System Checksums
System Checksums
System Checksums
By GULF CONSULT
1st Floor Variable Refrigerant Flow
COOLING COIL PEAK CLG SPACE PEAK HEATING COIL PEAK TEMPERATURES
Peaked at Time: Mo/Hr: 10 / 11 Mo/Hr: 4 / 10 Mo/Hr: Heating Design Cooling Heating
Outside Air: OADB/WB/HR: 90 / 72 / 90 OADB: 81 OADB: 5 SADB 57.1 71.4
Ra Plenum 74.4 69.9
Space Plenum Net Percent Space Percent Space Peak Coil Peak Percent Return 74.4 69.9
Sens. + Lat. Sens. + Lat Total Of Total Sensible Of Total Space Sens Tot Sens Of Total Ret/OA 76.0 63.5
Btu/h Btu/h Btu/h (%) Btu/h (%) Btu/h Btu/h (%) Fn MtrTD 0.0 0.0
Envelope Loads Envelope Loads Fn BldTD 0.1 0.0
Skylite Solar 0 0 0 0 0 0 Skylite Solar 0 0 0.00 Fn Frict 0.1 0.0
Skylite Cond 0 0 0 0 0 0 Skylite Cond 0 0 0.00
Roof Cond 0 0 0 0 0 0 Roof Cond 0 0 0.00
Glass Solar 44,254 0 44,254 37 61,927 59 Glass Solar 0 0 0.00 AIRFLOWS
Glass/Door Cond 5,012 0 5,012 4 2,320 2 Glass/Door Cond -24,719 -24,719 50.47 Cooling Heating
Wall Cond 2,148 511 2,659 2 5,601 5 Wall Cond -14,942 -18,659 38.10
Partition/Door 0 0 0 0 0 Partition/Door 0 0 0.00 Diffuser 6,108 5,529
Floor 0 0 0 0.00 0 Floor 0 0 0.00 Terminal 6,108 5,529
Adjacent Floor 0.00 0.00 0.00 0.00 0.00 0.00 Adjacent Floor 0.00 0.00 0.00 Main Fan 6,108 5,529
Infiltration 0 0 0 0 0 Infiltration 0 0 0.00 Sec Fan 0 0
Sub Total ==> 51,414 511 51,926 43 69,849 67 Sub Total ==> -39,660 -43,377 88.56 Nom Vent 620 546
AHU Vent 620 546
Internal Loads Internal Loads Infil 0 0
Lights 12,240 3,060 15,300 13 12,240 12 Lights 12,240 15,300 -31.24 MinStop/Rh 611 611
People 15,000 0 15,000 12 7,500 7 People 7,500 7,500 -15.31 Return 6,108 5,529
Misc 14,254 0 14,254 12 14,254 14 Misc 14,254 14,254 -29.10 Exhaust 620 546
Sub Total ==> 41,495 3,060 44,555 37 33,995 33 Sub Total ==> 33,995 37,055 -75.65 Rm Exh 0 0
Auxiliary 0 0
Ceiling Load 600 -600 0 0 653 1 Ceiling Load -120 0 0.00 Leakage Dwn 0 0
Ventilation Load 0 0 23,384 19 0 0 Ventilation Load 0 -39,838 81.34 Leakage Ups 0 0
Adj Air Trans Heat 0 0 0 0 0 Adj Air Trans Heat 0 0 0
Dehumid. Ov Sizing 0 0 Ov/Undr Sizing 0 0 0.00
Ov/Undr Sizing 0 0 0 0 0 Exhaust Heat 53 -0.11 ENGINEERING CKS
Exhaust Heat -302 -302 0 OA Preheat Diff. 0 0.00
Sup. Fan Heat 1,448 1 RA Preheat Diff. -2,871 5.86 Cooling Heating
Ret. Fan Heat 0 0 0 Additional Reheat 0 0.00 % OA 10.2 9.9
Duct Heat Pkup 0 0 0 cfm/ft² 1.41 1.28
Underflr Sup Ht Pkup 0 0 Underflr Sup Ht Pkup 0 0.00 cfm/ton 550.67
Supply Air Leakage 0 0 0 Supply Air Leakage 0 0.00 ft²/ton 390.47
Btu/hr·ft² 30.73 -11.31
Grand Total ==> 93,509 2,670 121,011 100.00 104,496 100.00 Grand Total ==> -5,785 -48,979 100.00 No. People 30