MSC.1/Circ.1434
31 May 2012
1 The Maritime Safety Committee, at its ninetieth session (16 to 25 May 2012), with
a view to providing more specific guidance for the application of the relevant requirements of
the 1974 SOLAS Convention, approved the unified interpretations of SOLAS chapter II-2
prepared by the Sub-Committee on Fire Protection, at its fifty-fifth session, as set out in
the annex.
***
I:\CIRC\MSC\01\1434.doc
MSC.1/Circ.1434
Annex, page 1
ANNEX
Insulated "A" class bulkheads and decks used on board ships, including the means of affixing
the insulation to the "A" class structural members, should be consistent with the materials,
details and arrangements used during, and documented in the test reports issued for, the
approval test for that insulating material.
.1 the battery room does not open directly onto an exposed deck;
.2 the ventilation opening for the battery room is required to be fitted with a closing
device according to the Load Line Convention (i.e. the height of the opening
does not extend to more than 4.5 m (14.8 feet) above the deck for position 1
or to more than 2.3 m (7.5 feet) above the deck in position 2; or
2 Where a battery room ventilator is fitted with a closing device, then a warning notice
stating, for example "This closing device is to be kept open and only closed in the event of fire or
other emergency – Explosive gas", should be provided at the closing device to mitigate the
possibility of inadvertent closing.
1 If adjacent spaces are not separated from cargo spaces by gastight bulkheads or
decks, then they should be considered as part of the enclosed cargo space and the ventilation
requirements should apply to the adjacent space as for the enclosed cargo space itself.
.1 two (2) fans per hold, a common ventilation system with 2 fans connected is
acceptable; and
.2 continuous ventilation, this does not prohibit ventilators from being fitted
with a means of closure as required for fire protection purposes under SOLAS
regulation II-2/5.2.1.1, provided the minimum height to the ventilator
opening is to be in accordance with regulation 19.3 of the 1966 International
Convention on Load Lines (4.5 m for position 1 and 2.3 m for position 2).
1 Access routes to the controls for closure of the ventilation system "permit a rapid
shutdown" and adequately "take into account the weather and sea conditions" if the routes:
I:\CIRC\MSC\01\1434.doc
MSC.1/Circ.1434
Annex, page 2
.2 are provided with a single handrail or wire rope lifeline not less than 10 mm in
diameter, supported by stanchions not more than 10 m apart in way of any
route which involves traversing a deck exposed to weather; and
.3 are fitted with appropriate means of access (such as ladders or steps) to the
closing devices of ventilators located in high positions (i.e. 1.8 m and above).
2 Alternatively, remote closing and position indicator arrangements from the bridge
or a fire control station for those ventilator closures is acceptable.
___________