Room Checksums: by Msu 1St-Extra Bedroom Heating Coil Peak CLG Space Peak Cooling Coil Peak Temperatures
Room Checksums: by Msu 1St-Extra Bedroom Heating Coil Peak CLG Space Peak Cooling Coil Peak Temperatures
Room Checksums: by Msu 1St-Extra Bedroom Heating Coil Peak CLG Space Peak Cooling Coil Peak Temperatures
By MSU
1st-Extra BedRoom
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 10 / 16 Mo/Hr: 4 / 17 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 100 / 76 / 99 OADB: 91 OADB: 5 SADB 57.2 70.0
Ra Plenum 74.6 69.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 74.6 69.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 76.9 10.1
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.1 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 0 0 0 0 0 Roof Cond 0 0 0.00
Glass Solar 2,750 0 2,750 26 3,193 43 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 427 0 427 4 285 4 Glass/Door Cond -1,031 -1,031 35.31 Cooling Heating
Wall Cond 237 53 290 3 288 4 Wall Cond -828 -1,017 34.83
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 438 44
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 438 44
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 438 44
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 3,413 53 3,466 33 3,767 51 Sub Total ==> -1,859 -2,049 70.14 Nom Vent 40 40
AHU Vent 40 40
Internal Loads Internal Loads Infil 0 0
Lights 999 250 1,249 12 999 13 Lights 999 1,249 -42.76 MinStop/Rh 44 44
People 1,500 0 1,500 14 750 10 People 750 750 -25.68 Return 438 44
Misc 1,874 0 1,874 18 1,874 25 Misc 1,874 1,874 -64.14 Exhaust 40 40
Sub Total ==> 4,373 250 4,623 45 3,623 49 Sub Total ==> 3,623 3,873 -132.58 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 64 -64 0 0 63 1 Ceiling Load -10 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 2,209 21 0 0 Ventilation Load 0 -2,921 99.99 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0 0 0.00
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 4 -0.13 ENGINEERING CKS
Exhaust Heat -25 -25 0 OA Preheat Diff. 0 0.00
Sup. Fan Heat 104 1 RA Preheat Diff. -1,754 60.04 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 9.1 91.4
Duct Heat Pkup 0 0 0 System Plenum Heat -75 2.55 cfm/ft² 1.20 0.12
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 460.18
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 384.74
Btu/hr·ft² 31.19 -7.98
Grand Total ==> 7,851 213 10,377 100.00 7,452 100.00 Grand Total ==> 1,754 -2,921 100.00 No. People 3.0 8.2/1000 ft²