0% found this document useful (0 votes)
272 views10 pages

Bacstat II

The document provides an installation guide for the Delta Network Thermostat BACstat II DNT-T221. It includes specifications for the thermostat such as its communication capabilities, temperature and humidity sensors, inputs and outputs. It also details the package contents, relevant documents, board layout, jumpers and wiring diagram to assist with installation.

Uploaded by

nhiahm nhiahm
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
272 views10 pages

Bacstat II

The document provides an installation guide for the Delta Network Thermostat BACstat II DNT-T221. It includes specifications for the thermostat such as its communication capabilities, temperature and humidity sensors, inputs and outputs. It also details the package contents, relevant documents, board layout, jumpers and wiring diagram to assist with installation.

Uploaded by

nhiahm nhiahm
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

INSTALLATION GUIDE

Delta Network Thermostat: BACstat II


DNT-T221 (Rev 2.2)
Document Edition 1.6

Product Description

The DNT-T221 is an intelligent room thermostat with a custom 3-


value, 96 segment, LCD display. The DNT-T221 has the ability to
communicate on Delta’s proprietary LINKnet network or directly on an
BACnet MS/TP network.
It is capable of displaying a wide range of digital or analog values,
including setpoints, temperature, air flow, heating and cooling status,
fan speed, valve and damper position, and more.
When connected on a BACnet MS/TP network the DNT-T221
functions as an independent BACnet thermostat. When connected to a
Delta Controller on a LINKnet network it provides programmable
remote sensor and expanded I/O capabilities.

Contents
MODEL NUMBERS & ACCESSORIES............................................................................ 2
PACKAGE CONTENTS ...................................................................................................... 2
OTHER RELEVANT DOCUMENTS................................................................................. 2
PRODUCT SPECIFICATIONS .......................................................................................... 2
BOARD LAYOUT................................................................................................................. 4
JUMPERS .............................................................................................................................. 5
MOUNTING .......................................................................................................................... 5
WIRING DIAGRAM ............................................................................................................ 6
POWER.................................................................................................................................. 7
NETWORK CABLING & REQUIREMENTS .................................................................. 7
NETWORK TOPOLOGY.................................................................................................... 8
CAUTIONS & WARNINGS ................................................................................................ 9
COMPLIANCE DECLARATIONS .................................................................................... 9

Document Edition 1.6 Page 1 of 10


Delta Network Thermostat: BACstat II DNT-T221 (Rev 2.2) Installation Guide

Model Numbers
Features DNT-T221 DNT-H121
Internal Thermistor Input
Internal Humitity Input
Additional I/O 2 IP, 3 OP 1 IP, 3 OP
Backlighting Option B
External Input Terminator Option X
Button Icons INT INT

An appended button icon code must be included to specify the desired icons embossed on the buttons as
follows:
[default] Bottom 2 buttons are ▼ and ▲ (Setpoint Adjust), top 2 are OFF and ON
INT Bottom 2 buttons are ▼ and ▲ (Setpoint Adjust), top 2 are O and I – International
You need not specify button icons if you want the default, but must specify INT if you want the international
button icons. (i.e., DNT-T221-INT).

Package Contents
• Delta Network Thermostat: BACstat II Product, DNT-T221 (Rev 2.2)
• DNT-T221 (Rev 2.2) Installation Guide

Other Relevant Documents


• Delta Controls Wiring Guidelines
• BACstat II Application Guide (for Configuration & Programming)
• ORCAview Operator Guide
• ORCAview Technical Reference Manual
• BACstat II, DAC and DCU Release Notes

Product Specifications
Power Requirements
• 24V AC, 50/60 Hz (Class 2)
• 17 VA maximum (with internally powered triac at full load)
(5VA without triac loading)

Ambient Ratings
• 32º to 131º F (0º to 55º C)
• 10 to 90% RH (non-condensing)

Page 2 of 10 Document Edition 1.6


Delta Controls

Communication Port
LINKnet Connection
• Communications Speed @ 76,800 bps
• Up to 12 Devices per segment (depending on the controller), only two of which can be DNT or DFM
devices
BACnet MS/TP Connection
• Communications Speed @ 9,600 or 19,200 or 38,400 or 76,800 bps (the default)
• Maximum of 99 nodes per MS/TP segment (50 without a repeater)

Temperature Sensor (IP1)


• Thermistor Input – 10,000 ohm @ 77 ºF (25 ºC)
• Accuracy of +/- 0.36 ºF from 32 - 158 ºF (+/- 0.2 ºC from 0 - 70 ºC)
• Display Resolution of 0.1 ºF or ºC
• Stability of 0.24 ºF over 5 years (0.13 ºC)
• Optional Termination point for an External Thermistor on Input 1
• Jumper Selectable for Internal or External Thermistor
• Use a standard 10 KΩ Thermistor (10,000 ohm @ 77 ºF / 25 ºC)
Humidity Sensor (DNT-H121 Model Only)
• Accuracy of +/-2% RH from 0-100% RH (25ºC, VSUPPLY = 5Vdc)
• Display Resolution of 0.1 %
• Stability of +/- 1% RH typical @ 50% RH over 5 years
*Note:Extended exposure to >90% RH causes a reversible shift of 3% RH

Inputs (Additional)
• 2 Universal Inputs (10 bit), jumper configurable for the following input types:
0-5 VDC
0-10 VDC
10 KΩ Thermistor
Dry Contact (using 10 KΩ Thermistor jumper setting)

Outputs
• 2 Analog Outputs
0-10 vdc @ 20 mA maximum per output
• 1 Binary Triac Output
Switching 24 VAC @ 0.5 Amp maximum per output
Leakage Current per Triac is 160 µA
Internally Powered with 24 VAC (so an external power source should not be used)
Software Configurable for Binary, PWM, Time Proportioned

Technology
• 8-bit Processor c/w internal A/D, Flash, and RAM
• 3-value LCD c/w icons (96 total segments) and optional backlighting
• 4 stylized momentary push buttons with tactile feedback

Document Edition 1.6 Page 3 of 10


Delta Network Thermostat: BACstat II DNT-T221 (Rev 2.2) Installation Guide

Device Addressing
LINKnet Connection
• Set via Keypad Configuration Setup
• Address Range: 1 to 12
BACnet MS/TP Connection
• Set via Keypad Configuration Setup, or Software Setup
• Keypad MAC Address Range: 1 to 99 per network segment
• Software Address Range: As per the BACnet standard
• Supports DNA – Delta’s intuitive addressing scheme

Size
• 5” x 3.25”x 1” (12.7 cm x 8.3 cm x 2.5 cm)

Weight
• 0.3 lb. (120 g.)

PCB Board Layout

NET PW R
AO1, AO2, BO3 & Network, Power and
IP3 Connector Posts IP2 Connector Posts
BO3 AO2 AO1 GND IP3 IP2 [-] [+] GND 24~

IP2 &IP3 Input Type


10k
10V 5V

Selection Jumpers

Note: All field wiring is


terminated on the Sensor
Backplate mounted on the
wall.
IP1
External Thermistor
GND
Wiring Terminals (10k)
DNT-T221
xxxxx/xxxx

Temp. Input (IP1) EXTERNAL

Connection Selection
RJ11 Service Port
INTERNAL

Jumper

Page 4 of 10 Document Edition 1.6


Delta Controls

Jumpers
INPUT SIGNAL TYPE
10K
The input type is selected by placing the jumper in the correct location on
the Input Type Selector Block. The diagram to the left shows the factory
5V
default selection of 10 KΩ.

10V
10K For 10 KΩ Thermistor temperature sensors, as well as Binary
or Dry Contact inputs.

5V For sensors and other field devices that use a 5 VDC signal.

10V For sensors and other field devices that use a 10 VDC signal.

INPUT CONNECTION SELECTOR – DNT-T103X MODELS ONLY


EXTERNAL
This jumper is used to select whether the internal Thermistor sensor or a
remotely located Thermistor is connected to IP1. The diagram to the left
INTERNAL
shows the factory default selection of the Internal 10 KΩ Thermistor.

External For connecting a remotely located 10 KΩ Thermistor


temperature sensor to IP1, which is wired to the connection
terminals provided.

Internal For connecting the internal 10 KΩ Thermistor temperature


sensor to IP1.

Mounting
The BACstat II backplate is designed for mounting directly on standard North American, European or
Australian electrical boxes.

Document Edition 1.6 Page 5 of 10


Delta Network Thermostat: BACstat II DNT-T221 (Rev 2.2) Installation Guide

Wiring Diagram

INPUT OUTPUTS
PWR NET INPUT
24~ GND + - IP2 IP3 GND AO1 AO2 BO3

24 VAC Power Connection


Input 3 Connection
Network Connection Output 1 (AO) Connection
Output 2 (AO) Connection
Input 2 Connection
Output 3 (BO) Connection

Refer to
Note 2 below.

BACKPLATE
CAUTION:
The network shield and any other bare wires should be bent back and taped to ensure that they do
not come into contact with the board electronics and cause a short. Otherwise you run the risk of
damaging the BACstat.

Notes:
1. Note that the DNT-T221 has different wiring connections from the DNS-24 and DNT-T103.
2. If wiring 2 or more outputs, you will need a wire nut to terminate all the outputs to GND.
3. Ensure you use the recommended balanced cable for the network and follow documented RS-485 installation
guidelines for MS/TP or LINKnet networks.
4. Do not use 4-wire multi-conductor cable for network and power, as it will not meet the balanced cable
requirements for the MS/TP or LINKnet networks. Use two separate cables: one for the network and the
other for power.
5. Do not terminate the network shield on the BACstats, but ensure shield conductivity is maintained along the
network from end-to-end with wire nuts (i.e., Marrettes™) as necessary.
6. If the same power source is used for more than one device, ensure that the transformer is properly sized for the
rated VA and ensure that the same polarity is observed from device to device.

Page 6 of 10 Document Edition 1.6


Delta Controls

Power
The DNT-T221 BACstat II requires a 24V AC Class 2 power supply rated for at least 17 VA. This includes
output loading of the internally powered triac (0.5A max @ 24 VAC) and the two analog outputs (20mA max
each).

More than one device – not including DCUs or V2 products – may be connected to the same transformer,
providing the transformer is properly sized, including line losses, and polarity is observed between controllers
(in regards to 24~ and GND). The transformer must ONLY be used to provide power to other MS/TP or
LINKnet devices and field devices powered through its outputs. Auxiliary field devices (i.e., 4-20 mA
devices) that don’t use ½ wave rectification must be powered separately.

For more information refer to the Delta Controls Wiring Guidelines.

Network & Cabling Requirements


To ensure network stability and reliable communications, particularly at high speeds on the RS-485 MS/TP or
LINKnet networks, it is imperative that you adhere to the following network and cabling requirements:

Item Description
Cabling For MS/TP and LINKnet networks it is recommended that you use network cabling that
matches the following specifications:
• Balanced 100 to 120 ohm nominal impedance Twisted Shielded Pair (TSP) Cable
• Nominal capacitance of 16 PF/FT or lower
• Nominal velocity of propagation of 66% or higher

Topology For MS/TP and LINKnet networks, ensure the cable is installed as a daisy-chain from one
device to the next.
Max. Nodes • MS/TP: The maximum number of devices per MS/TP network without any repeaters is 50.
• LINKnet: Up to a maximum of 12 Devices (depending on the controller), only two of
which can be DNT or DFM devices. (Refer to Appendix G in the Technical Reference
Manual for more information.)

Termination • MS/TP: A termination board must be installed at each end of each MS/TP network segment
Boards – or two per MS/TP or LINKnet network. Ensure you do not overlook this in laying out
your network architecture and ordering product.
• LINKnet: Termination boards need not be installed for only one or two nodes.
However, install a termination board on each end of the network when there are more
than 2 nodes.

Repeater • MS/TP: A repeater (RPT-768) is not necessary unless more than 50 nodes will be installed
on a network or you need to extend the network beyond 4000 ft (1220 m).
• LINKnet: Repeaters should not be necessary. Ensure the maximum distance is no
more than 1000 ft (300 m).

For more information refer to the Delta Controls Wiring Guidelines.

Document Edition 1.6 Page 7 of 10


Delta Network Thermostat: BACstat II DNT-T221 (Rev 2.2) Installation Guide

Network Topology
1. BACstats Configured as MS/TP Subnet Devices
With V3.21 firmware or higher, one possible MS/TP network architecture has the MS/TP devices configured as
Subnet devices, allowing BACstats to reside on the MS/TP network with other Subnet devices. Note that
V3.21 requires a DCU, while V3.22 or higher may use any System Controller instead.

2. BACstats Configured as LINKnet Devices


The BACstat may reside on LINKnet instead of MS/TP. However, this requires a controller that supports a
LINKnet network for I/O expansion. The maximum LINKnet devices with or without I/O depends on the
controller. All built-in applications must be disabled, but the I/O may be muxed (with V3.22 firmware).

Network Diagram (with V3.22 Firmware) Ethernet Note:

If the DCU or DSC has Ethernet capability, it may exist on an


TRM Ethernet network with other controllers in the same building, on which
ORCAview PTP the ORCAview OWS could reside as well (instead of PTP).
OWS

MS/TP Notes:

System Devices RS-232 RS-485 1. Ensure you use the recommended balanced cable.
2. Ensure the cable is installed as a daisy-chain from one device to
DSC-1616EX [DCU] the next (4,000' or 1220m maximum).
DSC-1616(H/E) DCU/DSC 3. Ensure you install an MS/TP terminator board (TRM-768) on each
DSC-1212(H/E) end of each MS/TP network.
DSC-1280(H/E) 4. The maximum nodes per MS/TP network is 50 without a repeater,
DSC-T305
(System Device) or up to 99 with at least one repeater (RPT-768).

Subnet Devices
TRM TRM
16x16 Controller BACnet (MS/TP) - Level 3 Network (Subnet)
12x12 Controller
12x8 Controller
6x6 Controller
Room Controller DFM
VAV/VVT Controller NET1 NET2 NET1 NET2
Lighting Controller DAC DAC
BACstat I
BACstat II (Subnet (Subnet
(with or without I/O) Device) Device)
Input Field Modules

LINKnet Notes: Level 4 Level 4


Network Network
1. Ensure you use the recommended (LINKnet) (LINKnet)
LINKnet Devices balanced cable.
TRM
BACstat I 2. Ensure the cable is installed as a
BACstat II daisy-chain from one device to the
next. (1000' or 300m maximum).
(with No I/O)
3. Ensure you install MS/TP terminator DFM DFM
BACstat II boards when you have more than 1 or
(with muxed I/O) 2 devices.
I/O Field Modules 4. Depending on the controller, up to 12
devices are supported on a LINKnet
network, with limitations on how many
of these may have I/O. (Refer to
the Technical Reference Manual.)

Page 8 of 10 Document Edition 1.6


Delta Controls

Cautions and Warnings


The DNT-T221 BACstat II is an Electro-statically sensitive device. However, since the
WARNING
electronics are contained within the housing, and if sufficient care is taken in handling, proper
ESD protection (ground strap) should be unnecessary.

Compliance Declarations
FCC Compliance Information
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to
Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may cause harmful interference to
radio communications. However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one
or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected.
• Consult the dealer or an experienced radio/TV technician for help.

Industry Canada Compliance Statement


ICES-003 This Class B digital apparatus meets all requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe B Respecte toutes les exigences du Règlement sur le matérial
brouiller du Canada.

UL Compliance Information

This product conforms to the following UL requirements:

• UL916: Energy Management Equipment

Document Edition 1.6 Page 9 of 10


Delta Network Thermostat: BACstat II DNT-T221 (Rev 2.2) Installation Guide

CE - DECLARATION OF CONFORMITY
according to ISO/IEC Guide 22 and EN 45014

Manufacturer's Name: Delta Controls

Manufacturer's Address: 17850 56th Avenue


Surrey, British Columbia
Canada
V3S 1C7

declares that the product (s):

Product Name: BACstat II - Analog

Model Numbers: DNT-T221

Product Options: All

conforms to the following Product Specifications:

EMC:
EN 55022:1994 Radiated and Conducted Emissions Class B

EN 50082-1:1997 Generic Immunity Standard


EN 61000-4-2:1995 + A1:1999 ESD Immunity Level A
EN 61000-4-3:1996 RF Electromagnetic Field Immunity Level A
ENV 50204:1995 RF Electromagnetic Field Immunity (Keyed) Level A
EN 61000-4-4:1995 EFT/Burst Immunity Level B
EN 61000-4-5:1995 Surge Immunity Level B
EN 61000-4-6:1996 Conducted RF Disturbances Immunity Level A
EN 61000-4-11:1994 Voltage Dips / Interruptions Level B/C

Supplementary Information:

The product(s) herewith comply with the requirements of the EMC Directive
89/336/EEC. The product(s) were tested in a typical configuration.

Lee Dickson
Quality Assurance Manager

Page 10 of 10 Document Edition 1.6

You might also like