ERIS Panel Maintenance Manual (Sandvik)
ERIS Panel Maintenance Manual (Sandvik)
Sandvik Mining
13500 NW Country Road 235
Alachua, Florida 32615 - USA
Tel. (386) 462-4100
Fax. (386) 462-3247
The following three hazard signal words are used throughout this manual to emphasize
important instructions. For the purpose of this manual, these signal words are defined as follows:
Table of Contents
The computer communicates to the main machine PLC over Ethernet. The
connection is made at internal computer and passed through a plug at the back of the
panel.
1-3
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
1-4
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
1-5
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
There will be instances where a technician will need to connect to the ERIS
console. A few of these instances may be:
• To install a newer or different version of the ERIS software.
• To configure the Joysticks.
• To verify the console is communicating with the PLC.
• Verify computer settings.
In order to communicate with the internal CPU in the ERIS panel without
disassembling the console, what is needed is a USB keyboard. The keyboard can
be plugged into the external USB port and the keyboard then can take over
control of the computer.
Note!
It is recommended that a special keyboard and flashdrive should be used for this
purpose that has been tested for compatibility to ensure reliable connectivity through
the USB port. This is available through your local dealer under the following Sandvik part
numbers:
-CP000272 USB keyboard with pointing device and two USB ports.
-CP000271 512MB USB flash drive.
1-6
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
In general, the joysticks should not need calibrating, even when they come from
the factory. However, optimum gain characteristics (the distance the joystick
moves vs the amount of output signal) may only be achievable through the
process of making certain the joysticks are properly calibrated.
Procedure:
• Proceed to the start button in Windows®, then to Control Panel, then
Game Controllers. The following screen will display:
Screen 1
1-7
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
This screen identifies that the A/D (analog to digital) Controller is communicating
with the computer.
Next select Properties. The following screen will appear.
LeŌ JoysƟck
Right JoysƟck
BuƩons
Screen 2
The buttons on the joysticks can then be checked for communication with the
computer. When pressing a button on the joystick, one of the lights will light on
the screen in accordance with Figure 1. The light number 13 will show as being
constantly on. This light represents the tilt switch that is built into the PCB
(printed circuit board). If the ERIS panel is tilted, this light should go out.
The following diagram reflects the button numbering sequence the computer
recognizes from the USB controller.
1-8
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
2 3 8 9
1 4 7 10
5 6 11
12
The visual graphics for testing the “X” (right to left) and “Y” (back and forth) axis
of the joysticks is slightly different between right and left joystick. As shown in
Screen 2, the left joystick is represented by cross hairs in a square. When the left
joystick is moved in its’ extreme pattern, the cross hairs should touch the sides
of the box. If it does not, the left joystick should be calibrated.
The right joystick is then confirmed through the slide bar graph as shown in
Screen 2. While moving the right joystick in its/ extreme travel, the slide bars
should touch the top and bottom of the graph.
If any of these conditions are not met, then the joystick should be re-calibrated.
1-9
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
Screen 3
• Click Calibrate.
• A calibration Wizard window will appear and lead you through a series of
steps to calibrate the joysticks.
Screen 4
1-1 0
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
Grasping the left joystick, move it around in a circle as far as it will go, then
press any button on the joystick.
Screen 5
Next, verify the center point of the left joystick by leaving it centered and clicking next.
Screen 6
1-1 1
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
Moving onto the right joystick, the screens will change. Even though the screen
will indicate “Y Rotation”, this is actually calibrating the “X Axis”.
Screen 7
Even though the screen will indicate “Z Rotation”, this is actually calibrating the
“Y Axis”.
Screen 8
1-1 2
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
The calibration of both right and left joysticks should now be complete.
Screen 9
1-1 3
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
1-1 4
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
There are two program groups inside the ERIS program group. Both have to be
uninstalled. We will start by first uninstalling the LLMC program group. Move the mouse
over the LLMC folder to expose its contents as shown below.
1-1 5
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
First click on the killswitch program to stop all background processes for the ERIS from
running. Next, go to the LLMC program group again and click on the uninstall icon.
Follow the prompts (see screens below).
Click on the Close button to complete the uninstallation process. You will now be
returned to the desktop.
1-1 6
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
We will now uninstall the OCC application. Navigate to the OCC program group as
shown below.
Click on the uninstall icon and follow the prompts as shown in the screens below.
1-1 7
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
Click on the ‘Close’ button to complete the uninstallation process. You will now be
returned to the desktop. The ERIS software is now completely removed from the
computer.
Note: Reboot the ERIS panel before proceeding to the next step.
1-1 8
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
• Double click on this icon. This one install program will re-install the OCC and LLMC.
Follow the prompts as shown below.
1-1 9
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
1-2 0
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
1-2 1
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
1-2 2
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
The new ERIS program is now fully installed. Reboot the ERIS panel and the ERIS
interface will load automatically.
Installing RS Linx
In order for the ERIS panel to communicate with the PLC a communication program
called RS Linx is used. This is installed at the factory and should be pre-configured. It is
possible that this configuration may become corrupt so we will outline the basic steps
below how to install and configure this program.
Activating RS Linx
• Proceed to Windows® Explorer. (right click start, click Explore)
• Find the USB Memory stick and locate the vfdwin file.
• Double click the vfdwin file and the “VFD Control Panel” appears.
• Click on install, then start
• Go to the Drive 0 Tab and click open.
• Set the drive letter by clicking on change and choosing “A” or “B”.
• Proceed to Windows® Explorer. (right click start, click Explore)
• Locate and double click EVMOVE in the directory “A” or “B” as you chose
1-2 3
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
1-2 4
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
5.Select the pull down menu adjacent to the Add New… button, and select
Ethernet/IP Driver, followed by Add New…
6. A window will pop up asking for a name, this can be left as is. Click OK.
7. The Configure driver window will pop up, select the Browse Remote Subnet
option and fill in the IP Address and Subnet Mask.
IP Address: 10.0.0.10
Subnet Mask: 255.255.255.0
1-2 5
ERIS Control Panel (Rev8) PLC Type MAINTENANCE MANUAL
Configuring RS Linx
1. Run RS Linx from Start->Rockwell->RS Linx
2. Select DDE/OPCConfigure Topic
1-2 6
ERIS Control Panel (Rev8) PLC Type
1-2 7
ERIS Control Panel (Rev8) PLC Type
1-2 8
ERIS Control Panel (Rev8) PLC Type
This will lead you to a DOS command prompt line in a separate window
on the screen as shown.
• From this command prompt, you can attempt to ping the other members
of the Ethernet bus. By pinging, it will provide a response on whether
there is communication with that other member of the circuit. It is like
ringing a phone number and seeing if there is a response from the other
party or not. To be able to ping, you must know the IP (Internet Protocol)
address of the other member(s) of the circuit. In general, must drill rigs
will only have one ERIS console, therefore there will only be one item you
can ping, and that is the PLC. However, if there is also a remote console,
you will be able to ping the PLC from either console, and even ping one
console to the other.
• To ping, at the command prompt, type in ping, then a space then the IP
address of what you are pinging. For instance, on the Aries drill rig the IP
address of the PLC is 10.0.0.10. (list of IP addresses given below)
Therefore, your DOS screen would show as:
1-2 9
ERIS Control Panel (Rev8) PLC Type
1-3 0
ERIS Control Panel (Rev8) PLC Type
1-3 1
ERIS Control Panel (Rev8) PLC Type
Plugged In
Turn Off Monitor – Never
Turn Off Hard Disks – Never
System Standby – Never
Running on Batteries
Turn Off Monitor – Never
Turn Off Hard Disks – Never
System Standby – Never
Alarms Tab
Low Battery Alarm (Disable)
Advanced Tab
When Close Lid : Do Nothing
When Power Pressed : Shutdown
Hibernate Tab
Disable Hibernate
1-3 2
ERIS Control Panel (Rev8) PLC Type
Network Connections
Display
1-3 3
ERIS Control Panel (Rev8) PLC Type
Please refer to the electrical schematic for the corresponding wire orientation in
the industrial plug in the rear of the ERIS console.
1-3 4
ERIS Control Panel (Rev8) PLC Type
Panel Layout and Component Replacement. All of these parts are available in a kit CP001096.
1-3 5
ERIS Control Panel (Rev8) PLC Type
There is only one power supply in the panel. It converts 24volts into 16volts to power
the laptop. To remove this you must first disconnect the two connectors shown below.
The power supply is held in place with a silicone adhesive and is pried up for removal.
To test the output of the power supply simply disconnect the 16volt connector (black) and
measure the voltage with a meter while the 24v is still connected. This will require the plug at
the back of the panel to be hooked up to a 24volt source.
1-3 6
ERIS Control Panel (Rev8) PLC Type
Remove the front bezel cover that is retained by 10 socket head cap
screws.
Remove the trough cover that is retained by 3 countersunk screws.
The start switch connector set screw can be loosened and the connector
disengaged from the start switch as shown in Figure 4.
Once all the electrical connections have been removed from the CPU, the
4 CPU Retaining screws can be removed.
Remove the power, Ethernet and USB cables from the CPU shown below.
1-3 7
ERIS Control Panel (Rev8) PLC Type
Although there is a Heat conductive plate built into the back of the ERIS console
enclosure, the CPU must make contact with this plate in order for efficient heat
transfer.
This connection is made mechanically with aluminum foil due to the irregular shape of
the back of the laptop. It is also important to ensure that the mechanical connection
can wrap slightly around the edge of the CPU as shown above in Figure 6.
The CPU should come with the heat connection foil in place. However, if it is
missing it can be made up simply by folding several layers of aluminum foil to fit
between the “feet” on the back of the CPU. Also ensure it is slightly wrapped
around the edge as shown. The aluminum foil can be held in place by placing 2
or 3 small drops of silicon on the back of the computer.
1-3 8
ERIS Control Panel (Rev8) PLC Type
TroubleshooƟng
1-3 9