1-05 Bridge Controller (BRC-300) Data Sheet
1-05 Bridge Controller (BRC-300) Data Sheet
ControlIT
Bridge Controller (BRC300)
Highlights
The Harmony Bridge Controller (BRC300) is a high-performance, high-capacity process controller.
It is designed to interface with Harmony I/O and S800 I/O in the ABB Symphony ™ Enterprise
Management and Control System. The BRC300 is fully compatible with the INFI 90 ® OPEN
system in functionality, communications, and packaging.
The BRC300 collects process I/O, performs control algorithms and outputs control signals to
process level devices. It also imports and exports process data from and to other controllers or
other system nodes, and accepts control commands from operators and computers connected to
the network. This controller communicates on the Controlway with other Harmony rack
controllers on a peer-to-peer basis. The BRC300 can be used in an one-for-one redundancy
configuration for unparalleled reliability and system availability. The BRC300 communicates with
other system nodes on the control network (Cnet) via the Harmony rack communication modules.
Multiple control languages are supported in the BRC300, including function codes and C. The
superior processing power and large capacity of the BRC300 enable it to meet the needs of a wide
range of requirements from data acquisition to the most complex process management and con-
trol strategies.
Specifications
Property Characteristic/Value
®
Microprocessor 32-bit Motorola Coldfire 5407 processor running at 160 MHz.
Memory All memory has 32-bit data path:
BRC300
SDRAM NVRAM Flash ROM
Total Available Total Available Total
8 Mbytes 7.56 Mbytes 512 kbytes 425 kbytes 2 Mbyte
Property Characteristic/Value
Dimensions
BRC300 35.56 mm wide (1.40 in.), 177.80 mm high (7.00 in.), 298.45 mm long (11.75 in.).
PBA 31.60 mm wide (1.24 in.), 166 mm high (6.54 in.), 102.56 mm deep (4.04 in.).
Weight
BRC300 0.70 kg (1 lb, 13.5 oz).
PBA 0.30 kg (10.6 oz).
Communication ports 2 RS-232-C or 1 RS-232-C and 1 RS-485, 1 SAC/DCS channel (128 SACs or 8 DCS
maximum).
Electromagnetic/radio Keep cabinet doors closed. Do not use communication equipment any closer than 2 m
frequency interference from the cabinet.
Ambient temperature 0° to 70°C (32° to 158°F).
Relative humidity 0% to 95% relative humidity up to 55°C (131°F) noncondensing,
0% to 45% relative humidity at 70°C (158°F) noncondensing.
Atmospheric pressure Sea level to 3 km (1.86 mi).
Certification (pending) CSA certified for use as process control equipment in ordinary (nonhazardous) loca-
tions.
CE mark compliant for EMC directive and LV directive.
Factory Mutual (FM) -Approved for use in Class I; Division II hazardous locations.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE