TFP725 08 2016

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

Worldwide

www.tyco-fire.com
Contacts

Model FH-1
Flexible Hose
Available in Asia and Pacific Territories Only
General NOTICE
Model FH-1 Flexible Hose described
Description herein must be installed and maintained
in compliance with this document
TYCO Model FH-1 Flexible Hose can and with the applicable standards
be used in wet sprinkler systems recognized by the Approval agency, in
between the branchline and sprinkler addition to the standards of any other
when installed in accordance with authorities having jurisdiction. Failure
NFPA 13, 13D, and 13R. Flexible Hose to do so may impair the performance
provides a unique sprinkler drop of these devices.
assembly comprised of the following
components: The owner is responsible for
maintaining their fire protection system
• Stainless steel flexible hose with and devices in proper operating
two slip nuts condition. Contact the installing
contractor or product manufacturer Materials of Construction
• Branchline inlet nipple The Flexible Hose is AISI (American Iron
with any questions.
• Straight sprinkler reducer and Steel Institute) Type 304 Stainless
• Reducer bracket, bar fixing clamps,
and support bar
Technical Steel. The connection at each end of
the Flexible Hose utilizes a Slip Nut,

Using Model FH-1 Flexible Hose saves Data NBR O-Ring, and Nylon 66 Washer.
The Inlet Nipple, Sprinkler Reducer, the
time and cost because the system can Reducer Bracket, Bar Fixing Clamps,
be installed in false ceilings without Approvals and Support Bar are Steel.
UL Listed (Refer to Table A)
cutting and threading pipes associated FM Approved (Refer to Table B)
with installing a drop, arm-over, and
elbows. Model FH-1 Flexible Hose Nominal Assembly Lengths
makes it possible to test and charge 700 mm, 1000 mm, 1200 mm,
the system with water before installing 1500 mm, 1800 mm
the ceiling grid. After the ceiling grid Styles
is in position, the Model FH-1 Flexible Braided and Unbraided
Hose can be reshaped to suit the final
sprinkler location without draining the Inlet Connection
system. ISO 7-R 1
Model FH-1 Flexible Hose is installed Outlet Connections
quickly without large and expensive 1/2 inch NPT
tools. Ideal applications include 3/4 inch NPT
offices, schools, libraries, hospitals, Maximum Service Pressure
and shopping complexes. 13,8 bar (Refer to Table A)
12,1 bar (Refer to Tables A and B)
Maximum Ambient Temperature
107°C
Discharge Coefficient
Refer to Tables A and B
Minimum Installation Bend Radius
Refer to Tables A and B
Bending Angles (Flow Direction)
Up to 180 degrees

Page 1 of 8 AUGUST 2016 TFP725


TFP725
Page 2 of 8

Discharge Equivalent
Hose Minimum
Outlet Coefficient Maximum Length
Part Assembly Bend
Connection Maximum Allowable Number of of Schedule 40
Number Length Radius
NPT K-factor 90° Bends Steel Pipe
mm mm
lpm/bar1/2 C = 120 in Meters

Braided 13,8 bar 1/2 Inch NPT

TYFH-T-1-0700 700 1/2 115,2 1 150 3,7

TYFH-T-1-1000 1000 1/2 115,2 1 150 5,2

TYFH-T-1-1200 1200 1/2 115,2 2 150 13,1

TYFH-T-1-1500 1500 1/2 115,2 2 150 16,2

TYFH-T-1-1800 1800 1/2 115,2 2 150 19,8

Braided 13,8 bar 3/4 Inch NPT

TYFH-T-3-0700 700 3/4 241,9 1 150 6,7

TYFH-T-3-1000 1000 3/4 241,9 1 150 10,7

TYFH-T-3-1200 1200 3/4 241,9 2 150 11,9

TYFH-T-3-1500 1500 3/4 241,9 2 150 14,3

TYFH-T-3-1800 1800 3/4 241,9 2 150 16,2

Unbraided 12,1 bar 1/2 Inch NPT

TYFH-O-1-0700 700 1/2 80,6 1 150 3,7

TYFH-O-1-1000 1000 1/2 80,6 1 150 5,2

TYFH-O-1-1200 1200 1/2 80,6 2 150 13,1

TYFH-O-1-1500 1500 1/2 80,6 2 150 16,2

TYFH-O-1-1800 1800 1/2 80,6 2 150 19,8

Unbraided 12,1 bar 3/4 Inch NPT

TYFH-O-3-0700 700 3/4 161,3 1 150 6,7

TYFH-O-3-1000 1000 3/4 161,3 1 150 10,7

TYFH-O-3-1200 1200 3/4 161,3 2 150 11,9

TYFH-O-3-1500 1500 3/4 161,3 2 150 14,3

TYFH-O-3-1800 1800 3/4 161,3 2 150 16,2

Notes
All Part Numbers have a Maximum Ambient Temperature of 107°C and a Flexibility Type of Limited.
These fittings are intended for use in hydraulically designed sprinkler systems. The hydraulic loss of these fittings needs to be included in hydraulic
design calculations. Losses vary depending upon the installed configuration. This table provides the maximum allowable number of bends with a
minimum bend radius of 150 mm for each model and associated pressure losses expressed in equivalent length of DN25 Schedule 40 Steel Pipe,
in meters, where C equals 120.
TABLE A
MODEL FH-1 FLEXIBLE HOSE
UL DESIGN CRITERIA
TFP725
Page 3 of 8

Discharge Equivalent
Hose Minimum
Outlet Coefficient Maximum Length
Part Assembly Bend
Connection Maximum Allowable Number of of Schedule 40
Number Length Radius
NPT K-factor 90° Bends Steel Pipe
mm mm
lpm/bar1/2 C = 120 in Meters

Braided 12,1 bar 1/2 Inch NPT

TYFH-T-1-0700 700 1/2 80,6 1 230 5,8

TYFH-T-1-1000 1000 1/2 80,6 2 230 7,1

TYFH-T-1-1200 1200 1/2 80,6 2 230 8,0

TYFH-T-1-1500 1500 1/2 80,6 3 230 9,4

TYFH-T-1-1800 1800 1/2 80,6 4 230 10,2

Braided 12,1 bar 3/4 Inch NPT

TYFH-T-3-0700 700 3/4 115,2 1 230 2,9

TYFH-T-3-1000 1000 3/4 115,2 2 230 4,2

TYFH-T-3-1200 1200 3/4 115,2 2 230 4,9

TYFH-T-3-1500 1500 3/4 115,2 3 230 6,8

TYFH-T-3-1800 1800 3/4 115,2 4 230 8,3

Notes
All Part Numbers have a Maximum Ambient Temperature of 107°C and a Flexibility Type of Limited.
These fittings are intended for use in hydraulically designed sprinkler systems. The hydraulic loss of these fittings needs to be included in hydraulic
design calculations. Losses vary depending upon the installed configuration. This table provides the maximum allowable number of bends with a
minimum bend radius of 300 mm for each model and associated pressure losses expressed in equivalent length of DN25 Schedule 40 Steel Pipe,
in meters, where C equals 120.
TABLE B
MODEL FH-1 FLEXIBLE HOSE
FM DESIGN CRITERIA

Design to proper placement of the Support


Bar and Sprinkler Reducer. 95mm
• ASTM C636 (Standard Practice for
Installation of Metal Ceiling Suspen-
Criteria clamps provide for greater clearance
than standard 58 mm clamps included
sion Systems for Acoustical Tile and
Lay-in Panels)
Criteria in this section must be with FH-1 assemblies. For instance, Model FH-1 Hose connections
considered and applied accordingly concealed sprinklers, which typically have been approved for use in all
for TYCO Model FH-1 Flexible Hose require a distance from the face of Intermediate-Duty and Heavy-Duty
installations. the Sprinkler Reducer to the mounting structural classifications.
surface greater than that for non-
Model FH-1 Flexible Hose can be used concealed sprinklers, necessitate Refer to relative regulations, codes,
in wet sprinkler systems between the installation with 95 mm clamps. Refer or standards for guidance and
branchline and sprinkler when installed to Figure 3 and Ordering Procedure. determination of desirable location for
in accordance with NFPA 13, 13D, and unit in use; e.g., commercial ceilings,
13R. Hose and fittings have limited flexibility clean rooms, and duct systems.
and are intended for direct connection
Approved components (Sprinkler to sprinklers in accordance with NFPA
Reducer, Reducer Bracket and 58 mm 13, 13D, or 13R.
Bar Fixing Clamps) included with FH-1
assemblies will accommodate exposed Referenced by IBC (International
or semi-recessed sprinkler installations Building Code), these connections are
only. (Refer to Figure 3.) designed for use in ceilings with grids
that meet the following standards:
NOTE: Separately ordered 95 mm
Bar Fixing Clamps may be used for • ASTM C635 (Standard Specification
installations in areas where structures for the Manufacture, Performance,
or equipment extending immediately and Testing of Metal Suspension
above the ceiling pose an interference Systems for Acoustical Tile and
Lay-in Panel Ceilings)
TFP725
Page 4 of 8

Part Number L
Nominal
Unbraided Braided Length
12,1 bar 13,8 bar mm L
TYFH-O-1-0700 TYFH-T-1-0700 700

TYFH-O-1-1000 TYFH-T-1-1000 1000

TYFH-O-1-1200 TYFH-T-1-1200 1200 INLET FLEXIBLE SPRINKLER


NIPPLE HOSE REDUCER
TYFH-O-1-1500 TYFH-T-1-1500 1500

TYFH-O-1-1800 TYFH-T-1-1800 1800

FIGURE 1
MODEL FH-1 FLEXIBLE HOSE
NOMINAL DIMENSIONS

BRANCHLINE
FITTING INLET
(NOT INCLUDED) NIPPLE UNBRAIDED
SYSTEM or BRAIDED
BRANCHLINE FLEXIBLE HOSE
WITH SLIP NUTS

ISO 7-R 1
PIPE THREADED HOSE SPRINKLER REDUCER:
END THREADED MALE THREADED HOSE
SLIP NUT CONNECTION WITH
1/2" NPT or 3/4" NPT
STANDARD FEMALE SPRINKLER
CEILING GRID CONNECTION
SPACING

HOSE
THREADED
SLIP NUT

REDUCER
BRACKET WITH CEILING
BAR FIXING HEX SCREWS GRID
CLAMP WITH
T-BAR
HEX SCREWS
DROP-IN
CEILING
PANEL

INSTALL TYPICAL
SPRINKLER ASSEMBLY *
(NOT INCLUDED)
SUPPORT
IN ACCORDANCE WITH * REFER TO DESIGN
BAR
MANUFACTURER'S CRITERIA SECTION
INSTRUCTIONS FOR SPRINKLER
COMPATIBILITY
FIGURE 2
MODEL FH-1 FLEXIBLE HOSE
ASSEMBLY
TFP725
Page 5 of 8

REDUCER FLEXIBLE
BRACKET HOSE

SUPPORT SPRINKLER
58 mm BAR BAR REDUCER
FIXING CLAMP *

* 58 mm BAR FIXING DROP-IN CEILING


TYPICAL EXPOSED CEILING PANEL GRID T-BAR
CLAMPS (QTY. 2) OR RECESSED
INCLUDED WITH FH-1 SPRINKLER
ASSEMBLY; ORDER
95 mm BAR FIXING
CLAMPS (QTY. 2)
SEPARATELY AS REDUCER FLEXIBLE
NEEDED BRACKET HOSE

SUPPORT SPRINKLER
95 mm BAR BAR REDUCER
FIXING CLAMP *

DROP-IN CEILING
TYPICAL CEILING PANEL GRID T-BAR
CONCEALED
SPRINKLER
FIGURE 3
MODEL FH-1 FLEXIBLE HOSE
BAR FIXING CLAMP APPLICATION

BRANCHLINE INLET SLIP FLEXIBLE


FITTING NIPPLE NUT HOSE TO
OUTLET SPRINKLER

ISO 7-R 1 MACHINE HOSE


THREADED THREADED
END END
PERMITTED NOT PERMITTED NOT PERMITTED

DO route the Flexible Hose to permit DO use the Inlet Nipple with
entire draining either back into the the direction of the flow arrow
branchline or through the Sprinkler properly oriented to avoid
Reducer. mismatched threads.
FIGURE 4
MODEL FH-1 FLEXIBLE HOSE
INSTALLATION GUIDANCE
TFP725
Page 6 of 8

Installation Step 8. Slide Reducer Bracket and two


Bar Fixing Clamps onto Support Bar,
Step 16. Verify that Sprinkler Reducer
is seated in Reducer Bracket. Precisely
With reference to Figures 2, 3 and 4, loosely tightening screws. locate the sprinkler in all three
TYCO Model FH-1 Flexible Sprinkler axes in accordance with sprinkler
Step 9. Attach Bar Fixing Clamps to
Hose must be installed in accordance manufacturer’s data sheet. Tighten Bar
tops of Ceiling Grid T-Bars, loosening
with this section. Fixing Clamps and the Reducer Bracket
screws as necessary to adjust clamp
Screws to a torque of 5,6 Nm.
positions. With Support Bar positioned
NOTICE across sprinkler location tighten screws Step 17. After tightening all screws,
Flexible Hoses are intended only to loosely to a torque of 2,8 Nm. verify sprinkler is properly located
connect sprinklers directly to system in accordance with manufacturer’s
Step 10. Retract Slip Nut at outlet end
piping; for an example, refer to Figure instructions. If not, loosen Bar Fixing
of Flexible Hose and ensure O-Ring is
2. Flexible Hoses cannot be joined Clamp or Reducer Bracket Screws
fully seated against Flexible Hose fitting
together to form longer hoses. Joining and re-adjust as required. Re-tighten
collar.
Flexible Hoses together creates an screws as previously described.
assembly with “unknown performance” Step 11. Insert Flexible Hose fitting into
that has not been accounted for in
system calculations or safe product
Sprinkler Reducer and hand tighten
Slip Nut onto Sprinkler Reducer. Care and
performance. Step 12. Apply adjustable wrench to
Flexible Hose Slip Nut and tighten onto
Maintenance
During and after installation, ensure TYCO Model FH-1 Flexible Hose must
that any sharp-edged material or tool Sprinkler Reducer to a torque of 12,1
Nm. be maintained, inspected, and serviced
does not damage the surface of the in accordance with this section in
flexible hose. NOTE: Higher levels of torque can addition to any specific requirements
Step 1. Ensure Inlet Nipple is separated distort Sprinkler Reducer and Slip Nut of the applicable authorities having
from Flexible Hose. and damage O-Ring inside Flexible jurisdiction ( e.g., NFPA ) . Any
Hose Assembly fitting with consequent impairment must be immediately
Step 2. Apply pipe-thread sealant to leakage or impairment of the assembly. corrected. It is also recommended that
ISO 7-R 1 tapered pipe thread end of fire protection systems be inspected by
Inlet Nipple. Step 13. Bend Flexible Hose into a
curve(s) that locates Sprinkler Reducer a qualified Inspection Service.
NOTE: Do not apply thread sealant to in area where the sprinkler will be Before closing a fire protection
straight machine thread end of Inlet located. Do not twist hose and ensure system control valve for inspection or
Nipple. that bend arc is large and smooth. maintenance work on the fire protection
Step 3. Install ISO 7-R 1 thread end Adhere to minimum bend radius in system that it controls, obtain
of Inlet Nipple into ISO 7-Rc 1 thread accordance with Table A or B as permission to shut down the effected
outlet of branchline fitting. applicable. fire protection system from the proper
For longer Flexible Hose, intermediate authorities and notify all personnel who
NOTE: Arrow on Inlet Nipple indicates
support is recommended to secure may be affected by this action.
appropriate direction of flow to
sprinkler. movement of the flexible hose. After placing a fire protection system
in service, notify the proper authorities
NOTE: Do not apply pipe wrench on NOTICE and advise those responsible for
pipe threads and straight threads of
For minimum bend criteria, refer to the monitoring proprietary and/or central
Inlet Nipple.
Technical Data section. Agency listing station alarms.
Step 4. Retract Flexible Hose Slip is based on this criteria. The owner is responsible for the
Nut and ensure O-Ring is fully seated
A bend radius smaller than provided inspection, testing, and maintenance of
against Flexible Hose fitting collar.
by the minimum bend criteria may their fire protection system and devices
Step 5. Insert Flexible Hose fitting into adversely effect the friction loss in compliance with this document, as
Inlet Nipple and hand tighten Slip Nut specifications stated by the Approval well as with the applicable standards
onto Inlet Nipple. laboratory. of the authorities having jurisdiction.
Step 6. Apply adjustable wrench to Contact the installing contractor
Step 14. Verify that Sprinkler Reducer or product manufacturer with any
Flexible Hose Slip Nut and tighten onto is correctly located before securing
Inlet Nipple to a torque of 12,1 Nm. questions.
Reducer Bracket. Adjust Sprinkler
NOTE: Higher levels of torque can Reducer by moving it vertically and Automatic sprinkler systems are
distort Inlet Nipple and Slip Nut and horizontally along Support Bar. Tighten recommended to be inspected,
damage O-Ring inside Flexible Hose all bolts securely and evenly by applying tested, and maintained by a qualified
Assembly fitting with consequent a torque of 5,6 Nm. Inspection Service in accordance with
leakage or impairment of the assembly. local requirements and/or national
Step 15. Attach Sprinkler to Sprinkler codes.
NOTE: Do not twist Flexible Hose to Reducer. Place a wrench on the
tighten Slip Nut onto Inlet Nipple. Sprinkler Reducer to counteract
tightening torque and to prevent
Step 7. Determine approximate Flexible Hose from twisting. Refer to
location of sprinkler, which should sprinkler manufacturer’s data sheets for
be as close as possible to center of appropriate sprinkler tightening torque,
distance between Ceiling Grid T-Bars, sprinkler wrench, and other installation
and select appropriate Support Bar guidance.
length to accommodate T-Bar spacing.
TFP725
Page 7 of 8

Limited REPLACEMENT PARTS


Inlet Nipple
Warranty Specify: Inlet Nipple for Model FH-1
Flexible Hose with 25 mm hose thread,
For warranty terms and conditions, visit ISO 7-R 1 inlet thread connection,
www.tyco-fire.com. P/N TYFHHOSENIP25

Ordering Straight Sprinkler Reducer


Specify: Straight Sprinkler Reducer
Procedure for Model FH-1 Flexible Hose for 25
mm hose threads with (specify) 1/2
This product is available for sale in the inch NPT or 3/4 inch NPT outlet thread
Asia and Pacific markets only. connection, P/N (specify):
1/2 inch NPT. . . . . . . . . . . . . . . . . . TYFHRBR120
Contact your local distributor for 3/4 inch NPT. . . . . . . . . . . . . . . . . . TYFHSBR120
availability. When placing an order,
indicate the full product description Reducer Bracket
and Part Number (P/N). Specify: Reducer Bracket for Model
FH-1 Flexible Hose, P/N TYFHRB0001
The Model FH-1 Flexible Hose
Assembly includes the following items: Bar Fixing Clamps
• Flexible Hose Specify: Bar Fixing Clamps for Model
• Inlet Nipple FH-1 Flexible Hose, P/N (specify):
• Straight Sprinkler Reducer 58 mm. . . . . . . . . . . . . . . . . . . . . . . TYFHRBF58T
95 mm. . . . . . . . . . . . . . . . . . . . . . . TYFHRBF95T
• Reducer Bracket
• Bar Fixing Clamps (58 mm, Qty. 2) a Support Bar
• Support Bar (1000 mm) b Select Suppor t Bar length to
a. If required, order 95 mm Bar Fixing Clamps accommodate ceiling grid spacing.
separately.
b. If required, order 700 mm or 1500 mm Specify: (length) Support Bar for Model
Support Bars separately. FH-1 Flexible Hose, P/N (specify):
Flexible Hose Assembly 700 mm. . . . . . . . . . . . . . . . . . . . . . TYFHSB0700
Specify: Model FH-1 Flexible Hose 1000 mm. . . . . . . . . . . . . . . . . . . . . TYFHSB1000
1500 mm. . . . . . . . . . . . . . . . . . . . . TYFHSB1500
Assembly, (specify) 13,8 bar or 12,1 bar
pressure, (specify) assembly length,
(specify) 1/2 inch NPT or 3/4 inch NPT
connection, and P/N (specify per Table
A or B)
TFP725
Page 8 of 8