 -0.010
9 155.32 120 2.0 1 0 -90.0 3.0 6.380 4.381 +0.060
9 9 150mm MW 2267.6 6.260 0 9.11 6.380 4.381 -0.027
10 155.32 120 2.0 1 0 0.0 3.0 6.380 4.354 +0.000
10 10 150mm MW 2267.6 23.190 270 26.04 6.380 4.354 -0.077
11 155.32 120 2.0 1 0 0.0 3.0 6.380 4.276 +0.000
11 11 150mm MW 2267.6 20.910 270 20.91 6.380 4.276 -0.062
12 155.32 120 2.0 0 0 0.0 3.0 6.380 4.214 +0.000
12 12 150mm MW 2267.6 0.560 180 3.41 6.380 4.214 -0.010
13 155.32 120 2.0 1 0 0.0 3.0 6.380 4.204 +0.000
13 13 150mm MW 2267.6 4.720 Dn 7.57 6.380 4.204 -0.022
14 155.32 120 2.0 1 0 -90.0 3.0 1.660 4.644 +0.462
14 14 150mm MW 2267.6 5.360 270 8.21 1.660 4.644 -0.024
15 155.32 120 2.0 1 0 0.0 3.0 1.660 4.620 +0.000
15 15 150mm MW 2267.6 12.450 270 12.45 1.660 4.620 -0.037
16 155.32 120 2.0 0 0 0.0 3.0 1.660 4.583 +0.000
16 16 150mm MW 2267.6 23.320 Up 26.17 1.660 4.583 -0.078
17 155.32 120 2.0 1 0 90.0 3.0 24.980 2.221 -2.284
17 17 150mm MW 1321.6 6.550 180 10.35 24.980 2.221 -0.011
18 155.32 120 1.2 1 0 GV 0.0 1.1 24.980 2.210 +0.000
18 18 100mm MW 1321.6 15.860 180 15.86 24.980 2.210 -0.116
19 105.14 120 2.5 0 0 0.0 7.3 24.980 2.094 +0.000
19 19 50mm MW 441.7 0.150 Up 3.34 24.980 2.094 -0.090
20 52.98 120 3.3 0 1 90.0 27.1 25.130 1.989 -0.015

Continued on the next page

FHC - Hydraulic Analysis Software - Ver: 1.8.4


By CANUTE LLP - Email [email protected] Web www.canutesoft.com
Program FHC
Full Hydraulic Calculations Computer Printout Page No 4
Submitted by user number Project: EMS APPARELS LIMITED.
Address: Bhumihin Road (Barenda), Kashimpur, Gazipur.
Number: 01
Area ref: MOST REMOTE AREA 5th Floor(1500SQFT)OHG2
Hazard: ORDINARY HAZARD GROUP-II
Authority: National Fire Protection Association
Source: 2267.6 l/min @ 5.109 bar
Tel: Fax: Printout: 29-July-23 at 19:34

Hydraulically Significant Pipes in System


NUMBERS | P I P E | F L O W |DIMENSIONS|ANGLE| VALUES |HEIGHT M|PRESSURES BARS
Pipe|Start|Size Type| L/min | Length VJ|Dir. | Eq.len | Start | Start Frict
no | End |Bore 'C'| Vel m/s |EL T VT|Slope| mbar/m | End | End Static
20 20 40mm MW 441.7 2.040 270 3.40 25.130 1.989 -0.290
21 41.86 120 5.4 1 0 0.0 85.2 25.130 1.699 +0.000
21 21 25mm MW 101.2 0.150 Up 1.87 25.130 1.699 -0.084
22 27.31 120 2.9 0 1 90.0 44.6 25.280 1.601 -0.015
22 21 40mm MW 340.5 3.180 270 3.18 25.130 1.699 -0.168
23 41.86 120 4.1 0 0 0.0 52.7 25.130 1.531 +0.000
23 23 25mm MW 96.0 0.150 Up 1.87 25.130 1.531 -0.076
24 27.31 120 2.7 0 1 90.0 40.5 25.280 1.441 -0.015
24 23 32mm MW 244.5 3.300 270 3.30 25.130 1.531 -0.197
25 35.97 120 4.0 0 0 0.0 59.7 25.130 1.334 +0.000
25 25 25mm MW 89.5 0.150 Up 1.87 25.130 1.334 -0.067
26 27.31 120 2.5 0 1 90.0 35.6 25.280 1.253 -0.015
26 25 25mm MW 155.0 3.180 270 3.18 25.130 1.334 -0.312
27 27.31 120 4.4 0 0 0.0 98.2 25.130 1.022 +0.000
27 27 25mm MW 78.2 0.150 Up 1.87 25.130 1.022 -0.052
28 27.31 120 2.2 0 1 90.0 27.7 25.280 0.955 -0.015
28 27 25mm MW 76.8 2.370 270 2.37 25.130 1.022 -0.064
29 27.31 120 2.2 0 0 0.0 26.8 25.130 0.958 +0.000
29 29 25mm MW 76.8 0.150 Up 0.84 25.130 0.958 -0.022
30 27.31 120 2.2 1 0 90.0 26.8 25.280 0.921 -0.015
30 19 80mm MW 879.9 3.280 180 3.28 24.980 2.094 -0.041
31 80.68 120 2.9 0 0 0.0 12.5 24.980 2.053 +0.000
31 31 80mm MW 442.7 3.200 180 3.20 24.980 2.053 -0.011
32 80.68 120 1.4 0 0 0.0 3.5 24.980 2.042 +0.000
32 31 50mm MW 437.2 0.150 Up 3.34 24.980 2.053 -0.089
33 52.98 120 3.3 0 1 90.0 26.5 25.130 1.949 -0.015
33 33 40mm MW 437.2 2.040 270 3.40 25.130 1.949 -0.284
34 41.86 120 5.3 1 0 0.0 83.6 25.130 1.665 +0.000
34 34 25mm MW 100.2 0.150 Up 1.87 25.130 1.665 -0.082
35 27.31 120 2.9 0 1 90.0 43.8 25.280 1.569 -0.015
35 34 40mm MW 337.0 3.180 270 3.18 25.130 1.665 -0.164
36 41.86 120 4.1 0 0 0.0 51.7 25.130 1.501 +0.000
36 36 25mm MW 95.0 0.150 Up 1.87 25.130 1.501 -0.074
37 27.31 120 2.7 0 1 90.0 39.7 25.280 1.412 -0.015
37 36 32mm MW 242.0 3.300 270 3.30 25.130 1.501 -0.193
38 35.97 120 4.0 0 0 0.0 58.6 25.130 1.308 +0.000
38 38 25mm MW 88.6 0.150 Up 1.87 25.130 1.308 -0.065
39 27.31 120 2.5 0 1 90.0 34.9 25.280 1.227 -0.015

Continued on the next page

FHC - Hydraulic Analysis Software - Ver: 1.8.4


By CANUTE LLP - Email [email protected] Web www.canutesoft.com
Program FHC
Full Hydraulic Calculations Computer Printout Page No 5
Submitted by user number Project: EMS APPARELS LIMITED.
Address: Bhumihin Road (Barenda), Kashimpur, Gazipur.
Number: 01
Area ref: MOST REMOTE AREA 5th Floor(1500SQFT)OHG2
Hazard: ORDINARY HAZARD GROUP-II
Authority: National Fire Protection Association
Source: 2267.6 l/min @ 5.109 bar
Tel: Fax: Printout: 29-July-23 at 19:34

Hydraulically Significant Pipes in System


NUMBERS | P I P E | F L O W |DIMENSIONS|ANGLE| VALUES |HEIGHT M|PRESSURES BARS
Pipe|Start|Size Type| L/min | Length VJ|Dir. | Eq.len | Start | Start Frict
no | End |Bore 'C'| Vel m/s |EL T VT|Slope| mbar/m | End | End Static
39 38 25mm MW 153.4 3.180 270 3.18 25.130 1.308 -0.306
40 27.31 120 4.4 0 0 0.0 96.3 25.130 1.001 +0.000
40 40 25mm MW 77.4 0.150 Up 1.87 25.130 1.001 -0.051
41 27.31 120 2.2 0 1 90.0 27.2 25.280 0.936 -0.015
41 40 25mm MW 76.0 2.370 270 2.37 25.130 1.001 -0.062
42 27.31 120 2.2 0 0 0.0 26.3 25.130 0.939 +0.000
42 42 25mm MW 76.0 0.150 Up 0.84 25.130 0.939 -0.022
43 27.31 120 2.2 1 0 90.0 26.3 25.280 0.902 -0.015
43 32 50mm MW 442.7 0.150 Up 1.11 24.980 2.042 -0.030
44 52.98 120 3.3 1 0 90.0 27.1 25.130 1.997 -0.015
44 44 40mm MW 442.7 2.040 270 3.40 25.130 1.997 -0.291
45 41.86 120 5.4 1 0 0.0 85.6 25.130 1.706 +0.000
45 45 25mm MW 101.4 0.150 Up 1.87 25.130 1.706 -0.084
46 27.31 120 2.9 0 1 90.0 44.8 25.280 1.607 -0.015
46 45 40mm MW 341.3 3.180 270 3.18 25.130 1.706 -0.168
47 41.86 120 4.1 0 0 0.0 52.9 25.130 1.538 +0.000
47 47 25mm MW 96.2 0.150 Up 1.87 25.130 1.538 -0.076
48 27.31 120 2.7 0 1 90.0 40.7 25.280 1.447 -0.015
48 47 32mm MW 245.0 3.300 270 3.30 25.130 1.538 -0.198
49 35.97 120 4.0 0 0 0.0 60.0 25.130 1.340 +0.000
49 49 25mm MW 89.7 0.150 Up 1.87 25.130 1.340 -0.067
50 27.31 120 2.6 0 1 90.0 35.7 25.280 1.258 -0.015
50 49 25mm MW 155.3 3.180 270 3.18 25.130 1.340 -0.314
51 27.31 120 4.4 0 0 0.0 98.6 25.130 1.026 +0.000
51 51 25mm MW 78.4 0.150 Up 1.87 25.130 1.026 -0.052
52 27.31 120 2.2 0 1 90.0 27.8 25.280 0.959 -0.015
52 51 25mm MW 77.0 2.370 270 2.37 25.130 1.026 -0.064
53 27.31 120 2.2 0 0 0.0 26.9 25.130 0.962 +0.000
53 53 25mm MW 77.0 0.150 Up 0.84 25.130 0.962 -0.023
54 27.31 120 2.2 1 0 90.0 26.9 25.280 0.925 -0.015

FHC - Hydraulic Analysis Software - Ver: 1.8.4


By CANUTE LLP - Email [email protected] Web www.canutesoft.com
Program FHC
Full Hydraulic Calculations Computer Printout Page No 6

FHC - Hydraulic Analysis Software - Ver: 1.8.4


By CANUTE LLP - Email [email protected] Web www.canutesoft.com
Program FHC
MRH