0% found this document useful (0 votes)
38 views

Flow Chart-Selection

The document outlines the selection process and parameters required for choosing refrigeration equipment for cold rooms and blast rooms. It involves first calculating the heat load, then selecting a condensing unit with sufficient capacity based on the heat load and operating temperatures. Finally, an evaporator is chosen that matches the condensing unit capacity and also accounts for the evaporator temperature and refrigerant type. The process ensures the selected equipment can adequately maintain the room temperature given the product load and conditions.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
38 views

Flow Chart-Selection

The document outlines the selection process and parameters required for choosing refrigeration equipment for cold rooms and blast rooms. It involves first calculating the heat load, then selecting a condensing unit with sufficient capacity based on the heat load and operating temperatures. Finally, an evaporator is chosen that matches the condensing unit capacity and also accounts for the evaporator temperature and refrigerant type. The process ensures the selected equipment can adequately maintain the room temperature given the product load and conditions.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Selection Process Software to be used essential Parameters required

Heat Load Calculation Blue cold app for heat load calculation For cold room
( To obtain the heat load KW required ) Identify if it is cold room or blast room Room size, Total Quantity of product that can be kept inside the room (kg)
( You can avoid this step if the customer directly gives the heat load ) Room temp, Daily load -quantity of product kg coming into the room per day
Product

For blast room


Room size, Quantity of product that is blast freezed or blast chilled per batch
Room temp, Pull down time

Selection of condensing unit Check whether you can select it in Blue select air cooled CDU or water cooled CDU software. heat load KW
Condensing unit cap = or > heat load KW If not go to bitzer software and select compressor. Evap temp or room temp
After selecting compressor get the condensing unit model no from blue cold software Refrigerant

Condensing temp/air cooled/water cooled

Selection of evaporator Use blue select software to select evaporator. KW-Cooling cap of CDU
Evaporator cap = or > condensing unit cap Identify the series (BLC,BHN,BFZ,BSL etc) Evap temp or room temp
Refrigerant

You might also like