Controller
Installation
Maintenance
Repair
Manual
Advantage Controls
4700 Harold Abitz Dr.
Muskogee, OK 74403
Phone: 800-743-7431
Fax: 888-686-6212
www.advantagecontrols.com 04/2023
email: [email protected]
1
MegaTronXS Controller
Instruction & Maintenance Manual
Table of Contents
Contents Page
I. Introduction.................................................................................. 3
Model Numbering........................................................................ 3
Description of Unit....................................................................... 3
II. Installation................................................................................... 4
Electrical Wiring........................................................................... 4
Wiring Diagrams.......................................................................... 5
Mounting Instructions.................................................................. 8
Electrode Installation................................................................... 8
A. Cooling Tower........................................................................ 8
B. Boiler.................................................................................... 10
III. Front Panel
Drawing..................................................................................... 12
Description................................................................................. 12
IV. System Operation Overview...................................................... 13
Start-Up..................................................................................... 13
Calibration................................................................................. 13
V. Menu Navigation....................................................................... 14
VII. Maintenance.............................................................................. 32
Electrode Cleaning Procedures................................................. 32
VIII. Troubleshooting......................................................................... 33
2
I. Introduction
The MegaTronXS microprocessor based controllers are designed to provide a wide range of control functions
for recirculating water treatment systems. The controller is programmed through a front panel keypad and
can be configured to provide a customized control system for your application. Your particular unit’s functions
can be determined by comparing the units model number to the Model Numbering table listed below.
Model Numbering
MegaTronXS units have several base system control functions and unit optional features. Your unit may be
supplied with one or more of the features described in this manual. To determine what features apply to your
unit check the model number label located on the controller enclosure.
Model numbers start XS followed by the System Control functions. A dash separates the whole unit options
listed after all base system control functions. Example: XSCPF3E-N4.
Notice: Your unit may not have all features and functions described in this manual. This list represents our
most popular options, additional option codes are available. Consult representative for more details.
Description of Unit
MegaTronXS controllers control a single recirculating water system including cooling tower and boiler
applications and may have various features depending on the model number.
Control Functions
Each of these control functions are based on an analog input from a probe and will include user settable relay
control settings along with a High and Low Alarm setting and Limit Timer. Each control function will include a
control relay output. When the reading reaches the Set Point the control relay is activated until the reading
changes by the Differential amount.
1. System Conductivity - The conductivity function of the controller is designed to monitor and
control Total Dissolved Solids (TDS) in a recirculating system like a cooling tower or boiler in terms
of electrical conductivity measured in MicroSiemens/cm. This control function is also referred to
as Bleed.
2. Make-up or Miscellaneous Conductivity -This conductivity with the probe installed in the fresh
make-up water line can be used to control the conductivity of the tower in terms of cycles of
concentration by calculating the difference between the make-up water’s conductivity and the
system’s conductivity. It can also be used to monitor another conductivity with no feed timers
associated with it.
3. pH - The pH function monitors and controls pH on a scale of 0-14 pH units.
4. ORP - The ORP function monitors and controls ORP on a scale of +/- 1000 mV.
3
Chemical Feed Timers
Chemical feed timers are designed to automate the addition of various chemicals by activating a relay output.
Multiple timers can be supplied depending upon the model number and each timer will include a relay output.
All timers can be programmed to be one of the following types.
1. Pulse Time - Accepts pulses from a make-up water meter (supplied separately). It can accumulate
1-9999 gallons before activating the timer to run.
2. Feed with Bleed - Activates the relay output simultaneously with the bleed and limits the amount
of time the relay output will be on during the bleed cycle.
3. Feed after Bleed - Activates the relay output based on a user defined percentage of time based
on the bleed off, another timer or digital input. The relay is activated after a bleed cycle and runs
for the set percentage of that bleed cycle.
4. Recycle - The relay is continuously repeating a defined OFF cycle time and a user defined ON
cycle time.
5. 28 Day - The timer is based on a 28 day cycle with four independent programmable feed cycles
with prebleed and bleed lockout settings.
II. Installation
Electrical Wiring
The MegaTron XS controller has an internal regulated fused power supply that will operate off of 90 to 250
VAC at 47 to 63 Hz on the incoming wiring. Each output relay is individually protected with a replaceable fuse.
Relay outputs will equal incoming line voltage.
! CAUTION !
1. There are live circuits inside the controller even when the power switch on the front panel is in
the OFF position. Never open the front panel without first disconnecting power from the outlet.
Prewired controllers are supplied with an 8 foot, 18 AWG power cord with USA style plug. A #1
Phillips driver is required to open the front panel.
2. Low voltage signal wires (probes, flow switch, water meter, etc.) should never be run
in conduit with high voltage (like 115VAC) wires.
3. Never attempt to land connections to the controller without first disconnecting power from the outlet.
4. Do not block access to disconnect power during mounting and installation.
5. The controller should be connected to its own isolated circuit breaker, and for best
results, the ground should be a true earth ground, not shared. Any attempt to bypass the grounding
will compromise the safety of users and property.
6. The electrical installation of the controller must be performed by trained personnel only and
conform to all applicable National, State and Local codes.
7. Operation of this product in a manner not specified by the manufacturer may result in damage
to equipment or persons.
8. Avoid mounting in locations that expose the controller to direct sunlight, vapors, vibration,
liquid spills or extreme temperatures; less than 0°F (-17.8°C) or greater than 120°F (50°C).
EMI(electromagnetic interference) from radio transmissions and electric motors can also cause
damage or interference and should be avoided.
NOTES:
1. Liquid tight fittings and some labeled signal leads are provided for all signal (low voltage)
4
connections for both pre-wired and conduit units.
2. Units should be ordered with the appropriate option to provide powered relays designed for the
incoming/outgoing power.
Pre-Wired
Pre-wired units are supplied with a 16 AWG cable(s) with 3-wire grounded USA 115 volt plug for incoming
power and 3-wire grounded receptacle cords for all control relay outputs also 16 AWG.
Conduit
Conduit units are predrilled at the factory and supplied with conduit knockouts for easy hard wiring to supplied
detachable connectors on the relay card(s) located in the lower section of the controller. Remove the screws
of the lower panel for access.
NOTES:
1. Do not drill holes in upper section of enclosure.
2. All relays provide a N.O. and N.C. output.
3. The control function that activates each relay output is pre-configured at the factory
based on the options selected. To change relay activation, see on page 24.
4. See page 35 for common bleed / blowdown valve wiring.
5. Refer to label inside lower panel cover for specific relay board configuration supplied.
6. Relays configured as “dry contact” should only have D.C. voltage ran through them. The GND
connection point replaces the NEU when configured for dry contact. (Example: Use GND and N.O.
for a normally open dry contact relay output.)
! WARNING: If jumpers are not configured Revfor
N dry contact,
Relay Boardline voltage will be supplied.
y on
MegaTron relay card revision N adds a 15 amp fuse on the incoming power
ollers
Relay Card Wiring to the board and small LED’s for each realy to indicate when the motherboard
has called for it to be activated.
Rev. I Relay Card Rev. N Relay Card
n Cable 10 Relays are shown configured for powered outputs.
9
[ Change jumpers to these configurations for dry contact. ]
Rev. D 2 10
Relay Fuses FUSE R1
ontact Powered relay Dry contact are 3 amp
1 9
olt relay R1 LED R4
elow Relay 1
FUSE R4
NEU 1 NEU
GND GND
LED Relay
N/O 4 4 N/O
N/C N/C
FUSE R2
Relays R2 R5 Relays
1-3 4&5
NEU LED
NEU
SE Relay
GND 2 GND
2
N/O N/O
LED Relay
N/C N/C
5 5
FUSE R5
R3
FUSE R3
NEU
USE GND LED
Relay
N/O 3
ange it 3 Incoming
N/C Rev N Power Fuse
GRD and
FUSE
5
Motherboard Connections
-12
+12
+12
+5
+5
6
4-20mA Output Card Wiring
A. Isolated Configuration
For isolated 4-20mA outputs an external power source for the loop must be supplied. JP4 and JP5 on the
board must be jumpered for isolated with an external power source supplied to the external VDC input. The
external power source must not exceed 24 volts DC.
B. Non-isolated Configuration
For non-isolated 4-20mA outputs the controller will supply the power for the loop. JP4 and JP5 must be
jumpered for non-isolated and no connections are made to the external VDC points.
NOTES:
1. If multiple outputs are being connected to a single energy management system, the negatives or
commons MUST remain isolated from each other.
2. The power for the mA output loop is always provided by the controller with either isolated or non-
isolated configuration.
The 4-20mA input card requires that the external device sending the 4-20mA input signal(s) supply the power
for the loop. The external power source must not exceed 24 volts DC.
03-
mA as non-isolated as shown. IN8 +
03+
Outputs For isolated outputs
02- IN7 -
J4 and J5 jumpers
ISO
1-4 IN7 +
ISO
02+
01- as shown to here. IN6 -
01+ J4 IN6 +
IN5 -
External VEXT-
IN5 +
VDC Input VEXT+
If J4 and J5 are set for isolated an VEXT-
V-
J8 external DC voltage must be VEXT+
V-
ISO
V- outputs. V-
Voltage
V-
Connections V+
If J8 & J6 and set for isolated as
V+ V-
shown instead of the standard non-
ISO
IN1+ IN2+
IN1-
LED
IN1+
LED
7
Mounting Instructions
Select a mounting location that provides the operator easy access to the unit and a clear view of the
controls through the cover of the controller. The location should be convenient to grounded electrical
connections, the needed sample line plumbing, and should be on a stable vertical surface.
Electrode Installation
MegaTronXS controllers may come configured for various circulating water systems. Listed below are
instructions for typical cooling tower and boiler installations. Your specific installation requirements may
differ but should conform to these instructions as much as possible for proper operation.
A. Cooling Tower
The standard probe(s) and/or flow assembly for cooling tower installations is constructed of schedule
80 PVC and supplied with 3/4” slip fittings for installing into a sample line. To insure proper operation the
sample line must have a flow rate of 3-10 gpm. Inlet pressure must be higher than outlet pressure in
order for water to flow past the electrode(s) to achieve the required rate. The probes are temperature
compensated for increased accuracy.
NOTES:
1. Install an isolation valve on either side of the flow assembly so electrodes can be
easily isolated for removal and cleaning.
2. A line strainer is recommended upstream from the probes to protect against fouling
and damage.
3. Mount pH or ORP electrodes vertically.
4. Green solution reference wire must be connected to either pH or ORP sensor. If both
pH & ORP are present on system card, only one solution reference connection is
needed.
5. Systems with a flow switch require 2-3 gpm flow rate to operate outputs.
WARNINGS:
1. Electrodes are O-ring sealed, which if damaged will cause a leak.
2. Do not allow pH sensor tips to dry out, damage will occur.
3. Do not exceed a water temperature range of 32°F to 140°F.
4. Do not exceed a maximum pressure of 125 psi.
8
Typical Cooling Tower Installation Diagram
COOLING TOWER
1 6
2 7
3 8
4 9
5 0
SET UP
ENTER HOME
RUN
BLOWDOWN
CANCEL HELP BACK
BLEED VALVE
MAKE-UP
WATERMETER TO DRAIN
TFS-C
FS-0C
1A9A000262 TFS-OC
E-30-PH
OR
pH Probe
PE-21 FS-T
-or-
OE-21
ORP Probe
PE-NUT
FS-B1-SP
9
B. Boiler
Standard boiler electrodes have a MNPT stainless steel bushing and are supplied with a FNPT cross
designed for mounting in the skimmer (surface) blowdown line. Sampling of the boiler’s water can be
achieved using one of two typical plumbing configurations (continuous sampling or timed and/or sample
& hold). For a successful installation, it is critical to observe the recommended distances and pipe sizes
provided in the installation drawings.
For best results, the electrode cross should be mounted in a 1”skimmer blowdown line within 4’ of
the boiler. Smaller line sizes and greater distances may affect the response time and accuracy of the
electrode. A flow-throttling device downstream from the probe (within 24 inches) is required to ensure that
the electrode is exposed to water and not steam. Properly installed and adjusted, this device will prevent
flashing in the electrode chamber.
NOTES:
1. Install a fully ported type valve between the electrode and the boiler. This
allows the electrode to be isolated for removal and cleaning.
2. A flushing line and 1/4 turn type ball valve should be installed in the bottom
of the cross to periodically “flush” sediment from the electrode chamber.
3. Make sure the alignment arrows on the probe end up parallel to the flow for
best performance.
WARNINGS:
1. The probe must be fully immersed in the system water to read correctly.
Steam flashing will result in incorrect readings.
2. Do not exceed a maximum water temperature of 436°F (224°C)
3. Do not exceed a maximum pressure of 350 psi (24.1 bar)
4. A throttling device must be installed downstream from the electrode.
Wiring Note: BE-4RTD probes require a 6-conductor cable from controller to probe, BE-32 probes only
require a 2-conductor cable.
10
Typical Continuous Sampling Installation
Fully ported
1
2
6
7
Throttling device gate or ball valve
3 8
4 9
5 0
SET UP
ENTER HOME
RUN
1" Continuous
CANCEL HELP BACK
! Warning - Do not use on bottom blowdown lines, only continuous or surface blowdown lines.
Throttling device
3 8
4 9
5 0
1" Continuous
blow down line
Fully ported
gate or ball
valve
Electrically actuated
blow down valve
! Warning - Do not use on bottom blowdown lines, only continuous or surface blowdown lines.
11
III. Front Panel Description
1 6
ACI MEGATRON
5 0
SET UP
ENTER HOME
RUN
NUMBER Keys- Used to enter new values in the SET UP mode and to access desired sub menus.
LEFT/RIGHT - Used to cycle through text or setting options to find desired setting.
SET UP/RUN - System initializes into RUN mode. Press this key to put the controller in SET UP
Mode and see HOME menu page.
BACK - Used to go back to last menu screen viewed or clear values keyed in that are not
wanted.
The bottom right box in the RUN screen mode is a hot key that will take you directly to a particular menu
screen. The default is the RELAY status menu, but this can be changed by navigating to the desired
screen and pressing the HELP button. Follow the on-screen instructions to set the new hot key location.
12
IV. System Operation Overview
Operation
RUN - This mode is for normal operation. In the RUN mode the display will show each system’s parameters.
If an alarm is present, the ALARM box will flash how many alarms are activated. No settings may be entered
or changed in the RUN mode. Readings are updated every 6 seconds on the screen while in the RUN mode.
Note: Conductivity readings from timed sampling or sample and hold systems (typically boilers) are only
updated at the end of a sampling period. Press the #2 key to force a sample and updated reading while in
the RUN screen.
SET-UP - This mode is used to adjust settings and readings on the controller. To access the SET UP mode
from the RUN screen, press the SETUP/RUN key.
Complete all installation steps before beginning this procedure. Ensure that all controlled devices (pumps,
solenoid valves, etc.) are operational and connected to the controller. Open the isolation valves to allow water
to pass through the sample stream assembly. Before beginning the startup procedure, familiarize yourself
with the programming and operation of the system by reviewing the menus available. Use the keys of the
controller to skim through all your options.
A. Calibration
All MegaTronXS controllers are factory calibrated for temperature, conductivity, pH and ORP. All units are
shipped with the date preset, and the clock set to your current time. These readings and settings should be
verified for accuracy and adjusted as per the instructions listed below.
1. Conductivity - To calibrate the conductivity reading, remove the electrode from the line and wipe the
flat surface with a clean cloth. Re-install the electrode and open the isolation valves to allow a sample
across the probe. Be sure to allow the reading to stabilize for one minute. Select “SYSTEM COND” from
the “CALIBRATION” menu. Then key in the corrected conductivity value. Press ENTER to log in that
reading.
Note: Boiler probes must have a fresh hot sample. See page 18 for more details.
2. pH - Under normal operating conditions, pH calibration is achieved using the following steps. From
the “CALIBRATION” menu, select “SYSTEM PH.” Enter the correct pH value. Press ENTER to log in the
new reading.
3. ORP - To calibrate ORP, from the CALIBRATION menu, select “SYSTEM ORP”. Compare the displayed
reading to the actual system ORP. If these readings do not match, key in the correct ORP value, and
push ENTER.
There are limits to how much the calibration can be adjusted. The instrument will only accept new conductivity
values which are from 1/3 to 8x the present reading. Any entry outside this range will cause a default to the
original reading. If this happens, call 1-918-686-6211 for technical assistance.
13
V. Menu Navigation
To access the menus press the Set Up / Run key on the front panel. This takes you to the Home menu.
MegaTronXS controller’s menus are easily navigated by pressing the associated number key next to a menu
box on the screen. Once you have stepped through the sub menus to reach a point at which a value or
selection is made a Pop-up window will appear prompting you to enter a desired value or selection.
NOTE: When entering new numeric values, enter all available digits (characters).
1. Home Menu
>HOME SETUP< From the HOME menu select the desired menu.
The menu name explains what parameters can be
SETPOINTS DATE/TIME programmed in the menu.
CALIBRATION CONFIGURE
TIMERS HISTORY
CUSTOMIZE WATER METER
ALARMS RELAYS
SET POINTS - Setting control set points for conductivity, temperature, pH and ORP.
CALIBRATION - Calibrating conductivity, temperature, pH and ORP if present.
TIMERS - Menu for selecting type and settings for all present feed timers.
CUSTOMIZE - Giving the controller, each system and all relays a user defined name.
ALARMS - View current alarms.
DAY/TIME - Menu for setting date and time.
CONFIGURE - Menus for configuring passwords, relay activations, setting history interval, flow
switch, contrast, temperature scale.
HISTORY - Allows for view history on board in a graph form.
WATER METER - Menu for configuring water meter totalizing.
RELAYS - Menu for resetting accumulated “ON” times and manual relay activation.
2. Set Points
The same basic format is used for defining each available analog probe input’s control parameters. Boiler
conductivity systems will also have an additional menu step for programming the sampling method desired
from continuous, timed or sample and hold.
SET POINTS - For setting the relay set points for the
>SYSTEM 1 SET POINTS<
available analog probe readings such as conductivity,
SYSTEM COND mA OUT pH, ORP, or temperature.
SYSTEM TEMP mA IN
SYSTEM pH AUX INPUTS
SYSTEM ORP
NOTE: In the Setpoint pop-up screen the direction (Rising or Falling) of the setpoint can also be set. Rising
setpoints will activate the control relay when the particular probe reading rises above the setpoint and will
stay activated until the reading comes down by the amount of the differential. If set for Falling the relay is
activated when the probe reading falls below the setpoint and stays on until the probe reading comes back
up by the amount of the differential.
14
2.1 Set Point Options
Note: Each alarm value can also be set-up to be displayed or not on the front screen as well as remotely
notified or not if connected to the Web Advantage server.
Note: If continuous is selected the standard settings are used for system conductivity and the
miscellaneous conductivity (labeled M COND) is the set points menus.
2.3 pH
The pH set point settings follow the same format as shown above in section 2.1.
Note: When the Limit Time value is met it will force off the control relay being driven by pH or ORP. To
reset the limit timer and get the control relay active again, enter a new Limit Timer value.
15
2.4 ORP
The ORP set point settings follow the same format as shown above in section 2.1 and 2.3.
Conductivity on boiler systems can be configured for Timed Sampling, Sample and Hold or Continuous for
the conductivity sampling method.
Timed sampling incorporates a sample timer which allows the boiler to be sampled at periodic intervals.
Sample intervals are adjustable from 1 minute to 99 hours, 59 min. Sample duration (on-time) is adjustable
from 1 second to 99 minutes, 59 seconds.
Sample and hold uses a sample timer for periodic sampling intervals. The unit will sample for its duration
and then hold the blowdown valve closed for a settable period (hold time). The conductivity is checked at the
end of the hold period, if additional blowdown is required the blowdown valve is held open for a preset amount
of time (blowdown time). Then sample cycle is repeated.
Pulse Sample allows the use of a defined “pulse” type feed timer to initiate a sample based on make-up
water instead of the sample interval timer.
Continuous sample has a sample of boiler or condensate water go past the probe continuously. If the
reading is above the set point, blowdown will continue until the set point has been satisfied.
16
2.6 Aux Inputs
Auxiliary inputs are the digital inputs for optional Flow Switch and other digital inputs such as low drum level
alarms. From these menus the user can set if they want each of the alarms Displayed, Remote Notification,
both or none.
Units with a 4-20mA output option will have a menu for setting up the 4-20mA output. The 4mA and 20mA
values can be defined by giving the output proportioning capability. i.e. 4mA = a pH of 6.0 and 20mA = a pH
of 8.0.
3. Calibration
Calibration is for adjusting the displayed value of a probes reading to match your tester or known solution.
Pick the system or mA input first. From a particular system pick the probe to calibrate.
17
3.1 Conductivity Calibration
NOTE: In the calibration pop-up window the raw analog to digital (A/D) value will be displayed. A new
calibration value should only be entered when the probe is sensing a stable A/D value. If the system is a
boiler the associated relay can be forced on in the pop-up to allow for a fresh hot sample. Boiler probes should
have fresh hot water blown past them for a minimum of 2 minutes before calibrating. The A/D reading has a
range of 0 to 32,767. If it is at one end of the range or the other when trying to calibrate something is
wrong with the probe or wire run.
>SYSTEM 1 pH CALIBRATION< 1 POINT - With a clean probe on-line seeing the system’s
water enter the known (tested from a calibrated hand-
1 POINT CAL held tester) value.
2 POINT CAL 2 POINT - Enter a known Low value with a clean probe
in a buffer solution. Then enter a known High value with
the clean probe in a buffer.
Notes: 1. Probes must be rinsed between buffers when doing a 2 Point calibration and given at least
30 seconds in solution to adjust to the buffer.
2. There must be at least 2 full pH points between buffer solutions. Using a buffer of 4 and 10
is the best procedure. ORP buffers should be at least 200 points apart.
>mA OUTPUT 1 CALIBRATION< While in the High or Low calibration pop-up screen use
the up and down arrows to change the output value
OUTPUT 1 CAL HIGH being read with the volt meter. Adjust the High value
4000 for the 20-mA reading and the Low value for the 4 mA
Use Up/Down arrows to change value.
Use Enter to save value
18
3.4 4-20mA Input Calibration
4-20mA inputs can be calibrated to ensure that the input seen by the controller from the external device
match. It also allows for setting the 4-20mA input into a number range that relates to the value being read.
The 20mA and 4mA values are where the controller’s raw analog to digital value is adjusted to match a
20mA (full scale) and 4mA (bottom of scale) signal from the external device inputting the 4-20mA input. The
external device must be connected to the controller and showing either full scale or bottom of scale when
calibrating each. The number shown along with either the 20mA or 4mA while calibrating is the raw A/D value
and is only a reference. A 20mA input should be around 5500 and 4mA around 1100. If the A/D numbers are
not in this range check input device.
The MAX and LOW calibration inputs are for telling the controller what to display for a 20mA input and a 4mA
input. For example, if the input is a drum level sensor monitoring a 55-gallon drum the value for MAX should
be 55 and LOW should be 0. The controller then displays a number automatically ranging between 55 and
0 based on the input value. The units of measure (gallons for example) is set in the Customize menu from
the Home page.
OFFSET - Changes the current displayed value of the 4-20mA input reading to allow for a manual 1pt
calibration of the displayed value.
FACTORY DEFAULT - If the 20mA or 4mA calibration has been incorrectly set (not at 4 or 20) this will reset
the settings back to a factory value for 4 and 20.
4. Timers
A unit may have up to 5 selectable timers for each system on a controller. All timers are associated with their
system, so for a % of post bleed timer looks at the bleed of that system.
>SYSTEM 1 TIMERS< TIMERS - Select the type (28-day, pulse, limit, percent,
recycle, percent of post bleed, or other event) as well
TIMER 1 as the run times of each timer available per system.
TIMER 2
TIMER 3
TIMER 4
TIMER 5
19
4.1 Timer Type Selection
A pop-up screen lets you scroll through the various timer types available.
Each timer type selected will have its own unique Set Up
>SYSTEM 1 TIMER 1 SET UP<
sub menu with additional selections specific to the type
TIMER TYPE: PULSE of timer selected. The page displayed before entering
GALLONS: 10 the Set Up menu of a timer provides an overall review
RUN TIME (MM:SS): 01:00
INPUT: WATER METER 1 of the timer’s current settings.
20
4.5 Post Bleed Timer
Each 28-day timer has Program 1-4 for programming the various feed times. While the programming steps
for four programs are the same each can have it’s own independent settings.
NOTE: ORP lock is only for systems with the ORP function. If interlocked the ORP set point will switch to
the 2nd setpoint for control during the timer’s programmed RUN time. The feed device must be connected
to a relay activated by the ORP setpoint/control function.
21
5. Customize
This menu allows the user to define the on-screen name of the unit plus the name of each system and relay.
The user can also setup the Notepad for each system and 4-20mA Input’s name and unit of measurement.
NOTE: When entering values for custom names use the numerical keys for numbers and the up / down
arrows to scroll through all the characters of a key board. Press the right arrow to advance the curser after
setting a desired value. Press the Help button to place the last entered character into the new cursor space
to speed up the process. The Help button will also jump advance through the characters.
5.1 Notepad
The Notepad function allows the user to set up a customized manually entered data field for each system with
ten notepad items. The NOTEPAD is ideal for setting up and storing into the controller’s history the items
typically tested for reporting a service call. The Notepad items come with no names but when an individual
note is selected a menu for setting it appears.
>NOTEPAD SYS 1 NOTE 1< NAME - Pick from a list of defined names or customize
your own.
NAME NUMBER - Set the number range.
NUMBER UNITS - Set the units of measurement.
UNITS ALARMS - Set Hi/Low alarm points and how frequently
ALARMS a new value is expected to be manually enter via the
History menu.
5.2 mA Inputs
5.3 pH Index
If the controller has the pH index option (must have pH control) user can select LSI or RSI indexing. The
controller will automatically set some Notepad entries for manually inputting needed data to perform the
calculation which will be displayed in the RUN screens.
22
5.4 Run Screen
6. Alarms
>SET DATE AND TIMES< DATE AND TIME - For setting the date, time, day and
week on the controller.
SET DATE
SET TIME
SET DAY
SET WEEK
Friday May 14, 2005 03:04:56
8. Configure
Provides access to menus to set-up passwords, relay activation, temp scale, display contrast, flow switch,
inputs, history time stamps, factory set-up and system information.
8.1 Password
23
8.2 Relays
Additional relay logic is available with up to 3 additional Activators and up to 4 Disablers allowing multiple
functions to activate the same relay and multiple functions to prevent the relay from coming on. There is
also a Daily Max amount of time that a relay can be on. If a relay is on for the max amount, it does not
let the relay come on anymore that day. (A 24-hour clock is used for the day with midnight being the start
of the day). The Delay setting is the amount of time a control function must come on before the relay will
react and activate. This is to prevent a relay from chattering on/off if a reading is bouncing around the set
point or alarm.
8.3 History
This menu is used to set the history “time stamp” interval, the water meter daily history starting hour, the
alarm delay period and the USB history save format.
This menu allows the user to select if a flow switch signal will represent a flowing condition when a “closed”
or “open” signal is seen for each system’s flow switch input. User can also select if timers can work always
or only with flow.
8.5 Contrast
This menu is used to adjust the contrast of the display.
24
8.7 Network
The Network menu is used when a controller is being remotely communicated with either a local network
connection or over the internet on the Web Advantage server.
System information will identify the version of firmware installed in the controller along with the controller’s
serial number.
9. History
The onboard history allows for viewing the history of the probe readings, relay activations, key-pad activity,
calibrations, water meter hourly and daily logs and alarms for each system present. It is also where Notepad
data is entered and reviewed. An initial overview page is displayed showing your current sample interval, the
calculated number of days the unit can keep probe history for before losing the oldest. The number of sensor
samples and relay/alarm events and Notepad entries currently stored is also displayed.
25
9.2 Notepad Entries
The water meter history allows the user to review both water meter one and two of a particular system in both
an hourly format (for the past 24 hours) or a daily format for the past 60 days. If an evaporation calculation
is being kept, a daily history of this value is also available.
Each system with a timer on it will have 2 water meter inputs. Each of these can have the incoming contact
defined allowing the controller to keep track of water usage. If desired the controller can calculate evaporation
loss by subtracting the deference between a systems 2 water meter inputs.
MegaTron XS controllers with “W” option may have 1 to 4 auxiliary flowmeter inputs. These additional inputs
are for tracking various flow meter devices (additional water meters or flowmeters in a metering pump’s
discharge tubing). They can also be linked to a system’s water meter input for additional tracking and alarm
capabilities including: bleed flow/no flow, exceeding too much flow in a 12- or 24-hour period. Units with
Auxiliary Flow meter inputs have a Home menu selection for Totalizers. The Totalizer menu has selections
for each of the System Water Meters plus one named Aux Meters.
AUX METERS
26
10.2 Aux Meters
A unit may have 1 to 4 Aux Meters. These additional inputs are for tracking various flow meter devices
like Advantage Controls’ FloTracker in a metering pump’s discharge tubing. They can also be linked to a
system’s water meter input for additional tracking and alarm capabilities.
VERIFY ALARM - If a flow meter is linked to a control relay the controller will give an alarm if it does not
receive a contact or pulse from the aux meter within the amount of time defined or if it gets a contact when
the relay is not on.
RELAY LINK - The relay link informs the particular aux meter input is relevant to the control function that the
selected relay is being driven by. For example, if the aux flow meter is a metering pump’s FloTracker then it
should be linked to the relay that is driven by the feed timer that pump will be controlled by. If the aux meter
is going to be linked to a water meter in a bleed of line, then it should be linked to the relay that is controlling
the bleed off valve.
27
VOLUME ALARM - If FloTracker has been selected as the Tracking method, an alarm will occur when the
defined VOLUME USED has passed through the flow device.
Note: If Rate and Volume tracking has been selected an alarm will occur if the defined MAX VOLUME
amount is measured within the defined TIME CYCLE which can be a 12-or-24 hour period.
METER LINK – This selection only shows if the tracking method is Rate and Volume and tells the auxiliary
flowmeter input to get its signals from one of the system water meters already wired to the controller’s water
meter inputs. If this is selected no wiring to the auxiliary input is required and the PULSE VALUE and UNITS
settings are auto populated from the particular water meter’s settings.
11. Relays
28
MegaTron Quick Steps
3 ALARMS! DR RELAYS
WebAdvantage Format Friday, February 6, 2015 15:50:47 Wk1
without header row
Step 3:
Push the SET UP RUN button to get this screen. From
here push CONFIGURE (Button 7) to go to the next
screen.
Sample Log Data “log.txt” files
>HOME SETUP<
SETPOINTS DATE/TIME
To change formats, see Step 2. CALIBRATION CONFIGURE
TIMERS HISTORY
CUSTOMIZE WATER METER
ALARMS RELAYS
29
MegaTron Quick Steps
30
MegaTron Quick Steps
The XS has the ability to copy the User Settings 3 ALARMS! DR RELAYS
from one XS to another. This process is referred to Friday, February 6, 2015 15:50:47 Wk1
as cloning.
The User Data will be loaded into the XS from the
1
2
3
6
7
8
1
2
3
6
7
8
1
2
3
6
7
8 USB drive. Once the pop-up window closes, cloning
has been completed.
4 9 4 9 4 9
5 0 5 0 5 0
SET UP SET UP SET UP
ENTER HOME ENTER HOME ENTER HOME
RUN RUN RUN
Notes:
• Not all customized names will be cloned.
Step 1: • If you have trouble reading clone files, insure
With the controller powered up, plug the USB drive that the XS you are cloning has current
into the XS USB port. The USB DRIVE DETECTED firmware.
31
VII. Maintenance
The only required maintenance for normal uninterrupted operation of your MegaTronXS controller is cleaning
of the electrode(s). After initial startup, it is a good idea to clean the electrode frequently until a schedule
based on need has been developed. Since each application is unique, it is difficult to estimate the required
frequency of cleaning. The first cleaning should take place after about one week of the system being on line.
To determine the required cleaning frequency, record the reading on the controller before the electrode is
removed for cleaning. After cleaning, record the new reading. If a change is observed in the two readings,
the electrode was dirty. The more significant the change, the dirtier the electrode. If no change occurs,
cleaning needs to be done less often.
Many times, an electrode can appear to be clean, but the unit still cannot be calibrated. If this is the case, use
one of the more aggressive electrode cleaning procedures listed in step 4 above. Recheck the calibration
after completion of this procedure. If no change was observed in the reading, replace the electrode. If a
change occurred but the unit still will not calibrate, repeat procedure as many times as necessary.
Slow response or non-reproducible measurements are signs that the electrode has become coated or
clogged. The pH glass is susceptible to mounting by many substances. The speed of response, normally
95% of the reading in less than 10 seconds, is dramatically degraded when the pH glass is coated.
To restore the speed of response for a pH electrode, clean the bulb with a high-quality detergent, methyl
alcohol or other suitable solvent using a “Q-tip”. Rinse well with distilled water and retest. If the electrode
now responds, but erratically, soak the sensor in 0.1 Molar HCl for 5 minutes. Remove and rinse with water
and place in 0.1 Molar NaOH for 5 minutes. Remove, rinse again and then place the sensor in pH 4. buffer
for 10 minutes before use.
32
VIII. Troubleshooting
The MegaTronXS controller is designed for many years of trouble-free operation. Should a problem occur,
refer to the following chart to help identify the problem. If replacement is required, follow the procedures
listed in the Warranty and Factory Service portion of this manual.
33
IX. Advantage Controls’ Product Warranty
Advantage Controls warrants control systems of its manufacture to be free of defects in material or
workmanship. Liability under this policy extends for 24 months from date of installation. Liability is limited
to repair or replacement of any failed equipment or part proven defective in material or workmanship
upon manufacturer’s examination. Removal and installation costs are not included under this warranty.
Manufacturer’s liability shall never exceed the selling price of equipment or part in question.
Advantage disclaims all liability for damage by its products caused by improper installation, maintenance,
use or attempts to operate products beyond their intended functionality, intentionally or otherwise, or any
unauthorized repair. Advantage is not responsible for damages, injuries or expenses incurred through the
use of its products.
The above warranty is in lieu of other warranties, either expressed or implied. No agent of ours is authorized
to provide any warranty other than the above.
FCC Warning
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in
strict accordance with the manufacturer’s instruction, may cause interference to radio communications. It
has been type-tested and found to comply with the limits for a class A computing device pursuant to subpart J
of part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when
operated in a commercial or industrial environment. Operation of this equipment in a residential area is likely
to cause interference in which case the user, at his own expense, will be required to take whatever measures
necessary to correct the interference.
34
Common boiler blowdown valve connections.
N.O.
COM
N.O.
N.C.
GND N.C.
N.O.
COM COM
COM
N.O.
N.C.
SOLENOID
1
1
2
1
3
2 3 4 5 6 7 8 9 10 1
3
MOTORIZED
4
2
BALL
M
5
VALVE
6
7
M N.O
CO
8
9
COM (1 - WHITE)
N.C
10
N.O. (2 - BLACK)
11 2
GND ( - GREEN)
11
12
SOLENOID VALVE
(TOP VIEW)
LIMIT SWITCH MBWA 1075
MBWB 1036 MOTORIZED BALL VALVE
(SIDE VIEW)
MBWB 1036 MBWA 1075 BLOWDOWN VALVE
(TOP VIEW)
(+
D
RE
Input 1 -
Input 1 +
LED
BROWN (-4-20)
ORANGE (+4-20)
35
Pyxis Fluorometer System 4-20mA Comm Card
Aux Flow Inputs
+5
Open Input 1
Wiring for Slot Slot Slot
Input 2
Input 3
Battery
full manual for +12
+12
additional +5
+5
information C
VD
2
)1
(-
C K
BLA C
VD
-12
+12
+5
+5
Input 1 -
Input 1 +
LED
GREEN (-4-20)
WHITE (+4-20)
36
CABLE-7P-2A
Wiring a Nano-M to a
MegaTronXS, or
*Other Building Management System
-12
+12
+12
+5
+5
BLACK (ground)
Input 1 -
Input 1 +
RED
LED
*Or to other Conductivity
Water Flow Contrast
Meter Meter
Building
Management
System - -
Red
Black
White
Green
+
+
OFF
ON
5
4 3 2
1
Nano-M
Motherboard
Ground - Black
Hot - Red
Corrosion 4-20mA
37
MegaTron wiring for Autorol Turbine Meters
1” METER = 65 PULSES / GALLON
MegaTron XS
2” METER = 15 PULSES / GALLON
Aux Flow Inputs
+5
System 4-20mA Comm Card
Note: Use 22 AWG (.76 mm) Slot
Open
Slot Slot Input 1
Input 2
twisted pair shielded wire Input 3
Input 4
for all of these low voltage VDC Output
Connections
Gnd
Gnd
signal connections. Gnd
Gnd
-12
Battery
-12
+12
+12
+5
+5
MegaTron Red
Aux Flow
LED
PIC Chip
B Ground
B Ground
Green
White
Black
Black
Black
R All 3
Red
Red
Red
W
W
W
Drum Level 2
Drum Level 4
Drum Level 3
Signal Aux Flow 3
Signal Aux Flow 2
Ground
pH
pH
Ground
Ground
ORP
Aux Flow +5 vdc
Ground
Ground
Aux Flow
ORP
Aux Flow
+5 VDC
Conductivity
Temperature
Flow Switch
38
Notes
39
Get the Advantage in Water Treatment Equipment
Advantage Controls can give you the Advantage in products, knowledge
and support on all of your water treatment equipment needs.
Solenoid Valves
Water Meters
Feed Timers
Filter Equipment
2 6
3 7
4 8
ENTER
5 9
SET UP 0
RUN ENTER
HOME
CHANGE
HELP
BACK
40